4150k and 4160k series wizard ii pressure … and 4160k series wizard ii pressure controllers ......

Download 4150K and 4160K Series Wizard II Pressure … and 4160K Series Wizard II Pressure Controllers ... Scope of Manual 2 ... the 4150K and 4160K Series Wizard II pressure controllers and

If you can't read please download the document

Upload: vuonglien

Post on 17-Apr-2018

236 views

Category:

Documents


8 download

TRANSCRIPT

  • www.Fisher.com

    D20

    0151

    X01

    2

    4150K and 4160K Series Wizard II PressureControllers and TransmittersContents

    Introduction 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Scope of Manual 2. . . . . . . . . . . . . . . . . . . . . . . . . . Description 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Specifications 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . Educational Services 2. . . . . . . . . . . . . . . . . . . . . .

    Installation 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard Installation 5. . . . . . . . . . . . . . . . . . . . . . . Panel Mounting 5. . . . . . . . . . . . . . . . . . . . . . . . . . . Wall Mounting 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . Pipestand Mounting 6. . . . . . . . . . . . . . . . . . . . . . . Actuator Mounting 6. . . . . . . . . . . . . . . . . . . . . . . . Pressure Connections 6. . . . . . . . . . . . . . . . . . . . .

    Supply Pressure 6. . . . . . . . . . . . . . . . . . . . . . . . . Process Pressure 7. . . . . . . . . . . . . . . . . . . . . . . .

    Vent Assembly 9. . . . . . . . . . . . . . . . . . . . . . . . . . . Controller Operation 9. . . . . . . . . . . . . . . . . . . . . . . .

    Proportional-Only Controllers 9. . . . . . . . . . . . . . . Adjustments 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Adjustment: Set Point 9. . . . . . . . . . . . . . . . . . Adjustment: Proportional Band 9. . . . . . . . . . .

    Calibration: Proportional-Only Controllers 9. . . Startup: Proportional-Only Controllers 12. . . . .

    Proportional-Plus-Reset Controller 12. . . . . . . . . Adjustments 12. . . . . . . . . . . . . . . . . . . . . . . . . . .

    Adjustment: Set Point 12. . . . . . . . . . . . . . . . . Adjustment: Proportional Band 13. . . . . . . . . . Adjustment: Reset 13. . . . . . . . . . . . . . . . . . . . Adjustment: Anti-Reset Windup 13. . . . . . . . .

    Calibration 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Calibration: Proportional-Plus-ResetControllers 13. . . . . . . . . . . . . . . . . . . . . . . . . . Calibration: Anti-Reset Windup 15. . . . . . . . .

    Startup: Proportional-Plus-Reset Controllers 16Differential Gap Controllers 16. . . . . . . . . . . . . . . .

    Adjustments 16. . . . . . . . . . . . . . . . . . . . . . . . . . . Adjustment: Set Point 16. . . . . . . . . . . . . . . . . Adjustment: Proportional Band 16. . . . . . . . . .

    Calibration: Differential Gap Controllers 16. . . . Startup: Differential Gap Controllers 18. . . . . . .

    Transmitter Operation 18. . . . . . . . . . . . . . . . . . . . . Adjustments 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Adjustment: Zero 18. . . . . . . . . . . . . . . . . . . . . . . Adjustment: Span 19. . . . . . . . . . . . . . . . . . . . . . .

    Calibration: Transmitters 19. . . . . . . . . . . . . . . . . .

    W3525-1 / IL

    Figure 1. Wizard II Controller Yoke-Mounted on ControlValve Actuator

    Startup: Transmitters 20. . . . . . . . . . . . . . . . . . . . . Principle of Operation 20. . . . . . . . . . . . . . . . . . . . . .

    Proportional-Only Controllers 20. . . . . . . . . . . . . . Proportional-Plus-Reset Controllers 21. . . . . . . . Controllers with Anti-Reset Windup 21. . . . . . . . . Differential Gap Controllers 22. . . . . . . . . . . . . . . . Transmitters 22. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Maintenance 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replacing Gauges 23. . . . . . . . . . . . . . . . . . . . . . . Replacing Bourdon Tube 24. . . . . . . . . . . . . . . . . . Replacing Bellows Sensing Element 24. . . . . . . . Changing Proportional or Reset Valve 25. . . . . . Changing Anti-Reset Windup Differential

    Relief Valve (4160KF) 26. . . . . . . . . . . . . . . . . . Changing Action 26. . . . . . . . . . . . . . . . . . . . . . . . .

    Proportional-Only to a DifferentialGap Controller 26. . . . . . . . . . . . . . . . . . . . . . .

    Direct to Reverse Action 26. . . . . . . . . . . . . . . . . Relay Replacement 27. . . . . . . . . . . . . . . . . . . . . . Changing Output Signal Range 27. . . . . . . . . . . .

    Parts Ordering 28. . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Instruction ManualForm 5177March 2006 4150K and 4160K Controllers and Transmitters

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    2

    Contents (Continued)Parts Kits 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

    Controller Repair Kits 29. . . . . . . . . . . . . . . . . . . . . Relay Replacement Kits 29. . . . . . . . . . . . . . . . . .

    Parts List 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assemblies 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Common Parts 29. . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Parts for Panel, Wall, Pipestand

    or Actuator Mounting 36. . . . . . . . . . . . . . . . . . .

    Introduction

    Scope of ManualThis instruction manual provides installation,operating, maintenance, and parts information forthe 4150K and 4160K Series Wizard II pressurecontrollers and transmitters shown in figure 1. Referto separate instruction manuals for informationregarding the control valve, actuator, andaccessories.

    No person may install, operate, or maintain 4150Kand 4160K Series Wizard II pressure controllersand transmitters without first being fully trainedand qualified in valve, actuator and accessoryinstallation, operation and maintenance, and carefully reading and understanding the contents ofthis manual. If you have any questions about theseinstructions, contact your Emerson ProcessManagement sales office.

    DescriptionThe 4150K and 4160K Series pneumatic pressurecontrollers and transmitters use a bellows orBourdon tube sensing element to sense the gaugepressure, vacuum, compound pressure, ordifferential pressure of a liquid or gas. The controlleror transmitter output is a pneumatic pressure signalthat can be used to operate a final control element,indicating device, or recording device.

    Unless otherwise noted, all NACE references are toNACE MR0175-2002.

    SpecificationsSpecifications for the 4150K and 4160K Seriescontrollers and transmitters are listed in table 1.Table 2 explains available configurations andoptions.

    Educational ServicesFor information on available courses for 1450K and4160K Series controllers and transmitters, as well asa variety of other products, contact:

    Emerson Process ManagementEducational Services, RegistrationP.O. Box 190; 301 S. 1st Ave.Marshalltown, IA 50158-2823Phone: 800-338-8158 orPhone: 641-754-3771 FAX: 641-754-3431e-mail: [email protected]

    Note

    Neither Emerson, Emerson ProcessManagement, Fisher, nor any of theiraffiliated entities assumesresponsibility for the selection, use,and maintenance of any product.Responsibility for the selection, use,and maintenance of any productremains with the purchaser andend-user.

    Installation

    WARNING

    To avoid personal injury or propertydamage resulting from the suddenrelease of pressure:

    Always wear protective clothing,gloves, and eyewear when performingany installation operations.

    Personal injury or propertydamage may result from fire orexplosion if natural gas is used as thesupply medium and preventativemeasures are not taken. Preventativemeasures may include: Remoteventing of the unit, re-evaluating thehazardous area classification,ensuring adequate ventilation, and theremoval of any nearby ignitionsources. For information on remoteventing of this controller/transmitter,refer to page 9.

    (Installation Warning continued onpage 5)

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    3

    Table 1. Specifications

    Available Configurations

    See table 2

    Input Signal(1)

    Type: Gauge pressure, vacuum, compound pressure, or differential pressureof a liquid or gasLimits: See table 3 or 4

    Output Signal(1)

    Proportional-Only or Proportional-Plus-ResetControllers and Transmitters: 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) pneumaticpressure signalDifferential Gap Controllers: 0 and 1.4 bar (0 and 20 psig) or 0 and 2.4 bar (0 and 35 psig) pneumaticpressure signalAction: Control action is field reversible between direct (increasing sensed pressure producesincreasing output signal) and reverse(increasing sensed pressure produces decreasingoutput signal). The suffix R is added to the typenumber of a construction specified for reverseaction.

    Supply Pressure Requirements(2)

    See table 5

    Supply Pressure Medium

    Air or natural gas(3)

    Steady-State Air Consumption(1)

    See figure 2

    Supply and Output Connections

    1/4-inch NPT female

    Common Signal Pressure Conversions

    See table 6

    Proportional Band(1) Adjustment

    For Proportional-Only andProportional-Plus-Reset Controllers: Fulloutput pressure change adjustable from 3 to100% for a 0.2 to 1.0 bar (3 to 15 psig), or 6 to100% for a 0.4 to 2.0 bar (6 to 30 psig) of thesensing element range.

    Differential Gap Adjustment

    For Differential Gap Controllers: Full outputpressure change adjustable from 15% to 100% ofsensing element range

    Reset(1) Adjustment

    For Proportional-Plus-Reset Controllers:Adjustable from 0.01 to 74 minutes per repeat(100 to 0.01 repeats per minute)

    Zero(1) Adjustment (Transmitters Only)

    Continuously adjustable to position span of lessthan 100% anywhere within the sensing elementrange

    Span(1) Adjustment (Transmitters Only)

    Full output pressure change adjustable from 6 to100% of sensing element range

    Performance

    Repeatability(1): 0.5% of sensing element rangeDeadband(1) (Except Differential GapControllers(4): 0.1% of output spanTypical Frequency Response at 100%Proportional BandOutput to Actuator: 0.7 Hz and 110 degree phaseshift with 1850 cm3 (113 inches3) volume,actuator at mid-strokeOutput to Positioner Bellows: 9 Hz and 130degree phase shift with 0.2 to 1.0 bar (3 to 15psig) output to 33 cm3 (2 inches3) bellows

    Ambient Operating Temperature Limits(2)

    Standard Construction: 40 to 93C (40 to200F) 4160KF (w/Reset Relief): 40 to 71C (40 to160F)

    Typical Ambient Temperature OperatingInfluence

    Proportional Control only: Output pressurechanges 3.0% of sensing element range foreach 28C (50F) change in temperaturebetween 40 and 71C (40 and 160F) for acontroller set at 100% proportional bandReset Control only: Output pressure changes2.0% of sensing element range for each 28C(50F) change in temperature between 40 and71C (40 and 160F) for a controller set at 100%proportional band

    Continued

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    4

    Table 1. Specifications (continued)

    Typical Ambient Temperature OperatingInfluence (continued)

    Transmitters only: Output pressure changes3.0% of sensing element range for each 28C(50F) change in temperature between 40 and71C (40 and 160F) for a transmitter set at100% span

    Hazardous Area Classification

    Complies with the requirements of ATEX Group IICategory 2 Gas and Dust

    Refer to figure 22 for location of ATEX label

    Approximate Weight

    8.2 kg (18 pounds)

    Options

    Case pressure tested to 0.14 bar (2 psig)

    Declaration of SEP

    Fisher Controls International LLC declares thisproduct to be in compliance with Article 3paragraph 3 of the Pressure Equipment Directive(PED) 97 / 23 / EC. It was designed andmanufactured in accordance with SoundEngineering Practice (SEP) and cannot bear theCE marking related to PED compliance.

    However, the product may bear the CE markingto indicate compliance with other applicable ECDirectives.

    1. This term is defined in ISA Standard S51.1.2. The pressure/temperature limits in this document and any applicable standard or code limitation should not be exceeded.3. This product can be used with natural gas. Natural gas should not contain more than 20 ppm of H2S.4. An adjustable differential gap (differential gap controllers) is equivalent to an adjustable deadband.

    Table 2. Available ConfigurationsTYPE NUMBER(1)

    DESCRIPTION Bourdon TubeSensing Element(Gauge Pressure

    Only)

    Bellows Sensing Element

    GaugePressure

    DifferentialPressure

    Proportional-only controller 4150K 4152K 4154K

    Proportional-plus-reset controllerWithout anti-reset windup 4160K 4162K 4164K

    With anti-reset windup 4160KF 4162KF - - -

    Differential gap controller 4150KS 4152KS - - -

    Transmitter 4157K 4158K 4155K1. The suffix R is added to the type number of a construction specified for reverse action.

    Table 3. Bourdon Tube Pressure Ranges and Materials

    PRESSURE RANGES(1)MAXIMUM ALLOWABLE STATIC PRESSURE(2) LIMITS(3)

    MATERIALStandard With Optional Travel Stop(4)

    Bar Psig Bar Psig Bar Psig

    0 to 2.00 to 4.00 to 7.0

    0 to 300 to 600 to 100

    2.04.07.0

    3060

    100

    3.36.611

    4896

    160

    316 stainless steel

    0 to 140 to 200 to 400 to 70

    0 to 2000 to 3000 to 600(5)

    0 to 1000(5)

    14204070

    200300600

    1000

    19295083

    280420720

    1200

    0 to 1000 to 2000 to 350

    0 to 1500(5)

    0 to 30000 to 5000

    100200350

    150030005000

    115230380

    165033005500

    0 to 5500 to 700

    0 to 80000 to 10.000

    550700

    800010,000

    550700

    800010,000

    1. Range marked on Bourdon tube may be in kPa (1 bar = 100 kPa)2. This term is defined in ISA Standard S51.1.3. Bourdon tube may be pressurized to limit shown without permanent zero shift.4. With travel stop set at 110% of the range.5. These Bourdon tubes are also available in N05500 for sour service.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    5

    Table 4. Bellows Pressure Ranges and Materials

    PRESSURE RANGES MAXIMUM ALLOWABLE STATICPRESSURE(1) LIMITS(2)

    BrassConstruction

    Stainless SteelConstruction

    Bar Psig Bar Psig

    Gauge Pressure

    Vacuum0 to 150 mbar (0 to 60 inch wc)0 to 340 mbar (0 to 10 inch Hg)0 to 1.0 bar (0 to 30 inch Hg)

    1.62.82.8

    204040

    ------6.9

    ------

    100

    Compound Pressure75 mbar vac. to 75 mbar (30 inch wc vac. to 30 inch wc)500 mbar vac. to 500 mbar (15 inch Hg vac. to 7.5 psig)1.0 bar vac. to 1.0 bar (30 inch Hg vac. to 15 psig)

    1.42.82.8

    204040

    ---6.96.9

    ---100100

    Positive pressure

    0 to 150 mbar (0 to 60 inch wc)0 to 250 mbar(3) (0 to 100 inch wc)0 to 350 mbar(4) (0 to 140 inch wc)0 to 0.35 bar (0 to 5 psig)0 to 0.5 bar (0 to 7.5 psig)

    1.41.42.82.82.8

    2020404040

    ---------------

    ---------------

    0 to 0.7 bar (0 to 10 psig)0 to 1.0 bar (0 to 15 psig)0 to 1.4 bar (0 to 20 psig)0 to 2.0 bar (0 to 30 psig)

    2.82.82.82.8

    40404040

    ---6.9---6.9

    ---100---

    100

    Differential Pressure(5)

    0 to 300 mbar (0 to 80 inch wc)0 to 0.7 bar (0 to 10 psi)0 to 1.4 bar (0 to 20 psi)0 to 2.0 bar (0 to 30 psi)

    1.42.82.8---

    204040---

    ---------6.9

    ---------

    1001. This term is defined in ISA Standard S51.1.2. Bellows may be pressured to limit shown without permanent zero shift.3. Type 4158K transmitter only.4. Except Type 4158K transmitter.5. The overrange limit for these sensing elements is a differential pressure equal to the maximum allowable static pressure limit.

    SU

    PP

    LY

    AIR

    FL

    OW

    , SC

    FH

    PROPORTIONALBAND SETTING OF 0OR 10

    PROPORTIONAL BANDSETTING OF 5

    OUTPUT, PSIG

    3 TO 15 PSIG (0.2 TO 1.0 BAR) OUTPUT SIGNAL RANGE

    SU

    PP

    LY

    AIR

    FL

    OW

    , SC

    FH

    OUTPUT, PSIG

    6 TO 30 (0.4 TO 2.0 BAR) OUTPUT SIGNAL RANGE

    PROPORTIONALBAND SETTING OF 5

    PROPORTIONAL BANDSETTING OF 0 OR 10

    NOTESTO CONVERT PSIG TO BAR, MULTIPLY BY 0.06895.SCFHSTANDARD CUBIC FEET PER HOUR (60F AND 14.7 PSIA).

    TO CONVERT TO NORMAL M3/HRNORMAL CUBIC METERS PER HOUR (0C AND 1.01325 BAR, ABSOLUTE), MULTIPLY BY 0.0268

    1

    1

    1

    2

    2

    2

    A7242 / IL

    Figure 2. Steady-State Air Consumption

    WARNING

    (Installation Warning, continued frompage 2)

    If installing into an existingapplication, also refer to the WARNINGat the beginning of the Maintenancesection in this instruction manual.

    Check with your process or safetyengineer for any additional measuresthat must be taken to protect againstprocess media.

    Standard InstallationThe instruments are normally mounted vertical withthe case/cover as shown in figure 1. If installing theinstrument in any other position, be sure that thevent opening shown in figure 3 is facing downward.

    Panel MountingRefer to figure 3.

    Cut a hole in the panel surface according to thedimensions shown in figure 3. Remove the capscrews (key 252), brackets (key 251), and ventassembly (key 15). Slide the controller or transmitter

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    6

    into the cutout and reattach the brackets. Tighten thecap screw located in the center of each bracket todraw the case snugly and evenly against the panel.Reinstall the vent unless a remote vent will be used.

    Wall MountingRefer to figure 3.

    Drill four holes in the wall using the dimensionsshown in figure 3. In the bracket (key 251) are 8.7mm (0.3438 inch) diameter holes. Back out the capscrew located in the center of each bracket. (Thescrews are used for panel mounting but are notrequired for wall mounting.) If tubing runs throughthe wall, drill holes in the wall to accommodate thetubings. Figure 3 shows the pressure connectionlocations in the back of the case.

    Mount the controller to the bracket using the four capscrews (key 252) provided. Attach the bracket to thewall, using suitable screws or bolts.

    Pipestand MountingRefer to figure 3.

    Attach the spacer spools (key 228) and the mountingplate (key 213) to the controller with cap screws,lock washers, and nuts (keys 215, 221, and 216).Attach the controller to a 2-inch (nominal) pipe withpipe clamps (key 250).

    Actuator MountingRefer to figure 4.

    Controllers specified for mounting on a control valveactuator are mounted at the factory. If the instrumentis ordered separately for installation on a controlvalve actuator, mount the instrument according tothe following instructions.

    Mounting parts for the different actuator types andsizes vary. Two typical actuator-mountinginstallations are shown in figure 4; see the parts listfor parts required for the specific actuator type andsize involved. Attach the spacer spools (key 228)and the mounting plate (key 213) to the controllerwith machine screws, lock washers, and nuts (keys215, 221, and 216).

    Attach the mounting bracket to the actuator yokewith cap screws (key 222) and, if needed, spacerspools. On some designs, the mounting bracket isattached to the actuator diaphragm casing ratherthan to the yoke.

    Pressure Connections

    WARNING

    To avoid personal injury or propertydamage resulting from the suddenrelease of pressure, do not install anysystem component where serviceconditions could exceed the limitsgiven in this manual. Usepressure-relieving devices as requiredby government or accepted industrycodes and good engineering practices.

    All pressure connections on 4150K and 4160KSeries instruments are 1/4-inch NPT female. Use 6mm (1/4-inch) or 10 mm (3/8-inch) pipe or tubing forsupply and output piping. The pressure connectionlocations are shown in figure 3.

    Supply Pressure

    WARNING

    Severe personal injury or propertydamage may occur from anuncontrolled process if the instrumentsupply medium is not clean, dry,oil-free and noncorrosive. While useand regular maintenance of a filter thatremoves particles larger than 40microns in diameter will suffice inmost applications, check with anEmerson Process Management fieldoffice and industry instrument supplymedium quality standards for use withhazardous gas or if you are unsureabout the proper amount or method ofair filtration or filter maintenance.

    Supply pressure must be clean, dry air ornoncorrosive gas that meets the requirements of ISAStandard S7.3. Use a suitable supply pressureregulator to reduce the supply pressure source tothe normal operating supply pressure shown in table5. Connect supply pressure to the SUPPLYconnection at the back of the case.

    If operating the controller or transmitter from a highpressure source [up to 138 bar (2000 psig)], use ahigh pressure regulator system, such as the Type1367 High Pressure Instrument Supply System. ForType 1367 system installation, adjustment, andmaintenance information, see the separateinstruction manual.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    7

    2 INCH(NOMINAL)PIPE

    VENT ASSEMBLY(KEY 15)

    FOUR HOLESFOR WALLMOUNTING

    CUTOUT FORPANEL MOUNTING

    8.7(11/32)MOUNTINGHOLES

    PANEL MOUNTING WALL MOUNTING

    BACK VIEWPIPESTAND MOUNTING

    mm(INCH)

    NOTES: 1. ALL CONNECTIONS ARE 1/4-INCH NPT FEMALE.

    HIGH-PRESSURE CONNECTION FOR DIFFERENTIAL-PRESSURE UNITS.23

    B1563-2 / ILGE07082-A

    LOW-PRESSURE CONNECTION FOR DIFFERENTIAL-PRESSURE UNITS.

    Figure 3. Panel, Wall, and Pipestand Mounting

    Process Pressure

    WARNING

    To avoid personal injury or propertydamage resulting from the suddenrelease of pressure when usingcorrosive media, make sure the tubingand instrument components thatcontact the corrosive medium are ofsuitable noncorrosive material.

    Also refer to the Installation Warningat the beginning of this section.

    The pressure connections to the controller dependupon the type of pressure sensing, gauge ordifferential. Gauge pressure controllers use either aBourdon tube or bellows as the sensing element, asindicated in table 2. Differential pressure controllersuse two bellows to sense differential pressure.

    For gauge pressure instruments: The controlpressure block (key 8 in figure 18) has twoconnections. Process pressure can be connectedeither to the CONTROL connection on the back ofthe case, or to the connection on the left side of thecase, shown in figure 3, depending on theinstrument application. Plug the unused connection.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    8

    Table 5. Supply Pressure RequirementsOUTPUT

    SIGNAL RANGE NORMAL OPERATING SUPPLYPRESSURE(1)

    MAXIMUM ALLOWABLE SUPPLYPRESSURE TO PREVENT INTERNAL

    PART DAMAGE

    Bar0.2 to 1.0 or 0 and 1.4 (differential gap) 1.4 2.8

    0.4 to 2.0 or 0 and 2.4 (differential gap) 2.4 2.8

    Psig3 to 15 or 0 and 20 (differential gap) 20 40

    6 to 30 or 0 and 35 (differential gap) 35 401. If this pressure is exceeded, control may be impaired.

    Table 6. Common Signal Pressure ConversionsMps kg/cm2 bar kPa Psi

    0.020.030.040.050.06

    0.20.30.40.50.6

    0.2(2)

    0.30.40.50.6

    20(1)

    3540(1)

    5060

    35679

    0.070.080.090.100.12

    0.80.81.0

    1.0(3)

    1.3

    0.80.81.0

    1.0(2)

    1.2

    758095

    100(1)

    125

    1112141518

    0.140.150.170.180.20

    1.41.51.81.92.0

    1.41.51.71.9

    2.0(3)

    140150170185

    200(1)

    2022252730

    0.220.230.240.340.55

    2.22.32.53.55.6

    2.22.32.43.45.5

    220230240345550

    3233355080

    0.691.03

    7.010.5

    6.910.3

    6901035

    100150

    1. Values as listed in ANSI/S7.4.2. Values as listed in IEC Standard 382.3. Values rounded to correspond with kPa values.

    For differential pressure instruments: Connectthe low pressure line to the CONTROL connectionon the side of the case and the high pressure line tothe CONTROL connection on the back of the caseas shown in figure 3.

    When installing process piping, follow acceptedpractices to ensure accurate transmission of theprocess pressure to the controller or transmitter.Install shutoff valves, vents, drains, or seal systemsas needed in the process pressure lines. If theinstrument is located such that the adjacent processpressure lines will be approximately horizontal, thelines should slope downward to the instrument forliquid-filled lines and upward to instruments forgas-filled lines. This will minimize the possibility ofair becoming trapped in the sensor with liquid-filledlines or of condensation becoming trapped withgas-filled lines. The recommended slope is 83 mmper meter (1 inch per foot).

    48B6020-A / DOC

    SUPPLY PRESSUREREGULATOR

    SUPPLY PRESSUREREGULATOR

    TYPICAL ROTARY ACTUATOR

    TYPICAL SLIDING STEM ACTUATOR

    38B6021-A / DOC

    Figure 4. Actuator Mounting

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    9

    If a controller is being used in conjunction with acontrol valve to control pipeline pressure, connectthe process pressure line in a straight section of pipeapproximately 10 pipe diameters from the valve butaway from bends, elbows, and areas of abnormalfluid velocities. For pressure-reducing service, theprocess line must be connected downstream of thevalve. For pressure-relief service, the processpressure line must be connected upstream of thecontrol valve. Install a needle valve in the processpressure line to dampen pulsations.

    Vent Assembly

    WARNING

    Personal injury or property damagecould result from fire or explosion ofaccumulated gas, or from contact withhazardous gas, if a flammable orhazardous gas is used as the supplypressure medium. Because theinstrument case and cover assemblydo not form a gas-tight seal when theassembly is enclosed, a remote ventline, adequate ventilation, andnecessary safety measures should beused to prevent the accumulation offlammable or hazardous gas. However,a remote vent pipe alone cannot berelied upon to remove all flammableand hazardous gas. Vent line pipingshould comply with local and regionalcodes, and should be be as short aspossible with adequate inside diameterand few bends to reduce casepressure buildup.

    CAUTION

    When installing a remote vent pipe,take care not to overtighten the pipe inthe vent connection. Excessive torquewill damage the threads in theconnection.

    The vent assembly (key 15, figure 3) or the end of aremote vent pipe must be protected against theentrance of all foreign matter that could plug thevent. Use 13 mm (1/2-inch) pipe for the remote ventpipe, if one is required. Check the vent periodicallyto be certain it has not become plugged.

    Controller Operation

    Proportional-Only ControllersThis section describes the adjustments andprocedures for calibration and startup. Adjustmentlocations are shown in figure 5 unless otherwisespecified. All adjustments must be made with thecover open. When the adjustments and calibrationprocedures are complete, close and latch the cover.

    To better understand the adjustments and overalloperation of the controller, refer to the Principle ofOperation section in this manual forproportional-only controllers. Refer also to theschematic diagram in figure 14.

    Adjustments

    Adjustment: Set Point

    Adjust the pressure-setting knob by turning the knobclockwise to increase the set point andcounterclockwise to decrease the set point. Note:The dial setting and actual process pressure mayvary significantly, especially with a wide proportionalband setting.

    Adjustment: Proportional Band

    To adjust the proportional band, rotate theproportional band knob to the desired value.

    The proportional band adjustment determines theamount of change in controlled pressure required tocause the control valve to stroke fully. It may beadjusted from 3-100 percent of the nominal sensingelement pressure rating.

    Calibration: Proportional-OnlyControllersUnless otherwise indicated, key number locationsare shown in figure 5.

    Provide a process pressure source capable ofsimulating the process pressure range of thecontroller. If an output pressure gauge is notprovided, install a suitable pressure gauge forcalibration purposes.

    Connect a pressure source to the supply pressureregulator and be sure the regulator is delivering thecorrect supply pressure to the controller. Thecontroller must be connected open loop (Open loop:The controller output pressure changes must be

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    10

    PROPORTIONAL BANDADJUSTMENT KNOB

    PRESSURE-SETTING KNOB(KEY 36)

    PRESSURE-SETTINGDIAL (KEY 38)

    FLAPPER (KEY 45)

    NOZZLE (KEY 57)

    CALIBRATION ADJUSTER (KEY 41)

    ADJUSTER SCREWS (KEY 43)48B6003-AA6038-1 / IL

    Figure 5. Proportional-Only Controller Adjustment Locations

    dead ended into a pressure gauge). The followingprocedures use a 0.2 to 1.0 bar (3 to 15 psig) outputpressure range as an example. For a 0.4 to 2.0 bar(6 to 30 psig) output range, adjust the values asappropriate.

    1. Complete the above connections and provide aprocess pressure equal to the sensing elementrange.

    2. Rotate the proportional band knob, shown infigure 5, to 1.5 (15 percent proportional band).

    3. Verify that the calibration adjuster screws (key 43) are at mid-position in the calibrationadjuster (key 41) slots.

    Depending upon the controller action, perform oneor the other of the following procedures.

    For direct-acting controllers:

    4. Apply an input pressure equal to the sensingelement lower range value.

    5. Rotate the pressure setting knob to the minimumvalue.

    6. Adjust the nozzle (key 57) until the controlleroutput pressure is between 0.6 and 0.7 bar (8 and 10 psig.)

    7. Apply an input pressure equal to the sensingelement upper range value.

    8. Rotate the pressure-setting knob to the maximumvalue.

    Note

    When performing the span adjustmentin step 9, do not watch the outputgauge while changing the calibrationadjuster. The change in output is not agood indication of the change in span.While moving the calibration adjuster,the output pressure may change in theopposite direction than expected. Forexample, while moving the calibrationadjuster to increase span, the outputpressure may decrease. This shouldbe disregarded since even though theoutput pressure decreases, the span isincreasing.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    11

    IF OUTPUT IS:

    BELOW8 TO 10 PSIG(0.6 TO 0.7 BAR)

    ABOVE8 TO 10 PSIG(0.6 TO 0.7 BAR)

    MOVE ADJUSTERLEFT

    MOVE ADJUSTERRIGHT

    FLAPPER

    NOZZLE

    NOTE:3 TO 15 PSIG (0.1 TO 1.0 BAR) OUTPUT SHOWN.FOR 6 TO 30 PSIG (0.2 TO 2.0 BAR) OUTPUT, ADJUSTVALUES AS APPROPRIATE.A6154 / IL

    Figure 6. Direct-Acting Controller SpanAdjustmentProportional-Only Controllers

    Proper controller response dependson nozzle-to-flapper alignment.

    When performing span adjustments,carefully loosen both calibrationadjuster screws while holding thecalibration adjuster in place. Thenmove the calibration adjuster slightlyin the required direction by hand orusing a screwdriver. Verify propernozzle-to-flapper alignment and holdthe calibration adjuster in place whiletightening both adjustment screws.

    9. If the output is not between 0.6 and 0.7 bar (8and 10 psig), adjust the controller span by looseningthe two adjusting screws (key 43) and moving thecalibration adjuster (key 41) a small distance asindicated in figure 6.

    10. Repeat steps 4 through 9 until no furtheradjustment is necessary.

    11. Proceed to the startup procedure forproportional controllers.

    For reverse-acting controllers:

    4. Apply an input pressure equal to the sensingelement upper range value.

    5. Rotate the pressure setting knob to the maximumvalue.

    6. Adjust the nozzle (key 57) until the controlleroutput pressure is between 0.6 and 0.7 bar (8 and 10 psig).

    7. Apply an input pressure equal to the sensingelement lower range value.

    8. Rotate the pressure-setting knob to the minimumvalue.

    Note

    When performing the span adjustmentin step 9, do not watch the outputgauge while changing the calibrationadjuster. The change in output is not agood indication of the change in span.While moving the calibration adjuster,the output pressure may change in theopposite direction than expected. Forexample, while moving the calibrationadjuster to increase span, the outputpressure may decrease. This shouldbe disregarded since even though theoutput pressure decreases, the span isincreasing.

    Proper controller response dependson nozzle-to-flapper alignment.

    When performing span adjustments,carefully loosen both calibrationadjuster screws while holding thecalibration adjuster in place. Thenmove the calibration adjuster slightlyin the required direction by hand orusing a screwdriver. Verify propernozzle-to-flapper alignment and holdthe calibration adjuster in place whiletightening both adjustment screws.

    9. If the output is not between 0.6 and 0.7 bar (8and 10 psig), adjust the controller span by looseningthe two adjusting screws (key 43) and moving thecalibration adjuster (key 41) a small distance asindicated in figure 7.

    10. Repeat steps 4 through 9 until no furtheradjustment is necessary.

    11. Proceed to the startup procedure forproportional controllers.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    12

    IF OUTPUT IS:

    ABOVE8 TO 10 PSIG(0.6 TO 0.7 BAR)

    BELOW8 TO 10 PSIG(0.6 TO 0.7 BAR)

    MOVE ADJUSTERLEFT

    MOVE ADJUSTERRIGHT

    FLAPPER

    NOZZLE

    NOTE:3 TO 15 PSIG (0.1 TO 1.0 BAR) OUTPUT SHOWN.FOR 6 TO 30 PSIG (0.2 TO 2.0 BAR) OUTPUT, ADJUSTVALUES AS APPROPRIATE.A6155-1 / IL

    Figure 7. Reverse-Acting Controller Span Adjustment Proportional-Only Controllers

    Startup: Proportional-Only Controllers(General Tuning Guidelines)Calibrate the controller prior to this procedure.

    1. Be sure that the supply pressure regulator isdelivering the proper supply pressure to thecontroller.

    2. Rotate the pressure-setting knob to the desiredset point.

    3. Set the proportional band adjustment to 100percent for fast processes (example: liquid pressureor liquid flow). For slow processes (example:temperature), calculate the percentage from theequation below:

    For a slow process, determine the initial proportionalband setting in percent from the following equation:

    200 Allowable OvershootPressure Span

    P.B.

    For example:

    200 1.4 bar2.1 bar

    13% 200 2 psig

    30 psig 13%( )

    (1.3 proportional band setting)

    4. Proportional Action

    Disturb the system by tapping the flapper lightly orchange the set point a small amount and check forsystem cycling. If the system does not cycle thenlower the proportional band (raising the gain) anddisturb the system again. Continue this procedureuntil the system cycles. At that point, double theproportional band setting.

    Note

    Proportional band adjustment affectsthe set point. Proportional-onlycontrollers will show some offset fromset point depending upon proportionalband setting and process demand.After adjusting the proportional band,re-zero by carefully rotating the nozzle(key 57) until the steady-state processpressure equals the process pressureknob reading.

    This tuning procedure may be too conservative forsome systems. The recommended proportional bandsetting should be checked for stability by introducinga disturbance and monitoring the process.

    Proportional-Plus-Reset ControllersThis section describes the adjustments andprocedures for calibration and startup. Theadjustment locations are shown in figure 8 unlessotherwise specified. All adjustments must be madewith the cover open. When the adjustments andcalibration procedures are complete, close and latchthe cover. To better understand the adjustments andoverall operation of the controller, refer to thePrinciple of Operation section in this manual forproportional-plus-reset controllers. Refer also to theschematic diagram in figure 14.

    Adjustments

    Adjustment: Set Point

    Adjust the pressure-setting knob by turning the knobclockwise to increase the set point andcounterclockwise to decrease the set point.

    Rotate the knob until the indicator points to thedesired set point pressure value. The pressuresetting dial will reflect the desired set point if thecontroller is accurately calibrated.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    13

    RESET ADJUSTMENT KNOB

    PROPORTIONAL BANDADJUSTMENT KNOB

    PRESSURE SETTING KNOB(KEY 36)

    PRESSURE SETTINGDIAL (KEY 38)

    ADJUSTER SCREWS (KEY 43)

    CALIBRATION ADJUSTER (KEY 41)FLAPPER (KEY 45)

    NOZZLE (KEY 57)48B6002-AA5433-3 / IL

    Figure 8. Proportional-Plus-Reset Controller Adjustment Locations

    Adjustment: Proportional Band

    To adjust the proportional band, rotate theproportional band knob to the desired value.

    The proportional band adjustment determines theamount of change in controlled pressure required tocause the control valve to stroke fully. It may beadjusted from 3-100 percent of the nominal sensingelement pressure rating.

    Adjustment: Reset

    To adjust reset action turn the knob clockwise todecrease the minutes per repeat. Turn the knobcounterclockwise to increase the minutes per repeat.Increasing the minutes per repeat provides a slowerreset action.

    The reset adjustment dial is calibrated in minutes perrepeat. By definition, this is the time in minutesrequired for the reset action to produce an outputchange which is equal to the change produced byproportional control action. This is in effect, the timein minutes required for the controller to increase (ordecrease) its output pressure by an amount equal to

    a proportional increase (or decrease) caused by achange in set point or process pressure.

    Adjustment: Anti-Reset Windup

    The externally mounted differential relief valve canbe mounted to relieve on increasing or decreasingoutput pressure.

    CalibrationCalibration: Proportional-Plus-Reset Controllers

    Unless otherwise indicated, key number locationsare shown in figure 8.

    Before starting this procedure:

    Provide a process pressure source capable ofsimulating the process pressure range of thecontroller.

    If an output pressure gauge is not provided,install a suitable pressure gauge for calibrationpurposes. The controller must be connected openloop (Open loop: The controller output pressurechanges must be dead ended into a pressuregauge).

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    14

    Note

    Type 4160KF and 4162KF (anti-resetwindup) controllers are supplied withtwo O-rings (key 367, not shown), ananti-reset windup cover (key 369, notshown), and two machine screws (key368, not shown). Use these parts in thenext step.

    1. For controllers with anti-reset windup (Type4160KF and 4162KF), record the direction of thearrow on the anti-reset windup assembly (key 186, infigure 19). Remove the assembly and install the twoO-rings (key 367, not shown), and cover (key 369,not shown) supplied with the controller. Secure thecover with the two machine screws (key 368, notshown) provided.

    2. Connect regulated supply pressure to thecontroller. Do not exceed the normal operatingpressure in table 5.

    3. Rotate the reset knob to 0.01 minutes per repeat(fastest setting).

    4. Rotate the proportional band knob to 1.5 (15percent proportional band).

    5. Verify that the calibration adjuster screws (key 43) are at mid-position in the calibrationadjuster (key 41) slots.

    Depending upon the controller action, perform oneor the other of the following procedures.

    For direct-acting controllers:

    6. Apply an input pressure equal to the sensingelement lower range value.

    7. Rotate the pressure setting knob to the minimumvalue.

    8. Adjust the nozzle (key 57) until the controlleroutput pressure is between 0.6 and 0.7 bar (8 and 10 psig).

    9. Apply an input pressure equal to the sensingelement upper range value.

    10. Rotate the pressure-setting knob to themaximum value.

    Note

    When performing the span adjustmentin step 11, do not watch the outputgauge while changing the calibrationadjuster. The change in output is not agood indication of the change in span.While moving the calibration adjuster,

    IF OUTPUT IS:

    BELOW8 TO 10 PSIG(0.6 TO 0.7 BAR)

    ABOVE8 TO 10 PSIG(0.6 TO 0.7 BAR)

    MOVE ADJUSTERLEFT

    MOVE ADJUSTERRIGHT

    FLAPPER

    NOZZLE

    NOTE:3 TO 15 PSIG (0.1 TO 1.0 BAR) OUTPUT SHOWN.FOR 6 TO 30 PSIG (0.2 TO 2.0 BAR) OUTPUT, ADJUSTVALUES AS APPROPRIATE.A6154 / IL

    Figure 9. Direct-Acting Controller Span AdjustmentProportional-Plus-Reset Controllers

    the output pressure may change in theopposite direction than expected. Forexample, while moving the calibrationadjuster to increase span, the outputpressure may decrease. This shouldbe disregarded since even though theoutput pressure decreases, the span isincreasing.

    Proper controller response dependson nozzle-to-flapper alignment.

    When performing span adjustments,carefully loosen both calibrationadjuster screws while holding thecalibration adjuster in place. Thenmove the calibration adjuster slightlyin the required direction by hand orusing a screwdriver. Verify propernozzle-to-flapper alignment and holdthe calibration adjuster in place whiletightening both adjustment screws.

    11. If the output pressure is not between 0.6 and 0.7bar (8 and 10 psig), adjust the controller span byloosening the two adjusting screws (key 43) andmoving the calibration adjuster (key 41) a smalldistance as indicated in figure 9.

    12. Repeat steps 6 through 11 until no furtheradjustment is necessary.

    13. For controllers with anti-reset windup (Type4160KF and 4162KF), remove the two machinescrews, anti-reset windup cover, and two O-ringsinstalled in step 1 of this procedure. Install theanti-reset windup assembly (key 186) with the arrowpointing in the direction recorded in step 1.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    15

    14. Proceed to the Startup procedures forproportional-plus-reset controllers.

    For reverse-acting controllers:

    6. Apply an input pressure equal to the sensingelement upper range value.

    7. Rotate the pressure setting knob to the maximumvalue.

    8. Adjust the nozzle (key 57) until the controlleroutput pressure is between 0.6 and 0.7 bar (8 and 10 psig).

    9. Apply an input pressure equal to the sensingelement lower range value.

    10. Rotate the pressure-setting knob to the minimumvalue.

    Note

    When performing the span adjustmentin step 11, do not watch the outputgauge while changing the calibrationadjuster. The change in output is not agood indication of the change in span.While moving the calibration adjuster,the output pressure may change in theopposite direction than expected. Forexample, while moving the calibrationadjuster to increase span, the outputpressure may decrease. This shouldbe disregarded since even though theoutput pressure decreases, the span isincreasing.

    Proper controller response dependson nozzle-to-flapper alignment.

    When performing span adjustments,carefully loosen both calibrationadjuster screws while holding thecalibration adjuster in place. Thenmove the calibration adjuster slightlyin the required direction by hand orusing a screwdriver. Verify propernozzle-to-flapper alignment and holdthe calibration adjuster in place whiletightening both adjustment screws.

    11. If the output pressure is not between 0.6 and 0.7bar (8 and 10 psig), adjust the controller span byloosening the two adjusting screws (key 43) and

    IF OUTPUT IS:

    ABOVE8 TO 10 PSIG(0.6 TO 0.7 BAR)

    BELOW8 TO 10 PSIG(0.6 TO 0.7 BAR)

    MOVE ADJUSTERLEFT

    MOVE ADJUSTERRIGHT

    FLAPPER

    NOZZLE

    NOTE:3 TO 15 PSIG (0.1 TO 1.0 BAR) OUTPUT SHOWN.FOR 6 TO 30 PSIG (0.2 TO 2.0 BAR) OUTPUT, ADJUSTVALUES AS APPROPRIATE.A6155-1 / IL

    Figure 10. Reverse-Acting Controller Span AdjustmentProportional-Plus-Reset Controllers

    moving the calibration adjuster (key 41) a smalldistance as indicated in figure 10.

    12. Repeat steps 6 through 11 until no furtheradjustment is necessary.

    13. For controllers with anti-reset windup (Type4160KF and 4162KF), remove the two machinescrews, anti-reset windup cover, and two O-ringsinstalled in step 1 of this procedure. Install theanti-reset windup assembly (key 186) with the arrowpointing in the direction recorded in step 1.

    14. Proceed to the Startup procedures forproportional-plus-reset controllers.

    Calibration: Anti-Reset Windup

    Controllers with anti-reset windup have a differentialrelief valve assembly (figure 19). This relief valve isset at the factory to relieve at a 0.3 bar (5 psi)pressure difference between the reset bellowspressure and the proportional bellows pressure. Thevalve can be adjusted to relieve from 0.14 to 0.4 bar(2 to 7 psig).

    The relief valve can relieve on either rising controlleroutput pressure or falling controller output pressure.If the arrow on the relief valve points toward thebottom of the controller case as shown in figure 19,the valve will relieve on falling output pressure. If thearrow points in the opposite direction, the valve willrelieve on rising output pressure. The valve can beremoved and reinstalled with the arrow pointing inthe opposite direction to change the relief action.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    16

    Startup: Proportional-Plus-ResetControllers (General Tuning Guidelines)Calibrate the controller prior to this procedure.

    1. Be sure that the supply pressure regulator isdelivering the proper supply pressure to thecontroller.

    2. Rotate the pressure-setting knob to the desiredset point.

    3. Start with a reset setting of 0.05 minutes perrepeat (m/r) for fast processes, and 0.5 m/r for slowprocesses.

    4. Set the proportional band adjustment to 100percent for fast processes (example: liquid pressureor liquid flow). For a slow process (example:temperature), calculate the percentage from theequation below:

    For a slow process, determine the initial proportionalband setting in percent from the following equation:

    200 Allowable OvershootPressure Span

    P.B.

    For example:

    200 1.4 bar2.1 bar

    13% 200 2 psig

    30 psig 13%( )

    (1.3 proportional band setting)

    5. Proportional Action:

    Disturb the system by tapping the flapper lightly orchange the set point a small amount and check forsystem cycling. If the system does not cycle thenlower the proportional band (raising the gain) anddisturb the system again. Continue this procedureuntil the system cycles. At that point, double theproportional band setting and begin tuning the reset.

    6. Reset Action:

    Disturb the system. If the system does not cycle thenspeed up the reset and disturb the system again.Continue this procedure until the system cycles.When the system cycles multiply the reset timesetting by a factor of three (3) and slow the resetdown to the new value. The reset is now tuned.

    This tuning procedure may be too conservative forsome systems. The recommended proportional bandand reset setting should be checked for stability byintroducing a disturbance and monitoring theprocess as previously described. For someapplications, tighter control may be desirable.

    Differential Gap ControllersThis section describes the adjustments andprocedures for calibration and startup. Theadjustment locations are shown in figure 5 unlessotherwise specified. The output of each controller ischecked at the factory before the instrument isshipped.

    To convert a differential gap controller to aproportional-only controller or vice versa, refer to theappropriate procedure in the Maintenance section.

    If the process pressure can be varied through all orpart of the sensing element range or through the twodesired switching points, use the process pressurefor calibration. If not, provide a pressure source tosimulate the process pressure range for calibrationprocedures.

    To better understand the adjustments and overalloperation of the controller, refer to the Principle ofOperation section in this manual for differential gapcontrollers and the schematic diagram in figure 14.

    AdjustmentsAdjustment: Set Point

    The position of the pressure-setting knob determinesthe location of the differential gap within the range ofthe pressure sensing element. Move the pointer tothe desired pressure where the output of thecontroller should switch from zero to full supplypressure with rising process pressure (direct-actingcontrollers) or with falling process pressure(reverse-acting controllers).

    Adjustment: Proportional Band

    The proportional band adjustment shown in figure 5determines the width of the differential gap. Thewidth of the gap is the difference between theprocess pressures at which the controller output willswitch from zero to full supply pressure, or from fullsupply pressure to zero. The relationship betweenthe proportional band dial setting and the differentialgap is shown in figure 11.

    Calibration: Differential Gap ControllersThe output of each controller is checked at thefactory before the unit is shipped. Before placing thecontroller in control of a process loop, check to verifythat the controller is calibrated correctly for theapplication. The controller must be connected openloop (Open loop: The controller output pressurechanges must be dead ended into a pressuregauge).

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    17

    A2202-3 / IL

    PR

    OP

    OR

    TIO

    NA

    L B

    AN

    D K

    NO

    B S

    ET

    TIN

    G

    DIFFERENTIAL GAP (PERCENT OF ELEMENT RANGE)

    Figure 11. Differential Gap Adjustment for Differential GapControllers

    1. Temporarily convert the differential gap controllerto a proportional-only controller by disconnecting theproportional tubing (key 104, figure 16) from themounting base. Reinstall the tubing into the otherconnection in the mounting base as shown infigure 16. Do not invert the reversing block (key 59,figure 16).

    2. Use the calibration procedures forproportional-only controllers.

    3. Upon completion of the calibration procedures,reinstall the tubing (key 104) in its original location,and continue with the following procedures.

    Note

    After reinstalling the tubing (key 104)in step 3 a slight offset of the outputpressure will be noticed due toswitching from the proportionalbellows to the reset bellows. This isbecause the effective area and springrate of the two bellows may not match.Performing step 5b below adjusts forthis offset.

    4. Refer to figure 11 to determine the proportionalband dial setting required for the desired differentialgap.

    For example, assume that a 0 to 100 psig sensingelement is being used and the controller is to switchfrom zero to full supply pressure at a processpressure of 80 psig with rising process pressure andfrom full supply pressure to zero at 20 psig with

    falling pressure. (This is for a direct-actingcontroller.) The differential gap is:

    5.5 bar 1.3 bar6.9 bar

    100 60%

    80 psig 20 psig100 psig

    100 60%( )From figure 11, the proportional band dial settingshould be approximately 4.5; rotate the proportionalband knob to 4.5.

    5. Setting the process pressure

    For a Direct-Acting Controller:

    a. Rotate the pressure-setting knob to thepressure at which the controller output is toswitch to the upper switching point (zero to fullsupply pressure) with rising process pressure. Inthe above example, this pressure is 5.5 bar (80psig).

    b. Increase pressure to the sensing elementwhile monitoring the output pressure gauge. Thecontroller output pressure should switch fromzero to full supply pressure when the upperswitching point is reached with rising inputpressure.

    Note

    If the upper switching point is notcorrect, adjust the nozzle to correctthe error. Repeat step 5b until theinput pressure and upper switchingpoint are at the desired setting.

    c. With falling input pressure, the output shouldswitch from full supply pressure back to zerowhen the lower switching point is reached.

    Reverse-acting controllers produce the oppositeresponse.

    6. Vary the process pressure and observe theswitching points. Widen or narrow the differentialgap by rotating the proportional band knob, thenrepeat the above steps.

    If the output is within the limits stated, refer to thestartup procedures in this section. If the outputpressure cannot be adjusted within the limits stated,refer to the maintenance procedures.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    18

    PRESSURE SETTINGDIAL (KEY 38)

    ADJUSTER SCREWS (KEY 43)

    CALIBRATION ADJUSTER (KEY 41)

    FLAPPER (KEY 45)

    NOZZLE (KEY 57)

    SPANADJUSTMENT KNOB

    ZERO ADJUSTMENT KNOB(KEY 36)

    48B6004-BA6039-3 / IL

    Figure 12. Transmitter Adjustment Locations

    Startup: Differential Gap ControllersCalibrate the controller prior to this procedure.

    1. Be sure that the supply pressure regulator isdelivering the proper supply pressure to thecontroller.

    2. Adjust the proportional band knob for the properdifferential gap (see figure 11).

    3. If the controller is used in conjunction with acontrol valve, slowly open the upstream anddownstream manual shutoff valves, and close thebypass valves.

    4. To change the differential gap, perform steps 1through 4 of the calibration for differential gapcontrollers procedure.

    Transmitter OperationThis section describes the adjustments andprocedures for calibration and startup. Refer tofigure 12 for the adjustment locations. Alladjustments must be made with the cover open.

    When the adjustments and calibration proceduresare complete, close and latch the cover.

    To better understand the adjustments and overalloperation of the transmitter, refer to the Principle ofOperation section in this manual for transmitters.Refer also to the schematic diagram in figure 14.

    Adjustments

    Adjustment: ZeroThe pressure-setting dial is marked ZEROADJUSTMENT PRESSURE SETTING. Zero is in thecenter of the dial, and the pressure values increaseto the right and left of the center as shown in figure12. To set the zero, rotate the pointer around thepressure setting dial. Rotate the pointer clockwise toincrease or counterclockwise to decrease the outputdepending on transmitter action and desired setting.

    For direct-acting transmitters, zero adjustmentdetermines the process pressure at which thetransmitter output signal will be at its lower rangelimit.

    The dial (key 38) graduations are approximateindications of the transmitter zero setting. Whenmaking adjustments, do not rely solely on the dial

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    19

    setting. Monitor the process pressure and outputpressure to be sure the desired settings are attained.

    Adjustment: SpanThe span adjustment dial is graduated from 0 to 10.A setting of 10 on the dial represents a span settingof 100 percent of the process sensing elementrange. The transmitter achieves the highestaccuracy when the span is 100 percent.

    The transmitter span adjustment shown in figure 12is the same as the controller proportional bandadjustment.

    Calibration: TransmittersThe output of each transmitter is checked at thefactory before the unit is shipped. The transmitterprovides an output signal that is proportional to thepressure applied to the sensing element. The outputpressure has no direct effect on the processpressure.

    The transmitter is calibrated at the factory andshould not need additional adjustment. Use thefollowing calibration procedures when the sensingelement has been changed or other maintenanceprocedures have altered the calibration of thetransmitter. The following procedures use a 0.1 to1.0 bar (3 to 15 psig) output pressure range as anexample. For other output pressure ranges [such as0.2 to 2.0 bar (6 to 30 psig)] adjust the values tomatch the application.

    Provide a process pressure source capable ofsimulating the process pressure range of thetransmitter. If an output pressure gauge is notprovided, install a suitable pressure gauge forcalibration purposes(1). Connect a pressure sourceto the supply pressure regulator and be sure theregulator is delivering the correct supply pressure tothe transmitter.

    Unless otherwise indicated, key number locationsare shown in figure 12.

    1. Complete the above connections and provide aprocess pressure equal to the sensing elementrange.

    2. Rotate the span adjustment knob to 10 on thedial (100 percent span).

    3. Verify that the calibration adjuster screws (key 43) are at mid-position in the calibrationadjuster (key 41) slots.

    Depending upon the transmitter action, perform oneor the other of the following procedures.

    For direct-acting transmitters:

    4. Rotate the zero adjustment knob to zero.

    5. Set the input pressure to zero.

    6. Adjust the nozzle (key 57) until the transmitteroutput pressure is at 0.1 bar (3 psig).

    7. Apply an input pressure equal to the sensingelement upper range value.

    Note

    Proper transmitter response dependson nozzle-to-flapper alignment.

    When performing the span adjustmentin step 8, carefully loosen bothcalibration adjuster screws whileholding the calibration adjuster inplace. Then move the calibrationadjuster slightly in the requireddirection by hand or using ascrewdriver. Verify propernozzle-to-flapper alignment and holdthe calibration adjuster in place whiletightening both adjustment screws.

    8. If the output pressure is not 15 psig, adjust thespan by loosening the two adjusting screws (key 43)and moving the calibration adjuster (key 41) a smalldistance as indicated in figure 13.

    9. Repeat steps 4 through 8 until no furtheradjustment is necessary.

    10. Proceed to the startup procedure fortransmitters.

    For reverse-acting transmitters:

    4. Rotate the zero adjustment knob to zero.

    5. Apply an input pressure equal to the sensingelement upper range limit.

    6. Adjust the nozzle (key 57) until the transmitteroutput pressure is at 0.1 bar (3 psig).

    7. Set the input pressure equal to zero.

    Note

    Proper transmitter response dependson nozzle-to-flapper alignment.

    When performing the span adjustmentin step 8, carefully loosen bothcalibration adjuster screws while

    1. For stability, some transmitter applications will require additional volume than just thegauge. Provide a minimum volume of approximately 25 cm3 (1.5 in3) or greater if stabilityis a problem.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    20

    IF OUTPUT IS:

    MOVE ADJUSTERLEFT

    MOVE ADJUSTERRIGHT

    NOTE:3 TO 15 PSIG (0.1 TO 1.0 BAR) OUTPUT SHOWN.FOR 6 TO 30 PSIG (0.2 TO 2.0 BAR) OUTPUT, ADJUSTVALUES AS APPROPRIATE.A6156 / IL

    ABOVE15 PSIG(1.0 BAR)

    BELOW15 PSIG(1.0 BAR)

    Figure 13. Transmitter Span Adjustment

    holding the calibration adjuster inplace. Then move the calibrationadjuster slightly in the requireddirection by hand or using ascrewdriver. Verify propernozzle-to-flapper alignment and holdthe calibration adjuster in place whiletightening both adjustment screws.

    8. If the output pressure is not 15 psig, adjust thespan by loosening the two adjusting screws (key 43)and moving the calibration adjuster (key 41) a smalldistance as indicated in figure 13.

    9. Repeat steps 4 through 8 until no furtheradjustment is necessary.

    10. Proceed to the startup procedure fortransmitters.

    Startup: Transmitters1. Be sure that the supply pressure regulator isdelivering the proper supply pressure to thetransmitter.

    2. Refer to the calibration procedures for thetransmitter initial settings.

    3. If the transmitter is used in conjunction with acontrol valve, slowly open the upstream and

    downstream manual shutoff valves, and close thebypass valves.

    Principle of OperationThe following sections describe the operation of acontroller or transmitter using a Bourdon tubesensing element. The operation is the same for aninstrument using a bellows sensing element (key 71,figure 21) except that movement of the beam iscaused by expansion or contraction of the bellows ordifferential bellows.

    Proportional-Only ControllersAs shown in figure 14, supply pressure enters therelay and bleeds through the fixed orifice beforeescaping through the nozzle. Nozzle pressure alsoregisters on the large relay diaphragm, and loadingpressure (controller output pressure) registers on thesmall relay diaphragm.

    A change in the process pressure moves the beamand flapper with respect to the nozzle by eitherexpanding or contracting the Bourdon tube arc. Anincreasing process pressure with direct action (ordecreasing pressure with reverse action) produces anozzle-flapper restriction that increases the loadingon the large relay diaphragm and opens the relayvalve. Additional supply pressure flows through therelay chamber to increase the loading pressure onthe control valve actuator. A decreasing processpressure with direct action (or increasing pressurewith reverse action) produces a nozzle-flapperopening that bleeds off pressure on the large relaydiaphragm and opens the relay valve to exhaustcontroller output pressure from the actuator.

    This controller output pressure change feeds back tothe proportional bellows, countering the pressurechange in the nozzle and equalizes the relaydiaphragm pressure differential. The relay valvemaintains a new loading pressure according to thechange in sensed pressure.

    If the proportional valve is wide open, all of thecontroller output pressure change feeds back to theproportional bellows. The more the proportionalvalve is closed, the more the controller outputpressure change bleeds out through the proportionalvalve exhaust and the less there is to feed back tothe proportional bellows. A fully open proportionalvalve results in a proportional band of 100 percent;closing the proportional valve reduces theproportional band.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    21

    CONSTANT SUPPLY PRESSURE

    EXHAUST

    EXHAUST END OF RELAY VALVE

    BOURDON TUBE

    FIXEDPIVOT

    BEAM ANDFLAPPER

    NOZZLE

    VENT

    INLET END OFRELAY VALVESMALL DIAPHRAGM

    LARGE DIAPHRAGM

    FIXED ORIFICE

    PROPORTIONAL BELLOWSPIVOTING CROSS SPRINGS

    RESET BELLOWS

    RESETVALVE

    PROPORTIONAL VALVEPROPORTIONAL VALVE

    EXHAUST

    SENSEDPRESSURE

    LOADINGPRESSURE

    NOZZLEPRESSURE

    PROPORTIONALPRESSURE

    RESETPRESSURE

    PROPORTIONAL-PLUS-RESET

    CONTROLLERPROPORTIONAL-ONLY CONTROLLER

    28A2970-A28A2971-AB1561-3 / IL

    Figure 14. Schematic of Direct-Acting Proportional-Only and Proportional-Plus-Reset Controllers

    Proportional-Plus-Reset ControllersAction of a proportional-plus-reset controller issimilar to that of a proportional-only controller exceptthat feedback from the controller output pressure ispiped to a reset bellows as well as to theproportional bellows as shown at the right in figure14.

    With an increasing controller output pressure,pressure in the reset bellows increases. Increases inreset bellows pressure moves the beam and flappercloser to the nozzle, starting another increase ofpressure throughout the system. Pressure buildupcontinues until the controlled pressure is broughtback to the set point. The reset valve is adjustable tovary the amount of delay in the reset action. Closingthe reset valve increases the delay in reset action.

    Controllers with Anti-Reset WindupDuring a prolonged difference between set point andthe controlled variable, such as encountered withintermittent control applications (e.g., batchtemperature control or wide open monitors onpressure control), reset ramps the controller outputto either zero or full supply pressure; this condition isreset windup. When the controlled variable crossesthe set point, there will be a delay before thecontroller output responds to the change in

    controlled variable. Anti-reset windup minimizes thisdelay and permits returning the controlled variable toset point more quickly with minimal overshoot.

    As shown in figure 15 a proportional-plus-resetcontroller with anti-reset windup includes adifferential relief valve. The valve consists of twopressure chambers separated by a spring-loadeddiaphragm.

    For the controller shown in figure 15, proportionalpressure registers rapidly on the spring side of therelief valve diaphragm as well as in the proportionalbellows, and reset pressure registers on theopposite side of the relief valve diaphragm. As longas controlled pressure changes are slow enough fornormal proportional and reset action, the relief valvespring will keep the relief valve diaphragm fromopening. However, a large or rapid decrease incontroller pressure will cause the relay to exhaustloading pressure from the control device rapidly, andalso from the proportional system and spring side ofthe relief diaphragm. If this decrease on the springside of the diaphragm is greater than the relief valvespring setting, the diaphragm will move off the reliefvalve orifice and permit the proportional pressure onthe opposite side of the relief valve diaphragm tobleed rapidly into the reset bellows. The anti-resetwindup action also can be reversed to relieve withan increasing proportional pressure.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    22

    CONSTANT SUPPLYPRESSURE

    TO FINALCONTROLELEMENT

    EXHAUST

    RESETBELLOWS

    ADJUSTINGSCREW

    ORIFICE RELIEF VALVEDIAPHRAGM

    WITH ARROW DOWN-RELIEVES ONDECREASING OUTPUT(OUTPUT AT SUPPLY DURING SHUTDOWN)

    SENSEDPRESSURE

    PROPORTIONALBELLOWS

    RESETVALVE

    LOADINGPRESSURE

    NOZZLEPRESSURE

    PROPORTIONALPRESSURE

    RESETPRESSURE

    38B6006-CB1562-5 / IL

    SENSEDPRESSURE

    RELIEF VALVESPRING

    PROPORTIONAL VALVE

    Figure 15. Schematic of Reverse-Acting Proportional-Plus-Reset Controller with Anti-Reset Windup

    Differential Gap ControllersWith a differential gap controller, feedback pressuredoes not counteract the change in flapper positionas it does in a proportional-only controller. Instead,feedback pressure is piped through the proportionalvalve to the bellows located on the side of the beamand flapper opposite the nozzle (the lower bellows infigure 14 for direct-acting controllers). Then, ascontroller output pressure increases, feedbackpressure moves the flapper closer to the nozzle toagain increase controller output pressure. Thisprocess continues rapidly until the controller outputpressure is at the upper range limit. The action of adifferential gap controller is so rapid that outputpressure changes from zero to maximum as soon asthe switching point is reached. The action is similarwith falling output pressure. Lower feedbackpressure lowers the bellows pressure, which movesthe flapper away from the nozzle. This againreduces the output pressure and continues until theoutput pressure is zero.

    TransmittersAction of a pneumatic transmitter is similar to that ofa proportional-only controller. Since the outputpressure of the transmitter has no effect on theprocess pressure, transmitter output pressure is aproportional measure of the process pressure. Theproportional valve determines the span of thetransmitter, and the pressure setting mechanismdetermines the zero of the transmitter.

    MaintenanceIf the installation includes a 67 Series filter regulator,periodically open the drain on the filter regulator todrain accumulated moisture. Also, push the cleanerwire on the relay orifice (key 88, not shown). Checkthe opening of the vent assembly (key 15, figure 3)or the opening of the remote vent pipe, if one isused. If necessary, clean the openings.

    Parts are subject to normal wear and must beinspected and replaced as necessary. Thefrequency of inspection and parts replacementdepends upon the severity of the service conditions.

    WARNING

    The following maintenance proceduresrequire taking the controller out ofservice. To avoid personal injury andproperty damage caused by therelease of pressure or process fluid,observe the following before startingmaintenance:

    Always wear protective clothing,gloves, and eyewear.

    Provide some temporary meansof control for the process beforetaking the controller out of service.

    Provide a means of containing theprocess fluid before removing anymeasurement devices from theprocess.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    23

    Use lock-out procedures to besure that the above measures stay ineffect while you work on theequipment.

    Personal injury or propertydamage may result from fire orexplosion if natural gas is used as thesupply medium and preventativemeasures are not taken. Preventativemeasures may include: Remoteventing of the unit, re-evaluating thehazardous area classification,ensuring adequate ventilation, and theremoval of any nearby ignitionsources. For information on remoteventing of this controller/transmitter,refer to page 9.

    Check with your process or safetyengineer for any additional measuresthat must be taken to protect againstprocess media.

    Replacing Gauges

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    Refer to figures 18 and 19 for key number locationsunless otherwise directed.

    Three gauge configurations are available for 4150Kand 4160K units.

    Output and supply pressure indications

    Output and process pressure indications

    Output, process, and supply pressureindications

    One gauge type (key 13) is used for both output andsupply pressure indications when the gauges areinstalled inside the controller case. Key 13 features a1/8-inch connecting stem that matches the threadedgauge boss extending from the relay base.

    In some cases, a process pressure gauge (key 106)covers the position of the internal supply pressuregauge. The supply pressure gauge has beenremoved and replaced with a pipe plug (key 108).

    The pressure control block (key 8) is different toaccommodate a different control tubing assembly(key 132) with a pressure connection (key 107) for aprocess pressure gauge. If a supply pressure gaugeis required, a gauge with a 1/4-inch connecting stem(key 14) must be mounted on the supply pressureregulator.

    CAUTION

    Before performing this procedure, besure the replacement gauges are thecorrect range so they are not damagedby overpressure.

    Note

    Key 13 is used as both a supply gaugeand an output gauge on units withouta process pressure gauge. A quantityof 2 is required for these units. Onunits with a process pressure gauge(key 106), key 13 is used for the outputgauge. A quantity of 1 is required forthese units.

    Use key 14 for supply pressureindication when a process pressuregauge is installed. Key 14 installs onthe supply pressure regulator.

    1. Shut off the supply pressure and process lines tothe controller or transmitter.

    2. Remove the gauge to be replaced:

    Unscrew the output or supply gauge (key 13)from the relay base.

    Unscrew the process pressure gauge (key 106)from the process connection (key 107).

    Unscrew the supply gauge (key 14) from thesupply pressure regulator.

    3. Coat the threads of the replacement gauge with asealant.

    4. Screw the replacement gauge into the relay base,process connection, or supply pressure regulator.

    5. Check for leaks by applying the correct supplypressure with the nozzle capped to produce fulloutput pressure.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    24

    Replacing Bourdon Tube

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    Refer to figure 20 for key number locations unlessotherwise directed.

    1. Shut off the supply pressure and process lines tothe controller or transmitter.

    2. Unscrew the machine screw (key 63) todisconnect the link (key 64) and bearing (key 65)from the beam (key 44). Be careful to avoid losingthe bearing (key 65). Washer(s) (key 370) for themachine screw (key 63) are at times furnished forinsertion at the beam (key 44) connection to ensurealignment of the connecting link (key 64).

    3. Disconnect the control tubing (key 132). Unscrewtwo screws (key 77) and washers (key 76), andremove the Bourdon tube (key 62).

    4. Unscrew the machine screw (key 63), andremove the link and bearing (keys 64 and 65) fromthe Bourdon tube. Be careful to avoid losing thebearing (key 65).

    5. Attach the link and bearing to the replacementBourdon tube.

    6. Attach the Bourdon tube with two machinescrews and washers (keys 77 and 76).

    7. Connect the link and bearing to the beam(key 44).

    8. After connecting the link to the beam, make surethe nozzle is centered in the slot in the beam. If not,carefully loosen the machine screw (key 63) enoughso that you can slip a washer (key 370) between thebearing (key 65) and beam (key 44). Retighten themachine screw and check the nozzle and beamalignment.

    9. Check to be sure that the beam is parallel withthe bottom of the case and that the link (key 64) is intension. If the beam is not parallel with the case,loosen the machine screws (key 77), reposition theBourdon tube to get the beam parallel, and retightenthe screws.

    10. If a Bourdon tube with a different range wasinstalled, remove the machine screw and washer(keys 40 and 39) and dial (key 38). Install a new dialhaving an adjustment range corresponding to therange of the Bourdon tube. If an optional processpressure gauge (key 106, figure 18) is being used,

    install a new gauge with the appropriatemeasurement capability.

    11. Check all tubing connections for leaks and theBourdon tube machine screws, tighten asnecessary. Perform the appropriate calibrationprocedures.

    Replacing Bellows Sensing Element

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    Refer to figure 21 for key number locations unlessotherwise directed.

    1. Shut off the supply pressure and process lines tothe controller or transmitter.

    2. Disconnect the tubing from the mounting base(key 30) and calibration adjuster (key 41).Disconnect the tubing that connects the pressureblock (key 8, figure 18) to the bellows assembly (key 71), at the pressure block end.

    3. Unscrew the four machine screws (key 28, figure 18 or 19), and remove the pressure sensingsubassembly from the case.

    4. Remove the bellows yoke machine screws andwashers (keys 75 and 76), and move the bellowsyoke to the right to permit access to the link screw.

    5. Disconnect the link (key 71M) and bearing (key 71L) from the beam. Be careful to avoid losingthe bearing.

    6. Loosen the nuts that secure the bellowsassembly (key 71), and remove this assembly fromthe bellows yoke (key 70).

    7. For a gauge-pressure sensing element (only onebellows in the assembly), install the proper bellowsspring (key 80) into the bellows assembly if the inputsignal range is being changed. See the parts list forthe correct part number.

    8. Install the new bellows assembly into the bellowsyoke.

    9. Attach the link and bearing to the bellowsassembly. Position the bellows yoke (key 70) on themounting base (key 30), and attach the link andbearing to the beam. Start but do not tighten the fourmachine screws (key 75) with washers (key 76) thatattach the yoke to the mounting base. Slide the yokeup or down as necessary to position the beamhorizontally, as shown in figure 21. Tighten themachine screws.

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    25

    PROPORTIONALTUBING (KEY 104)

    RELAY TUBING (KEY 103)

    REVERSINGBLOCK (KEY 59)

    DIRECTACTING POSITION

    BEAM (KEY 44)BELLOWS(KEY 52)

    REVERSEACTING POSITION

    REVERSINGBLOCK (KEY 59)

    PROPORTIONAL TUBING(KEY 104)

    REVERSEPOSITION

    RESET VALVE

    RELAY TUBING(KEY 103)

    REVERSINGBLOCK (KEY 59)

    DIRECTACTING POSITION

    BEAM (KEY 44)

    PROPORTIONALTUBING(KEY 104)

    RESET TUBING(KEY 117)

    REVERSE ACTINGPOSITION

    REVERSINGBLOCK (KEY 59)

    PROPORTIONALTUBING

    RESETTUBING

    NOTES:P = PROPORTIONAL BELLOWSR = RESET BELLOWSX = NO PRESSURE

    DIRECT ACTING REVERSE ACTING

    DIRECT ACTING REVERSE ACTING

    PROPORTIONAL-ONLY CONTROLLER OR TRANSMITTER

    PROPORTIONAL-PLUS-RESET CONTROLLERB1564-5 / IL10C2008-B

    FLAPPER/SCREW(KEY 45)

    FLAPPER/SCREW(KEY45)

    FLAPPER/SCREW(KEY 45) FLAPPER/SCREW

    (KEY 45)

    Figure 16. Direct/Reverse Acting Tubing Connections

    10. Replace the subassembly in the case andsecure with the four machine screws (key 28,figure 18 or 19). Reconnect all tubing.

    11. If a bellows assembly with a different range isinstalled, remove the machine screws and washer(keys 40 and 39) and dial (key 38), and install a newdial having an adjustment range corresponding tothe range of the bellows. If an optional processpressure gauge (key 106, figure 18) is being used,install a new gauge with the appropriatemeasurement capability.

    12. Check all tubing connections for leaks and thebellows yoke machine screws, tighten as necessary.Perform the appropriate calibration procedures.

    Changing Proportional or Reset Valve

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    1. Disconnect the appropriate tubing and removethe proportional band valve assembly (figure 18or 19) or the reset restriction valve assembly(figure 19) by unscrewing it from the relay base(key 4, figure 18 or 19). Install the desiredreplacement assembly.

    2. Connect the tubing, check all connections forleaks and perform the appropriate calibrationprocedures.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    26

    PROPORTIONALTUBING (KEY 104)

    REVERSE ACTINGPOSITION

    REVERSINGBLOCK (KEY 59)

    REVERSEPOSITION

    DIRECT ACTING REVERSE ACTING

    NOTES:P = PROPORTIONAL BELLOWSX = NO PRESSURE

    DIFFERENTIAL GAP CONTROLLERB2671 / IL10C2008-B

    FLAPPER/SCREW(KEY45)

    RELAY TUBING (KEY 103)

    REVERSINGBLOCK (KEY 59)

    DIRECTACTING POSITION

    BEAM (KEY 44)

    FLAPPER/SCREW(KEY 45)

    Figure 16. Direct/Reverse Acting Tubing Connections (Continued)

    Changing Anti-Reset WindupDifferential Relief Valve (4160KF)

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    Refer to figure 19 for key number locations.

    1. Note the controller output pressure (zero orsupply) when the process is shut down.

    2. Remove the differential relief valve assembly.

    3. Refer to figure 19. Install the replacement reliefvalve with the arrow positioned so that the controlleroutput will be as noted in step 1 when the process isshut down.

    Changing Action

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    Proportional-Only to a Differential GapControllerA proportional-only controller may be changed to adifferential gap controller, or vice versa, by changingthe position of the proportional tubing (key 104,figure 16). Refer to figure 16 for key numberlocations.

    1. Isolate the controller from process, control, andsupply pressure. Vent any trapped pressure from thecontroller before proceeding with the following steps.

    2. Disconnect the proportional tubing (key 104) fromthe mounting base (key 30, figure 20 or 21) andreinstall it in the other connection in the mountingbase.

    3. Do not invert the reversing block unless alsochanging the controller action.

    4. Check all connections for leaks with asoap-and-water solution. Perform the appropriatecalibration procedure.

    Direct to Reverse ActionUse the numbered steps below to change fromdirect action (increasing pressure producesincreasing output pressure) to reverse action(increasing pressure produces decreasing outputpressure), or vice versa. Changing the action isaccomplished by reversing the positions of thereversing block and bellows tubing(s). Refer to figure16 for key number locations unless otherwisedirected.

    1. Isolate the controller or transmitter from process,control, and supply pressure. Vent any trappedpressure from the controller or transmitter beforeproceeding with the following steps.

    2. Locate the new tubing and reversing blockpositions for the action desired.

    3. Locate the two bellows and the reversing block(key 59, figure 16).

    4. Disconnect the tubing:

    a. For a proportional-only controller or for atransmitter, disconnect the proportional tubing

  • 4150K and 4160K Controllers and TransmittersInstruction ManualForm 5177March 2006

    27

    (key 104) from the mounting base (key 30, figure20 or 21) and reconnect it in the opposite hole.

    b. For a proportional-plus-reset controller,disconnect the proportional tubing (key 104) andreset tubing (key 117) from the mounting base(key 30, figure 20 or 21), and reconnect them inthe opposite hole.

    5. Change the reversing block assembly (key 59):

    a. Remove the sealing screw (key 56, figure 20or 21). Inspect the O-ring (key 55, figure 20 or 21)located in the recessed area under the sealingscrew head. Replace the O-ring if necessary.

    b. Remove the reversing block screw (key 61,figure 20 or 21) and reversing block assembly(key 59). Inspect the O-rings (key 55) located inthe recessed area under the reversing blockscrew head and between the reversing blockassembly and the calibration adjuster (key 41,figure 20 or 21). Replace these O-rings, ifnecessary.

    c. Position the reversing block assembly, withO-ring, on the calibration adjuster (key 41) so thatthe nozzle is on the opposite side of the beam(key 44, figure 20 or 21) from which it wasremoved. Properly position the reversing blockassembly so that the alignment pin engages thehole in the calibration adjuster. Install thereversing block screw (key 61) with O-ring (key 55).

    d. Install the sealing screw (key 56) with O-ringin the hole previously covered by the reversingblock assembly.

    6. Check all connections for leaks with asoap-and-water solution. Perform the appropriatecalibration procedures.

    Relay Replacement

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section.

    Key numbers used in this procedure are shown infigure 18 or 19 except where indicated.

    1. Shut off the supply pressure and processpressure line(s) to the controller or transmitter.

    2. Disconnect the tubing (key 103) from the relay.

    3. Unscrew the output or supply pressure gauge(key 13).

    4. To remove the relay assembly, unscrew twoPhillips-head machine screws (key 81, not shown)located behind the relay on the back of the case.

    5. Remove the relay gasket (key 7, figure 18).

    6. A new relay can be installed as a replacement. Ifa new relay is being installed, continue with the nextstep.

    7. Attach the replacement relay and new relaygasket with machine screws inserted through theback of the case. Reinstall the output or supplygauge.

    8. Connect the tubing, and check all connections forleaks. Perform the appropriate calibrationprocedures.

    Changing Output Signal Range

    WARNING

    Refer to the WARNING at thebeginning of the Maintenance Section..

    Use the following information and subsequentprocedures when changing the output signal rangeof the controller or transmitter. Use the followingprocedure:

    For a controller or transmitter, use thisprocedure to change from a 0.2 to 1.0 bar (3 to 15psig) to a 0.4 to 2.0 bar (6 to 30 psig) output signalrange or vice versa.

    For a differential gap controller, use thisprocedure to change from a 0 and 1.0 bar (0 and 20psig) to a 0 and 2.4 bar (0 and 35 psig) output signalrange or vice versa.

    When changing the supply pressure source toa new range, refer to table 5 for supply pressurerequirements for the output signal range selected.

  • 4150K and 4160K Controllers and TransmittersInstruction Manual

    Form 5177March 2006

    28

    0-RING(KEY 55)

    A6281-1 / IL

    Figure 17. Bellows Screw Detail

    Also, make appropriate changes to the nameplate ofthe controller or transmitter, reflecting the new rangeselections. Refer to figure 20 or 21 for key numberlocations unless otherwise directed.

    1. Shut off the supply pressure and process lines tothe controller or transmitter.

    2. Disconnect the tubing from the mounting base(key 30) and calibration adjuster (key 41).Disconnect the tubing that connects the pressureblock (key 8, figure 18 or 19) to the Bourdon tube orbellows assembly (key 62 or 71), at the pressureblock end.

    3. Unscrew the machine screws (key 28, figure 18or 19), and remove the subassembly from the case.

    4. If the controller or transmitter uses a Bourdontube sensing element, disconnect the Bourdon tubefrom the beam (key 44) by removing the screw(key 63). Be careful to avoid losing the bearing (key 65). Unscrew the machine screws (key 77), andremove the washers and Bourdon tube (keys 76 and 62).

    5. Unscrew the bellows screws (key 54) from eachend of the mounting base (key 30). [Note: Thebellows screws (key 54) have an O-ring (key 55,figure 17) installed beneath the bellows screw head.Remove the O-ring and obtain a replacement whenre-assembling the bellows.]

    6. Compress the bellows so that the end of thebellows and beam can be removed from the end ofthe mounting base (key 30) and unscrewed from thestud (key 51, not shown) that connects the bellows.

    7. With the stud that connects the two bellows inplace in the spacer (key 50), screw the new bellowsonto the stud. Install new gaskets (key 53) on eachbellows.

    Note

    The bellows screw (key 54) has anO-ring (key 55) installed beneath thebellows screw head as shown in figure17. Be sure this O-ring is in placebefore installing the screw into themounting base.

    8. Compress the bellows, and install them into themounting base (key 30). With the beam parallel withthe mounting base, secure the bellows with thebellows screws (key 54).

    9. After tightening the bellows screws, make surethat the nozzle (key 57) is centered on the flapper(key 45).

    10. Replace the subassembly in the case andsecure with the machine screws (key 28, figure 18 or 19). Install the Bourdon tube if it was removed;refer to the Replacing Bourdon Tube section ifneeded. Reconnect all tubing.

    11. Unscrew the supply and output gauges (key 13,figure 18 or 19) and install new gauges with correctranges.

    12. Check all tubing connections and the bellowsmachine screws for leaks, tighten as necessary.Perform the appropriate calibration procedures.

    Parts OrderingWhenever corresponding with your EmersonProcess Management sales office about thisequipment, mention the serial number of the unit.The serial number can be found on the nameplate(key 22, figure 18). When ordering replacementparts, also state the complete 11-character partnumber of each part required as found in thefollowing parts list.

    Note

    Use only genuine Fisher replacementparts. Components that are notsupplied by Emerson ProcessManagement should not, under anycircumstances, be used in any Fisherinstrument. Use of comp