4643two way slabs1
TRANSCRIPT
-
8/9/2019 4643Two Way Slabs1
1/75
-
8/9/2019 4643Two Way Slabs1
2/75
Comparison of One-way and Two-way
slab behavior
One-way slabs carry load in
one direction.
Two-way slabs carry load intwo directions.
-
8/9/2019 4643Two Way Slabs1
3/75
-
8/9/2019 4643Two Way Slabs1
4/75
Comparison of One-way and Two-way
slab behavior
Flat slab Two-way slab with beams
-
8/9/2019 4643Two Way Slabs1
5/75
Comparison of One-way and Two-way slab
behavior
For flat plates and slabs the column connections can vary
between:
-
8/9/2019 4643Two Way Slabs1
6/75
Comparison of One-way and Two-way
slab behavior
Flat Plate Waffle slab
-
8/9/2019 4643Two Way Slabs1
7/75
Comparison of One-way and Two-way
slab behavior
The two-way ribbed slab and waffled slab system: eneral
thic!ness of the slab is " to #$cm.
-
8/9/2019 4643Two Way Slabs1
8/75
Comparison of One-way and Two-way slab
behavior %conomic Choices
Flat Plate &for relatively li'ht loads as in apartments or offices(
suitable span )."m to *.$m with ++, -"/0m1.
Advantages
+ow cost formwor!
%2posed flat ceilin's
Fast
Disadvantages +ow shear capacity
+ow Stiffness ¬able deflection(
-
8/9/2019 4643Two Way Slabs1
9/75
Comparison of One-way and Two-way slab
behavior %conomic Choices
Flat Slab &for heavy industrial loads( suitable span * to 3m with
++, "-4."/0m1.
Advantages
+ow cost formwor!
%2posed flat ceilin's
Fast Disadvantages
/eed more formwor! for capital and panels
-
8/9/2019 4643Two Way Slabs1
10/75
Comparison of One-way and Two-way slab
behavior %conomic Choices
Waffle Slab &two-way 5oist system( suitable span 4."m to #1m
with ++, )-4."/0m1.
Advantages
Carries heavy loads
6ttractive e2posed ceilin's
Fast
Disadvantages Formwor! with panels is e2pensive
-
8/9/2019 4643Two Way Slabs1
11/75
Comparison of One-way and Two-way slab
behavior %conomic Choices
One-way Slab on beams suitable span to *m with ++, -"/0m1.
Can be used for lar'er spans with relatively hi'her cost and hi'herdeflections
One-way 5oist system suitable span * to 3m with ++, )-*/0m1.
7eep ribs8 the concrete and steel 9uantities are relative low
%2pensive formwor! e2pected.
-
8/9/2019 4643Two Way Slabs1
12/75
-
8/9/2019 4643Two Way Slabs1
13/75
?ehaviour of slabs loaded to
failure p*1)-*14
-
8/9/2019 4643Two Way Slabs1
14/75
Comparison of One-way and Two-way slab
behavior
ws ,load ta!en by short direction
wl , load ta!en by lon' direction
δ6 ,
δ?
Rule of Thumb: For ?06 @ 18
desi'n as one-way slab
EI
Bw
EI
Aw
A)
"
A)
" )l)
s =
ls)
)
l
s
#*16?For ww A
B
w
w
=⇒==
-
8/9/2019 4643Two Way Slabs1
15/75
Two-Way Slab 7esi'n
Static Equilibrium of Two-Way Slabs
6nalo'y of two-way slab to plan! and beam floor
Section 6-6:
Boment per m width in plan!s
Total Boment
1
# !/-m0mA
wl m⇒ =
( )
1
#
6-6 1 !/-mA
l
M wl ⇒ =
-
8/9/2019 4643Two Way Slabs1
16/75
Two-Way Slab 7esi'n
Static Equilibrium of Two-Way Slabs
6nalo'y of two-way slab to plan! and beam floor
niform load on each beam
Boment in one beam &Sec: ?-?(1
# 1lb !/.m
1 A
wl l M
⇒ = ÷
# !/0m1
wl ⇒
-
8/9/2019 4643Two Way Slabs1
17/75
Two-Way Slab 7esi'n
Static Equilibrium of Two-Way Slabs
Total Boment in both beams
Full load was transferred east-west by the plan!s and then wastransferred north-south by the beamsD
The same is true for a two-way slab or any other floor system
where:
( )1
1# !/.m
A B B
l M wl −⇒ =
( ) ( )
1 1
# 1
6-6 1 #
!/-m8 !/.mA A B B
l l M wl M wl
−= =
-
8/9/2019 4643Two Way Slabs1
18/75
7istribution of moments in slabs
Read p631-637
-
8/9/2019 4643Two Way Slabs1
19/75
eneral 7esi'n Concepts
-
8/9/2019 4643Two Way Slabs1
20/75
eneral 7esi'n Concepts
&1( %9uivalent Frame Bethod &%FB(
6 7 buildin' is divided into a series of 17 e9uivalent
frames by cuttin' the buildin' alon' lines midway
between columns. The resultin' frames are consideredseparately in the lon'itudinal and transverse directions of
the buildin' and treated floor by floor.
+imited to slab systems to uniformly distributed loads andsupported on e9ually spaced columns. Bethod uses a set
of coefficients to determine the desi'n moment at critical
sections.
( 7irect 7esi'n Bethod &77B(
-
8/9/2019 4643Two Way Slabs1
21/75
-
8/9/2019 4643Two Way Slabs1
22/75
%9uivalent Frame Bethod &%FB(
%levation of the frame Perspective view
-
8/9/2019 4643Two Way Slabs1
23/75
-
8/9/2019 4643Two Way Slabs1
24/75
Bethods of 6nalysis
&1( Plastic 6nalysis
The yield method used to determine the limit state of slab by
considerin' the yield lines that occur in the slab as a collapse
mechanism.
The strip method 8 where slab is divided into strips and the
load on the slab is distributed in two ortho'onal directions
and the strips are analy>ed as beams.
-
8/9/2019 4643Two Way Slabs1
25/75
-
8/9/2019 4643Two Way Slabs1
26/75
Column and Biddle Strips
The slab is bro!en up
into column and
middle strips for
analysis
-
8/9/2019 4643Two Way Slabs1
27/75
-
8/9/2019 4643Two Way Slabs1
28/75
?asic Steps in Two-way Slab 7esi'n
). Calculate positive and ne'ative moments in the slab.". 7etermine distribution of moments across the width of the
slab. ?ased on 'eometry and beam stiffness.
*. 6ssi'n a portion of moment to beams8 if present.
4. 7esi'n reinforcement for moments from steps " and *. Steps-4 need to be done for both principal directions.
A. Chec! shear stren'ths at the columns
-
8/9/2019 4643Two Way Slabs1
29/75
-
8/9/2019 4643Two Way Slabs1
30/75
7efinition of ?eam-to-Slab Stiffness Eatio8 α
With width bounded laterally by centerline of ad5acent
panels on each side of the beam.
cb b cb b
cs s cs s
)% 0 %
)% 0 % f
I l I
I l I α = =
slabuncrac!edof inertiaof Boment;
beamuncrac!edof inertiaof Boment;
concreteslabof elasticityof Bodulus%concrete beamof elasticityof Bodulus%
s
b
sb
cb
=
===
-
8/9/2019 4643Two Way Slabs1
31/75
?eam and Slab Sections for calculation of α
-
8/9/2019 4643Two Way Slabs1
32/75
?eam and Slab Sections for calculation of α
-
8/9/2019 4643Two Way Slabs1
33/75
?eam and Slab Sections for calculation of α
7efinition of beam cross-section
Charts may be used to calculate α
-
8/9/2019 4643Two Way Slabs1
34/75
%2ample #-#
-
8/9/2019 4643Two Way Slabs1
35/75
Binimum Slab Thic!ness for Two-way
Construction
The 6C; Code 3.". specifies a minimum slab thic!ness to
control deflection. There are three empirical limitations for
calculatin' the slab thic!ness &h(8 which are based on
e2perimental research. ;f these limitations are not met8 it will be
necessary to compute deflection.
-
8/9/2019 4643Two Way Slabs1
36/75
Binimum Slab Thic!ness for Two-way
Construction
f $.1 1α ≤ ≤&a( For
( )
y
n
fm
$.A#)$$
* " $.1
f l
hβ α
+
÷ =+ −
f y in BPa. ?ut not less than #1."cm
-
8/9/2019 4643Two Way Slabs1
37/75
Binimum Slab Thic!ness for Two-way
Construction
fm1 α
-
8/9/2019 4643Two Way Slabs1
38/75
Binimum Slab Thic!ness for 1-way Construction
fm $.1α
-
8/9/2019 4643Two Way Slabs1
39/75
Binimum Slab Thic!ness for two-way
construction
The definitions of the terms are:
h , Binimum slab thic!ness without interior beams
ln ,Clear span in the lon' direction measured face to face
of column
β = the ratio of the lon' to short clear span
αfm,the avera'e value of α for all beams on the sides ofthe panel.
-
8/9/2019 4643Two Way Slabs1
40/75
-
8/9/2019 4643Two Way Slabs1
41/75
7irect 7esi'n Bethod for Two-way Slab
+imitations on use of 7irect 7esi'n method
. Successive span in each direction shall not differ by more
than #0 the lon'er span.
). Columns may be offset from the basic rectan'ular 'rid ofthe buildin' by up to $.# times the span parallel to the offset.
". 6ll loads must be due to 'ravity only &/06 to unbraced
laterally loaded frames8 foundation mats or pre-stressedslabs(
*. Service &unfactored( live load 1 service dead load≤
-
8/9/2019 4643Two Way Slabs1
42/75
7irect 7esi'n Bethod for Two-way Slab
4. For panels with beams between supports on all sides8 relative
stiffness of the beams in the 1 perpendicular directions.
Shall not be less than $.1 nor 'reater than ".$
+imitations 1 and 4 do not allow use of 77B for slab panels
that transmit loads as one way slabs.
+imitations on use of 7irect 7esi'n method
1# 1
1
1 #
f
f
l l
α α
-
8/9/2019 4643Two Way Slabs1
43/75
7istribution of Boments
Slab is considered to be a series of frames in two directions:
-
8/9/2019 4643Two Way Slabs1
44/75
7istribution of Boments
Total static Boment8 M o
( )-#6C;
A
1
n1u$
l l w M =
( )cn
n
1
u
$.AA*dhusin'calc.columns8circularfor
columns betweenspanclear
striptheof widthetransvers
areaunit perloadfactored
==
=
=
l
l
l
wwhere
-
8/9/2019 4643Two Way Slabs1
45/75
%2ample #.1
-
8/9/2019 4643Two Way Slabs1
46/75
Column Strips and Biddle Strips
Boments vary across width of slab panel
7esi'n moments are avera'ed over the width
of column strips over the columns middle
strips between column strips.∴
-
8/9/2019 4643Two Way Slabs1
47/75
Column Strips and
Biddle Strips
Column strips 7esi'n
width on either side of a
column centerline e9ual to
smaller of
#
1
1".$
1".$
l
l
l#, len'th of span in
direction moments are bein' determined.
l1, len'th of span
transverse to l#
-
8/9/2019 4643Two Way Slabs1
48/75
Column Strips
and Biddle
StripsBiddle strips: 7esi'n
strip bounded by two
column strips.
-
8/9/2019 4643Two Way Slabs1
49/75
-
8/9/2019 4643Two Way Slabs1
50/75
Boment 7istribution
-
8/9/2019 4643Two Way Slabs1
51/75
7istribution of B$
-
8/9/2019 4643Two Way Slabs1
52/75
Positive and /e'ative Boments in Panels
B$ is divided into G B and -B Eules 'iven in 6C; sec. #.*.
( ) A
1
n1u
$av'uu
l l w
M M M =≥−+⊕
-
8/9/2019 4643Two Way Slabs1
53/75
Transverse 7istribution of Boments
The lon'itudinal moment values mentioned are for the entire
width of the e9uivalent buildin' frame. The width of two half
column strips and two half-middle stripes of ad5acent panels.
-
8/9/2019 4643Two Way Slabs1
54/75
Transverse 7istribution of Boments
Transverse distribution of the lon'itudinal moments to middle andcolumn strips is a function of the ratio of len'th l10l#8αf#8 and bt.
torsional constant
cb b cb# t
cs s cs s
1
$.*
#
f E I E C
E I E I
x x y
C y
α β = =
= − ÷ ÷ ∑
-
8/9/2019 4643Two Way Slabs1
55/75
7istribution of B$
6C; Sec #.*..)
For spans framin' into a common support ne'ative moment
sections shall be desi'ned to resist the lar'er of the 1 interior B u=s
6C; Sec. #.*.."
%d'e beams or ed'es of slab shall be proportioned to resist in
torsion their share of e2terior ne'ative factored moments
-
8/9/2019 4643Two Way Slabs1
56/75
Factored Boment
in Column Strip
F t d B t i C l St i
-
8/9/2019 4643Two Way Slabs1
57/75
Factored Boment in Column Strip
Eatio of torsional stiffness of ed'e beam to fle2ural stiffness of
slab&width, to beam len'th(
βt
=
-
8/9/2019 4643Two Way Slabs1
58/75
Factored Boments
Factored Boments in
beams &6C; Sec.
#.*.(: resist a
percenta'e of columnstrip moment plus
moments due to loads
applied directly to
beams.
-
8/9/2019 4643Two Way Slabs1
59/75
Factored Boments
Factored Boments in Biddle strips &6C; Sec. #.*.(
The portion of the G Bu and - Bu not resisted by column
strips shall be proportionately assi'ned to correspondin' halfmiddle strips.
%ach middle strip shall be proportioned to resist the sum of
the moments assi'ned to its 1 half middle strips.
-
8/9/2019 4643Two Way Slabs1
60/75
%2ample #- and #-) pa'e *"$
-
8/9/2019 4643Two Way Slabs1
61/75
6C; Provisions for %ffects of Pattern +oads
T f f l
-
8/9/2019 4643Two Way Slabs1
62/75
Transfer of moments to columns
%2terior columns shall be desi'ned for $.Bo assumed
to be about the centroid of the shear perimeter8 and should be
divided between columns above and below the slab in proportion to
their stiffnesses.
;nterior Columns: refer to te2tboo! pa'e *"4
-
8/9/2019 4643Two Way Slabs1
63/75
Shear Stren'th of Slabs
;n two-way floor systems8 the slab must have ade9uate thic!nessto resist both bendin' moments and shear forces at critical section.
There are three cases to loo! at for shear.
#. Two-way Slabs supported on beams
1. Two-Way Slabs without beams
. Shear Eeinforcement in two-way slabs without beams.
-
8/9/2019 4643Two Way Slabs1
64/75
Shear Stren'th of Slabs
#. Two-way slabs supported on beams
The critical location is found at d distance from the column8 where
The supportin' beams are stiffand are capable of transmittin' floor loads to the columns.
( )c c 0 *V f bd φ φ =
Sh St th f Sl b
-
8/9/2019 4643Two Way Slabs1
65/75
Shear Stren'th of Slabs
There are two types of shear that need to be addressed
1. Two-Way Slabs without beams
#. One-way shear or beam shear at distance d from the column
1. Two-way or punch out shear which occurs alon' a truncated
cone.
-
8/9/2019 4643Two Way Slabs1
66/75
Shear Stren'th of Slabs
One-way shear considers critical section a distance d from the
column and the slab is considered as a wide beam spannin'
between supports.
( )ud c c 0 *V V f bd φ φ ≤ =
-
8/9/2019 4643Two Way Slabs1
67/75
Shear Stren'th of Slabs
Two-way shear fails alon' a a truncated cone or pyramid around the
column. The critical section is located d01 from the column face8
column capital8 or drop panel.
-
8/9/2019 4643Two Way Slabs1
68/75
Shear Stren'th of SlabsShear Stren'th of Slabs
;f shear reinforcement is not provided8 the shear stren'th ofconcrete is the smaller of:
#.
1.
bo , perimeter of the critical section
βc ,ratio of lon' side of column to short side
( )c c o c o
c
1$.#4 # $.V f b d f b d φ φ φ
β
= + ≤
÷
sc c o
o
$.$A 1d V f b d b
α φ φ = + ÷
αs is )$ for interior columns8 $ for ed'e columns8 and 1$ for
corner columns.
Sh St th f Sl b
-
8/9/2019 4643Two Way Slabs1
69/75
Shear Stren'th of Slabs
. Shear Eeinforcement in two-way slabs without beams.
For plates and flat slabs8 which do not meet the condition for
shear8 one can either
-;ncrease slab thic!ness
- 6dd reinforcement
Eeinforcement can be done by shearheads8 anchor bars8conventional stirrup ca'es and studded steel strips &see 6C;
##.##.).
Sh St th f Sl b
-
8/9/2019 4643Two Way Slabs1
70/75
Shear Stren'th of Slabs
Shearhead consists of steel ;-beams or channel welded into four
cross arms to be placed in slab above a column. 7oesnot apply to e2ternal columns due to lateral loads and
torsion.
Sh St th f Sl b
-
8/9/2019 4643Two Way Slabs1
71/75
Shear Stren'th of Slabs
6nchor bars consists of steel reinforcement rods or bent barreinforcement
Sh St th f Sl b
-
8/9/2019 4643Two Way Slabs1
72/75
Shear Stren'th of Slabs
Conventional stirrup ca'es
Sh St th f Sl b
-
8/9/2019 4643Two Way Slabs1
73/75
Shear Stren'th of Slabs
Studded steel strips
-
8/9/2019 4643Two Way Slabs1
74/75
Eeinforcement 7etails +oads
6fter all percenta'es of the static moments in the column and middle
strip are determined8 the steel reinforcement can be calculated for
ne'ative and positive moments in each strip.
Ba2imum Spacin' of Eeinforcement
6t points of ma2. G0- B:
Bin Eeinforcement Ee9uirements
( )
( )
1 6C; #..1
and )" 6C; 4.#1.
s t
s cm
≤
≤
( ) ( ) ( )s min s TFS from 6C; 4.#1 6C; #..# A A=
Binimum e2tension for reinforcement in
-
8/9/2019 4643Two Way Slabs1
75/75
slabs without beams&Fi'. #..A(