527 series split system 'hlr' models - · pdf fileinstallation instruction...

8
Installation Instruction 52708008-13 Page 1 of 8. 527 Series Split System 'HLR' Models HILO 527 series indoor units operate via a hard wired remote controller and are designed to operate with 550 series outdoor condensing units or 551 series heat pump outdoor units: these instructions should be used with the installation instructions for those units. An envelope containing important user information is supplied with the indoor unit. Please pass this to the end user. Indoor Unit Cabinet Removal 1. Press the filter tray at both sides to spring it and the filter out (Fig.1). 2. Remove the two outer self tap screws then release the quarter turn fasteners. 3. Pivot the cabinet forward from the bottom and lift upwards to clear the chassis top flange and remove, this will reveal the polystyrene fan scrolls which should NOT be removed. Weight (kg) HLR 380 61 HLR 460 62 HLR 540 69 4. The unit is shipped with a bracket to protect the motor during transit. Remove and discard the bracket, and fit the motor wiring plug and socket as shown. Mounting 1. It is generally easier to fit kits prior to mounting the unit and brazing the pipework. 2. Ensure that the wall or ceiling will accept the operating weight of the unit. 3. Mark off the mounting holes as Fig.2 and drill holes to suit M6 rawlbolt shields or equivalent fasteners. Allow 130mm minimum from ceiling to holes for cabinet removal on wall mounted units. Allow 150mm at the base plate (wall or ceiling mounted) to maintain design airflows. 4. If a fresh air facility is required, apertures must be prepared as shown in Fig.2. This must be suitably lined and screened on the internal wall to prevent brick dust from entering the unit, (apertures are 35mm high), filters are fitted as standard. 5. Mount the unit and secure the fixings. On ceiling mounted units two extra holes are provided for screws to prevent movement on the keyhole slots. 6. Check the unit is square and level. Use the extra self tap screws to additionally secure ceiling mounted cabinets. Fig 2 Model 'A' 'B' 'C' 'D' No. of air inlets No. of spaces HLR 380 961 921 461 250 2 1 HLR 460 1111 1071 536 300 2 1 HLR 540 1311 1271 626 240 3 2 Heronhill - for all your Marstair requirements Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Upload: hoangthien

Post on 30-Mar-2018

217 views

Category:

Documents


3 download

TRANSCRIPT

Installation Instruction 52708008-13

Page 1 of 8.

527 Series Split System 'HLR' ModelsHILO 527 series indoor units operate via a hard wired remote controller and are designed to operate with 550 seriesoutdoor condensing units or 551 series heat pump outdoor units: these instructions should be used with the installationinstructions for those units.

An envelope containing important user information is supplied with the indoor unit. Please pass this to the end user.

Indoor Unit Cabinet Removal1. Press the filter tray at both sides to spring it and the filter out (Fig.1).2. Remove the two outer self tap screws then release the quarter turn fasteners.3. Pivot the cabinet forward from the bottom and lift upwards to clear the chassis

top flange and remove, this will reveal the polystyrene fan scrolls which shouldNOT be removed.

Weight (kg)HLR 380 61HLR 460 62HLR 540 69

4. The unit is shipped with a bracket to protect the motor during transit. Remove and discard

the bracket, and fit the motor wiring plug and socket as shown.

Mounting1. It is generally easier to fit kits prior to mounting the unit and brazing the pipework.2. Ensure that the wall or ceiling will accept the operating weight of the unit.3. Mark off the mounting holes as Fig.2 and drill holes to suit M6 rawlbolt shields or equivalent fasteners.

Allow 130mm minimum from ceiling to holes for cabinet removal on wall mounted units.Allow 150mm at the base plate (wall or ceiling mounted) to maintain design airflows.

4. If a fresh air facility is required, apertures must be prepared as shown in Fig.2. This must be suitably lined andscreened on the internal wall to prevent brick dust from entering the unit, (apertures are 35mm high), filters are fittedas standard.

5. Mount the unit and secure the fixings. On ceiling mounted units two extra holes are provided for screws to preventmovement on the keyhole slots.

6. Check the unit is square and level. Use the extra self tap screws to additionally secure ceiling mounted cabinets.

Fig 2

Model 'A' 'B' 'C' 'D' No. ofair inlets

No. ofspaces

HLR 380 961 921 461 250 2 1HLR 460 1111 1071 536 300 2 1HLR 540 1311 1271 626 240 3 2

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 2 of 8.

Unit Combinations

Comfort combinations High Sensible combinations Heat Pump SystemsSystem C 380 C 460 C 540 HS 320 HS 460 HS 540 HP 320 HP 380 HP 460Indoor Unit HLR 380 HLR 460 HLR 540 HLR 380 HLR 460 HLR 540 HLR 380 HLR 460 HLR 540MCU(+) 100 130 165 90 100 130 MHPUE 90 MHPUE 100 MHPUE 130

Application1. To maximise performance, pipe runs should be kept as short as possible, avoiding sharp bends. However, individual

pipe runs to a maximum of 80m are permissible provided good refrigeration practice is followed.Published performance duties are based on 7.5m pipe runs. Correctly sized pipes for each installation, and fitting thecorrect expansion orifice (restrictor) will result in no significant loss of capacity on extended pipe runs.

a) Pipe sizes are based on:-Minimum of 3.8 m/s (750 fpm) suction gas velocity for horizontal or downflow.Minimum of 7.6 m/s (1500 fpm) suction gas velocity for upflow.Maximum of 15.2 m/s (3000 fpm) suction gas.

b) Where vertical risers exceed 3m, oil traps must be formed in the pipe. This will help ensure that oil returns tothe compressor. Typically fit an oil trap every 3m with a trap at the bottom of the riser.

2. Add 25 grams of refrigerant oil (Polyolester Oil) for every 350 grams of charge added to systems with pipe runsexceeding 25m, up to a maximum of 300 grams; preferably by slowly pumping into the suction side with the unitrunning, after charging the system.

3. The maximum pipe lengths to be used for each pipe size and outdoor unit are shown in the table below. Use of thesesizes and lengths is recommended in order to achieve optimum system performance.

MAXIMUM EQUIVALENT LENGTH OFSUCTION LINE

PIPES (m)

EXPANSIONLINES

(m)

FACTORY

CHARGE(g)

ADDITIONALREFRIGERANTREQUIRED FOR7.5M RUNS AT

NEMACONDITIONS (g)

UNIT 3/8 1/2 5/8 3/4 7/8 1-1/8 1-3/8 1/2 5/8 3/4 R407C R407CMCU(+) 90 10 25 55 80 20 80 2060 115MCU(+) 100 7.5 22 45 80 15 80 2520 145MCU(+) 130 15 30 80 12 60 80 4170 250MCU(+) 165 8 18 60 80 7.5 40 80 4540 200MHPUE 90 25 55 80 20 60 80 2260 180MHPUE 100 22 45 80 15 50 80 3380 250MHPUE 130 15 30 80 12 60 80 3410 200

Restrictors

Outdoor units are supplied with restrictors fitted; refer to the following tables for any restrictor changes; those tickeddo not require changing. Where appropriate, the alternative restrictor will be supplied in either the indoor or theoutdoor unit. A capillary is fitted to HLR units for refrigerant control during a heat pump heating cycle.

AIR CONDITIONING AT U.K.CONDITIONS

AIR CONDITIONING ATNEMA CONDITIONS

HEAT PUMP COOLING ATU.K. CONDITIONS

HEAT PUMP COOLING ATNEMA CONDITIONS

MCU+ Fitted HLR MCU+ Fitted HLR MHPUE Fitted HLR MHPUE Fitted HLR380 460 540 380 460 540 380 460 540 380 460 540

90 63 63 90 63 066 90 67 90 67 070100 68 100 68 071 71 100 68 100 68 71130 71 130 71 74 074 130 76 130 76 080165 79 165 79 083

4. In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into account.Information concerning the equivalent lengths of line fittings and bends etc. is generally available to the designengineer. The table opposite covers the fittings most likely to be encountered in this type of installation. Theequivalent lengths of all the fittings in a particular pipe run must be added together and the total added to theactual length of pipe in the run, in order to calculate its total equivalent length.

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 3 of 8.

Pipe Size (outside diameter in inches)Fitting 3/8 1/2 5/8 3/4 7/8 1-1/845° Bend 0.12 0.15 0.18 0.21 0.24 0.390° Bend R/d = 1 0.37 0.43 0.49 0.55 0.61 0.7990° Bend R/d = 2 0.24 0.27 0.30 0.37 0.43 0.52180° Bend C/d = 1 0.73 0.91 1.10 1.28 1.46 1.83180° Bend C/d = 2 0.46 0.55 0.64 0.76 0.85 1.0790° Elbow 0.67 0.85 1.04 1.25 1.46 1.89

R = Radius of bend d = Diameter of tube C = Centres of bend

Fitting losses, in equivalent straight lengths of pipe (metres).

5. Use the shortest possible route, avoiding sharp bends.6. Fully insulate both the suction and expansion lines, including the expansion device, since both lines may sweat.

Refrigeration Installation1. The refrigerant connections are terminated on the left hand side of the indoor coil and the lower front of the right

end panel on outdoor units; (indoor units are brazed connections, outdoor units are flare fittings).Units are supplied with the following pipes: (MCU+ are the same as MCU models).

HLR 380 HLR 460 HLR 540 MCU 90 MCU 100 MCU 130 MCU 165 MHPUE 90 MHPUE 100 MHPUE 130EXPANSION 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"SUCTION 5/8" 5/8" 5/8" 5/8" 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"

2. Using a tube cutter, remove sealed ends of suction and expansion pipes on the indoor unit. This will release asmall holding charge of dry nitrogen.

3. Pipe exit will normally be via knockouts in the base or cutouts in the back panel.Alternatives are:For top left hand exit, turn your pipework through 180° and exit via the gap provided in the back panel. Thecabinet will need to be locally notched as Fig. 3 - do not completely cut away as this will weaken the structure.

BOTTOM RIGHT HAND EXIT can be achieved by running pipework underneath the scroll attached to the back panel. Remove the lower grille (4 screws) for access, fit suitable lengths of insulation to the pipework and braze in. It isrecommended that the liquid and suction lines be kept to ½" and 5/8" respectively until exit, when the full pipe size canbe run. Exit is preferably made via notches to be cut to suit in the right hand side panel.

4. It is recommended that the drip tray is removed during brazing to prevent it being melted. Remove the top three screws on the front scroll, and remove drip tray and the support bracket together.

5. Connect pipework between units ensuring:a) Only refrigeration quality copper is used.b) The ends are capped on tubes and parts when not working on them to prevent moisture or dirt entering the

system.c) If pipes are brazed, use a copper phosphorous alloy containing 5% silver, ensuring that dry nitrogen is passed

through the components involved to prevent oxidation.d) The suction and expansion lines are fully insulated, including inside the cabinet of the indoor unit up to the

drip deflector. Bend pipework back to ensure it is over the drip tray; if in doubt, use non-drip tape.e) The system is leak tested and evacuated before final charging.

6. If a sight glass is fitted to aid charging it must be positioned before the expansion device on the outdoor unit.

Condensate DrainThe condensate drain connection is at the left hand end of the drain tray. A ½" O.D. plastic drain pipe is provided inthe drain tray sump for connection with non-kink plastic tubing secured with a suitable clip. Should it be necessary forthe drain pipe to go through the bottom of the unit a knockout is provided at the left hand end of the base plate.

The drain line must have a constant fall to open drain using a ''U' trap if required. Check that the water will run freelyand that there are no leaks.

Details of ceiling mounted drain and fitting of optional condensate pump are provided in the kit installationinstructions.

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 4 of 8.Discharge Grille position

The discharge grille is supplied for front down discharge. The alternatives are achieved by:

i) Remove and retain grille and blanking panel screws (12 in total).ii) Slacken but do not remove all other fixing screws.iii) Remove blanking panel.iv) Remove grille.v) Slide blanking panel into new position and fix.vi) Clip panel location bracket under return edge of blanking panel and screw down into return edge of

front panel.

REMOTE CONTROLLER (RCC 30).

The thermostat should be wired with 7 cores of double insulated cable, 0.5mm2 minimum, preferably in plastic conduitfor good appearance.

Select a position to mount the thermostat taking into account the following comments:a. The thermostat must be mounted on a flat surface within the area conditioned by the indoor unit to which it is

connected.b. Avoid draughts, heat from radiators, temperature variations from hot/cold water pipes and direct sunlight.c. Avoid corners of the room where air is likely to stagnate.d. Avoid direct air discharge from the indoor unit; in heating the air is deflected downwards; in cooling and

deadband (neither heating nor cooling) the air flows across the ceiling and down the walls.e. Avoid positions where the thermostat may be covered or obscured.f. If the room contains pillars, mount on the side of the pillar furthest away from the unit. If necessary, consider

blocking off the air discharge from the side facing the thermostat.

REMOTE CONTROLLER MOUNTING

Using a flat-bladed screwdriver in the slot at the bottom of the casing, lever off the cover.Mount the backpanel directly to a wall or onto a plinth, using the fasteners supplied.

Wire between the remote control and the 600 unit as shown, using multi-core cable.

OPERATION RETURN AIR SENSOR NEUTRAL LIVE HEAT COOL MAX MED MIN

RCC 30 B1, M N L Y11 Y21 Q3 Q2 Q1

HLR unit *97200212 N 2 7 6 3 4 5

*Optional return air sensor 97200212 can detect return air temperature at the unit rather than the controller.

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 5 of 8.

The temperature range is factory set to 17°C - 30°C: it is recommended that this is maintained, but if adjustment isneeded (eg. to save energy, a range of 21°C - 25°C might be desired) carefully prise off the rotary dial and reset thestops to suit.

Heating is possible only if the system includes a heat pump outdoor unit, or if an LPHW has been fitted.

DIP switches (bottom rear of the controller)are factory set as shown below: these are the recommended settings.

DIP switch Function ON position OFF position1 Fan control Fan control is temperature dependent in all

operating modesFan control in normal operation istemperature independent

2 Operating mode changeovervia external switch

Changeover between normal operationand energy saving mode

Changeover between normal operationand standby

3 Action of switch for externallyoperated mode changeover

Changeover activated when contact ofswitch is closed

Changeover activated when contact ofswitch is open

4 Standby Frost protection disabled Frost protection enabled5 Switching differential 1K in heating mode, 0.5K in cooling mode 4K in heating mode, 2K in cooling mode6 Dead zone in normal operation 2K 5K

= factory settings

--o--o--O--O--O--o--o--

Electrical ConnectionsSupply, control and connecting cables are fitted by the installer.Wiring should be carried out in accordance with IEE regulations, BS7671 (IEC 60364), and/or local codes.Cables must be size compatible with the recommended fuse for a given system. (see chart for fuse ratings).A double pole isolator switch should be positioned adjacent to the indoor unit.The equipment must be earthed.Systems should have the supply taken to the outdoor unit; a single phase supply (L1), is run back to the indoor unit.Power should be connected to the outdoor unit for 4 hours to allow the lubricating oil to be heated prior to compressorstart up.

Indoor Unit WiringConnections for internal wiring are made at the right hand side of the unit. The mains supply, if brought from below,should be routed to the terminal block in the unit through slots behind the fan motor.Cable grips are provided above the terminal block to give a secure installation.Note that the electrics assembly can be quickly removed if required by removing 2 screws from the evaporator flangeand springing the electrics mounting plate free of locating slots in rear of the panel. These screws and washers formthe earth connection to the air handler and must be securely re-fitted. Make sure all connections are secure and allwires are clear of any rotating parts. Interconnect as shown on pages 7 and 8.

Conversion of indoor unit for air conditioner useThe indoor unit is supplied wired for use as a HEAT PUMP.For AIR CONDITIONER MODE, remove the pink link between relay 1 terminal 14 and relay 2 terminal 22.

Outdoor Unit WiringCable entry for the outdoor unit electrics is via the right hand side of the chassis to terminal blocks.Ensure that all connections are secure and both units are earthed.

Data PlatesData plates give information on either an indoor or outdoor unit. To obtain the system details, input power andcurrents from indoor and outdoor units should be added.

Recommended Fuse SizesThe system and its supply/interconnecting wiring must be protected by fuses, preferably High Rupture Current (HRC)motor rated types (to EN60269) or miniature circuit breakers (to EN60898) or local codes having similar time lagcharacteristics, that allow starting of the compressor yet still afford close overcurrent protection under runningconditions. The ratings below are for HRC motor rated fuses:

Air ConditionersSystem HS 320 C 380 HS 380 C 460 HS 460 C 5401 Phase 25A --- 32A --- --- ---3 Phase 16 A/PH 16 A/PH 16 A/PH 20 A/PH 20 A/PH 20 A/PH

Heat PumpsSystem HP 320 HP 380 HP 4601 Phase 32A --- ---3 Phase 16 A/PH 16 A/PH 16 A/PH

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 6 of 8.EVACUATING

Connect a vacuum pump to the service ports on the outdoor unit valves and evacuate the interconnecting pipeworkand indoor unit to 1000 microns (1 Torr) or better and allow to be held for a minimum of 15 minutes.

After evacuating the indoor unit and interconnecting pipework, open the outdoor unit valves using a 5mm Allen key.The high and low side pressures should equalise within a minute.

Run the system for a few minutes to allow it to stabilize. If a manual HP cutout is fitted, ensure the reset button is depressed (in the compressor compartment, outdoor unit).

MHPUE units: if no extra refrigerant is to be added REMOVE link JP6 (in the electrics box, outdoor unit, identified bya white label), otherwise the unit will always run at full speed.

ADDING REFRIGERANT

Each outdoor unit is charged with refrigerant, as below.

MCU(+)90 MCU(+) 100 MCU(+) 130 MCU(+) 165 MHPUE 90 MHPUE 100 MHPUE 130FACTORY CHARGE (g)(sufficient for up to 7.5mruns at UK conditions)

R22 1960 2400 3970 4320 2330 3490 3520

R407C 2060 2520 4170 4540 2260 3380 3410

1. Ensure the refrigerant being added is the same refrigerant that the system was originally charged with.

2. Additional charge for all systems, including heat pumps, should be introduced with the system in the AIRCONDITIONING MODE.

3. Refrigerant should be introduced through the Schrader valve on the indoor unit, or the service port on the suctionservice valve on the outdoor unit.

4. Indoor and outdoor units should be run at maximum fan speed during charging:

Set the indoor unit to operate in cooling mode at maximum speed.

MHPUE are supplied with link JP6 fitted on the outdoor unit pcba; this is only for charging, overriding alarms andrunning the MHPUE fan at maximum speed during the charging process. (Do not forget to remove it once charging is complete: see 10)

MCU+ outdoor units are fitted with head pressure control; before charging, isolate the unit and transfer the whitewire on the head pressure control from terminal 4 to terminal 1. (Do not forget to transfer it back once charging is complete: see 10)

5. All systems with pipe runs longer than 7.5m (UK or NEMA) require added refrigerant.As a guide:- 1/2" Expansion line add 30 g/m; 5/8" Expansion line add 48 g/m.

6. Further refrigerant needs to be added if the system is to be run at NEMA conditions (27°C/19°C indoor, 35°C ambient) :-

MCU(+)90 MCU(+) 100 MCU(+) 130 MCU(+) 165 MHPUE 90 MHPUE 100 MHPUE 130Extra refrigerant requiredfor NEMA conditions (g)

R22 110 140 240 190 190 260 210R407C 115 145 250 200 180 250 200

7. Run the system for a few minutes to allow it to stabilize.

8. If a sight glass is fitted, it should be just clear of bubbles (flooded).

9. Indications of incorrect charge are:-Undercharged unit: The top few tubes of the evaporator are dry and there are (possibly) slight signs of

frosting at the inlet to the evaporator coil.Overcharged unit: The suction line 'sweats' all the way back to the compressor.

10. MHPUE units: once refrigerant has been added, REMOVE link JP6 (in the electrics box, outdoor unit, identified bya white label), otherwise the unit will always run at full speed.

MCU(+) units: once refrigerant has been added, transfer the white wire on the head pressure control back from terminal 1 to terminal 4.

11. MHPUE units: a random start delay of up to 1 minute occurs when mains is first applied. A 3 minute delay occursbetween successive compressor operations on all systems incorporating MHPUE units, or MCU(+) units fittedwith a 3 minute timer kit.

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 7 of 8.

HLR WIRING DIAGRAM

INTERCONNECTING WIRING DIAGRAMS

HLR 380 + 1 Phase MCU(+) 90 HLR 380 to 460 + 3 Phase MCU(+) 90 to 100

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807

Installation Instruction 52708008-13

Page 8 of 8.

HLR 380 + 1 Phase MHPUE 90 HLR 380 to 460 + 3 Phase MHPUE 90 to 100

HLR 460 to 540 + 3 Phase MCU(+) 130 to 165 HLR 540 + 3 Phase MHPUE 130

TEV Ltd.Armytage Road, Brighouse,West Yorkshire. HD6 1QF, UK.Tel: +44 (0) 1484 405600Fax: +44 (0) 1484 405620EmaIL: [email protected]

Heronhill - for all your Marstair requirements

Tel: 01823 665660 www.heronhill.co.uk Fax: 01823 665807