Configuration & Interfacing the DC Motor with Siemens 6RA70 Dc Drive
I] CUD Pin Configuration:
1] Connector no:X171
Pin No: 36 ( Forward/ Reverse command) ( User functions)
Pin No:37 ( Run Command ) ( Siemens Standed Pin )
Pin No:38 ( Drive Enable Signal ) ( Siemens Standed Pin )
Pin No:39 ( Jog Mode Selection ) (User Function )
Ii] Sequence of drive operation
1] E.Stop realize ON Drive enable signal ( Pin no:38)
2] Spindle run in jog mode = ON both Run command + Jog mode selection 3] Spindle run in continous mode = ON both Run command + Forward for spindle.
Pin 36 Configuration: (Forward/ Reverse command) ( User functions) If Pin 36 is high (1) it is reverse command.
If pin 36 is Low (0) it is forward Command.
Parameter no: P671 = 11 & P672 = 10
Pin 39 Configuration: ( Jog Mode Selection ) (User Function )
If Pin 39 is high (1) it is reverse command.
-
Vhs Mechatronices Services 2010
S.M
uth
am
izh
Selv
an
3
If pin 39 is Low (0) it is forward Command.
Parameter no: P401 = (Forward RPM in % )
P402 = ( Reverse RPM in % )
P456 = 10
P455 (1)= 401
P455 (2)=402
P436 (1) =230
P668 (1) = 16
Iii] OutPut Pin Configuration:
1] Pin no:14 & 15 ( RPM Meter output from drive ) Operating voltage is 0-10V
Change parameter: P750=167
2] Pin no: 48 & 54 (Alarm for Drive fault ) When drive is fault ,24V Dc voltage comes from the Pin
Change parameter: P772= 106
3] Zero speed output:Pin no:47 & 46
When the motor is in Zero speed the drive gives 24V Dc.
Change Parameter: P771 = 121
P373= 0.2% ( Speed is mentioned in this parameter )
-
Vhs Mechatronices Services 2010
S.M
uth
am
izh
Selv
an
4
Iv] DC Motor Interfacing with 6RA70 Simoreg Drive
Parameter List:
P 051 Parameter can be changed = 40
P 051 Default setting = 21
P 052 To visible all parameters = 3
P 078.001 ( 3 phase input for drive ) =
P 078.002 ( 2 phase input for field ) =
P 100 ( Armature rated current ) =
P 101 ( Armature rated voltage ) =
P 102 ( Rated field current ) =
P 104 ( Speed ) =
P 108 ( Maximum operating speed ) =
P 083 ( we are using tacho ) = 1 (If tacho is used 1, If not 0)
P 741 ( Tacho voltage at maximum speed ) =
Eg: 1000RPM/10V means
Max RPM is 3000 ,then tacho voltage will be 30.
P 082 ( Field gets ON together with line contactor ) = 1
P 081 ( Field weakening is done ) =
P 303 ( Acceleration ) =
P 304 ( Deceleration ) =
P 305 ( Initial rounding ) =
P 306 ( Final rounding ) =
-
Vhs Mechatronices Services 2010
S.M
uth
am
izh
Selv
an
5
V] After Entering the Above all Parameters & Pin configuration. Do the
below mentioned Tuning.
P051 = 25 ( Lock the motor shaft and do this tuning )
Step 1 : ON the Run command.
Step 2 : Main contactor gets ON automatic for few seconds.
Step 3 : Main contactor gets OFF automatic.
Step 4 : Now switch OFF the run command.
P 051 = 27 ( Without locking the shaft we can do this tuning )
Step 1 : ON the Run command.
Step 2 : Main contactor gets ON automatic for few seconds.
Step 3 : Main contactor gets OFF automatic.
Step 4 : Now switch OFF the run command.