DETAILED MODELING OF STATICVAR COMPENSATORS USING
THE ELECTROMAGNETIC TRANSIENTS PROGRAM (EMTP)
SangY.Lee Subroto Bhattacharya Tommy Lejonberg Adel Hammad Serge Lefebvre
Member IEEE Senior Member IEEE Non-Member Fellow IEEE Member IEEE
ABB Power Systems Inc. ABB Power Systems ABB Power Systems IREQ
Pittsburgh, Pennsylvania
Advanced Systems Technology Viisterh, Sweden Baden, Switzerland
Montreal,Canada
ABSTRACT
A detailed model of Static VAr Compensators has
been developed for digital simulation of electrical
transients. The model
is
applicable to SVC configurations
employing thyristor-switched capacitors (TSC) and
thyristor-controlled reactors (TCR). A modeling
technique based
on
EMTP data modularization isused to
represent essential parts of the SVC main circuit and
control system. To verify the model, an actual SVC
is
simulated with the EMTP and the results are compared
with the TNA-type simulator using actual SVC controls.
Keywords
Static VAr Compensator (SVC), Thyristor Switched
Capacitor (TSC), Thyristor Controlled Reactor (TCR),
Electromagnetic Transients Program (EMTP) Modeling
Techniques.
INTRODUCTION
Static VAr Compensators (SVC) installed in power
transmission systems serve in various ways to improve the
system performance. By the rapid control of their reactive
power output, the SVCs regulate system voltages, improve
transient stability, increase transmission capacity, reduce
temporary overvoltages, increase damping
of
power
oscillations, and damp subsynchronous resonances and
torsional oscillations.
Power system simulation plays an important role in
the design and analysis of SVCs. Two types of simulation
tools are currently available. The Transient Network
Analyzer (TNA) generally uses scaled models of the
network and the SVC main circuit combined with the
actual SVC control system. Digital computer programs
employ mathematical models to simulate the entire system.
The
EMTP
is
one of the most widely used programs
for simulation of electrical power system transients. The
program offers accurate representation of power system
equipments including sources, lines, transformers,
breakers, loads, arresters, thyristors, etc.
The EMTP
s
well suited for simulation of SVCs
as
demonstrated in References
[l
2,
31.
Transient Analysis
of Control Systems (TACS) allows detailed modeling of
the SVC control system so that power system and control
system transients c n be simulated simultaneously. The
EMTP data modules (EDM), which became available in
1983,
have significantly improved the EMTP usage
[4,5].
This
paper presents a detailed model of SVCs
employing thyristor-switched capacitors (TSC) and
thyristor-controlled reactors (TCR). The characteristicsof
the model are as follows:
The model is flexible enough to represent different
SVC configurations including the two most widely
used the fured capacitors and thyristor-controlled
reactors (FC/TCR), and the combined
thyristor-switched capacitors and thyristor-controlled
reactors (TSC/TCR).
The model represents anSVC control circuit based
on
the phase-locked loop (PLL) and voltage regulation
loop. The control functions are modeled with TACS.
A modeling technique based on EMTP data
modularization (EDM) has been adopted for the
model development. The model, therefore, takes the
form
of
modularized EMTP data stored in
a
EMTP
module library.
The steady-state model initialization
is
improved by
using the calculation section, an enhanced feature
added to the EDM. This feature, which was
developed with the model,
allows
the EDM to
calculate system parameters and incorporate them
into the EMTP data.
The model has been developed with the DCG/EPRI-
released version
2.0 of EMTP.
0-7803-0219-2/91/0009-0941 01.001991IEEB
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
2/12
The model has been tested using an existing SVC
design. The comparison of test results with the
transient responses obtained by TNA-type simulation
has served
as
verification of the EMTP model.
Selected test results are presented in t h i s paper.
The modeling work described in this paper is part of
the development efforts conducted by the Advanced
Systems Technology Division of
ABB
Power Systems as a
participant in the
EMTP
Development Coordination
Group (DCG). These development efforts are jointly
coordinated by DCG and the Electric Power Research
Institute (EPRI).
reactor (TSC/TCR) .
The SVC control system is an integral part of the
power network. Providmg firing signals to the SVC
thyristors allows the system to interact with the power
network over a wide frequency range. An objective for the
detailed SVC model development is to produce a control
system representation which
is
valid over a frequency band
from a few Hertz up to a few
kHz.
The heart of the SVC
control system is the two feed-back control loops: the
phase-locked loop (PLL) and the voltage regulator loop.
2.
Essential Model Elements
The major elements of the SVC main circuit are: the
step-down transformer, the TCR unit, the TSC Unit, and
the harmonic filters. These are modeled with EMTP
branch and switch
cards.
Thyristor valves are represented
by TACS controlled switches. Essential control circuits
are: the phase-locked loop (PLL), the voltage regulator,
the measurement circuit, the allocator, the linearizer, and
the TCR and TSC firing circuits.
a. Thyristor controlled reactor (TCR)
A three-phase TCR unit is formed by three
delta-connected single-phase branches. Each branch has
a pair of anti-parallel thyristor valves connected in series
between
two
reactor units. Each thyristor valve is
modeled by a type-11 TACS controlled switch. The
FC/TCR
TSC/TCR
capacitor/thyristor controlled
reactor (FC/TCR) and
(TSC/TCR)
switched
The TCR is usually connected to the trammission system
1 Fixed
~pacitor/th~istor controued
thyristors in the three-phase TCR unit are controlled as a
&pulse group by gate signals from a TCR firing circuit.
through a step-down transformer.
VC configurations
b.
Thyristor
switched
capacitor (TSC)
STATIC VAr COMPENSATOR (SVC)
MODEL
1.
s v c c o fieurations
SVCs consist of thyristor and mechanically switched
shunt devices which generate or absorb reactive power.
The SVC model takes intd account three
t y p e s
of shunt
devices: the thyristor-codtrolled reactor (TCR), the
thyristor-switched capacitor (TSC), and the
fixed
or
mechanically switched capacitor (FC) bank or harmonic
filter. A TCR c n change its reactive power output
continuously.
A
TSC provides step MVAr changes.
Properly combining these shunt devices, an SVC can
control its reactive power output continuously over a wide
range from inductive to capacitive. Figure
1
depicts the
most widely used combinations: the fured capacitor and
thyristor-controlled eactor (FC/TCR)
,
nd the combined
thyristor-switched capacitors and thyristor-controlled
A three-phase TSC unit consists of three branches in
delta connection. Each TSC branch has a pair of anti-
parallel thyristor valves connected in series with a
capacitor bank and a tuning and/or current limiting
reactor. The thyristor valves switch the capacitor banks
either fully on or fully off. A TSC firing circuit controls
the TSC unit. The model allows connection of a number
of
TSC units in parallel to achieve a multiple-step control
of capacitive MVAr.
c. Harmonic
filters
Two
ypes of harmonic filters are included in the SVC
model: the single-tuned band-pass type and the high-pass
type damped filters.
A
three-phase filter unit consists of
three identical filter branches in a wye-connection with the
neutral floating. The neutral can be grounded through an
942
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
3/12
impedance branch if desired. Electrical characteristics of
these fdters are well
known
[6].
UPPER UMK
Figure 2 shows the fdter configurations.
Pl REGULATOR
I
ACBUSA ACBUSB ACBUSC
=
I
f
ACBUSN
ACBUSA ACBUSB ACBUSC
ACBUSN
Figure
2.
SVC fdter configurations
PHCOMPA - PHASE COUPMATOR.
BCOUNTER - FREQUENCY DIVIDER.
PlREG -
PROPORTIOW
INTEGRAL REGULATOR.
EASE
WEOUENCY
FRZPLl
PLlATC
NORMI
PHCOMPA
PLlAPC
PLlANc DEWATION
BCOUNTER
phase-locked loop consists of four functional blocks: a
phase comparator, a regulator, a voltage controlled
oscillator (VCO), and a frequency divider.
Figure 3 shows the block diagram of the PLL circuit
with a proportional-integral (PI) type regulator,
e. Voltage
regulator
The voltage regulator performs the closed loop voltage
control. The difference between the voltage reference
(UREF) and the network voltage response (URESP)
is
fed as the control error signal to a PI-regulator which
changes the totalSVC usceptance reference (BREF). The
input AUREF
is
provided for interface with higher-level
controlblocks.
Figure 4 shows the block diagram of the voltage
regulator.
: :-
BREF
LOWER
UMlT
Figure
4.
The SVC voltage regulator
Figure3. The phase-locked loop control
f. Allocator
d. Phase-locked-loop
The phase-locked loop
(PLL)
produces an output
pulse train
in
response to an input ac voltage signal,
reducing the phase error between the two signals by the
negative feed-back control. When the two signals have the
same frequency and phase, the control system
is
said to
be
phase-locked. When this happens, the output pulseswill
come exactly at the peaks of the sinusoidal input voltage.
The output signal of the
PLL
s
used
as
the reference
for the TCR and TSC thyristor valve firing angles. The
The allocator converts the susceptance reference
(BREF) signal from the voltage regulator to logicalorders
(on/off signals) for the TSCs and arithmetic orders for the
TCRs. The module outputs two quantities: the
number
of
TSC
units
required to
be on
(NOTSCS) and the
susceptance order for the TCRs (BTCR). The two output
signals are piece-wise functions
of
BREF.
Since
the range
of BTCR isnormally greater than the susceptanceofeach
TSC, there is a hysterisis between BREF and the two
outputs.
In
the hysterisii region, there are two output
states causing the same MVAr supply from the SVC to the
network.
943
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
4/12
Figure5 shows the block diagram of the allocator.
TS wIr1
Figure 5. The SVC allocator
PLlHLD-
1 o
Figure6. The SVC linearher
g. Linearizer
The linearher converts the susceptance order (BTCR)
from the allocator to a firing angle order a which is
measured from the time of the last voltage peak To
maintain the same control response over the entire SVC
operating range, the anglea isdetermined as a non-linear
function of the BTCR. This function is given
as
a table
which is derived from the following formula:
s i n ( 3 t . U )
l - X , - B ( a )
= a +
x
where
is
the TCR reactance at the fundamental
frequency, B (a)
is
the susceptance of the TCR fired at
a , and a
is
the angle in per unit of 90 degrees.
The module generates wo output signals derived from
a: the anglea given in per unit of 90degrees (ALPHON)
and the angle of thyristor turn-off (ALPHOF) The
~
944
difference between ALPHON and ALPHOF
is
the firing
pulse width which is approximately equal to the thyristor
conduction angle
Q
:ALPHOF ALPHON =
Q
Figure
6
shows the block diagram of the linearizer.
h. TCR
iring circuit
The TCR firing circuit generates firing pulses to the
three-phase TCR unit. Inputs to the Circuit are: the
synchronizing signal from the PLL circuit and the firing
angles determined by the linearizer (ALPHON and
ALPHOF).
A
firing pulse
is on
while the elapsed time
since the occurrence of the last peak voltage
is
greater
than the current value of the ALPHON signal but less
than that of the ALPHOF. The pulse is directed to one
of the anti-parallel thyristor valve pairs.
Figure
7
shows the block diagram of the TCR firing
circuit.
i.
TSC
firing circuit
The TSC firing circuit generates firing pulses to
a
three-phase TSC unit. Each TSC unit is assigned a
priority number by the user and the TSC
is
activated when
the NOTSCS signal from the allocator
is
greater than or
equal to this number. In this way, TSC units are turned
on sequentially from the lowest priority number to the
highest.
Figure 8 shows the block diagram of the TSC iring
circuit.
j. Measurement circuit
The main function of the measurement circuit
is
to
provide the voltage regulator with the power system
voltage response measurement (URESP). The
measurement circuit also provides the signal conditioning
required to achieve a typical steady-state SVC regulation
characteristic with the slope determined by a control
setting SLOPE. The output signal AURESP represents
this feature.
The model allows representation of measurement circuits
with different techniques. Figure 9 shows the block
diagram for one of such circuits.
3.
Additional Control Functions
Other typical SVC control functions are also included
in the EMTP module library:
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
5/12
reactive power modulations, are not included n the SVC
model. The characteristics of these circuits are normally
unique for each specific SVC application and c n easily be
modeled with the TACS program.
Figure 7. The TCR firing circuit
TCR
overcurrent control. This circuit prevents
excessive current in the TCR during system
overvoltage conditions by imposing a delay of the
trigger pulses to the TCR.
Secondary overvoltage limiter. This circuit prevents
excessive voltage on the secondary side
of
the SVC
transformer by acting on the limits for the voltage
regulator output.
Undervoltage strategy. To prevent excessive voltages
in
connection with fault clearing, this circuit applies
predetermined control actions during conditions of
abnormally low ac voltages.
PLLAPC
SClABG
s c l BAG
SC1 ECG
P u s p c
PLLBNC SClCEG
PLLCPC
PLLCNC- = sclACc
Figure 8.
The TSC firing circuit
L q 7 URESP
BASE
IV
BASE SUSCEPTANCE-
Figure
9. The measurement circuit
Higher level control functions, such as power and
945
MODELING TECHNIQUE
A modeling techniaue based on EMTP data
modularization (IEDM) h& been adopted for the model
development. The technique c n be described in terms of
design rules observed during the model development
and
testing. These rules help avoiding duplicateuse
of names
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
6/12
for different variables and to facilitate the trace of names
of electrical nodes or control signals inside a device.
1 Variable Names
in
a Module
Each module has three sections: the declaration, the
The calculation section
is
alculation, and the body.
optional and c n be omitted.
During the model development, the variable names in
a module were specified in the declaration
as
follows:
2.
The first three characters of the names of selected
electrical nodes and control signals used only within
the module are declared
as
ARG .
ll
these names,
therefore, have the identical first three characters. The
remaining three characters are determined by the
module to make the names unique. The three-
character root name is the device name.
The names of the electrical nodes and the control
signals connected to the outside of the module are
declared ARG .Only the five-character root name
may be specified for a three-phase node. The last
character
is
determined by the module to distinguish
the phase,
All other six-character variables within a module that
are neither fully nor partially specified through the
ARG are declared 'DUM'.
Module Connection
The detailed SVC model can represent various SVC
configurations including TCR and TSC units and harmonic
filters. The EMTP user is required to connect the
modules by following simple rules and to supply proper
data to the modules:
Name all three-phase electrical nodes adjacent to each
power component with five-character strings, and all
single-phase nodes with six-character strings.
Name each power component with a distinct three-
character string if the module requires it. This naming
eliminates the possibility of a duplicated EMTP node
name for two distinct variables, especially when two
similar components are connected in parallel.
Name all TACS control signals exchanged between
the control function blocks with six-character strings.
Name each control function block with a three-
character string if the module requires
it.
Any number
of identical function blocks may, therefore, be used.
After the naming is completed, connect the system by
supplying proper names
as
arguments to the modules.
This
is
done by listing the names
in
the $INCLUDE
statements
in
the EMTP data file.
To complete the system representation,
ll
necessary
numerical data must be supplied to the $INCLUDE
statements. Attention must be given not to exceed the
maximum width
of
numerical field allowed by the
modules.
It should be noted that,
if
the first three characters of
all devices, nodes and control signals are distinct, there
will be
no
duplication of names.
3.
The EMTP simulations take place in two steps: the
steady-state initialization followed by the time-step
solution.
The initialization of a power system with SVCs is
usually difficult. The reasons are:
The EMTP uses a sinusoidal steady-state solution
of
the linearized a.c. system to calculate the initial
condition without taking full account of the control
system.
TCR is a harmonic source and the EMTP calculates
the steady-state solution only at one frequency.
Ignoring the harmonics, the initialization is only
approximate.
Some control blocks need time to be correctly
initialized.
A simple but effective initialization method
is
used.
The SVC model is initialized by using the EMTP's a.c.
system initialization. The TCRs are blocked during the
steady-state initialization. All thyristor valves of initially
operating TSC units are CLOSED or initialization. The
control system
is
not allowed to operate in full closed-loop
control mode immediately after t = 0 The control
system initialization produces equally spaced fuing pulses
for a specified initialization period. The SVC model
automatically sets the length
of
this period to
U)
ms, but
the length can easily be increased by the user.
MODEL APPLICATION
AND
TESTING
1
Test Svstem Description
The test system
is
an existing SVC scheme installed in
a 345-kV transmission system and fed by a
345/18-kV
946
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
7/12
step-down transformer. The SVC is a combined
TCR/TSC type consisting of three TSCs rated
121
MVAr
each, one TCR rated
163
MVAr, and
31-MVAr
f 5th and
7th harmonic filters. The overall rating of the SVC is
from 125 MVAr inductive to
425
MVAr capacitive,
referred to 1.0 pu primary voltage.
The control system includes undervoltage strategies
and power modulation controls.
The undervoltage strategies take the following actions
when the voltage response signal from the measurement
circuit drops below a preset
limit
of
0.6
pu:
Clamp the voltage regulator output (BREF) to zero
Block all TSCs
These actions are removed after a
30
ms delay when
the voltage increases above
0.69
pu.
A power modulation control block
is
added to the
SVC control system.
This
high-level control function
u t i l i s the power system response as the input and acts on
the voltage regulation to provide damping for slow electro-
mechanical
swings
in the power system. The input
is
the
RMS current in the 345 kV transmission line. The output
is added to the voltage reference through AUREF input
of
the voltage regulator. AUREF is provided for interface
with high-level control blocks. The transfer function is
shown below
as
an example of a typical high-level control
block
Figure
10
shows the equivalent 345-kV transmission
network with the SVC located in the .middle of a 345-kV
line. The network data are provided in Appendix.
2.
m m
Figure
11
shows the model of the SVC. The figure
indicates the names of the electrical nodes, devices and
control signals.
3.
Test Cases and Resulb
The initial operating point
is
1.0
pu voltage at the
345-kV SVC bus and 14 MVAr inductive output from the
~
947
BUS 3 BUS 2
345 kV 345 kV
SVS BUS BUS 1
345 kV 345 kV
BUS 4
115 kV {LINE 2 LINE ZEQl
4 T f
T T T
Figure
10.
Equivalent transmission network
SVC. Initially, there is 700
W
of power
flowing
from
Bus
1
to Bus 2.
The simulated sequence of events
is:
A three-phase to ground fault at Bus 1 occurring at t
= 0.1
second.
Removal of the fault at t
= 0.2
second.
Figure12 shows the results of the EMTP simulation
using the detailed SVC model. Figure
13
shows the SVC
performance
in
the TNA. The results include the
waveforms of currents in the TSC and TCR units and two
control signals, i.e., the voltage response and the
susceptance reference.
The waveforms in Figure
12
show that the system
is
initialized well within
0.1
second. The two plots
show
hat
the SVC susceptance (BREF)
is
clamped
to
zero by the
undervoltage strategy almost immediately after the fault.
Both plots also show a similar depression in the primary
bus voltage.
After the fault
is
cleared and the voltage
is
restored
above 0.69 per unit, the BREF starts to increase. Both
plots show that there
is
a delay between the time
of
recovery and removal of the clamp
on
he BREF.
This is
because of the
30
ms delay
in
the undervoltage strategy.
For a short
time
period of about 80 ms,both plots show
BREF in the capacitive region with TCS unit
1
operating
and the TCR unit almost fully
on.
After
this
period, the
operation slowly settles down
to
the
original
steady-state
operating point. The two plots show good agreement.
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
8/12
J SCPULS
LIA
H U S U R E A
TSCPULS
ALLOCATOR
"REF-
Figure
11
Complete SVC test model
SUMMARY
The EMTP is a useful tool for simulation of power
system and SVC performance. A detailed model of Static
VAr Compensators (SVC) has been implemented as a set
of EMTP data modules. The model c n be applied to
various SVC configurations including the widely-used
FC/TCR type and the combined TSC/TCR type SVCs.
Extensive model validation tests have proved that the
currently available EMTP can accurately simulate the
transient behavior of SVCs
in
power system.
The paper describes a modeling technique which can
be used for the developmentofcomplex power equipment.
The paper also describes an effective initialization method
used for the SVC model. The model initialization is
significantly improved due to the calculation section of the
enhanced EDM.
The described SVC model
will
be available in the
coming version
3.0
of the DCG/EPRI-released EMTP.
ACKNOWLEDGEMENT
The authors wish to thank Prof. W. F. Long
University of Wisconsin-Madison, for his review of and
comments on the functional specification of the model,
and Messrs. D. Dickmander, D. Nickel, and R. Rosenqvist
at ABB s Advanced Systems Technology Division in
Pittsburgh, for their
useful
advice during the model
development and testing.
REFERENCES
[l]
R.H. Lasseter, S.Y.Lee, Digital Simulation of Static
VAr System Transients , EEE Transactions
on
Power
Apparatus and Systems, Vol. PAS-109, No. 10,
October 1982.
[2]
A.N. Vasconcelos, et al, Detailed Modeling of an
Actual Static VAr Compensator for Electromagnetic
Transient Studies , IEEE/PES 1991 Winter Meeting,
New York, New York, February 3-7, 991.
94
8
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
9/12
m
m F
RFSPIINSF
1 "
m
d
5
p ?
- 8 . 0 0
e :a
8 .
20
d.33
e . 48 . se
d.60
8 70 8 B0 0 90 d 80
1 8 /2 5 / 98 8 3 . 1 5 . 8 2 1 2
PLOT TYPE 9
TCR # l CURRENT, PHASE BC
m
SVS
SUSCEPTQNCE
1 Q
Figure
12.
EMTP imulation of the SVC performance for a three-phase to ground fault at Bus 1
949
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
10/12
r 1
O L T G E R E S P O N S E
t
1
T C R B C U R R E N T
T C R B C C U R R E N T
Figure
13.
TNA
simulation of the
SVC
performance for a three-phase to ground fault at
Bus
1
950
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
11/12
[3]
A.M. Gole and V.K. Sood, A Static Compensator
Model for Use With Electromagnetic Transients
Simulation Programs, IEEE Transactions on Power
Delivery, Vol. 5 No. 3 July 1990.
[4] W. Scott Meyer, EMTP Data Modularization and
Sorting by Class: A Foundation Upon Which EMTP
Data Bases Can Be Built, EMTP Newsletter, Volume
4 Number 2, November 1983.
[ 5 ]
User Manual: EMTP Data Module (Enhanced
Version), April 1990.
[6]
Direct Current Transmission Volume
I E.W.
Kimbark, John Wdey
Sons,
nc., 1971
[7l DCG/EPRI EMTP Rule Book for EMTP Version
2.0
March 1989.
APPENDIX
EquivalentTransmissionNetwork Data
ll
impedances are referred to the 345 kV side.
ZEQ1:
Equivalent impedance at Bus
1
R1 = 22.00
R
L1 = 95.03 mH C1 = 9.43 p F
R2 =
80.90
R
L2 = 335.10 mH C2 = 0.75 p F
R3 = 4.87R
L3 =
142.84 mH
R4 =100.80~
C4 =100.80pF
ZEQ2:
L = 132.60 mH
ZEQ3:
L
= 789.00 mH
The lines
1
and 2 are represented as PI-circuits.
Transformer:
L = 110.50
mH
Capacitors
at
Bus 4:
3 x 67MVAr
Sang
Y.
Lee
(M89) Mr. Lee attended University of
Saskatchewan, Canada, receiving his BSc. and M.Sc.
degrees in Electrical Engineering. He joined the ASEA
Power Systems Center in 1985as an engineer in the digital
computer study group. He conducted various electrical
system studies for utility and industrial power systems. In
1989,
Mr.
Lee transferred to
ABBs
Advanced Systems
Technology division, where
his
responsibilities include
model development and studies of power system transients
using the EMTP.
Subroto
Bhattacharya
(M81, SM90) received hisB.Tech.
in Electrical
Engineering
from Mysore University, India,
in 1981 and his M.Tech. from the Indian Institute of
Technology in 1983.
H e
pent five months in 1985 at the
ASEA
Power Systems Center
as
a
visiting research
trainee.
Dr. Bhattacharya earned his Ph.D. in Electrical
Engineering
n
1987. After graduation he joined
ABBs
Systems Study Center in Milwaukee,
WI
nd in 1989 he
was transferred to the Advanced Systems Technology
Division in Pittsburgh. His main expertise
is
in the
modeling and analysis of power system transients. He is
ABBs
representative in the EMTP Development
Coordination Group (DCG).
Dr. Bhattacharya has authored and co-authored several
technical publications on digital simulation of SVC and
HVDC controls including an IETE Prize paper. He has
co-authored a reference manual on the EMTP Theory
book.
Tommy Lejonberg received
his
M.Sc. in Electrical
Engineering from Chalmers University
of
Technology in
Goteborg, Sweden, in 1979. Since graduation in 1979, Mr.
Lejonberg has been with ASEA and now ABB in Vasterk,
Sweden. He started
his
careerwith the R&D department
for power electronics and became manager for
t s
department
in
1983. Three years later he became
manager for the department of
high
power Converters,
which included the responsibility for development, design
and production of control systems and thyristor valves for
svc.
Line
1:
L = 164.18 mH C = 0.89pF
Line
2:
L
=
82.09mH
C
=
0.47pF
Line 3: L = 88.75 mH reactive power compensator equipment.
In 1988, Mr. Lejonberg joined ABB Power Systems where
he today is responsible for system design and R&D for
951
-
8/10/2019 7-Detailed Modeling of Static Var Compensators Using-00169616[1]
12/12
During his professional career withMEA and ABB, Mr.
Lejonberg has taken an active part in the development of
the SVC technology, especially in the areas of control
systems and thyristor valves.
Adel
E Hammad
(M'76, SM'83, F89) received his B.Sc.
(hons.) and M.Sc. from Cairo University and his Ph.D.
from University of Manitoba, all in Electrical Engineering
in 1972, '74 and '78 respectively. From 1975 to '78 he was
with the system planning of Manitoba Hydro in Winnipeg,
Canada. In 1978 he was the chief electrical engineer of
UNIES Engineering Consultants in Winnipeg. Since 1979
he is with Asea Brown Boveri where he is now chief
engineer for HVDC and SVC system applications at ABB
Power Systems, Baden, Switzerland.
Dr. Hammad has numerous publicationsin his field and
is supervising research activities and giving courses at
several universities. He is a registered Professional
Engineer in the province of Manitoba and a member of
the IEEE PES Power System Engineering Committee. He
serves on the System Dynamic Performance and the DC
Transmission subcommitteesand
is
active on several IEEE
and CIGRE working groups.
Serge
Lefebvre (M'76) received the B.ScA. and M.ScA.
degrees in electrical engineering from Ecole Polytechnique
de Montreal, Canada in 1976 and 1977 respectively, and a
Ph.D. from Purdue University, Indiana, in 1980. He is
working at the Research Department of Hydro-QuCbec
(IREQ) since 1981 while being an invited professor at
Ecole Polytechnique de MontrCal. His research interests
are in power system analysis techniques, computer
applications, and dc systems. Dr. Lefebvre is Chairman of
the IEEE working group Dynamic Performance and
Modeling of DC Systems .