7. heat shrink cable joint (hv) - 11kv trifurcating (3 core xlpe to 3 x single core xlpe-cws...
TRANSCRIPT
TMI 130/36-7506
INSTALLATION INSTRUCTIONHEASHRINK TRIFURCATING JOINT TO SUIT 3 CORE 12kV
XLPE/SWA/PVC CABLE TO 3 x SINGLE CORE 12kV NON ARMOURED XLPE/CWS/PVC CABLES REFERENCE TYPE: SPAJ 12X-3C-TRIF
DATE OF ISSUE: 24.01.14
THESE INSTRUCTIONS SHOULD BE FOLLOWED BY A TRAINED COMPETENT JOINTER
A PROPANE GAS TORCH IS THE PREFERRED METHOD FOR SHRINKING THESE MATERIALS
ENSURE THAT THE MATERIALS ARE KEPT CLEAN AND DRY AND ARE FREE FROM DUST, SAND AND GREASE
PLEASE CALL SHRINK POLYMER SYSTEMS FOR ANY ADVICE
TMI 130/36-7506 TMI 130/36-7506
Use free software on yoursmart phone to scan the QR code
below to watch an installation videoon 3 core to 3 core xlpe cables
Use free software on yoursmart phone to scan the QR code
below to watch an installation video on3 core Pilc to 3 x Single Core Xlpe Cables
1. Ensure the cables overlap before preparing the cables to the dimensions shown above and in accordance with the Table 1 below for conductor size. Ensure you use the same cable range dimensions as the kit supplied.
2. Before proceeding, position the outer shrink tube and clamps over the 3 core cable end and the 3 core breakout boot over the single core cables as shown above in Fig 1.
3070BA
C
XX
CABLE PREPARATIONALL DIMENSIONS SHOWN IN mm
Fig 1
3 COREBREAKOUT
BOOTOUTER
SHRINKTUBE
CONDUCTOR2SIZE (mm )
35-70
95-185
185-300
A
500
500
600
B
250
250
270
C
600
600
700
X (mm)
160
170
180
MAX CONNECTORLENGTH (mm)
100
130
140
Table 1
Note:- These joints are designed for use with MV compression ferrules and “tapered centralised conductor” mechanical connectors.
3. Lift the wire armours of the 3 core cable and apply a two bands of 212D black mastic tape as shown in Fig 2. Secure the three earth braids to the copper tape screens using the constant force springs supplied.
4. Fit the under armour support ring and fold down the armours as shown in Fig 3+4.
5. Remove the backing papers from the piece of black mastic tape labelled crutch wedge and form into a wedge. Open up the cores and insert the these as far as possible into the crutch of the cable
Apply a further layer of 212D black mastic tape over the screen earth braids, See Fig 4.
6. Prepare the cores to the dimensions shown in Fig 1 and Table 1.
7. Using a suitable tool, remove thesemi-conductive layer, taking care not to damage the primary insulation, particularly at the screen ends.
Thoroughly de-grease the exposed insulation using the cleaning tissues provided.
It may be advisable to secure the copper tape screens to prevent them from unwinding.
Note:- Screen removal tools can be provided. See website for screen removal advice/video.
X X
15
Earth Braids
Single core shown for clarity
212D BlackMastic
ArmourSupport
Ring
Mastic CrutchWedge
ArmourWires
212D BlackMastic
Fig 2
Fig 3
Fig 4
Fig 5
Fig 6
Fig 7
Fig 8
Fig 9
Fig 11
10mm 25mmStress Control
Tube
Stress ControlTube
Mechanical or CompressionType Connectors
Yellow Stress Relief Mastic
10mm
8. Stretch the yellow stress relief tape and apply over the screen cut area, extending onto the primary insulation by 10mm and catching the copper tape screens as shown in Fig 7.
9. Position the stress control tubes as shown 5mm back from the insulation and starting from the insulation end, apply heat all around the tubes using a soft flame torch. Heat until fullyrecovered.
10. Fit the approved MV ‘tapered’ connectors using the appropriate tool. Clean and de-grease before proceeding.
11. Stretch and apply the yellow stress relief mastic over the connector area with a 50%overlap. Extend onto the short stress control tubes by 10mm, as shown in Fig 9.
Important:- Fill in the gap between primary insulation and ensure a smooth taper to the connector. Also if mechanical connectors used, fill any voids that the bolts leave after they have been sheared with the grey hv mastic tape supplied.
12. Stretch and apply the short red mastic tape pieces at the end’s of the stress control tubes as shown in Fig 10, so that the red/black tubes sit upon it. This will create an additional moisture seal.
13. Finally, centrally position the red/black dual wall tubes so that they cover the screen end points. Starting in the middle and working towards the ends, shrink them whilst keeping the flame moving all around the tubes to ensure an even recovery and wall thickness.
DUAL WALL RED/BLACK TUBE
5mm
STRESS CONTROL TUBE STRESSCONTROL
TUBE
Yellow Stress Relief Mastic
STRESS CONTROL TUBE STRESS CONTROL TUBE
STRESS CONTROL TUBE STRESS CONTROL TUBE
Fig 10
RED/BLACKDUAL WALL
TUBE
RED/BLACKDUAL WALL
TUBE
3 COREBREAKOUT
BOOT
KM50 Copper Mesh
Fig 12
Black MasticRoll
75mm
Fig 13
212D BlackMastic
Armourclamps
212D BlackMastic
GREY MASTICTAPE
Fig 14
14. Starting from the single core end, wrap each core insulation tube with the tinned copper mesh applied with a slight overlap. Extend onto thecopper screens on the 3 core side as shown inFig 12.
With an open spiral take the tinned copper mesh and wrap around the armours.
15. Secure the tinned copper mesh tails, screen earth braids and one end of the long earth braid/s, to the armours, using the worm drive clampsprovided.
16. Using a suitable connector, join the 3 single core wire earth screens to the tinned copper earth braid/s as shown in Fig 13.
17. Abrade the outer sheaths for approximately 100mm on each side.
18. Create a roll from the 212D black mastic tape and insert between the 3 single cores, approx. 75mm from the sheath cut. Apply a layer of black mastic over the cables as shown in Fig 13.
Apply a further layer of black mastic over the worm drive clamps on the 3 core side.
19. Position the large 3 core breakout just onto the cable sheaths. Using a suitable heat source shrink the main body before shrinking the legs to the single core cables.
Apply a band of the grey mastic tape over the breakout body as shown in Fig 14.
3 COREBREAKOUT
BOOT
3 COREBREAKOUT
BOOT
OUTERSHRINK
TUBE
OUTERSHRINK
TUBE
OUTERSHRINK
TUBE
Apply Grey MasticOver Connector
20. Position the outer shrink tube centrally so that once recovered, it overlaps the main body of the3 core breakout and the outer sheath of the3 core cable. Note: abrade the cable jacket to ensure a good sealant bond.
Start shrinking from the middle to one end at a time. Apply heat evenly all around the tube. Once fully recovered sealant should be visible at the ends of the tube.
Allow the joint to completely cool before applying any mechanical strain.
IMPORTANT NOTICE TO PURCHASER:- Sellers and Manufacturere’s only obligation shall be to replace such quantity of the product proved to be defective. Neither the Seller nor Manufacturer shall be liable for any injury, loss or damage, direct or consequential, arising out of the use or inability to use the product. Before using, User shall determine thesuitability of the product for his or her intended use and User assumes all risk and liability whatsoever in connection therewith.
UNIT E3 CROWN WAY CROWN PARK INDUSTRIAL ESTATE RUSHDEN NORTHANTS NN10 6FDTEL: +44 (0)1933 356758 FAX: (0)1933 413821 E-MAIL: [email protected]
WEBSITE: www.shrinkpolymersystems.co.uk
OUTER SHRINK TUBE OUTER SHRINK TUBE
Fig 15
OUTER SHRINK TUBE
Important: user/circuit designer should determine whether or not special earthing requirements are needed to reduce the possible effects of induced sheath voltages or circulating currents in armoured cables. The decision to single point earth/solid point earth or install cross bonding kits needs to be considered once length of run, loading and positioning of cables is known.