JAL International
SITE INSPECTION AND TEST RECORD
Description
7SD522 LINE DIFF.RELAY &DISTANCE PROTECTION.Sheet No: 0f
CustomerSEC-ERBCustomer Ref:
Site115/34.5KV JUBAIL(44BC)S/SContract No :
1. GENERAL DATA AND INFORMATION.Panel No.6L1BDesignation87L1-1/21-1/67N-1
MakeSIEMENSModel No7SD5221-5DB29-7HM7-2A
Serial NoBF0710070Aux.volts125 VDC
No of BO contactsBO31No of BIContactsBI24
2. MECHANICAL CHECKS AND VISUAL INSPECTION.ITEMDESCRIPTIONREMARKS
1.Inspect for any physical damage or defects.( Yes( N/A
2.Verify connections as per approved drawing.( Yes( N/A
3.Check tightness of all connections.( Yes( N/A
4.Test switch / plug checked for correct function.( Yes( N/A
3. ELECTRICAL TESTS
FUNCTION TEST
ITEMDESCRIPTIONREMARKS
1.Case Earthing checked( Yes( N/A
2.Indication checked( Yes( N/A
3.Trip/Output contacts checked( Yes( N/A
4.Binary input checked( Yes( N/A
4. METERING CHECK. 4.1 CURRENT INPUT CHECK:
PhaseInjected Amps(A)CT Ratio AppliedDisplayed secondary value(A)Displayed Primary value (A)
RN1.00800/1A1.00799
YN1.00800/1A1.00798
BN1.00800/1A1.00799
RN0.50800/1A0.50399
YN0.50800/1A0.50399
BN0.50800/1A0.50399
4.2 VOLTAGE INPUT CHECK:
PhaseInjected Voltage(V)PT Ratio AppliedDisplayed secondary value(V)Displayed Primary value (KV)
RN66.40115KV/115V66.3566.00
YN66.40115KV/115V66.3366.00
BN66.40115KV/115V66.3566.00
RN33.20115KV/115V33.1733.00
YN33.20115KV/115V33.1633.00
BN33.20115KV/115V33.1733.00
RY115115KV/115V114.89115.00
YB115115KV/115V114.90115.00
BR115115KV/115V115.00115.00
INPUTINJECTED VALUEEXPECTED VALUEDISPLAYED VALUE
RYB Frequency3 ph nominal voltage & Current with 0 degree Phase shift.
Voltage = 66.4 P-N
Current = 1A60HZ60 .0HZ
RYB P159 MW159.0 MW
RYB Q0 MVAR0.00 MVAR
RYB S159 MVA159 MVA
RYB PF1.001.00
Calculated :
P = 3 VI Cos Q = 3 VI Sin
S = 3 VIINPUT & OUTPUT FUNCTIONAL CHECK: BINARY
INPUT
CONTACTS
REMARKS
BINARY
OUTPUT
CONACTS
REMARKSLED
REMARKS
BI 1K17-K18OKBO 1K5-K6OK1OK
BI 2J1-J2OKBO 2K5-K7OK2OK
BI 3J3-J5OKBO 3K5-K8OK3OK
BI 4J4-J5OKBO 4K9-K10OK4OK
BI 5J6-J5OKBO 5K11-K12OK5OK
BI 6J7-J8OKBO 6K13-K14OK6OK
BI 7J9-J10OKBO 7K15-K16OK7OK
BI 8J11-J12OKBO 8R1-R5OK8OK
BI 9P17-P18OKBO 9R2-R5OK9OK
BI 10N1-N2OKBO 10R3-R5OK10OK
BI 11N3-N5OKBO 11R4-R5OK11OK
BI 12N4-N5OKBO 12R6-R5OK12OK
BI 13N6-N5OKBO 13R7-R8OK13OK
BI 14N7-N8OKBO 14R9-R10OK14OK
BI 15N9-N10OKBO 15R11-R12OK
BI 16N11-N12OKBO 16P3-P4OK
BI 17H17-H18OKBO 17P6-P5OK
BI 18G1-G2OKBO 18P7-P5OK
BI 19G3-G5OKBO 19P8-P5OK
BI 20G4-G5OKBO 20P9-P10OK
BI 21G6-G5OKBO 21P11-P12OK
BI 22G7-G8OKBO 22P13-P14OK
BI 23G9-G10OKBO 23P15-P16OK
BI 24G11-G12OKBO24H3-H4OK
BO 25H6-H5OK
BO 26H7-H5OK
BO 27H8-H5OK
BO 28H9-H10OK
BO 29H11-H12OK
BO 30H13-H14OK
BO 31H15-H16OK
5. DIFFERENTIAL PROTECTION.Operating unit: 87L1: I diff> Remarks: Pick up tolerance 5% of set value or 10mA
PhaseSetting current(A)Pick up value (A)Drop off value(A)Remarks
R0.30.3170.164OK
Y0.30.3170.162OK
B0.30.3170.164OK
RY0.30.3170.164OK
YB0.30.3160.162OK
BR0.30.3160.162OK
RYB0.30.3170.162OK
5.1 Time measurement. SETTING CURRENT:2.50 x Is :2.50 x 0.3 =0.750 A
PhaseSetting current(Is)Measured time at 2.5xIs(m.sec)Tolerance
RN0.328.4Typical :29.0mse
YN0.328.1
BN0.328.7
RY0.3 28.6
YB0.328.0
BR0.328.7
5.2 MEASUREMENTS FOR DIFF & BIAS CURRENT WITH LOCAL RELAY.Measurements are made in % of Idiff.L1 set.I diff L1 set: 0.3PhaseInj.
ampsLocal end measurement in % of I diff set.Remote end measurement in % of I diff se
Idiff. L1I diff.
L2I diff.
L3I rest. L1I rest. L2I rest. L33I0I diffI diff.L1Idiff.L2I diff.L3I rest. L1I rest. L2I rest. L33I0I diff
A1.099.60.000.0031.931.431.499.599.50.000.0031.631.331.499.5
B1.00.0099.60.0031.332.131.699.60.0099.50.0031.432.431.499.4
C1.00.000.0099.731.331.631.699.60.000.0099.631.331.432.499.7
ABC1.099.799.699.632.132.131.90.0099.399.599.632.132.532.40.00
Note :I diff = Vector sum of local +remote amps.Bias =magnitude of I diff L1 set + errors in measurements.
5.3 RESTRAIN CHARECTERISTIC MEASUREMENT.I Diff set: 1A
I bias: I diff set (Diff Characteristic Angle 45 deg.)
PhaseLocal end injected amps(A)Remote injected amps(A)I Diff Measured(%)I Restrain measured(%)
A11.33333.233.6
B11.33333.333.6
C11.33233.033.3
5.4 87 L2 second stage diff. I Diff.: >>
Set Amps: 1.0 A Injected amps : 2.5 x In=2.5 A PhasePU AmpsTrip time (ms)Tolerance
R0.98613.5Pick up 5% or 10 mA.
Y0.98713.4
B0.98513.7
6. DISTANCE PRORECTION:ZONE AND TIME SETTINGS: RELAY CHARACTERISTICS (Quadrilateral)
ParameterZ1Z1BZ2Z3Z4Z5
DirectionForwardForwardForwardForwardReverse Non-directional
R1.001.502.003.004.05.00
X1.001.502.003.004.05.00
Re1.001.502.003.004.05.00
Time (sec)0.000.000.600.801.01.50
Set XE/XL: 1.0 RE/RL:1.0R-resistive reaches for phase to phase Fault.
Re-resistive reach for phase to earth fault.
X-reactive reaches for phase to phase & phase to earth fault.
6.1 IMPEDENCE REACH TEST:
Sl.No.DescriptionChecked
1Print out from freja attachedOK
6.2 OPERATING TIME TEST:
Sl.No.DescriptionChecked
1Print out from freja attachedOK
7. POWER SWING DETECTION:
1. Operation checked : OK2. Blocking time measured using oscilographic recorder : 83 ms8. DISTURBANCE RECORDER:
Checked event recording through DIGSI software: OK9. FAULT LOCATER:X=0.15 ohm/Km Distance: 10.0 KM Tolerance 2.5% DistanceApplied X valueExpected distanceMeasured distance(KM)
ANBNCNABBCCAABC
25
0.3752.52.52.52.52.52.52.62.5
50
0.7505.05.05.05.05.05.05.05.0
75
1.1257.57.57.57.57.57.57.57.5
100
1.50010.010.010.010.010.010.010.010.0
10.TELE PROTECTION SCHEME FOR DISTANCE PROTECTION:
Permissive under reach scheme: (PUTT)Set Z1=80% Z1B Z1B=100%Check CS with Z1.Trip Logic ZIB x CR: OKTrip Time With Out CR: 624 msTrip Time with CR: 21.6 msPermissive over reach scheme: POTT
Set: Z2=Z1B
Check Cs With Z2: OK
Trip Time With Out CR : 623.4 msTrip Time with CR: 21.9 msBlocking scheme:Z3 reverse
CS with reverse zone: OK
Trip Time with CR : 635ms Trip Time with out CR : 35.5 ms11. RESIDUAL EARTH FAULT PROTECTION (DEF): Angular measurement: Tolerance: 2DIRECTIONSET VALUEMEASURED TRIPPINGMEASURED BLOCKING
FORWARED =338
=122
337.7 - 121.1121.3-337.8
REVERSE= 338
= 122
121.1 - 338.1338 -121.1
Sensitivity check:
Characteristics: DEF forwardSet value Io (Amp)Measured Io (amp)Set value Vo (Volts)Measured Vo (Volts)
Pick upDrop offPick upDrop off
0.50.5040.47422.011.86
1.01.0060.94655.014.66
TIME MEASUREMENT: set Io = 1.5 x Is= 1.5 ASl.noSet time (sec)Actual time(sec)
1
11.03
2
22.02
12. TELE PROTECTION SCHEME FOR DEF PROTECTION:Directional comparison:
Send logic : forward fault. : OK Trip time with CR : 26.9ms Trip logic: forward fault +CR: OK Trip time without CR: 1.02 Sec.Week in feed: Trip and Echo Set V 25. Measured volts: OKBlocking
Send logic: reverse Fault: OK Trip time with CR l: 1.02 SecTrip logic: Forward fault +NO CR: OK Trip time without CR: 26.1 ms13. AUTOMATIC SWITCH ON TO FAULT FUNCTION:Distance + CB close command.
Zone used for non directional Acceleration: non directional.
External activation of SOTF function: Z5+ CB close command.
Operating time : 39.4 ms14. FUSE FAILURE SUPERVISION (ZERO SEQUENCE) FUNCTION:PhaseSet 3U0>(Volts)Pick up VoltsSet 3I0>(Amps)Pick up(Amps)
A3036.350.10.101
B36.390.101
C
36.400.101
Blocking of tripping zone in case of fuse fails in any phase: OK15.1. BACK UP OVER CURRENT PROTECTION I>:PhaseSet value I>Operate value(Amps)Set time delay
(Sec)Op.time at 1.5 x Is (sec)
PICK UPDROP OFF
AN10.9990.9333.03.03
BN11.0000.9343.03.03
CN10.9980.9283.03.03
BACK UP OVER CURRENT PROTECTION I>>:PhaseSet value I>Operate value(Amps)Set time delay
(Sec)Op.time at 1.5 x Is (sec)
PICK UPDROP OFF
AN1.01.0000.9345.05.03
BN1.01.0020.9345.05.03
CN1.01.0000.9335.05.03
BACK UP OVER CURRENT PROTECTION I Inverse:Normal Inverse Pickup value: Expected 10% set value above PhaseSet value I>Operate value(Amps)Set time delay
(Sec)Op.time at 3 x Is (sec)
PICK UPDROP OFFActual timeExpected time
AN11.1001.0270.503.153.18
BN11.1011.0280.503.153.18
CN11.1001.0260.503.153.18
Very InversePhaseSet value I>Operate value(Amps)Set time delay
(Sec)Op.time at 3 x Is (sec)
PICK UPDROP OFFActual timeExpected time
AN11.1001.0290.503.373.375
BN11.1001.0280.503.373.375
CN11.1031.0260.503.373.375
Extremely InversePhaseSet value I>Operate value(Amps)Set time delay
(Sec)Op.time at 3 x Is (sec)
PICK UPDROP OFFActual timeExpected time
AN11.1001.0270.505.05.0
BN11.1001.0270.505.05.0
CN11.1001.0260.505.05.0
Long time InversePhaseSet value I>Operate value(Amps)Set time delay
(Sec)Op.time at 3 x Is (sec)
PICK UPDROP OFFActual timeExpected time
AN11.1021.0270.5030.0330.0
BN11.1001.0250.5030.0230.0
CN11.1001.0260.5030.0030.0
16. TEST EQUIPMENT USED:1. Freja 300 relay test unit
2. FluKe-187 Multitester.
3. TOSHIBA laptop with DIGSI software.
4. DELL laptop with DIGSI SOFTWARETested By JAL INTLTest Witnessed By SEC
Name: SENTHIL KUMAR.AName: Mr. MOEED
Sign:Sign:
Date:Date: