Kein FolientitelProductmanager Distance Protection
Phone: +49 911 433 8261
Fax: +49 911 433 8301
Email: [email protected]
SIPROTEC 4
What does SIPROTEC 4 mean?
SIPROTEC 4 is a new family of digital protection- and control-devices
All SIPROTEC 4 relays include control-functions and user-definable logic (PLC)
SIPROTEC 4 assists you with:
a simplified handling together with DIGSI 4
a better adaptation to local requirements
SIPROTEC 4 uses modern communication-technology for system integration
SIPROTEC 4 uses a common hardware platform
20
7SA522
20
SIPROTEC 7SA522
Front design
assignment and slot
4 freely assignable
SIPROTEC 7SA522
4 Voltage Transformers (VT)
4 Current Transformers (CT)
Time synchronization
in future DNP3.0, MODBUS and Profibus DP
Service interface
DIGSI 4 via Modem
Remote relay interface (plan)
for protection signalling
process or 2nd remote relay interface
2.unknown
20
7SA522
7SA522
SIPROTEC 7SA522
three phase and single phase tripping
five independent zones and one controlled overreach zone
all zones can be set forward/reverse/non-directional
with/without parallel line compensation
special algorithm for detection and compensation of CT saturation
Fault Locator with/without parallel line compensation
Universal teleprotection interface
ANSI-No.
17.10.97
en513all7
SIPROTEC 7SA522
for earthed systems
directional and/or non-directional
backup protection running in parallel to the distance protection
Teleprotection interface for earth fault protection
(Directional comparison, Blocking, Unblocking)
SIPROTEC 7SA522
Overvoltage protection
STUB Bus Overcurrent protection
Synchro-check
SIPROTEC 7SA522
User-(Service-)interface #2 (on the rear, DIGSI 4/Modem)
System interface (IEC60870-5-103/Profibus FMS*/others)
Remote relay interfaces #1 (planned for teleprotection)
Remote relay interfaces #2 (planned for teleprotection)
ANSI-No.
74TC
86
FR
47
20
SIPROTEC 7SA522
SIPROTEC 7SA522
MHO characteristic
Symbols:
I B, I C measured fault currents
k pol polarization factor (0.15%)
363.unknown
20
7SA522 - Trip time curves at SIR = 1
Diagramm1
0
15.1
20
5
15.3
21
10
23
15.2
22
15
24
16.5
23
20
24
16.8
24
25
25
16.6
24
30
26
16.6
24
35
27
16.5
24
40
28
16.7
24
45
28
17
24
50
29
17.1
24
55
30
17
24
60
31
17.2
24
65
32
17.2
24
70
34
18.6
24
75
35
19.3
24
80
36
20.5
24
85
36
21.6
90
37
22.5
95
24.9
100
31.9
20
7SA522 - Fault locator
7SA522 - Teleprotection Schemes
7SA522 - Phase segregated Teleprotection
Maximum of Selectivity
Note: 3 binary channels for both directions are requested or (in preparation) one serial link
456.unknown
20
7SA522 - Teleprotection with three-terminal lines
Software provides teleprotection of three-terminal lines without additional logic
20
7SA522 - Echo and Tripping in case of no-infeed or weak-infeed
17.10.97
en513ase2
Configuration
Settings
Note: The echo signal must be marshalled in addition to the send signal on the transmission signal contact
Matrix
and
!
7SA522
Earth (zero sequence) current protection, 4 stages
3 definite-time stages
1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic
this stage can also be used as a 4th definite-time stage
Directional determination with 3V0 and/or Ipol of an earthed power transformer
Directional determination with V2 and I2 (negative sequence)
Sensitive 3I0-measurement with a dynamic from 0.005 A to 100 x In
Elimination of higher harmonics with special digital filters
Inrush-stabilisation with I0/100Hz
Operation with weak infeed trip and echo
Instantaneous trip after switch-onto-fault
7SA522
Definite-time characteristic
7SA522
Inverse-time characteristic: IEC
7SA522
IEC-characteristic:
_917095999.unknown
_985770710.unknown
20
7SA522
322.unknown
20
7SA522
t
T3I0pmax (P3145)
T3I0p (P3144)
7SA522
Filter characteristic for stages 3I0>>> and 3I0>>
-160
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-30
-20
-10
0
10
dB
0
1
2
3
4
5
6
7
8
9
10
11
f/
fn
_985772134.doc
-160
-150
-140
-130
-120
-110
-100
-90
-80
-70
-60
-50
-40
-30
-20
-10
0
10
dB
0
1
2
3
4
5
6
7
8
9
10
11
f/fn
20
7SA522
Filter characteristic for stages 3I0> and Inverse time stage
550.unknown
20
7SA522 - STUB protection for 11/2-circuit breaker arrangement
Release of STUB-stage with open line isolator:
458.unknown
20
7SA522 - Monitoring
=
=
(~)
Version
Width
No.
of
Binary
Inputs
No.
of
Output
Relays
Basic
two redundant channels to