The copyright and other intellectual property rights in this document, and in any model or article produced from it (and including any registered or unregistered design rights) are the property of Siemens Protection Devices Limited. No part of this document shall be reproduced or modified or stored in another form, in any data retrieval system, without the permission of Siemens Protection Devices Limited, nor shall any model or article be reproduced from this document unless Siemens Protection Devices Limited consent. While the information and guidance given in this document is believed to be correct, no liability shall be accepted for any loss or damage caused by any error or omission, whether such error or omission is the result of negligence or any other cause. Any and all such liability is disclaimed. ©2011 Siemens Protection Devices Limited
7SR210 Non-Directional Relay
7SR220 Directional Relay Installation Guide (Software Version 2435H85008R7a-7a) (7SR210) (Software Version 2435H85009R7a-7a) (7SR220)
![Page 2: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/2.jpg)
7SR210 & 7SR220 Installation Guide
Document Release History
This document is issue 2010/05.
2011/05 First issue
Page 2 of 24 ©2011 Siemens Protection Devices Limited
![Page 3: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/3.jpg)
7SR210 & 7SR220 Installation Guide
Table of Contents
Document Release History....................................................................................................................2 Table of Contents ...................................................................................................................................3 List of Figures.........................................................................................................................................4 Section 1: Installation ............................................................................................................................5
1.1 Unpacking, Storage and Handling ............................................................................................5 1.2 Recommended Mounting Position............................................................................................5 1.3 Wiring ........................................................................................................................................5 1.4 Earthing.....................................................................................................................................5 1.5 Ancillary Equipment ..................................................................................................................5
Section 2: Equipment Operating Conditions.......................................................................................6 2.1 Current Transformer Circuits ....................................................................................................6 2.2 External Resistors.....................................................................................................................6 2.3 Fibre Optic Communication ......................................................................................................6 2.4 Front Cover ...............................................................................................................................6
Section 3: Dimensions and Panel Fixings ...........................................................................................7 3.1 Relay Dimensions and Weight..................................................................................................7 3.2 Fixings.......................................................................................................................................8
3.2.1 Crimps ..........................................................................................................................8 3.2.2 Panel Fixings................................................................................................................8 3.2.3 Fibre Optic Connectors ................................................................................................8
Section 4: Rear Terminal Drawings......................................................................................................9 4.1 E6 Case ....................................................................................................................................9 4.2 E8 Case ..................................................................................................................................11
Section 5: Connection/Wiring/Diagrams............................................................................................13 5.1 Wiring Diagram: 7SR21 OC/EF Relay....................................................................................13 5.2 Wiring Diagram: 7SR22 Directional OC/EF Relay..................................................................14
Section 6: Data Comms Connections ................................................................................................15 6.1 Standard RS485 Connections ................................................................................................15 6.2 IRIG-B Connections ................................................................................................................15 6.3 Additional (Optional) Fibre Optic Connections........................................................................16 6.4 Additional (Optional) RS485 Connections ..............................................................................17 6.5 Additional (Optional) RS232 Connections ..............................................................................17 6.6 Additional (Optional) Ethernet Connection for IEC 61850 ......................................................18
Section 7: Connection Diagrams........................................................................................................19 7.1 Typical Connection: 7SR22 Directional OC/EF and REF.......................................................19 7.2 Typical Connection: 7SR22 Directional OC/EF and NVD ......................................................20 7.3 Typical Connection: 7SR22 Directional OC/EF and NVD ......................................................21 7.4 Typical Connection: 7SR22 Directional OC/EF and NVD ......................................................22 7.5 Typical Connection: 7SR22 Directional OC and EF ...............................................................23 7.6 Typical Connection: 7SR22 Connected to VTs and Capacitor Cone Unit..............................24
©2011 Siemens Protection Devices Limited Page 3 of 24
![Page 4: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/4.jpg)
7SR210 & 7SR220 Installation Guide
List of Figures Figure 3.1-1 Overall Dimensions (mm) and panel Drilling for Size E6 Epsilon case
(Typically 4.2 kg)..................................................................................................................7 Figure 3.1-2 Overall Dimensions (mm) and Panel Drilling for Size E8 Epsilon Case
(Typically 5.3 kg)..................................................................................................................7 Figure 4.1-1 E6 Standard Comms (USB Front Port, Rear RS485) (See Note 2) ....................................9 Figure 4.1-2 E6 Standard + Additional Comms (IRIG-B, 2 x F.O. (ST Connectors))...............................9 Figure 4.1-3 E6 Standard + Additional Comms (IRIG B + RS485) (See Note 2)...................................10 Figure 4.1-4 E6 Standard + Additional Comms (IRIG B + RS232) ........................................................10 Figure 4.2-1 E8 Standard Comms (USB Front Port, Rear RS485) (See Note 2) ..................................11 Figure 4.2-2 E8 Standard + Additional Comms (IRIG B, 2 x F.O. (ST Connectors)).............................11 Figure 4.3-1 E8 Standard + Additional Comms (IRIG B + RS485) (See Note 2)...................................12 Figure 4.3-2 E8 Standard + Additional Comms (IRIG B + RS232) ........................................................12 Figure 5.1-1 Connection Diagram for 7SR21 Relay...............................................................................13 Figure 5.2-1 Connection Diagram for 7SR22 Relay...............................................................................14 Figure 6.1-1 RS485 Data Comms Connections Between Relays..........................................................15 Figure 6.3-1 Data Comms to Multiple Devices Using 7SG24 and F.O. Star Network ...........................16 Figure 6.3-2 Data Comms to Multiple Devices Using 7SG24 and F.O. Ring Network ..........................16 Figure 6.4-1 RS485 Data Comms Connections Between Relays..........................................................17 Figure 6.5-1 RS232 Data Comms Pin Connections...............................................................................17 Figure 6.5-1 Ethernet connection for IEC 61850 (star connection)........................................................18 Figure 6.5-1 Ethernet connection for IEC 61850 (ring connection)........................................................18 Figure 7.1-1 7SR22 Applied to Transformer Incomer ............................................................................19 Figure 7.2-1 7SR22 Applied to Transformer Incomer Including HV NVD Protection.............................20 Figure 7.3-1 7SR22 Applied to Feeder Including NVD Protection .........................................................21 Figure 7.4-1 7SR22 Applied to Feeder...................................................................................................22 Figure 7.5-1 7SR22 Applied to Feeder - No Zero Sequence Voltage Source .......................................23 Figure 7.6-1 7SR22 Applied to Feeder with Capacitor Cones Fitted .....................................................24
Page 4 of 24 ©2011 Siemens Protection Devices Limited
![Page 5: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/5.jpg)
7SR210 & 7SR220 Installation Guide
Section 1: Installation 1.1 Unpacking, Storage and Handling On receipt remove the relay from the container in which it was received and inspect it for obvious damage. It is recommended that the relay not be removed from its case.
If damage has been sustained a claim should be immediately be made against the carrier, also inform Siemens Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this manual.
When not required for immediate use, the relay should be returned to its original carton and stored in a clean, dry place.
The relay contains static sensitive devices, which are susceptible to damage due to static discharge. The relay’s electronic circuits are protected from damage by static discharge when the relay is housed in its case.
There can be no requirement to disassemble any relay, since there are no user serviceable parts in the relay. If any modules have been tampered with, then the guarantee will be invalidated. Siemens Protection Devices Limited reserves the right to charge for any subsequent repairs.
1.2 Recommended Mounting Position The relay uses a liquid crystal display (LCD) which is used in the programming and for operation. The LCD has a vertical viewing angle of ± 30˚ and is back–lit. However, the best viewing position is at eye level, and this is particularly important given its control features.
The relay should be mounted on the circuit breaker (or protection panel) to allow the operator the best access to the relay functions
1.3 Wiring The product should be wired according to the scheme requirements, with reference to the appropriate wiring diagram. Refer to the appropriate Diagrams and Parameters document for a cross reference of wiring diagrams and models.
1.4 Earthing Terminal 28 of the PSU (Power Supply Unit) should be solidly earthed by a direct connection to the panel earth. The Relay case earth stud connection should be connected to terminal 28 of the PSU.
It is normal practice to additionally 'daisy chain' together the case (safety) earths of all the Relays installed in a panel to prevent earth current loops posing a risk to personnel.
1.5 Ancillary Equipment The relay can be interrogated locally or remotely. For local interrogation a portable PC with suitable version of MS Windows (2000 SP4 or XP SP2)and Reydisp Evolution™ s/w (Latest Version available 32 bit) using USB port situated on front of the relay.
©2011 Siemens Protection Devices Limited Page 5 of 24
![Page 6: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/6.jpg)
7SR21 & 7SR22 - Installation Guide
Section 2: Equipment Operating Conditions
2.1 Current Transformer Circuits The secondary circuit of a live CT must not be open circuited. Non-observance of this precaution can result in injury to personnel or damage to equipment.
!
2.2 External Resistors ! Where external resistors are fitted to relays, these may present a danger of electric shock or burns, if touched.
! 2.3 Fibre Optic Communication Where fibre optic communication devices are fitted, these should not be viewed directly. Optical power meters should be used to determine the operation or signal level of the device.
2.4 Front Cover ! The front cover provides additional securing of the relay element within the case. The relay cover should be in
place during normal operating conditions.
Page 6 of 24 ©2011 Siemens Protection Devices Limited
![Page 7: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/7.jpg)
7SR210 & 7SR220 Installation Guide
Section 3: Dimensions and Panel Fixings
3.1 Relay Dimensions and Weight Relays are supplied in the modular size E6 or E8
The following drawings are available which give panel cut-out and mounting details.
PANEL CUT-OUT168
182
201.5
159
9.75
SIDE VIEW
31 216.5
FRONT VIEW
207.5
177
151.
5
NOTE:THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS. THESE ARE SUPPLIED AS STANDARD AND ARE SUITABLE FOR USE IN FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER PANELS, HOLES TO BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT).
THE RETAINING SCREW AT THE REAR OF THE CASE FOR THE ETHERNET VARIANT MUST BE FITTED FOR THE DEVICE TO COMPLY WITH PERFORMANCE CLAIMS.
11Case Earthconnection
Typical when fitted
Diameter 3.6 - 4 holes (see note)
MINIMUM CLEARANCES:25mm FOR TERMINAL WIRING45mm FOR ETHERNET COMMS MODULE70mm FOR F/O COMMS CABLE
75 m
m M
IN
CLE
AR
AN
CE
FO
R E
THE
RN
ET
CO
MM
S W
IRIN
G
Figure 3.1-1 Overall Dimensions (mm) and panel Drilling for Size E6 Epsilon case (Typically 4.2 kg)
PANEL CUT-OUT168
182
201.5
159
9.75
SIDE VIEW
31 216.5
FRONT VIEW
207.5
177
151.
5
NOTE:THE 3.6 HOLES ARE FOR M4 THREAD FORMING (TRILOBULAR) SCREWS. THESE ARE SUPPLIED AS STANDARD AND ARE SUITABLE FOR USE IN FERROUS / ALUMINIUM PANELS 1.6mm THICK AND ABOVE. FOR OTHER PANELS, HOLES TO BE M4 CLEARANCE (TYPICALLY 4.5 DIAMETER) AND RELAYS MOUNTED USING M4 MACHINE SCREWS, NUTS AND LOCKWASHERS (SUPPLIED IN PANEL FIXING KIT).
THE RETAINING SCREW AT THE REAR OF THE CASE FOR THE ETHERNET VARIANT MUST BE FITTED FOR THE DEVICE TO COMPLY WITH PERFORMANCE CLAIMS.
11Case Earthconnection
Typical when fitted
Diameter 3.6 - 4 holes (see note)
MINIMUM CLEARANCES:25mm FOR TERMINAL WIRING45mm FOR ETHERNET COMMS MODULE70mm FOR F/O COMMS CABLE
75 m
m M
IN
CLE
AR
AN
CE
FO
R E
THE
RN
ET
CO
MM
S W
IRIN
G
Figure 3.1-2 Overall Dimensions (mm) and Panel Drilling for Size E8 Epsilon Case (Typically 5.3 kg)
©2011 Siemens Protection Devices Limited Page 7 of 24
![Page 8: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/8.jpg)
7SR21 & 7SR22 - Installation Guide
Hardware Model Net Weight kg
7SR2102 3.3 7SR2103 4.6 7SR2104 4.8 7SR2202 4.8 7SR2203 4.9 7SR2204 5.0
NB: If supplied with communication interface devices please add an additional 0.165 kg
3.2 Fixings
3.2.1 Crimps Ring tongued crimps with 90˚ bend are recommended.
3.2.2 Panel Fixings Typical mounting screw kit per Relay)
Consists of 4 off M4x10mm Screws
4 off M4 Nuts
4 off M4 Lock Washer
Typical rear terminal block fixing kit (1kit per terminal block fitted to relay) Consists of:
28 x M4, 8mm Screws
28 x M4 Lock Washer
3.2.3 Fibre Optic Connectors The relay has Fibre-Optic STTM (BFOC/2.5) bayonet connectors fitted when specified.
Page 8 of 24 ©2011 Siemens Protection Devices Limited
![Page 9: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/9.jpg)
7SR210 & 7SR220 Installation Guide
Section 4: Rear Terminal Drawings
4.1 E6 Case B A
Figure 4.1-1 E6 Standard Comms (USB Front Port, Rear RS485) (See Note 2)
Figure 4.1-2 E6 Standard + Additional Comms (IRIG-B, 2 x F.O. (ST Connectors))
Notes
1) Recommended terminations are pre-insulated & must be crimped using approved tooling.
2) RS485 (block ”B” terms 14, 16, 18, 20) connections to this communication facility is by screened, twisted pair cable. On site when wiring other facilities ensure that these terminals are not obscured by other wiring runs. Cable should be RS485 compliant.
©2011 Siemens Protection Devices Limited Page 9 of 24
![Page 10: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/10.jpg)
7SR21 & 7SR22 - Installation Guide
Figure 4.1-3 E6 Standard + Additional Comms (IRIG B + RS485) (See Note 2)
Figure 4.1-4 E6 Standard + Additional Comms (IRIG B + RS232)
Page 10 of 24 ©2011 Siemens Protection Devices Limited
![Page 11: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/11.jpg)
7SR210 & 7SR220 Installation Guide
©2011 Siemens Protection Devices Limited Page 11 of 24
BC A
4.2 E8 Case
Figure 4.2-1 E8 Standard Comms (USB Front Port, Rear RS485) (See Note 2)
Figure 4.2-2 E8 Standard + Additional Comms (IRIG B, 2 x F.O. (ST Connectors))
Notes
1) Recommended terminations are pre-insulated & must be crimped using approved tooling.
2) RS485 (block ”B” terms 14, 16, 18, 20) connections to this communication facility is by screened, twisted pair cable. On site when wiring other facilities ensure that these terminals are not obscured by other wiring runs. Cable should be RS485 compliant.
![Page 12: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/12.jpg)
7SR21 & 7SR22 - Installation Guide
Figure 4.2-3 E8 Standard + Additional Comms (IRIG B + RS485) (See Note 2)
Figure 4.2-4 E8 Standard + Additional Comms (IRIG B + RS232)
Notes
1) Recommended terminations are pre-insulated & must be crimped using approved tooling.
2) RS485 (block ”B” terms 14, 16, 18, 20) connections to this communication facility is by screened, twisted pair cable. On site when wiring other facilities ensure that these terminals are not obscured by other wiring runs. Cable should be RS485 compliant.
Page 12 of 24 ©2011 Siemens Protection Devices Limited
![Page 13: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/13.jpg)
7SR210 & 7SR220 Installation Guide
Section 5: Connection/Wiring/Diagrams
5.1 Wiring Diagram: 7SR21 OC/EF Relay
Figure 5.1-1 Connection Diagram for 7SR21 Relay
©2011 Siemens Protection Devices Limited Page 13 of 24
![Page 14: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/14.jpg)
7SR21 & 7SR22 - Installation Guide
Page 14 of 24 ©2011 Siemens Protection Devices Limited
5.2 Wiring Diagram: 7SR22 Directional OC/EF Relay 7SR22
BO 1
GND.
BI 1
+ve
+ve
-ve
-ve
IL1(IA)
3
1
22
24
28
2
4
BI 2-ve
+ve6
8
BI 3-ve
+ve10
12
1
2
5
6
9
10
13
14
BO 2 9
5
7
BO 3 15
11
13
BO 419
17
BO 523
21
BO 6
A
17
18
19
20
VL1(VA)
21
22
VL2(VB)
23
24
VL3(VC)
25
26
V4(VX)
27
28
BI 4-ve
+ve2
4
BI 5-ve
+ve6
8
BI 6+ve10
BO 73
1
BO 87
5
BO 911
9
BI 7+ve12
BI 8+ve14
BI 9-ve
+ve16
18
BI 1020
BI 11+ve22
BI 12+ve24
BI 13-ve
+ve26
28
+ve
BO 1015
13
21
19
17BO 11
BO 12
27
25
23BO 13
BO 14
1A
5A
1A
5AIL2(IB)
1A
5AIL3(IC)
1A
5AI4
(IG)15
16
11
12
1A
5AI5
(ISEF)3
4
7
8
A
Analogue
B
PSU
C
OptionalI/O
1 2
27 28
1 21 2
27 2827 28
DataComms
(Optional)
Rear ViewArrangement of terminals and modules
B
C
A
RS
485Screen
B
Term.
14
16
18
2025
26
27
Shows contacts internal to relay case assembly.Contacts close when the relay chassis is withdrawn from case
NOTES
BI = Binary InputBO = Binary Output
Figure 5.2-1 Connection Diagram for 7SR22 Relay
![Page 15: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/15.jpg)
7SR210 & 7SR220 Installation Guide
Section 6: Data Comms Connections
6.1 Standard RS485 Connections The standard RS485 communication port is located on terminal block 2 at the rear of the relay and can be connected using a suitable RS485 120Ω screened twisted pair cable.
The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support and use the Auto Device Enable (ADE) feature.
The last device in the connection must be terminated correctly in accordance with the master driving the connection. A terminating resistor is fitted in each relay, when required this is connected in circuit using an external wire loop between terminals 18 and 20 of the power supply module.
Up to 64 relays can be connected to the RS485 bus.
The RS485 data communications link with a particular relay will be broken if the relay element is withdrawn from the case, all other relays will still communicate.
A
RS485
Scr
een
B
Term
.
14 16 18 20
RS 485 Twisted pair screened Cable To
ControlSystem
To Control System
14161820
RS485 Screened twisted pair Rear terminals
141618
141618
RS485 Screened twisted pairRear terminals
Ext Wire loop to Include line
terminating Res
A
RS485
Scr
een
B
Term
.
14 16 18 20
A
RS485
Scr
een
B
Term
.
14 16 18 20
Figure 6.1-1 RS485 Data Comms Connections Between Relays
6.2 IRIG-B Connections A BNC plug is provided on the optional additional communication interface modules to connect a co-axial cable carrying IRIG-B time synchronisation signals. Ensure that the stub length is minimised by connecting the tee-connector directly to the rear of the relay. A suitable co-axial cable would be type RG 58 50ohms.
©2011 Siemens Protection Devices Limited Page 15 of 24
![Page 16: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/16.jpg)
7SR21 & 7SR22 - Installation Guide
6.3 Additional (Optional) Fibre Optic Connections Rear Com ports 3 and 4 comprise Fibre–Optic ST™ (BFOC/2.5) bayonet connectors-4 per product. 62.5 / 125μm glass fibre is recommended for all distances.
When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used- typically 50mm is acceptable.
Figure 6.3-1 Data Comms to Multiple Devices Using 7SG24 and F.O. Star Network
Figure 6.3-2 Data Comms to Multiple Devices Using 7SG24 and F.O. Ring Network
The F.O. data communications link with a particular relay will be broken if the relay element is withdrawn from the case, all other relays will still communicate.
Page 16 of 24 ©2011 Siemens Protection Devices Limited
![Page 17: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/17.jpg)
7SR210 & 7SR220 Installation Guide
6.4 Additional (Optional) RS485 Connections The additional (optional) RS485 communication port is located at the rear of the relay and can be connected using a suitable RS485 120 ohm screened twisted pair cable.
The RS485 electrical connection can be used in a single or multi-drop configuration. The RS485 master must support and use the Auto Device Enable (ADE) feature.
The last device in the connection must be terminated correctly in accordance with the master device driving the connection. The relays are fitted with an internal terminating resistor which can be connected between the A and B by fitting an external wire loop between terminals 18 and 20 on the power supply module.
A
RS485
Scr
een
B
Term
.
14 16 18 20
RS 485 Twisted pair screened Cable To
ControlSystem
To Control System
14161820
RS485 Screened twisted pair Rear terminals
141618
141618
RS485 Screened twisted pairRear terminals
Ext Wire loop to Include line
terminating Res
A
RS485
Scr
een
B
Term
.
14 16 18 20
A
RS485
Scr
een
B
Term
.
14 16 18 20
Figure 6.4-1 RS485 Data Comms Connections Between Relays
6.5 Additional (Optional) RS232 Connections The additional (optional) RS232 (9 pin plug) (DTE) communication port is located at the rear of the relay and can be connected using a suitable RS232 cable.
Where there is a requirement for multi-drop RS232 connection, a suitable device to facilitate this should be obtained.
Pin Relay Function 1 Not Connected 2 Receive Data (RXD) 3 Transmit Data (TXD) 4 Input Supply +5 V 5 Signal Ground (GND) 6 Input Supply +5 V 7 Linked to 8 (volts free) 8 Linked to 7 (volts free) 9 Output Supply +5 V 50mA
Figure 6.5-1 RS232 Data Comms Pin Connections
©2011 Siemens Protection Devices Limited Page 17 of 24
![Page 18: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/18.jpg)
7SR21 & 7SR22 - Installation Guide
6.6 Additional (Optional) Ethernet Connection for IEC 61850 Rear Ethernet Comms port Ch 1 and Ch 2 comprises Fibre–Optic ST™ (BFOC/2.5) bayonet connectors or electrical RJ45 connectors.
When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used- typically 50mm is acceptable, 62.5 / 125μm glass fibre is recommended for all distances.
Figure 6.6-1 Ethernet connection for IEC 61850 (star connection)
Figure 6.6-2 Ethernet connection for IEC 61850 (ring connection)
Page 18 of 24 ©2011 Siemens Protection Devices Limited
![Page 19: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/19.jpg)
7SR210 & 7SR220 Installation Guide
Section 7: Connection Diagrams
7.1 Typical Connection: 7SR22 Directional OC/EF and REF
Figure 7.1-1 7SR22 Applied to Transformer Incomer
©2011 Siemens Protection Devices Limited Page 19 of 24
![Page 20: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/20.jpg)
7SR21 & 7SR22 - Installation Guide
7.2 Typical Connection: 7SR22 Directional OC/EF and NVD
Figure 7.2-1 7SR22 Applied to Transformer Incomer Including HV NVD Protection
Page 20 of 24 ©2011 Siemens Protection Devices Limited
![Page 21: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/21.jpg)
7SR210 & 7SR220 Installation Guide
7.3 Typical Connection: 7SR22 Directional OC/EF and NVD
S1
S2
P1
P2
L1 L2 L3
VL
VN
NOTES1) CT circuits are shown connected to 1A tap – use alternative tap for 5A rated CTs.2) CT and Earth connections are typical only.3) Application shows use of V4 as an NVD input.4) Star Connected VT: Phase Voltage Config:-Van,Vbn,Vcn
IL1(IA)
1
2
5
6
9
10
13
14
A
17
18
19
20
21
22
23
24
2526
27
28
1A
5A
1A
5A
1A
5A
1A
5A15
16
11
12
1A
5A3
4
7
8
B
C
V4(VX)
VL3(VC)
VL2(VB)
VL1(VA)
IL2(IB)
IL3(IC)
I4(IG)
I5(ISEF)
Figure 7.3-1 7SR22 Applied to Feeder Including NVD Protection
©2011 Siemens Protection Devices Limited Page 21 of 24
![Page 22: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/22.jpg)
7SR21 & 7SR22 - Installation Guide
7.4 Typical Connection: 7SR22 Directional OC/EF and NVD
VL
VN
L1 L2 L3
3Vo
S1
S2
P1
P2
IL1(IA)
1
2
5
6
9
10
13
14
A
17
18
19
20
21
22
23
24
2526
27
28
1A
5A
1A
5A
1A
5A
1A
5A15
16
11
12
1A
5A3
4
7
8
B
C
V4(VX)
VL3(VC)
VL2(VB)
VL1(VA)
IL2(IB)
IL3(IC)
I4(IG)
I5(ISEF)
NOTES1) CT circuits are shown connected to 1A tap – use alternative tap for 5A rated CTs.2) CT and Earth connections are typical only.3) Voltage Config:-Vab, Vbc, 3V0
Figure 7.4-1 7SR22 Applied to Feeder
Page 22 of 24 ©2011 Siemens Protection Devices Limited
![Page 23: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/23.jpg)
7SR210 & 7SR220 Installation Guide
7.5 Typical Connection: 7SR22 Directional OC and EF
L1 L2 L3
A
C
B
S1
S2
P1
P2
IL1(IA)
1
2
5
6
9
10
13
14
A
17
18
19
20
21
22
23
24
2526
27
28
1A
5A
1A
5A
1A
5A
1A
5A15
16
11
12
1A
5A3
4
7
8
B
C
V4(VX)
VL3(VC)
VL2(VB)
VL1(VA)
IL2(IB)
IL3(IC)
I4(IG)
I5(ISEF)
NOTES1) CT circuits are shown connected to 1A tap – use alternative tap for 5A rated CTs.2) CT and Earth connections are typical only.3) Vee Connected VT: Phase Voltage Config:-VA,VB,VC4) DEF elements must be NPS polarised (Vo polarising not applicable)
Figure 7.5-1 7SR22 Applied to Feeder - No Zero Sequence Voltage Source
©2011 Siemens Protection Devices Limited Page 23 of 24
![Page 24: 7SR210 & 7SR220 Installation Guide and 7SR220 Tec… · Protection Devices Limited, and to the nearest Siemens agent, using the Defect Report Form in the Maintenance section of this](https://reader033.vdocuments.net/reader033/viewer/2022060709/60750211ad7eed1cf932017c/html5/thumbnails/24.jpg)
7SR21 & 7SR22 - Installation Guide
7.6 Typical Connection: 7SR22 Connected to VTs and Capacitor Cone Unit
L1 L2 L3
A
C
B
S1
S2
P1
P2
IL1(IA)
1
2
5
6
9
10
13
14
A
17
18
19
20
21
22
23
24
2526
27
28
1A
5A
1A
5A
1A
5A
1A
5A15
16
11
12
1A
5A3
4
7
8
B
C
V4(VX)
VL3(VC)
VL2(VB)
VL1(VA)
IL2(IB)
IL3(IC)
I4(IG)
I5(ISEF)
NOTES1) CT circuits are shown connected to 1A tap – use alternative tap for 5A rated CTs.2) CT and Earth connections are typical only.3) Vee Connected VT: Phase Voltage Config:-Va,Vb,Vc4) DEF elements must be NPS polarised (Vo polarising not applicable)5) V4 used for NVD input
CapacitorCones
AdaptorUnit
Figure 7.6-1 7SR22 Applied to Feeder with Capacitor Cones Fitted
Page 24 of 24 ©2011 Siemens Protection Devices Limited