    Fire and Gas system

    A basic understanding with our day

    to day job

  • 7/25/2019 84084810 Fire and Gas Recovered

    2/32

    WHY DO WE NEED FIRE & GAS PROTECTION

    SYSTEM????

    How it

    Works

    Looks?

    Fire Detection /Mitigationsystems:

    Fire Detection

    Gas Detection

    Fire Suppression systems

    CO2, FM200, Deluge

    Emergency Shutdown (ESD)Systems

    ICSS DCS/F&G/ESD systems.

    Emergency Alarm Systems

    PA system

  • 7/25/2019 84084810 Fire and Gas Recovered

    3/32

    Combustible Gases-Lower & Upper Limits*

    Too lean for ignition Too rich for ignition

    Clean Air

    Combustibles

    Lower

    Explosive

    Limit (LEL)

    Upper

    Explosive

    Limit (UEL)

    Typical Combustible

    Gas Detector Range

    of Measurement

    50%

    *No differentiation between the terms Explosive and Flammable as applied to the lower and

    upper limits of flammability

  • 7/25/2019 84084810 Fire and Gas Recovered

    4/32

    How does Gas Detector work?

    Detect & measurevapor before

    hazardous

    concentration is

    present

    Provide outputs to

    enable emergency

    action24 VDC

    + -

    LEL

    0

    0

    Flammable

    hydrocarbon

    gas

    No fault

    4.0 milliamperes

  • 7/25/2019 84084810 Fire and Gas Recovered

    5/32

    Types of Gas Detectors

    As per operating principle:

    1. Catalytic: Combustibles

    2. Infrared: Combustibles

    3. Electrochemical: Mainly Toxic gases (H2S,Oxygen,Cl, SO2,)

    In our plant, we are having Catalytic and Infrared types, they again may bedivided into point or open path detectors

    1. Pointwatch Eclipse 2. Open Path Eclipse 3. Catalytic Sensor/CGS

  • 7/25/2019 84084810 Fire and Gas Recovered

    6/32

    Catalytic Sensor Operation

    Combustible Gas Sensor (CGS)with DCUEX Tx

    Flammable

    gas

    Active Element - Hot wire resistor

    coated with catalytic material

    Reference Element - Same as active but

    without catalyst

    Catalytic reaction when contact with

    flammable gas generates heat &

    changes Active resistance; reference

    resistance unchanged

    Explosion is prevented by Flame

    Arrestor

    Constant E or I power source required

  • 7/25/2019 84084810 Fire and Gas Recovered

    7/32

    Point Infrared Detector Elements

    Gas

    Concentration(LEL)

    IR Source LampPermeable Gas

    Cell

    Reference

    Signal Detector

    Measurement

    Signal Detector

    Optical Beamsplitter

    Optical Filters

    IR Transparent Window

    Microprocessor

    andElectronics

    Permeable GasCellSapphire Mirror Theory of OperationThe infrared (IR) method of

    gas detection relies on the IR

    absorption characteristics of

    gases to determine their

    presence and concentration.

    IR gas detectors consist of anIR light source (transmitter) and

    light detector (receiver) to

    measure the intensity both at

    the absorption wavelength and

    a non-absorbed wavelength.

    If gas is present in the optical path, it will affect the intensity of

    light transmitted between the light source and the detector.

    This change in intensity provides the data for determining that a

    specific gas, or type of gas is present.

  • 7/25/2019 84084810 Fire and Gas Recovered

    8/32

    8

    Open Path Gas Detector System Elements

    IR Source

    Microprocessor

    and

    Electronics

    Gas

    Concentration

    (LEL)

    Reference

    Signal Detector

    Measurement

    Signal Detector

    Optical Beamsplitter

    Optical Filters

    10 - 60 m

    Flammable

    hydrocarbon

    gas

    As the IR beam reaches the receiver, it passes through a focusing lens and then passes

    through two narrow band IR filtersan active and a reference wavelength. The detector

    computes the ratio between the two signals

    The instrument's output is a function of gas concentration times the length of thesurveillance path

  • 7/25/2019 84084810 Fire and Gas Recovered

    9/32

    9

    Fail-Safe Operation

    DirtyOpticsandCleanAir

    Active Reference

    IR Signal Level

    HydrocarbonGas

    Active Reference

    IR Signal Level

    CleanAir

    Active Reference

    IR Signal Level

    Active Reference

    IR Signal Level

    FailedSensor

    Active Reference

    IR Signal Level

    FailedIR-Source

    Failed Microprocessor = 0 mA

  • 7/25/2019 84084810 Fire and Gas Recovered

    10/32

    EQP Field Devices - Flame

    UV/IR (X5200) - Single Frequency Infrared Flame Detector

    UV (X2200)UV flame detector

    IR (X9800) - Single Frequency Infrared Flame Detector

    Multispectrum IR (X3301) -

  • 7/25/2019 84084810 Fire and Gas Recovered

    11/32

    Ultraviolet Sensor Operating Principle

    Anode

    Cathode OiTest Source

    Plastichousing

    connectors(a,b,c,d)

    QuartzEnvelope

    Det-Tronics UV Sensor

    circuit board

    UV photons strike tube cathode

    Cathode releases electron

    Electron strikes gas molecule

    Cascade effect occurs to anode

    Discharge is quenched, creates pulse(count) output

    Pulse output measured in CPS (countsper second)

    counts/gate: # of pulses (cps) requiredto occur within one gate in order toqualify

    gate length: unit of time consec. gates: # of consecutive gates

    required to be satisfied before a firealarm output is provided

  • 7/25/2019 84084810 Fire and Gas Recovered

    12/32

    Arc Rejection Signal Processing

  • 7/25/2019 84084810 Fire and Gas Recovered

    13/32

    Analyzes the raw IR sensor signal randomness

    Rejects signals that do not meet randomness criteriaNo Fire Alarm

    Fire Alarm !

    Signal Processing

    Automatic optical integrity calibrated to

    perform at all operating temperaturesInternal lamps test each sensor at the

    precise wavelength once per minute

    to verify operation.

  • 7/25/2019 84084810 Fire and Gas Recovered

    14/32

    LOGIC & C&E SYMBOL LEGEND

    CUSTOMER:

    PROJECT: REVDRAWING NUMBERSIZE

    B

    DRAWING TITLE

    CONFIDENTIAL-

    THISDRAWINGANDSPECIFICATIONCONTAINPROPRIETARYINFORMATION

    ANDANYREPRODUCTION,DISCLOSURE,ORUSETHEREOF IS EXPRESSLYPROHIBITEDWITHOUT WRITTENPERMISSION OF DETECTORELECTRONICSCORPORATION

    SCALE:NONE DETECTOR ELECTRONICS CORPORATION6901 WEST 110TH STREETMINNEAPOLIS, MN 55438DESIGN BY:

    DATE:

    CHECKED

    BY:

    P.O.

    F.O.

    ONEPLACETWOPLACESTHREEPLACESFRACTIONS

    ANGLES

    0.00.000.000X/XXDEGREES

    +/-.020+/-.010+/-.005+/-1/32+/-1

    TOLERANCEUNLESSOTHERWISESPECIFIED

    DESCRIPTIONDATEREV

    12345678

    D

    C

    B

    A

    D

    C

    B

    A

    12345678

    INITIAL RELEASE03/12/01AA

    XXX

    Simon Pate

    03/12/01

    XXX

    DETECTOR ELECTRONICS

    EAGLE QUANTUM

    Lube Oil console

    Fuel Gas System

    GT Exit/Entry

    Enclo

    sure

    exha

    ust

    System Cabinet

    RRFlextronics

    Control Net

    X3301

    Thermals

    DUCTWATCH

    DCIO

    Area with Detection & Suppression

  • 7/25/2019 84084810 Fire and Gas Recovered

    15/32

    Fire Detector Cone of Vision

  • 7/25/2019 84084810 Fire and Gas Recovered

    16/32

    How it Communicates

    UV/IR Fire Detection

    X5200

    IR Fire

    Detection

    X9800

    Supervised Inputs Heats,

    Smokes and MACsAgent Release

    PRESSHERETRYKK HERKNUS GLASSET

    BREAK GLASS

    BN-300BRANNALARM

    Tilpasningsen het

    FIREALARM

    Interfaceunit

    Nr.

    No.

    UV Fire DetectionX2200

    Premier Controller

    Operator Interface

    Station

    running S3

    software

    Ver 2.8

    Ports

    Configuration (serial port)RS-485 serial Link (Modbus RTU)

    Redundant media ControlNet

    OPC

    option

    MIR Fire Detection

    X3301

    24 vdc

    power supply

    Battery PSM

    DCIO

    Module

    HC Gas Detection

    Eclipse

    Network

    Extender

    ARM

    Signal / Audible

    Devices

    SAM

    IDC

    Supervised

    Digital

    inputs

    Toxic Gas Detection

    DCU / DCUEX

    I/O Modules

    Relay

    AIM

    IPM

  • 7/25/2019 84084810 Fire and Gas Recovered

    17/32

    X3301 Multispectrum Infrared Flame Detector

    Extended Cone of Vision

    Combines the longest detection

    range with the best false alarm

    rejection capabilities

    a calibrated performance test that is

    automatically performed once per minute to

    verify complete detector operation

    capabilities. No testing with an external test

    lamp is required. The detector automatically

    performs the same test that a maintenance

    person with a test lamp would perform

    Automatic oi

    Magnetic oi / Manual oi

  • 7/25/2019 84084810 Fire and Gas Recovered

    18/32

    Smoke Detector

  • 7/25/2019 84084810 Fire and Gas Recovered

    19/32

    Ionization Smoke Detector

  • 7/25/2019 84084810 Fire and Gas Recovered

    20/32

  • 7/25/2019 84084810 Fire and Gas Recovered

    21/32

    Heat Detector

  • 7/25/2019 84084810 Fire and Gas Recovered

    22/32

    Fire Detection Systems

    Fusible loopSmoke detector UV/IR detector

    3IR detectorThermal detector

    Sprinkler

  • 7/25/2019 84084810 Fire and Gas Recovered

    23/32

    Suppression Systems

    TPP- EG LQ-MCC

    TCPP Control Room

    TCPP Deluge

    ATF

    Deluge

  • 7/25/2019 84084810 Fire and Gas Recovered

    24/32

    Fire & Gas Panel

    Mini-vesda for LQ MCC

    FGP#2 - Mimic PanelFGP#1FGP#3 TCPP Mimic Panel

    TPP FGP computer

    Fusible loop panel

  • 7/25/2019 84084810 Fire and Gas Recovered

    25/32

    Alarms

    Platform Emergency AlarmAbandon Platform Alarm

    Extinguishing Gas to be Released alarm

  • 7/25/2019 84084810 Fire and Gas Recovered

    26/32

    Emergency Manual operation

  • 7/25/2019 84084810 Fire and Gas Recovered

    27/32

    Enclosed Area Protection

  • 7/25/2019 84084810 Fire and Gas Recovered

    28/32

    Manual Release

  • 7/25/2019 84084810 Fire and Gas Recovered

    29/32

    Manual Release

  • 7/25/2019 84084810 Fire and Gas Recovered

    30/32

    FM-200 Bank

  • 7/25/2019 84084810 Fire and Gas Recovered

    31/32

    Emergency Beckons

  • 7/25/2019 84084810 Fire and Gas Recovered

    32/32