    8ME SYSTEM

    36 kV 2500 A 25 kA

    AIR INSULATED

    METAL ENCLOSED WITH HANDCART

    MEDIUM VOLTAGE CUBICLE

  • 7/30/2019 8me Metal Enclosed Eng

    2/8

    Medium Voltage (M.V.) Cubicles are one of the key points on uninterrupted energy & operational

    safety. For these purpose we manufacture 8ME-36R1 cubicles according to the IEC6271-200

    standards, those can be used in industrial plants & kiosk type transformer buildings. Cubicle is

    modular unit type & equipped either with vacuum type of SF6 gas type breaking system,

    withdrawable handcart & metal-clad system.

    Cubicle is built with 4 separate compartments; cable inlet, busbar, low voltage & breaker

    compartments. By this, during a fault, only the faulty area is defected & other compartments are

    protected.

    Vacuum breaker technology provides long term high performance.

    Easy assembly system of the cubicles & having withdrawable handcart provides fast intervention

    to the breaker during a fault.

    8 ME CUBICLES

    - Operator & operational safety

    - Maintenance free circuit components

    - Modular structure type & compatibility- Easy assembly at site

    - Expansion possibility to right side & left side

    - Possibility of adding new unit & deducting existing unit in future

    - It can be used on distribution systems by its safe operational features (type tested)

    8ME SYSTEM 36 kV 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

    GENERAL INFORMATION

  • 7/30/2019 8me Metal Enclosed Eng

    3/8

    Places Of Application

    - Rated voltages up to 36 kV

    - Rated short-circuit breaking currents up to 25 kA

    - Feeder and busbar rated currents up to 2500A

    8ME Type Cubicles Can Be Used At

    - Power stations, transformer stations and switching

    substations of public utilities

    - Cement industry

    - Iron and steelworks

    - Rolling mills

    - Mines

    - Chemical industry

    - Oil industry

    - Pipelines

    - Oshore installations

    - Electrochemical industry

    - Petrochemicals industry

    - Railway power supplies- Shipbuilding industry

    - Diesel power stations

    - Emergency power supplies

    - Airports

    - MV motor starter systems

    - Air Compressor Applications

    Advantages

    - Long term usage with maintenance free vacuum breaker & drive mechanism.

    - Handcart can be taken out of the cubicle by one person using the guidescrew mechanism

    - Usage of standard isolator

    - Usage of standard measurement transformer

    - Usage of standard circuit breakers

    - Maintenance and addition can easily been done by using the standard copper busbar.

    8ME SYSTEM 36 Kv 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

    PLACES OF APPLICATION

  • 7/30/2019 8me Metal Enclosed Eng

    4/8

    8ME series Cubicles had been designed to be used indoors. Protection level is IP4X.

    Cubicle Body

    It has been manufactured with 2-2, 5 mm thick galvanized metal sheets. The outer body & the base

    have earthing.

    Earthing System

    In 8ME metal body cubicles, in order to provide security during maintenance procedures, the chassis

    of the main circuit components & all the other components that requires earthing, which are

    normally accessible, have been connected directly to the earthing busbar, located in the cubicle.

    Each cubicles earthing busbar has been located & visible in the front side in order to have the

    continuity of the earthing. If more than 1 piece of these cubicles will be used to make a plant by xing

    them side by side, the earthing busbars are connected by bolts & it appears in the front of the cubicle

    group. This earthing busbar then connected to the systems earthing & by this the earthing

    procedure is completed.

    Mimic Diagram

    On the 8ME Metal Clad cubicles front panel, where control unit is located, there is a simple mimic

    diagram that can easily been understood. By this the location of the cubicles main circuit

    components can easily been identied.

    Operational & Maintenance Safety Points

    - Operation of the circuit breaker can be done only when

    the door is closed.

    - In order to open the door of the cubicle,

    the handcart should be separated & locked on that position.- Changing of the position of the handcart from separated

    position to operation can be done only when the

    door is closed.

    - All locks can be done only by a mechanically

    working special key.

    - The cubicles body is completely closed all

    around on all the operation modes. The

    external security is provided by this.

    - When the handcart set to TEST position, inner

    security is provided by the automatically

    closing metal curtains.

    STRUCTURAL SPECIFICATIONS

    8ME SYSTEM 36 Kv 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

  • 7/30/2019 8me Metal Enclosed Eng

    5/8

    STRUCTURAL SPECIFICATIONS

    1-Main Busbar compartment

    2-Current Transformer

    3-L.V. & Protection Relay Compartment

    4-Vacuum Breaker

    5-Breaker Handcart6-Pressure Releasing Plate

    7-Earthing switch

    8-M.V. Cable connection

    9-Busbar Bushing

    10-Operation mechanism of earthing switch.

    8ME SYSTEM 36 Kv 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

    8ME 36 R1 METAL ENCLOSED PANEL

    DOOR OPENED FRONT VIEW DOOR CLOSED FRONT VIEW

  • 7/30/2019 8me Metal Enclosed Eng

    6/8

    8ME SYSTEM 36 Kv 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

    Outgoing Cubicle

    Incoming Cubicle with Breaker Incoming Cubicle with

    Breaker & Potential TransformerMeasuring Cubicle

    Coupling Cubicle Bus Riser Cubicle

    8ME SYSTEM 36 Kv 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

    STRUCTURAL SPECIFICATIONS

    VCB & SF6 : Vacuum & SF6 Breaker ES : Earthing Switch

    CT : Current Transformer VT : Voltage Transformer

  • 7/30/2019 8me Metal Enclosed Eng

    7/8

    TECHNICAL SPECIFICATIONS OF 8ME CUBICLES

    Cubicle Type

    Rated Voltage

    Rated Current

    Rated Frequency

    Rated Short Time withstand current

    Rated Peak withstand current

    Rated Insulation Level

    Power Frequency

    (phase to earth / across open contacts)

    Lightning impulse withstand voltage

    Rated Short Circuit Continuous TimeMaximum Operating Temperature

    Protection Degree

    Main Busbar Material

    Cubicle Sizes

    8ME-36R1

    36 kV

    1250-2000-2500 A

    50-60 Hz25 kA (1s)

    63 kA

    120 kV

    1s45C

    IP4X

    Electrolytic Copper

    W1600 X D1800 X H2500

    70 kV

    TECHNICAL SPECIFICATIONS

    8ME SYSTEM 36 Kv 25kA 2500 A Air Insulated Metal Enclosed M.V.Cubicles With Handcart

  • 7/30/2019 8me Metal Enclosed Eng

    8/8

    www.egesim.com.tre g e s i m @ e g e s i m . c o m . t r

    EGESIM HIGH TECHNOLOGYElectric & Electronic Co. Ltd.

    Istanbul FactoryGebze Organized Industrial Zone400 Street No:410 41480Gebze-Kocaeli/TURKEYTel: +90 262 751 28 00 PbxFax: +90 262 751 27 28

    EGESIM ELECTRIC &AUTOMATION SYSTEMS Co.Ltd.

    EGESIM ELECTRIC Co.Ltd.

    Izmir office1204 Street No.41/1-I 35110Yenisehir IZMIR / TURKEYTel +90 232 433 30 25 PbxFax +90 232 459 90 42

    Izmir FactoryAtaturk Bulvari No.4Menemen Free Zone 35660Menemen IZMIR / TURKEYTel +90 232 842 60 85 PbxFax +90 232 842 60 86

    GERMANY / Cologne (Office)

    Schanzenstrasse 2251063 KlnGERMANYTel +49 (0)221 65092750Fax +49 (0)221 65092755

    RUSSIA / Moscow (Office)JORDAN / Amman(Middle East Office)

    PO. Box 608,Stari Oskol 12,Russia 309 512Tel: +7 909 697 07 23

    Shami Plaza Building,Ilya Abu Madi Street,Shmaisani, P.O.Box:942325,Amman 11194 JORDAN