Page 1: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

04/19/23 1Variable Speed LowdownVariable Speed Lowdown

Page 2: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

TYPICAL EUROPEAN SYSTEM

TRV’s, No T-stats

Pump runs 24/7 (6k hrs)

TRV’s modulate

Page 3: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

TYPICAL US SYSTEM

Series loop, fin-tube baseboard CI bb/radiators/convectors Radiant floor heating

Mutliple zones, circs or ZV’s

Approx 2,100 – 2,500 hrs of operation

Page 4: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

WHY USE A VARIABLE SPEED CIRCULATOR? Good question…

Best applications… Zone valve or RFH Zone pump?

Electrical savings?

Page 5: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

5 007’s @ 80W each = 400 Watts

400 Watts ÷ 1000 = 0.4 kW

ELECTRICAL SAVINGS????

Page 6: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

04/19/23TACO – EMERSON SWAN MEETING 6

Page 7: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

5 007’s @ 80W each = 400 Watts

400 Watts ÷ 1000 = 0.4 kW

0.4 kW × 2,500 “on” hrs = 1,000 kWh

1,000 kWh × 15¢/kWh = $150.00/yr

ELECTRICAL SAVINGS????

Page 8: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

1 007 (80W) + 5 Zone Sentry zone valve (1.44W each)= 87.2 Watts

87.2 Watts ÷ 1000 = 0.0872 kW

0.0872 kW × 2,500 “on” hrs = 218 kWh

218 kWh × 15¢/kWh = $32.25/yr

WITH ZONE VALVES…

Page 9: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

1 Pump (20W) + 5 Zone Sentries (1.44W each)= 27.2 Watts

27.2 Watts ÷ 1000 = 0.0272 kW

0.0272 kW × 2,500 “on” hrs = 68 kWh

68 kWh × 15¢/kWh = $10.20/yr

WITH SUPER DUPER ECM…

Page 10: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

5 ZONE SYSTEM

70,000 BTUH

7 GPM @ 5’ head

Where does systemreally work?

Page 11: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

• GPM = BTUH

• T = BTUH

• T = 70,000

• < 14.50

T × 500

GPM 500

9.5 500

NUMBERS DON’T LIE…

Page 12: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

1 ZONE CALLING

10,000 BTUH

1 GPM @ 5’ head

Where does itreally work?

Page 13: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

• GPM = BTUH

• T = BTUH

• T = 10,000

• 100

T × 500

GPM 500

2 500

NUMBERS STILL DON’T LIE…

Page 14: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

The Result?

And And when it’swhen it’s353500 out? out?

And And when it’swhen it’s353500 out? out?

Page 15: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

SO WHAT SO WHAT ABOUT THE ABOUT THE

VR 1816?VR 1816?

04/19/23 15

Page 16: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

04/19/23 16

Page 17: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

04/19/23 17

Page 18: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

04/19/23 18

Page 19: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate
Page 20: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

SO, SO, PROGRAMMING PROGRAMMING

THE VR THE VR 1816????1816????

04/19/23 20

Page 21: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

KEEP IT SIMPLE…

CP Settings – zone pump: 85’ total length = CP I (5’ hd) 165’ total length = CP II (10’ hd) 250’ total length = CP III (15’ hd)

Based on ML × 1.5 × .04

04/19/23TACO – EMERSON SWAN MEETING 21

Page 22: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

04/19/23 22

Page 23: 9/19/2015 1 Variable Speed Lowdown. TYPICAL EUROPEAN SYSTEM  TRV’s, No T-stats  Pump runs 24/7 (6k hrs)  TRV’s modulate

STEPLESS/INFINITE ADJUST

Min = 003 Low = 006 Med = 007/0015 Low High = 008/0015 Med Max = 0015 Hi Or for guys who actually

calculate flow & head…