04/19/23 1Variable Speed LowdownVariable Speed Lowdown
TYPICAL EUROPEAN SYSTEM
TRV’s, No T-stats
Pump runs 24/7 (6k hrs)
TRV’s modulate
TYPICAL US SYSTEM
Series loop, fin-tube baseboard CI bb/radiators/convectors Radiant floor heating
Mutliple zones, circs or ZV’s
Approx 2,100 – 2,500 hrs of operation
WHY USE A VARIABLE SPEED CIRCULATOR? Good question…
Best applications… Zone valve or RFH Zone pump?
Electrical savings?
5 007’s @ 80W each = 400 Watts
400 Watts ÷ 1000 = 0.4 kW
ELECTRICAL SAVINGS????
04/19/23TACO – EMERSON SWAN MEETING 6
5 007’s @ 80W each = 400 Watts
400 Watts ÷ 1000 = 0.4 kW
0.4 kW × 2,500 “on” hrs = 1,000 kWh
1,000 kWh × 15¢/kWh = $150.00/yr
ELECTRICAL SAVINGS????
1 007 (80W) + 5 Zone Sentry zone valve (1.44W each)= 87.2 Watts
87.2 Watts ÷ 1000 = 0.0872 kW
0.0872 kW × 2,500 “on” hrs = 218 kWh
218 kWh × 15¢/kWh = $32.25/yr
WITH ZONE VALVES…
1 Pump (20W) + 5 Zone Sentries (1.44W each)= 27.2 Watts
27.2 Watts ÷ 1000 = 0.0272 kW
0.0272 kW × 2,500 “on” hrs = 68 kWh
68 kWh × 15¢/kWh = $10.20/yr
WITH SUPER DUPER ECM…
5 ZONE SYSTEM
70,000 BTUH
7 GPM @ 5’ head
Where does systemreally work?
• GPM = BTUH
• T = BTUH
• T = 70,000
• < 14.50
T × 500
GPM 500
9.5 500
NUMBERS DON’T LIE…
1 ZONE CALLING
10,000 BTUH
1 GPM @ 5’ head
Where does itreally work?
• GPM = BTUH
• T = BTUH
• T = 10,000
• 100
T × 500
GPM 500
2 500
NUMBERS STILL DON’T LIE…
The Result?
And And when it’swhen it’s353500 out? out?
And And when it’swhen it’s353500 out? out?
SO WHAT SO WHAT ABOUT THE ABOUT THE
VR 1816?VR 1816?
04/19/23 15
04/19/23 16
04/19/23 17
04/19/23 18
SO, SO, PROGRAMMING PROGRAMMING
THE VR THE VR 1816????1816????
04/19/23 20
KEEP IT SIMPLE…
CP Settings – zone pump: 85’ total length = CP I (5’ hd) 165’ total length = CP II (10’ hd) 250’ total length = CP III (15’ hd)
Based on ML × 1.5 × .04
04/19/23TACO – EMERSON SWAN MEETING 21
04/19/23 22
STEPLESS/INFINITE ADJUST
Min = 003 Low = 006 Med = 007/0015 Low High = 008/0015 Med Max = 0015 Hi Or for guys who actually
calculate flow & head…
04/19/23TACO – EMERSON SWAN MEETING 23