a new control scheme for pid load frequency controller of ......3.2. design of the controller g c...

10
A new control scheme for PID load frequency controller of single-area and multi-area power systems Dola Gobinda Padhan n , Somanath Majhi Department of Electronics and Electrical Engineering, Indian Institute of Technology Guwahati, Guwahati 781039, India article info Article history: Received 5 April 2012 Received in revised form 11 October 2012 Accepted 19 October 2012 Available online 7 November 2012 This paper was recommended for publication by Dr. Ahmad B. Rad. Keywords: LFC PID Laurent series Disturbance rejection Time delay Relay feedback identification abstract A new control structure with a tuning method to design a PID load frequency controller for power systems is presented. Initially, the controller is designed for single area power system, then it is extended to multi-area case. The controller parameters are obtained by expanding controller transfer function using Laurent series. Relay based identification technique is adopted to estimate power system dynamics. Robustness studies on stability and performance are provided, with respect to uncertainties in the plant parameters. The proposed scheme ensures that overall system remains asymptotically stable for all bounded uncertainties and for system oscillations. Simulation results show the feasibility of the approach and the proposed method improves the load disturbance rejection performance significantly even in the presence of the uncertainties in plant parameters. & 2012 ISA. Published by Elsevier Ltd. All rights reserved. 1. Introduction The active power and frequency control is referred to as load frequency control (LFC) which has been used as an effective ancillary service in power systems for many years [1]. Several papers have been published to address the LFC [24]. For large scale power systems with interconnected areas, LFC is important to keep the system frequency and the inter-area tie-line power as near to the scheduled values as possible. In addition, the LFC has to be robust against unknown external disturbances and system model and parameter uncertainties. Many control strategies for load frequency control in power systems had been proposed by researchers over the past decades [521]. This extensive research is due to fact that LFC constitutes an important function of power system operation where the main objective is to regulate the output power of each generator at prescribed levels while keeping the frequency fluctuations within predetermined limits. Most of the reported works of the LFC problem have been tested for their robustness against large step load change. However, very few of the published researches deal with parameter uncertainties. In this paper, a design method for the LFC PID is proposed, which is able to consider uncertainties in power systems. Even though many advanced control theories have been established, most industrial controllers still use conventional applications such as PI or PID. PID controllers are preferred due to their simple structures, robustness, applicability over a wide range and easy in implementation on analog or digital platform [22]. We espe- cially pay attention in modeling of the power system dynamics using relay feedback identification method and PID controller design for the developed model. In the proposed method, a Laurent series has been used in order to derive the expression for the controller’s parameters. The proposed scheme leads to substantial control performance improvement, especially for the disturbance rejection. Simulation examples are provided to show the superiority of the proposed design method, compared with recently reported methods. For clear interpretation, the proposed control structure is presented in Section 2. The modeling of power system dynamics, controller design, simulation results and robustness analysis for single area power system are given in Section 3. Multi-area power system is addressed in Section 4 followed by the conclusions in Section 5. 2. Proposed control structure The proposed control structure for LFC is shown in Fig. 1 which has only one controller (G c ). Unlike the conventional LFC control Contents lists available at SciVerse ScienceDirect journal homepage: www.elsevier.com/locate/isatrans ISA Transactions 0019-0578/$ - see front matter & 2012 ISA. Published by Elsevier Ltd. All rights reserved. http://dx.doi.org/10.1016/j.isatra.2012.10.003 n Corresponding author. Tel.: þ91 361 2582508; fax: þ91 361 2690762. E-mail addresses: [email protected] (D.G. Padhan), [email protected] (S. Majhi). ISA Transactions 52 (2013) 242–251

Upload: others

Post on 13-Mar-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

ISA Transactions 52 (2013) 242–251

Contents lists available at SciVerse ScienceDirect

ISA Transactions

0019-05

http://d

n Corr

E-m

smajhi@

journal homepage: www.elsevier.com/locate/isatrans

A new control scheme for PID load frequency controller of single-areaand multi-area power systems

Dola Gobinda Padhan n, Somanath Majhi

Department of Electronics and Electrical Engineering, Indian Institute of Technology Guwahati, Guwahati 781039, India

a r t i c l e i n f o

Article history:

Received 5 April 2012

Received in revised form

11 October 2012

Accepted 19 October 2012Available online 7 November 2012

This paper was recommended for

publication by Dr. Ahmad B. Rad.

Keywords:

LFC

PID

Laurent series

Disturbance rejection

Time delay

Relay feedback identification

78/$ - see front matter & 2012 ISA. Published

x.doi.org/10.1016/j.isatra.2012.10.003

esponding author. Tel.: þ91 361 2582508; fa

ail addresses: [email protected] (D.G. Padhan

iitg.ernet.in (S. Majhi).

a b s t r a c t

A new control structure with a tuning method to design a PID load frequency controller for power

systems is presented. Initially, the controller is designed for single area power system, then it is

extended to multi-area case. The controller parameters are obtained by expanding controller transfer

function using Laurent series. Relay based identification technique is adopted to estimate power system

dynamics. Robustness studies on stability and performance are provided, with respect to uncertainties

in the plant parameters. The proposed scheme ensures that overall system remains asymptotically

stable for all bounded uncertainties and for system oscillations. Simulation results show the feasibility

of the approach and the proposed method improves the load disturbance rejection performance

significantly even in the presence of the uncertainties in plant parameters.

& 2012 ISA. Published by Elsevier Ltd. All rights reserved.

1. Introduction

The active power and frequency control is referred to as loadfrequency control (LFC) which has been used as an effectiveancillary service in power systems for many years [1]. Severalpapers have been published to address the LFC [2–4]. For largescale power systems with interconnected areas, LFC is importantto keep the system frequency and the inter-area tie-line power asnear to the scheduled values as possible. In addition, the LFC hasto be robust against unknown external disturbances and systemmodel and parameter uncertainties. Many control strategies forload frequency control in power systems had been proposed byresearchers over the past decades [5–21]. This extensive researchis due to fact that LFC constitutes an important function of powersystem operation where the main objective is to regulate theoutput power of each generator at prescribed levels while keepingthe frequency fluctuations within predetermined limits. Most ofthe reported works of the LFC problem have been tested for theirrobustness against large step load change. However, very few ofthe published researches deal with parameter uncertainties. Inthis paper, a design method for the LFC PID is proposed, which isable to consider uncertainties in power systems. Even though

by Elsevier Ltd. All rights reserve

x: þ91 361 2690762.

),

many advanced control theories have been established, mostindustrial controllers still use conventional applications such asPI or PID. PID controllers are preferred due to their simplestructures, robustness, applicability over a wide range and easyin implementation on analog or digital platform [22]. We espe-cially pay attention in modeling of the power system dynamicsusing relay feedback identification method and PID controllerdesign for the developed model. In the proposed method, aLaurent series has been used in order to derive the expressionfor the controller’s parameters. The proposed scheme leads tosubstantial control performance improvement, especially for thedisturbance rejection. Simulation examples are provided to showthe superiority of the proposed design method, compared withrecently reported methods.

For clear interpretation, the proposed control structure ispresented in Section 2. The modeling of power system dynamics,controller design, simulation results and robustness analysis forsingle area power system are given in Section 3. Multi-area powersystem is addressed in Section 4 followed by the conclusions inSection 5.

2. Proposed control structure

The proposed control structure for LFC is shown in Fig. 1 whichhas only one controller (Gc). Unlike the conventional LFC control

d.

Page 2: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

+

+

+

Fig. 1. Proposed control structure.

1 R

dP

f11g

G

GT s

11t

T

GT s

u GPGXGovernor Turbine

Load & Machine

1P

pP

KG

T s

DroopCharacteristic

+ +

Fig. 2. Block diagram of a single-area power system.

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251 243

structure, the proposed structure uses the controller Gc in thefeedback path. Although, Gc is primarily meant for load distur-bance rejection, it also takes part in stabilizing the oscillatoryprocess in the loop. G represents the transfer function of overallplant. ym is the time delay part and Gm is the transfer function ofthe delay free part of the plant model.

The closed-loop transfer function relating the output (y) to thereference (r) can be written as

y

GþGGcGme�yms

Gmð1þGGcÞð1Þ

When the model used exactly matches the plant dynamics,(1) reduces to

y

r¼ e�yms ð2Þ

this indicates the system output can reach the setpoint value justafter the process time delay. It is to be noted that the block V

primarily helps in improving the overall servo performance of theclosed-loop system. It is popularly known that for LFC design, theload disturbance rejection is more important than the setpointresponse [15]. Therefore, the controller Gc has been designedmainly for power system load disturbances.

3. Single area power system

3.1. Modeling of power system dynamics

A linear model of a single-area power system is shown in Fig 2,in which a single generator is supplying power to a single-area. Inthe present work, non-reheat turbine (NRT) and reheat turbine(RT) are considered for LFC modeling. The plant model used forLFC without droop characteristics is

G¼ GgGtGp ð3Þ

where Gg, Gt and Gp are the dynamics of the governor, turbine andload&machine, respectively. The governor dynamics Gg ¼ 1=ðTGsþ1Þand the Load and machine dynamics, Gp ¼ Kp=ðTpsþ1Þ. Non-reheatturbines are first-order units. The dynamics of the non-reheat turbineis represented as Gt ¼ 1=ðTT sþ1Þ. Reheat turbines are modeled assecond-order units, since they have different stages due to high andlow steam pressure. The transfer function of the reheat turbine is inthe form of Gt ¼ ðcTrsþ1Þ=ðTrsþ1ÞðTT sþ1Þ where Tr stands for thelow pressure reheat time and c is the portion of the power generatedby the reheat turbine in the total generated power.

The plant model used for LFC with droop characteristic is

G¼GgGtGp

1þGgGtGp=Rð4Þ

For LFC, G generally results in higher order plant models whichmay be inconvenient for controller design. There are manyprocess identification techniques suggested by various researchers[23–25]. In control theory, Majhi [26] introduces a relay basedidentification method for reducing a higher order process dynamicsto a low order dynamics with time delay. This technique has beenmodified and applied for the first time in power systems to design anew PID load frequency controller for single-area and multi-areapower system. Therefore, these higher order models are approxi-mated by lower order transfer functions with time delay using relaybased identification method [26]. Eqs. (3) and (4) can be representedby the second order transfer function model

G¼ke�yms

ðT1sþ1ÞðT2sþ1Þð5Þ

Its state space equations in the Jordan canonical form become

_xðtÞ ¼ AxðtÞþbuðt�ymÞ ð6Þ

yðtÞ ¼ cxðtÞ ð7Þ

where

�1T1

0

0 �1T2

24

35, b¼

1

1

� �, c¼

k

T1�T2½1 �1�

when a relay test is performed with a symmetrical relay of height7h, then the expression for the limit cycle output for 0rtrym is

yðtÞ ¼ ceAtxð0ÞþcA�1ðeAt�IÞbh ð8Þ

Let the half period of the limit cycle output be t. Then the expressionfor the limit cycle output for ymrtrt is

yðtÞ ¼ ceAðt�ymÞxðymÞ�cA�1ðeAðt�ymÞ�IÞbh ð9Þ

The condition for a limit cycle output can be written as

yð0Þ ¼ cxð0Þ ¼ �yðtÞ ¼ 0 ð10Þ

Substitution of t¼ t in (9) and use of (8) gives the initial value of thecycling states

xð0Þ ¼ ðIþeAtÞ�1A�1ð2eAðt�ymÞ�eAt�IÞbh ð11Þ

When tp is the time instant at which the positive peak output occursand tpZym, then the expression of the peak output Ap becomes

Ap ¼ cðeAðtp�ymÞxðymÞ�A�1ðeAðtp�ymÞ�IÞbhÞ ð12Þ

and the expression for the peak time becomes

tp ¼ ymþT1T2

T1�T2ln

1þe�t=T1

1þe�t=T2

� �ð13Þ

Substitution of A, b and c in (11) and (12) gives

T1ð1þe�t=T2 Þð2e�ðt�ymÞ=T1�e�t=T1�1Þ�T2ð1þe�t=T1 Þ

� ð2e�ðt�ymÞ=T2�e�t=T2�1Þ ¼ 0 ð14Þ

Ap ¼ khð2ð1þe�t=T1 Þ�T1=ðT1�T2Þð1þe�t=T2 Þ

T2=ðT1�T2Þ�1Þ ð15Þ

Eqs. (13)–(15) are solved simultaneously to estimate ym, T1 and T2

from the measurements of t, Ap and tp. The steady state gain k isassumed to be known a priori or can be estimated from a step signaltest. Care has been taken to solve the set of non-linear equations sothat convergence may not take place to a false solution.

110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
Page 3: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

−20 0 20 40 60 80 100 120−70

−60

−50

−40

−30

−20

−10

0

10

Real Axis

Imag

inar

y A

xis

IdentifiedActual

Fig. 3. Nyquist plots for the power system with NRTWD for example-1.

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251244

3.2. Design of the controller Gc

For easy implementation of PID controller, Gc is considered inthe following form:

Gc ¼ Kc 1þ1

Tisþ

Tds

eTdsþ1

� �ð16Þ

where the derivative filter constant is typically fixed by themanufacture [27] and e¼ 0:1 throughout the paper. In theproposed control structure shown in Fig. 1, the nominal comple-mentary sensitivity function for load disturbance rejection can beobtained as

T ¼GGc

1þGGcð17Þ

In order to reject a step change in load of power system, theasymptotic constraint

lims-� 1

T1,� 1

T2

ð1�TÞ ¼ 0 ð18Þ

should be satisfied so that the closed-loop internal stability can beachieved. The desired closed-loop complementary sensitivityfunction is proposed as

T ¼ða2s2þa1sþ1Þ

ðlsþ1Þ4e�yms ð19Þ

where l is a tuning parameter for obtaining the desirableperformance of the power system. a1 and a2 can be obtainedfrom (18) and (19) as a1 ¼ ðT

21ðð1�l=T1Þ

4e�ym=T1�1Þ�T22ðð1�l=T2Þ

4

e�ym=T2�1ÞÞ=ðT2�T1Þ and a2 ¼ T22ðð1�l=T2Þ

4e�ym=T2�1ÞþT2a1.Using (17) and (19), we get

Gc ¼ðT1sþ1ÞðT2sþ1Þða2s2þa1sþ1Þ

k½ðlsþ1Þ4�e�ymsða2s2þa1sþ1Þ�ð20Þ

The resulting controller Gc does not have a standard PID controllerform. Therefore, in order to produce the desired disturbancerejection controller, the following procedure is employed. Gc canbe approximated by an approximation series in a complex plane,by expanding it near vicinity of zero. Laurent series has been usedfor approximation instead of Taylor or MacLaurin series (whereterms with s0, s1, and s2 appear), Laurent series has been chosen(because the controller is given by (16), where terms with s0, s�1,and s1 appear, the series no longer belongs to the Taylor orMaclaurin type, but becomes Laurent type, with other coefficientsas zeros) because it addresses complex coefficients that areimportant especially to investigate the behavior of functions nearsingularity. A practical desired disturbance rejection controllershould possess an integral characteristic to eliminate any systemoutput deviation arising from load disturbances. Therefore, let

Gc ¼f ðsÞ

sð21Þ

or

Gc ¼gðsÞ

sð1þbsÞð22Þ

Now, expanding Gc in the vicinity of zero by Laurent series

Gc ¼1

sðbsþ1Þ� � � þgð0Þþg0ð0Þsþ g00ð0Þs2

2!þ � � �

� �ð23Þ

The parameters of Gc obtained from (16) and (23)

Kc ¼ g0ð0ÞKc

Ti¼ gð0Þ

KcTd ¼g00ð0Þ

2!

8>>>>><>>>>>:

ð24Þ

where gð0Þ ¼ f ð0Þ, g0ð0Þ ¼ bf ð0Þþ f 0ð0Þ, g00ð0Þ ¼ 2bf 0ð0Þþ f 00ð0Þ, f ð0Þ ¼1=kð4l�a1þymÞ,

f 0ð0Þ ¼T1ymþT2ymþðy

2m=2Þ�T2a1þ4a1l�a2

1þa2þ4T1l�T1a1�6l2þ4T2l

kð16l2�8a1lþ8ymlþa2

1�2yma1þy2mÞ

and

f 00ð0Þ ¼

48yma2lþ72yma1l2�24yma2a1þ48y2

ma1lþ24T2ly2m

þ48T2la2þ6T2y3mþ48a2l

2

þ48T2lyma1�12T2a2a1þ264T1l2a1�24T1T2a1ym

�96T1a21lþ24T1ly

2mþ48T1la2

þ12T1T2y2mþ48T1lyma1þ12T1T2a2

1þ96T1T2yml

þ192T1T2l2�72T2l

2ym�96T2a21l

�96T1T2a1l�48yma21lþ6T1y

3m�48a2la1þ264T2l

2a1

þ12T2a31þ12yma3

1þ12a22

þy4m�12T1a2a1þ12T2yma2�288T2l

3�288T1l

3

�240a1l3þ12T1yma2þ12T1a3

1

�72y2ml

2�48yml

3�12y2

ma21þ240l4

�6T2y2ma1

�6T1y2ma1�12T1yma2

1þ72l2a12

�72T1l2ym�8y3

mlþ2y3ma1þ12y2

ma2�12T2yma21

0BBBBBBBBBBBBBBBBBBBBBBBBBBBBBBB@

1CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCA

384kl3�288ka1l

2þ288kyml

2þ72kla2

1

�144klyma1þ72ky2ml�6ka3

1

þ18kyma21�18ky2

ma1þ6ky3m

0BB@

1CCA

Thus, Kc, Ti and Td can be obtained from (24).

3.3. Simulation results for single area power system

Example 1. Consider a power system with a non-reheatedturbine and a reheated turbine studied by Tan [17]. The modelparameters are

Non-reheated turbine: KP¼120, TP¼20, TT¼0.3, TG¼0.08,R¼2.4.Reheated turbine: KP¼120, TP¼20, TT¼0.3, TG¼0.08, R¼2.4,Tr¼4.2 and c¼0.35.

The Nyquist plots of the identified and actual models for the non-reheat turbine without droop (NRTWD) are shown in Fig. 3 toillustrate the accuracy of the identification method. By selectingsuitable value of l and b, the controller settings (see Table 1)

110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
Page 4: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

Table 1

Identified model Controller parameters

NRTWD 120e�0:4626s

ð28:4952sþ1Þð0:2202sþ1Þ

Kc ¼ 1:0326,Ti ¼ 1:2116,Td ¼ 0:3420

NRTD 250e�0:05s

2:028s2þ12:765sþ106:2

Kc ¼ 1:4978,Ti ¼ 1:1481,Td ¼ 0:1574

RTWD 120e�0:541s

ð23:2137sþ1Þð0:9057sþ1Þ

Kc ¼ 3:6317,Ti ¼ 1:0998,Td ¼ 0:4828

RTD 235:3e�0:035s

1:79s2þ16:9sþ100

Kc ¼ 6:164,Ti ¼ 3:1934,Td ¼ 0:1882

NRTWD, non-reheat turbine without droop; NRTD, non-reheat turbine with

droop; RTWD, reheat turbine without droop; RTD, reheat turbine with droop.

0 2 4 6 8 10 12 14 16 18 20−18

−16

−14

−12

−10

−8

−6

−4

−2

0

2 x 10−3

time in sec

Δ f

(Hz)

Proposed (Nominal)Tan (Nominal)Proposed (+ 50% Variation in KP, TP, TT, TG )Tan (+ 50% Variation in KP, TP, TT, TG)

Fig. 4. Frequency deviation for NRTWD.

0 2 4 6 8 10 12 14 16 18 20−18

−16

−14

−12

−10

−8

−6

−4

−2

0

2x 10−3

time in sec

Δ f (

Hz)

Proposed (Nominal)Tan (Nominal)Proposed (− 50% Variation in TP)Tan (− 50% Variation in TP)

Fig. 5. Frequency deviation for NRTD.

0 2 4 6 8 10 12 14 16 18 20−14

−12

−10

−8

−6

−4

−2

0

2 x 10−3

time in sec

Δ f (

Hz)

Proposed (Nominal)Tan (Nominal)Proposed (+ 50% Variation in TP)Tan (+ 50% Variation in TP)

Fig. 6. Frequency deviation for RTWD.

0 2 4 6 8 10 12 14 16 18 20−10

−8

−6

−4

−2

0

2x 10−3

time in sec

Δ f (

Hz)

Proposed (Nominal)Tan (Nominal)Proposed (+ 50% Variation in TP)Tan (+ 50% Variation in TP)

Fig. 7. Frequency deviation for RTD.

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251 245

for the power system with non-reheated and reheated turbinescan be obtained using (24). By the help of extensive simulationstudy, l¼ 0:13 and b¼ 0:012 for NRTWD, l¼ 0:11 and b¼ 1 forNRTD, l¼ 0:05 and b¼ 0:0035 for RTWD and l¼ 0:1 and b¼ 3for RTD. Figs. 4–7 show the frequency changes of the powersystem following a load demand DPd ¼ 0:01. The stabilityrobustness is tested by changing the parameters (KP, TP, TT,TG) of the system by 750%. From the simulation results, it isevident that the proposed method gives improved performancethan Tan’s method.

Example 2. Consider a power system with a non-reheatedturbine studied by Khodabakhshian and Edrisi [15]. The modelparameters are KP¼1.25, TP¼12.5, TT¼0.5, TG¼0.2, R¼0.05.

The Nyquist plots of the identified and actual models areshown in Fig. 8 to illustrate the accuracy of the identificationmethod. The PID controller parameters in the case of Khoda-bakhshian and Edrisi are Td¼0.01, Kp¼36.22, Ki¼2.77 andKd¼19.6. For the proposed method, the controller parametersare obtained as Kc¼55.2051, Ti¼1.1797, Td¼0.5173 by choos-ing l¼ 0:19 and b¼ 0:3. With these controller settings, a loaddemand DPd ¼ 0:02 is introduced at t¼1 s. The correspondingfrequency deviations are shown in Fig. 9. Now, to test therobustness of the systems, �20% variation in TP and þ10%variation in KP have been considered simultaneously. Thefrequency deviations for perturbed systems are given inFig. 10. From the simulation results, it is clear that the proposedmethod gives smaller undershoot and settling time than Kho-dabakhshian and Edrisi’s method.

110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
110
Highlight
Page 5: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

−0.05 −0.04 −0.03 −0.02 −0.01 0 0.01 0.02 0.03 0.04 0.05−0.08

−0.07

−0.06

−0.05

−0.04

−0.03

−0.02

−0.01

0

0.01

Real Axis

Imag

inar

y A

xis

IdentifiedActual

Fig. 8. Nyquist plots for the power system with NRTD for example-2.

0 5 10 15 20 25 30−6

−5

−4

−3

−2

−1

0

1

2 x 10−4

time in sec

Δ f (

Hz)

ProposedKhodabakhshian and Edrisi

Fig. 9. Frequency deviations for nominal systems.

0 5 10 15 20 25 30−7

−6

−5

−4

−3

−2

−1

0

1

2 x 10−4

time in sec

Δ f (

Hz)

ProposedKhodabakhshian and Edrisi

Fig. 10. Frequency deviations for perturbed systems.

0 5 10 15 20 25 30−10

−8

−6

−4

−2

0

2x 10−4

time in sec

Δ f (

Hz)

abc

Fig. 11. Impact of saturation on frequency deviations: saturation limit (a) 0.03,

(b) 0.04 and (c) 0.05.

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251246

3.4. Impact of saturation, windup and derivative kick

Consider the case of a power system with a non-reheatedturbine without droop characteristic. The model parameters aresame as that of example-2. For the proposed method, in order toget satisfactory closed-loop responses, the controller parametersare considered as Kc¼41.2454, Ti¼1.7243, Td¼0.4889. With anactuator saturation non-linear element given by saturation limits0.03, 0.04 and 0.05, the related responses of the system are shownin Figs. 11 and 12. When there is an initial load change, the errorsignal is initially so large that the control signal quickly reachesits actuator saturation limit. Even when the output signal reachesthe reference value, which gives a negative error signal due to thelarge value of the integrator output. The control signal stillremains at the saturation value, which causes the output of thesystem to continuously increase until the negative action of theerror signal begins to have effect. This phenomenon is referred toas the integrator windup action, which is undesirable in controlapplications.

When the output saturates, the integral is recomputed so thatits new value gives an output at the saturation limit. The rate atwhich the controller output is reset is governed by the feedbackgain, 1=Tt , where Tt can be interpreted as the time constant

(tracking time constant), which determines how quickly theintegral is reset. When introducing anti-windup in power systemswith derivative action, some care must be taken. If Tt is chosen toosmall, the errors can cause saturation of the output, whichaccidentally resets the integrator. Tt should be larger than Td

and smaller than Ti. For different Tt, the output signals arecompared in Fig. 13. It can be seen that for smaller values of Tt,the windup phenomenon can be reduced more significantly.

In industrial applications, the pure derivative action is neverused, due to the derivative kick produced in the control signal andto the undesirable noise amplification. It is usually cascaded by afirst-order low pass filter. The effect of derivative filter onfrequency deviations and control signals are shown in Figs. 14and 15, respectively.

3.5. Robustness analysis

A study of robustness analysis is an important task in controlsystem design because the behaviour of the real system is almostalways different from the behavior of the model. The notion ofrobustness expresses the capability of a system to be insensitiveto the effects of parameters variability. From (1), it is observed

110
Highlight
110
Highlight
Page 6: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

0 5 10 15 20 25 30 35 40 45 50−8

−6

−4

−2

0

2

4

6x 10−4

time in sec

Δ f (

Hz)

abc

Fig. 13. Effect of tracking time on frequency deviations: (a) 10 s, (b) 6 s and (c) 1 s.

0 5 10 15 20 25 30−7

−6

−5

−4

−3

−2

−1

0

1

2x 10−4

time in sec

Δ f (

Hz)

ab

Fig. 14. Frequency deviations: (a) with derivative filter and (b) without derivative

filter.

0 5 10 15 20 25 300

0.01

0.02

0.03

0.04

0.05

0.06

time in sec

Con

trol v

aria

ble

(u)

ab

Fig. 15. Control efforts: (a) with derivative filter and (b) without derivative filter.

0 5 10 15 20 25 300

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0.04

0.045

0.05

time in sec

Con

trol v

aria

ble

(u)

abc

Fig. 12. Impact of saturation on control efforts: saturation limit (a) 0.03, (b) 0.04

and (c) 0.05.

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251 247

that the robust control performances can be studied by analyzingGc as it affects the process model G in a single feedback path. Thetype of uncertainties affecting the design of Gc are the parametricuncertainties such as uncertainty in process gain, time constantand time delay.

According to the Small gain theorem [28], the closed loopsystem for the load disturbance rejection is robustly stable if andonly if

JDmðsÞTðsÞJ1o1 ð25Þ

where TðsÞ is the closed loop complementary sensitivity functionand DmðsÞ is the process multiplicative uncertainty i.e.DmðsÞ ¼ 9ðGðsÞ� ~GmðsÞÞ= ~GmðsÞ9 where ~GmðsÞ ¼ GmðsÞe�yms. In orderto show the robustness analysis more qualitatively, consider theprocess for which the closed-loop complementary sensitivityfunction is

T ¼kKcð1þTisþTiTdð1þeÞs2Þe�yms

ð1þðT1þT2ÞsþT1T2s2ÞðTisþeTiTds2ÞþkKcð1þTisþTiTdð1þeÞs2Þe�yms

ð26Þ

where the controller parameters Kc, Ti and Td are functions of thetuning parameters l. Now, substituting (19) into (25) yields therobust stability constraint

a2s2þa1sþ1

ðlsþ1Þ4

����������1

o1

JDmðsÞJ1ð27Þ

for the control structure. where DmðsÞ is the multiplicativeuncertainty bound of the process G. For the process gain uncer-tainty, the tuning parameter should be selected in such a way that

ðo2l2þ1Þ2ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi

o2a21þð1�a2o2Þ

2q 4

9Dk9k

, 8o40 ð28Þ

For the process time delay uncertainty Dym, the robust stabilityconstraint for tuning l isffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffio2a2

1þð1�a2o2Þ2

q

ðo2l2þ1Þ2

o1

9e�jDyms�19, 8o40 ð29Þ

If uncertainty exists in both process gain and time delay, thetuning parameter should be selected in such a way that

ðo2l2þ1Þ2ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi

o2a21þð1�a2o2Þ

2q 4 1þ

Dk

k

� �e�jDymo�1

��������, 8o40 ð30Þ

If the uncertainty exists in the parameters a1 and a2 then, bysimilar analysis, the value of l should satisfy the following

Page 7: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

-0.5 0 0.5 1 1.5 2 2.5 3 3.5 4x 108

-1

0

1

2

3

4

5

6

7

8 x 108

Re

Im

(0, 0)

Fig. 16. Kharitonov’s rectangles for the NRTWD.

1

2

3

4

5

6

7

8 x 108

Im

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251248

constraint:

JTðjoÞJ1oa2s2þa1sþ1

Da2s2þDa1sþ1

�������� ð31Þ

According to robust control theory [29], the closed-loopperformance for load disturbance rejection is robust, the follow-ing constraints have to be followed by the sensitivity andcomplementary sensitivity functions:

JDmðsÞTðsÞþw1ðsÞð1�TðsÞÞJo1 ð32Þ

where w1ðsÞ is the weight function of the sensitivity function,SðsÞ ¼ 1�TðsÞ. Therefore, the tuning parameter l should beselected such that the resulting controller satisfy the robustperformance and robust stability constraints.

When modeling a high-order power systems, the model andparameter approximations cannot be avoided. A study of robustnessanalysis is an important task in LFC design because no mathematicalmodel of a system will be a perfect representation of the actualsystem. If the controller tuning is too tight, the closed-loop systemmay become unstable with a small mismatch in the systemparameters. Now, we will examine the closed-loop stability propertyof the proposed controller design with some mismatch in the plantparameters. Kharitonov’s theorem is the well-known and simplesttool for robust stability analysis [30,31]. This theorem has been usedfor the robustness analysis considering parametric uncertainties inthe plant parameters. The family of polynomials

P¼ fpðs,qÞ : qAQg ð33Þ

is a set of polynomials pðs,qÞ such that the uncertainty parameter q

is an element of the uncertainty space Q. For a Q, the family is aninterval polynomial family

Xn

i ¼ 0

pðs,qÞ ¼Xn

i ¼ 0

xisi9Xn

i ¼ 0

½li,hi�si ð34Þ

where xi ¼ ½li,hi� is an interval with an infinite set of xi regardinglioxiohi. According to the Kharitonov’s theorem, an nth degreeinterval polynomial family is robustly stable if and only if each of thefour Kharitonov polynomials are Hurwitz stable and value sets movein a anti-clockwise sense through n quadrants of the complex planewithout passing through or touching the origin of the plane. Apolynomial is Hurwitz stable if all roots are located in the left half ofcomplex plane which is checked with the help of Routh criterion.

Table 2The roots of Kharitonov polynomials for NRTWD.

K1ðsÞ K2ðsÞ K3ðsÞ K4ðsÞ

�0:56þ j0:8632 �0.9119 �0:1682þ j0:4189 �1.602

�0:56�j0:8632 �0.292 �0:1682þ j0:4189 �0.6671

�0.702 �0:0131þ j0:1537 �0:1628þ j0:0614 �0:0063þ j0:0743

�0:0318þ j0:0332 �0:0131�j0:1537 �0:1628�j0:0614 �0:0063þ j0:0743

�0:0318�j0:0332 �0.0253 �0.014 �0.0502

Table 3The roots of Kharitonov polynomials for NRTD.

K1ðsÞ K2ðsÞ K3ðsÞ K4ðsÞ

�1.0912 �1.3406 �0.7835 �1.9953

�0:161þ j0:1225 �0:0044þ j0:1417 �0:054þ j0:2093 �0.1495

�0:161�j0:1225 �0:0044�j0:1417 �0:054þ j0:2093 �0:032þ j0:092

�0.0575 �0.1259 �0.0919 �0:032�j0:092

�0.0188 �0.0142 �0.0096 �0.0255

The four Kharoitonov polynomials are given by

K1ðsÞ ¼ h0þ l1sþ l2s2þh3s3þh4s4þ l5s5þ l6s6þh7s7þ � � �

K2ðsÞ ¼ h0þh1sþ l2s2þ l3s3þh4s4þh5s5þ l6s6þ l7s7þ � � �

K3ðsÞ ¼ l0þh1sþh2s2þ l3s3þ l4s4þh5s5þh6s6þ l7s7þ � � �

-0.5 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5x 108

-1

0

Re

(0, 0)

Fig. 17. Kharitonov’s rectangles for the NRTD.

+

++ +

+

– –

Fig. 18. Block diagram representation of control area i.

Page 8: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251 249

K4ðsÞ ¼ l0þ l1sþh2s2þh3s3þ l4s4þ l5s5þh6s6þh7s7þ � � �

Now, consider the parameters of the non-reheated turbine withoutor with droop characteristic as discussed in the previous section. Theparameters (KP, TP, TT and TG) variation of 30% and 20% areconsidered simultaneously for NRTWD and NRTD, respectively.The closed-loop characteristic equation of the system is given by

1þGGc ¼ 0

Area# 1

Area# 4

Area# 3

Reheat thermal turbine

Non-reheat thermal turbine

Area# 2

Reheat thermal turbine

Reheat thermal turbine

Fig. 19. Simplified diagram of a four area power systems.

Fig. 20. Frequency deviation for four area power syste

The four Kharoitonov polynomials

K1ðsÞ ¼ 357:9498þ449:4338sþ435:6944s2þ54:0864s3

þ2:5926s4þ0:0575s5

K2ðsÞ ¼ 664:7639þ834:6629sþ234:6047s2þ29:1234s3

þ4:8148s4þ0:1067s5

K3ðsÞ ¼ 664:7639þ449:4338sþ234:6047s2þ54:0864s3

þ4:8148s4þ0:0575s5

K4ðsÞ ¼ 357:9498þ834:6629sþ435:6944s2þ29:1234s3

þ2:5926s4þ0:1067s5

for NRTWD and

K1ðsÞ ¼ 260:918þ388:6268sþ130:7567s2þ19:8579s3

þ0:9999s4þ0:0126s5

K2ðsÞ ¼ 391:377þ582:9403sþ87:1711s2þ13:2386s3

þ1:4998s4þ0:0188s5

K3ðsÞ ¼ 391:377þ388:6268sþ87:1711s2þ19:8579s3

þ1:4998s4þ0:0126s5

ms: (a) area 1; (b) area 2; (c) area 3; and area 4.

Page 9: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251250

K4ðsÞ ¼ 260:918þ582:9403sþ130:7567s2þ13:2386s3

þ0:9999s4þ0:0188s5

for NRTD.The coefficients of Kharitonov polynomials for NRTWD and

NRTD are checked for Hurwitz condition. It is observed that all theroots of the Kharitonov polynomials (see Tables 2 and 3) havenegative real part i.e. all roots are in the left half of the complexplane. From Figs. 16 and 17, it is clear that Kharitonov rectanglesmove about the origin in counter-clockwise sense in order to havethe monotonic phase increase property of Hurwitz polynomials.The graph is zoomed to show what is happening in the neighbor-hood of the point ð0,0Þ. Since the origin is excluded from theKharitonov rectangles (Figs. 16 and 17) it is concluded that theclosed-loop control system is robustly stable. By following asimilar procedure as above the robustness analysis consideringparametric uncertainties in the plant parameters for RTWD andRTD can be checked.

4. Multi-area power system

A multi-area power system comprises areas that are intercon-nected by high voltage transmission lines or tie-lines. The trend offrequency measured in each control area is an indicator of the trend

Fig. 21. Tie line power deviation for four area power syst

of the mismatch power in the interconnection and not in the controlarea alone [32]. In case of a decentralized power system, areafrequency and tie-line power interchange vary as power loaddemand varies randomly. The objectives of decentralized LFC areto minimize the transient deviations of these variables and to ensuretheir steady state errors to be zero. When dealing with the LFCproblem of power systems, unexpected external disturbances,parameter uncertainties and the model uncertainties pose bigchallenges for controller design. For N control areas (Fig. 18), thetotal tie-line power change between area 1 and other areas is

DPtiei ¼XN

j ¼ 1j a i

DPtieij ¼1

s

XN

j ¼ 1j a i

TijDf i�XN

j ¼ 1j a i

TijDf j

264

375

The balance between connected control areas is achieved bydetecting the frequency and tie line power deviations to generatethe area control error (ACE) signal, which is in turn utilized in thecontrol strategy as shown in Fig. 18. The ACE for each control areacan be expressed as a linear combination of tie-line power changeand frequency deviation.

ACEi ¼ BiDf iþDPtiei ð35Þ

where Bi is the frequency bias coefficient. The LFC system in eachcontrol area of an interconnected (multi-area) power system should

ems: (a) area 1; (b) area 2; (c) area 3; and (d) area 4.

Page 10: A new control scheme for PID load frequency controller of ......3.2. Design of the controller G c For easy implementation of PID controller, G c is considered in the following form:

D.G. Padhan, S. Majhi / ISA Transactions 52 (2013) 242–251 251

control the interchange power with the other control areas as wellas its local frequency. The plant model for multi-area power systemis given by

Gi ¼ Bi

GgiGtiGpi

1þGgiGtiGpi=Rið36Þ

For the tuning of multi-area LFC, the same procedure can befollowed as in single-area LFC tuning.

4.1. Simulation results for four area power systems

The simplified diagram of a four area power systems is shownin Fig. 19. In the simulation results, area 1, area 2 and area 3 aredenoted as the area with reheat unit, and area 4 is denoted as thearea with non-reheat unit.

The parameters of the non-reheat and reheat units in differentareas are chosen as

Nominal parameters for area 1, area 2 and area 3: TP1 ¼

TP2 ¼ TP3 ¼ 20, TT1 ¼ TT2 ¼ TT3 ¼ 0:3, TG1 ¼ TG2 ¼ TG3 ¼ 0:2,KP1 ¼ KP2 ¼ KP3 ¼ 120, R1 ¼ R2 ¼ R3 ¼ 2:4, Tr1 ¼ Tr2 ¼ Tr3 ¼ 20and c1 ¼ c2 ¼ c3 ¼ 0:333.Nominal parameters for area 4: KP4 ¼ 120, TP4 ¼ 20, TT4 ¼ 0:3,TG4 ¼ 0:08, R4¼2.4.

The synchronizing constants are T12 ¼ T23 ¼ T31 ¼ T41 ¼ 0:0707and the frequency bias constants are B1 ¼ B2 ¼ B3 ¼ B4 ¼ 0:425.The identified model for reheat unit with droop characteristic isobtained as G¼ 0:9965e�0:5s=ð0:72s2þ1:7sþ1Þ and that for non-reheat unit with droop is same as that of given in Table 1. Bychoosing l¼ 0:7 and b¼ 0:35, the controller settings for area 1,area 2 and area 3 are Kc ¼ 1:1895, Ti¼1.9090 and Td¼0.5454.Similarly, the controller parameters for area 4 are Kc ¼ 1:9822,Ti¼0.5242 and Td¼0.1756 by taking l¼ 0:1 and b¼ 0:35.

To show the performance of the decentralized PID controller, astep load DPd1 ¼ 0:01 is applied to area 1 at t¼5 s, followed by astep load DPd3 ¼ 0:01 to area 3 at t¼100 s. Fig. 20 illustrates thefrequency errors of the four different areas. Fig. 21 shows the tie-line power errors of the four areas. From the simulation results, itcan be seen that the frequency errors, and tie-line power devia-tions have been driven to zero by proposed controller in thepresences of power load changes.

In order to test the robustness of the controller, the variationsof the parameters of the non-reheat and reheat units in the fourareas are assumed to be 750% of their nominal values. However,the controller parameters are not changed with the variations ofthe system parameters. Fig. 20 illustrates the frequency errors offour areas with the variant parameter values. Fig. 21 shows thetie-line power errors of the four areas with the variant parametervalues. From the simulation results, it can be seen that despitesuch large parameter variations, the system responses do notshow notable differences from the nominal values. Therefore, thesimulation results demonstrate the robustness of proposed con-troller against system parameter variations. It is observed that theproposed decentralized PID controller achieves better dampingfor frequency and tie-line power flow deviations in all the four-areas.

5. Conclusion

The LFC characteristics of a single-area power system with non-reheat and reheat turbines have been studied. A relay feedback testhas been conducted to estimate the parameters of the powersystem. The robustness of the LFC is tested using Kharitonov’stheorem. The results show that the proposed PID controller with a

new structure gives a better performance than reported methods.The proposed method is applied to a four-control area power systemand tested with different plant parameters uncertainty scenarios.

References

[1] Kundur P. Power system stability and control. New York: McGraw-Hill; 1994.[2] Jaleeli N, VanSlyck LS, Ewart DN, Fink LH, Hoffmann AG. Understanding

automatic generation control. IEEE Transactions on Power Systems1992;7(August (3)):1106–22.

[3] Ibraheem, Kumar P, Kothari DP. Recent philosophies of automatic generationcontrol strategies in power systems. IEEE Transactions on Power Systems2005;20(1):346–57.

[4] Shayeghi H, Shayanfar H, Jalili A. Load frequency control strategies: a state-of-the-art survey for the researcher. Energy Conversion and Management2009;50:344–53.

[5] Agathoklis P, Hamza MH. Comparison of three algorithms for load frequencycontrol. Electric Power Systems Research 1984;7:165–72.

[6] Aly G, Abdel-Magid YL, Wali MA. Load frequency control of interconnectedpower systems via minimum variance regulators. Electric Power SystemsResearch 1984;7:1–11.

[7] Park YM, Lee KY. Optimal decentralized load frequency control. ElectricPower Systems Research 1984;7:279–88.

[8] Pan CT, Liaw CM. An adaptive controller for power system load frequencycontrol. IEEE Transactions on Power Systems 1989;4(1):122–8.

[9] Rubaai A, Udo V. An adaptive control scheme for load-frequency control ofmultiarea power systems Part I. Identification and functional design. ElectricPower Systems Research 1992;24:183–8.

[10] Rubaai A, Udo V. An adaptive control scheme for load-frequency control ofmultiarea power systems Part II. Implementation and test results by simula-tion. Electric Power Systems Research 1992;24:189–97.

[11] Rubaai A, Udo V. Self-tuning load frequency control: multilevel adaptiveapproach. IEE Proceedings: Generation, Transmission and Distribution1994;141(4):285–90.

[12] Chang C, Fu W. Area load frequency control using fuzzy gain scheduling of PIcontrollers. Electric Power Systems Research 1997;42:145–52.

[13] Ray G, Prasad A, Prasad G. A new approach to the design of robust load-frequency controller for large scale power systems. Electric Power SystemsResearch 1999;51:13–22.

[14] Hosseini S, Etemadi A. Adaptive neuro-fuzzy inference system based auto-matic generation control. Electric Power Systems Research 2008;78:1230–9.

[15] Khodabakhshian A, Edrisi M. A new robust PID load frequency controller.Control Engineering Practice 2008;16:1069–80.

[16] Khodabakhshian A, Hooshmand R. A new PID controller design for automaticgeneration control of hydro power systems. Electrical Power and EnergySystems 2010;32:375–82.

[17] Tan W. Unified tuning of PID load frequency controller for power systems viaIMC. IEEE Transactions on Power systems 2010;25(1):341–50.

[18] Tan W. Tuning of PID load frequency controller for power systems. EnergyConversion and Management 2009;50:1465–72.

[19] Tan W. Decentralized load frequency controller analysis and tuning formulti-area power systems. Energy Conversion and Management 2011;52:2015–23.

[20] Tan W, Xu Z. Robust analysis and design of load frequency controller forpower systems. Electric Power Systems Research 2009;79:846–53.

[21] Dong L, Zhang Y, Gao Z. A robust decentralized load frequency controller forinterconnected power systems. ISA Transactions 2012;51(3):410–9.

[22] Panda RC. Synthesis of PID tuning rule using the desired closed-loopresponse. Industrial and Engineering Chemistry Research 2008;47:8684–92.

[23] Balaguer P, Alfaro V, Arrieta O. Second order inverse response processidentification from transient step response. ISA Transactions 2011;50(2):231–8.

[24] Mei H, Li S. Decentralized identification for multivariable integrating pro-cesses with time delays from closed-loop step tests. ISA Transactions2007;46(2):189–98.

[25] Natarajan K, Gilbert A, Patel B, Siddha R. Frequency response adaptation of picontrollers based on recursive least-squares process identification. ISATransactions 2006;45(4):517–28.

[26] Majhi S. Relay based identification of processes with time delay. Journal ofProcess Control 2007;17:93–101.

[27] O’Dwyer A. Handbook of PI and PID controller tuning rules. 2nd editionIm-perial College Press; 2006.

[28] Zhou K, Doyle JC. Essentials of robust control. Upper Saddle River: PrenticeHall; 1998.

[29] Morari M, Zafiriou E. Robust process control. Englewood Cliffs: Prentice Hall;1989.

[30] Chapellat H, Dahleh M, Bhattacharyya SP. Robust stability under structuredand unstructured perturbations. IEEE Transactions on Automatic Control1990;35(10):1100–8.

[31] Bhattacharyya SP, Chapellat H, Keel LH. Robust control: the parametricapproach. Prentice Hall; 1995.

[32] Bevrani H. Robust power system frequency control. Springer; 2009.