a new method for preventing air-source heat pumps and ... ·...

22
Central Research Institute of Electric Power Industry A new method for preventing air-source heat pumps and refrigerators from frosting 12 th IEA Heat Pump Conference 2017 15-18 May, 2017 ROTTEROAM L. Zhang, T. Fujinawa, K. Hashimoto*, M. Saikawa

Upload: others

Post on 02-May-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Central Research Institute of Electric Power Industry

A new method for preventing air-source heat pumps and refrigerators from frosting

12th IEA Heat Pump Conference 2017

15-18 May, 2017 ROTTEROAM

L. Zhang, T. Fujinawa, K. Hashimoto*, M. Saikawa

Page 2: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

ContentsuBackgrounduIntroduction of the proposed frost-free heat pump

and simulation resultsuIntroduction of the proposed frost-free refrigerator

and simulation resultsuConfirming experimentally whether frost-free could

be realizeduConclusions

2

Page 3: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Background

3

Page 4: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Background −frosting problem of heat pumpu Frost formation on the outdoor heat exchanger (evaporator) is one of the major

problems for air source heat pump in winter.

Outdoor heat exchanger(evaporator)of heat pump

refrigeranttubefin

frosthumid air

H2O H2O

H2O H2OH2O H2O

H2OH2O H2O

Decrease heat transfer and obstruct air flow

Defrosting operation

Heating operation

Problems:• Reduced energy efficiency • Heating shutdown

4

Page 5: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Background −frosting problem of refrigerator

5

<Frost layer on the surface of the evaporator of a refrigerated display cabinet>

Defrosting heater

Frost

As shown in thisphoto, althoughthe fin pitch of theheat exchanger isover 10mm, the airflow is obstructedby the frost layer.

u Frost formation is a common phenomenon observed in refrigerators, includinghousehold refrigerator-freezers, refrigerated display cabinets, refrigeratedwarehouses and so on.

Defrosting operation

Cooling operation

Problems:• Reduced energy efficiency • Cooling shutdown• Overflowing of defrosted

water from tray

Page 6: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

How to realize frost-freeuConcept of frost-free

Heat exchanger(evaporator etc.)

refrigerant

tubefin

Frost-freeHumid air

H2O H2OH2O H2OH2O H2O

H2OH2O H2O

desiccant

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

Dried air

Regeneration airExhausted air

heating

H2O

H2O

H2O

H2O

H2O

H2OH2O

H2OH2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

H2O

uEnergy is needed to regenerate the desiccant

The humid air is dehumidified via desiccant before it enters evaporator . Therefore, frost-free could be achieve.

6

Page 7: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Introduction of the proposed frost- free heat pump and simulation results

7

Page 8: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

The proposed frost-free heat pump water heater system

compressor

V1

V2

Hot water

D1 D2D3

DCHE Evaporator

Air pass V1, V2-expansion valveD1, D2, D3- damper

Condenser or gas-cooler

refrigerant

8

• The system is composed of compressor, condenser or gas-cooler, DCHE, evaporator,two expansion valves (V1-V2) and three air dampers (D1-D3).

• With respect to the moisture moving between the desiccant and the air, the operationprocess of the proposed system can be classified into two modes: adsorption mode(AD mode) and desorption mode(DE mode).

Desiccant-coated heatexchanger (DCHE):desiccant is coated onthe surface of the heatexchanger

Page 9: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

uAdsorption mode (AD mode)

Enthalpy

P

DCHEEvaporator

Condenser

compressor

V1

V2

Hot water

D1 D2D3

DCHE Evaporator

Condenser or gas-cooler

throttled

throttled

open openclose

OA- outside airAA- adsorption airEA- exhausted airOA EA

AA

(1) P-h diagram of refrigerant (AD)

frost -free

9

• During AD mode, refrigerant isthrottled by V1 and V2 sequentially.So DCHE works as anotherevaporator. Hot water is produced atthe condenser.

• Dampers D1 and D2 are opened andD3 is closed. Outside air (OA) ispassed through DCHE, in which it isdehumidified. The dry air leaving fromDCHE exits heat to refrigerant at theevaporator, and exhausted asexhausted air (EA).

• Because the dew point of the dry air(AA) is lower than the evaporationtemperature of evaporator, frost-freecan be realized.

Page 10: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

10

uDesorption mode(DE mode)

Enthalpy

P

Evaporator

CondenserDCHE

QDCHE=Qeva QCon=Wcom

(2) P-h diagram of refrigerant (DE)

compressor

V1

V2

Hot water

D1 D2D3

DCHE Evaporator

Condenser or gas-cooleropen

throttled

close closeopen

DA- desorption airRA- recycled air

RA

DA

water

• During DE mode, V1 is opened and V2 isthrottled. So DCHE works as anothercondenser and the condensation heat isused to regenerate the desiccant .

• Dampers D1, D2 are closed and D3 isopened. So the air recycles between theDCHE and evaporator. As a result, thecondensation heat of DCHE iscompletely recovered at the evaporator.Therefore, the electrical consumption ofthe compressor is equal to the heatoutput to the water.

• Heating shutdown caused byconventional defrosting methods issolved by applying the air-recyclingmethod of the system.

Page 11: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

11

uSimulation results

2.0

3.0

4.0

5.0

-8 -6 -4 -2 0 2 4 6

COP

Toa (ºC)

The proposed system

RHoa=80%

RHoa=70%

The main parameters of the calculation:• Air temperature (Toa) : -7 - 5ºC, relative humidity (RHoa): 60 - 80%; • Inlet and outlet water temperatures: 5, 65ºC;• The adiabatic efficiency of the compressor (ηcom): 0.75 (assumed); Refrigerant: CO2• COP: the ratio of the heat output to water to the electrical consumption of the compressor

Be calculated by assuming that COP will bereduced by 20% [1] compared to a base system[2], which operates at non-frosting conditions.

The COP of the proposedsystem is 5-20 % higherthan that of the hot gasdefrosting system.

[1]: Byun JS, et al. 2008, Frost retardation of an air-source heat pump by the hot gas bypass method, Int. J. Refrig. 31: 328-334.[2]: Neksa P, et al. 1998, CO2 –heat pump water heater: characteristics, system design and experimental results, Int. J. Refrig. 21 (3): 172-179.

Fig.1 Comparison of COP between the proposed system and a conventional hot gas defrosting system

Page 12: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Introduction of the proposed frost-free refrigerator and simulation results

12

The method of using a desiccant to prevent the heat pump from frosting can also be applied torefrigeration systems, such as household refrigerator-freezers, refrigerated display cabinets,refrigerated warehouses and so on.

Page 13: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

The proposed frost-free household refrigerator-freezer

13

Freezer Compartment

Refrigerator Compartment

Air-cooled HE

Compressor

Expansion valve

gas-liquid separator

Air cooling HE

capillary

DCHE (desiccant-coated HE)

• The system comprises a compressor,an air-cooled HE, an expansion valve,a DCHE, a gas-liquid separator, acapillary and an air cooling HE.

• With respect to the available coolingload temperature and the moistureremoving of the desiccant, the systemcan be classified into two modes:u Freezing-Refrigeration-ADsorption

mode (F-R-AD mode) u Refrigeration-DEsorption (R-DE

mode).

Page 14: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

14

uFreezing-Refrigeration-ADsorption mode (F-R-AD mode)

• The expansion valve (3) is throttled, so theDCHE works as another evaporator.

• The air (MA) mixed by the freezer air (FA)and refrigerator air (RA) is dehumidified atDCHE due to the adsorption process of thedesiccant.

• The dry air (DA) exiting DCHE is split intotwo air streams: SA(R) is supplied to therefrigerator compartment, the rest (SA(F)) isfurther cooled at the evaporator andsupplied to the freezer compartment.

• Because the dew point of the dry air (DA) islower than the evaporation temperature ofevaporator, frost-free can be realized.

Freezer Compartment

Refrigerator Compartment

OA

EA

RA

FA

MA

SA(R)

SA(F)

DA

DA

3throttled

DCHE(Adsorption)

Evaporator

Condenser

Page 15: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

15

Freezer Compartment

Refrigerator Compartment

OA

EA

RA

SA(R)

3

Evaporator

opened

DCHE(Desorption)

uRefrigeration-DEsorption (R-DE mode)

• The expansion valve (3) is opened, so theDCHE (4) works as a condenser

• The DCHE is heated by the condensationheat of the refrigerant and is regenerated bydischarging moisture to the outside air (OA).

• The refrigerator air (RA) is cooled at theevaporator and returned to the refrigeratorcompartment.

• Note that the evaporation temperature of theevaporator should be operated to keep ithigher than the dew point of RA, thereforefrost-free operation is also feasible in R-DEmode.

Page 16: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

16

uSimulation results

0

2

4

6

8

overall cooling load electricityconsumption

MJ/d

ay

4.08MJ(1.13kWh)

60%(R. compartment)

40%(F. compartment)

7.42MJ • The total cooling load including F. and R.compartments, the electric powerconsumption of the compressor is 7.42MJand 4.08MJ for one day.

• So the average COP , the ratio of thecooling load to electric power consumption,is calculated to be 1.82.

The main parameters of the calculation:• The air flow rates of the refrigerator (R.) and freezer (F.) compartments are 0.1 and 0.3 m³/min.• The air temperature and relative humidity in R. and F. compartments are (4ºC, 50%) and (-18ºC, 50%). • The adiabatic efficiency of the compressor (ηcom) is assumed to be 0.7. • Refrigerant: Isobutane (R600a)

Fig.2 The overall cooling load and electric power consumed by the compressor for one day

Page 17: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Confirming experimentally whether frost-free could be realized

The results of the theoretical analysis show that the two proposed systems can preventevaporators from frosting and have high energy efficiency. In the following, we want to confirmexperimentally whether a frost-free state could be realized and whether the DCHE could beeffectively regenerated under the condensation temperature of heat pumps and refrigerators.

17

Page 18: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

18

uExperimental apparatus

Parameters DCHE (AQSOA) DCHE (polymer)Height (m) 0.242 0.2Length (m) 0.3 0.5Width (m) 0.0508 0.016Fin (m) 1.8 × 10-3 1.2 × 10-3

Mass of desiccant(kg) 0.756 0.0878

AQSOA DCHE Polymer DCHE

DCHE

AQSOA: a kind of desiccant belonging to the zeolitefamily, developed by Mitsubishi Chemical Corporation).Polymer: a kind of sorption material, developed by JapanExlan.

(Aluminum fin and copper tube)

(All aluminum, plate tube with corrugated fins)Process air

DCHE

Cooling brine

Hot brine

DPinDPout

Objectives of this experiment:Ø Whether can frost-free be realized?Ø Regeneration temperature of DCHE

Page 19: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

19

uExperimental resultsØ Whether can frost-free be realized?

• The evaluation criteria of the frost-free operation of the proposed heat pump and refrigerator are given as,

𝐷𝑃#$% < 𝑇()*

• Experimental result of AQSOA-DCHE for frost-free heat pumpapplication

The evaluation criteria were satisfiedand the operation time of frost-freewas about 20 minutes.

DPout: is the measured dew point of theDCHE outlet airTeva: is the evaporation temperatures,assumed to be -5ºC and -28ºC for theproposed frost-free heat pump andrefrigerator, individually.

Page 20: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

20

• Experimental result of polymer DCHE for frost-free refrigerator application

The polymer sorbent is capable ofadsorbing moisture from the air of -18ºC and the operation timesatisfying the evaluation criteria ofthe frost-free is about 30 minutes.

Ø Whether can the DCHE be regenerated under the condensation temperature level?

The above experimental results of AQSOA and polymer DCHEs were obtained after the DCHEs were regenerated by passing 55ºCand 43ºC hot brines, separately.

• 55ºC: the same temperature levels as the condensation temperature of the heat pump• 43ºC: the same temperature levels as the condensation temperature of the refrigerator

Page 21: A new method for preventing air-source heat pumps and ... · CentralResearchInstituteofElectricPowerIndustry A new method for preventing air-source heat pumps and refrigerators from

Conclusions

21

• The frost-free air-source heat pump and frost-free household refrigerator-freezer were proposed in our study. Theoretical study shows that the two proposed systems have high energy efficiency.

• Experimental results showed that the frost-free operation of the proposed systems could be realized when the two kinds of desiccants: AQSOA and polymer, were applied.

• Furthermore, it was verified that AQSOA and polymer could be regenerated under the condensation temperatures of heat pumps and refrigerators.