Hytronik Microwave motion sensor 46 Model: HC003V/RF Mechanical structure This is a combination of motion sensor and RF radio wave wireless transmission. The motion at 1 sensor (the master unit) can be passed onto other pre-defined individuals (the slave units) through R F transmission. Up to 15 units can be programed and grouped by means of Teach-and-Learn method. With KEELOQ coding technology, 1 master can triger max. 15 slaves , and 1 slaves can respond up to 15 masters respectively. With both 1-10v output signal and 220-240v signal, it can switch on/off & dim any lighting applications. The motion signal from 1 sensor (the master sensor) can be transmitted to and trigger on other sensors (the slave unit) by RF transsmmion. This wireless radio wave transmission can reach 100 meters in open area. detection area Motion Hold-time Stand-by period Stand-by dimming level installation hole Antenna module Detachable light sensor N L L , L ,, 1-10V Daylight sensor Brightness on RF signal Wireless Transmission Control This is a combination of motion sensor and RF radio wireless, wireless transmission is the perfect solution for retrofit projects, easy installation and free of wiring. with KEELOQ coding system, by "Teach & Learn" method, selected and directional communication can be easily setup.Up to 15 channels can be grouped and programmed, and up to 30 meters indoor transmission and 100 meters in open area. 10% 100% Off Off 100% 10% 100% Off Function and options while the 1st sensor detects motion at 1st floor, the 1st sensor switch on 100%, the 2nd one to be standby brightness The person walks to 2nd floor, the 2nd sensor at 100% and 3rd sensor to be standby brightness 1 1 2 2 R F communication version Model: HC003V/RF

Upload: shanu-s-sooranad

Post on 03-Nov-2014

19 views

Category:

Documents


5 download

DESCRIPTION

aaa

TRANSCRIPT

Hytronik Microwave motion sensor 46

Model: HC003V/RF Mechanical structure

This is a combination of motion sensor and RF radio wave wireless

transmission. The motion at 1 sensor (the master unit) can be passed onto

other pre-defined individuals (the slave units) through R F transmission. Up

to 15 units can be programed and grouped by means of Teach-and-Learn

method.

With KEELOQ coding technology, 1 master can triger max. 15 slaves , and

1 slaves can respond up to 15 masters respectively.

With both 1-10v output signal and 220-240v signal, it can switch on/off &

dim any lighting applications.

The motion signal from 1 sensor (the master sensor) can be transmitted

to and trigger on other sensors (the slave unit) by RF transsmmion. This

wireless radio wave transmission can reach 100 meters in open area.

detection area

Motion Hold-time

Stand-by period

Stand-by dimming level

installation hole

Antenna moduleDetachablelight sensor

N L L,

L,,

1-10V

Daylight sensor

Brightness on RF signal

Wireless Transmission Control

This is a combination of motion sensor and RF radio wireless, wireless transmission is the perfect solution for retrofit projects, easy installation and free of wiring. with KEELOQ coding system, by "Teach & Learn" method, selected and directional communication can be easily setup.Up to 15 channels can be grouped and programmed, and up to 30 meters indoor transmission and 100 meters in open area.

10%

100%

Off

Off

100%

10%

100%

Off

Function and options

while the 1st sensor detects motion at 1st floor, the 1st sensor switch on 100%, the 2nd one to be standby brightness

The person walks to 2nd floor, the 2nd sensor at 100% and 3rd sensor to be standby brightness

1

1

2

2

R F communication version

Model: HC003V/RF

Hytronik Microwave motion sensor 47

Detection Pattern

area of high sensitivity area of lower sensitivity

wal

l mou

ntin

g he

ight

wall mounting pattern(m)

2

3

4

5

2

1

0

1

3

4

5

1 2 3 4 5 6 7 8 9 10ceiling mounting pattern(m)

ceili

ng m

ount

ing

heig

ht

1

2

3

4

5

101 22 33 44 55

100%

100%

10%

10% Off

10%

100%

100%

The person walks to 3rd floor, the 3rd sensor at 100% and 4th to be standby brightness,at same time, 1st sensor dims to standby brightness after hold time

The person walks to 4th floor, the next sensor is 100%...... and at the same time, 1st sensor is off after standby period and 2nd sensor dims to standby brightness

3

4

3 4

HC003V/RF HC003V/RF

sensorDIM Wiring Diagram 1-10VDmimable Wiring Diagram

Hytronik Microwave motion sensor 48

Settings

RF grouping (max. 15 channels)

I - maximum range up to 100% II – 75%III – 50%IV- 30%V- 10%

Detection area can be reduced by selecting the combination on the DIP switches to fit precisely for each specific application.

I – 5SII – 30SIII – 1 minuteIV – 5 minutesV – 10 minutesVI – 20 minutes

Hold-time means the time period you would like to keep the lamp on 100% after the person has left the detection area.

Hold-time

Detection area1

2

I – DisableII – 1 hourIII – 30 minIV – 10 minV – 5 minVI – 1 min

I – 5V (45~50%)II – 4V (35~40%)III – 3V (25~30%)IV – 2V (15~20%)V – 1.4V (5~10%)

This is the time period you would like to keep at the low light output level before it is completely switched off in the long absence of people.

This is the dimmed low light output level you would like to have after the hold-time in the absence of people.

Press LEARN button on the recieving unit , the sensor goes into a 180s of teach-and-learn period, in which electrician have enough time to go back to master unit to release transmission.

red LED is on, and the beeper gives long indication:

Press the SEND button on the master unit to send RF signal, the green

LED on the master unit is then on to indicate the success of

transmission. and the beeper turns to short indication:

Upon receiving the transmission signal, the red LED on receiving unit will

flash 2-3 times, which is the indication of successful teach-and-learn;

and the beeper turns to short indiction:

Stand-by period(corridor function)

Stand-by dimming level

4

5

1 short press this Learn button

Red LED is on

beeper is on

master unit

beeper is on

Press this send buttonGreen LED is on

Red LED flashes 2-3 times.

step1

step2

slave unit

slave unit

The daylight threshold can be set on the potentiometer, from 2 lux up to 2000 lux, to fit for any particular application.

Detachable daylight sensor32 lux 2000 lux

Hytronik Microwave motion sensor 49

Wait for 180s period elapses, till the short beeper stops as well as the

red LED on receiving unit goes off. The whole teach-and-learn process is

completed. Or--

Short press the Learn button again within the 180s period to finish the

whole teach-and-learn process.

Red LED goes off after 180s.

beeper is off after 180s

800w

<1mw

Max. ( x H ): 8m x 5m

30--150 O

Detection area

Daylight threshold

Standby period

2--2000 lux

Max. 5m.

-20 +60

220-240v

5s/30s/1min/5min/10min/20min

1min/5min/10min/30min/1hour / disable

RF. Transmission distance 100 meters in open area

RF. Communicatin Chanels 15 channels for grouping

RF Frequency 433 MHz

Coding Keeloq rolling code (tech/learn/reset/memory)

~

step3

step4

beeper is offRed LED goes off.2nd short press this Learn button

slave unit

beeper keeps on beeping, , then goes off in 10s

Long press this Learn button

Red LED keeps on flashing then goes off in 10s.

(if necessary) ( slave unit )

slave unit (Optional )

If you want to RESET:A long press on Learn button (about 10s) resets and clears all previous commands it has received–-

The red LED keeps on flashing and then goes off in the end ; this is the indication of a successful reset and erase of all the previous groupings.