abb ag –calor emag medium voltage products gas · pdf fileabb ag –calor emag...
TRANSCRIPT
1
ABB AG – Calor Emag Medium Voltage Products
Gas-insulated switchgear Type ZX0.2
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
2
Medium voltage switchgear Type ZX0.2Single busbar systems
12 kV, …2500 A,…31.5 kA
24 kV, …2500 A,…31.5 kA
36 kV, …2500 A, …31.5 kA
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
3
With IAC classificationAFL 31.5 kA 1sAFLR 31.5 kA 1s
1) Dependent on current
Rated voltage kV 12 24 36
Rated current of busbars A …2500 …2500 …2500
Rated current of tee-offs
with circuit-breaker
with switch-disconnector/fuse combination
A …2500 …2500 …2500
A …80 …63 -
Rated short-circuit breaking current kA …31,5 …31,5 …31,5
Width a mm 450 / 600 / 1200 1)
Heightb mm 2400
Depth c mm 1330
ac
b
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
4
ZX0 individually partitionedfor extended application range
Up to 36kV rated voltage
Currents up to 2500A for busbars and incoming feeders
Short-circuit currents up to 31.5 kA for all voltage levels
Local manual operation of all switching devices
Optionally also with remote control
Suitable for any protection or control device
Replacement of a panel in the row without gas work
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
5
1 Removable low voltage compartment2 Three position disconnector operating mechanism3 Mechanism bay with operator controls4 Circuit-breaker operating mechanism5 Cable connector6 Window-type current transformer7 Bushing with outer cone8 Isolatable voltage transformer on the cable9 Pressure relief disk
10 Vacuum circuit-breaker11 Three position disconnector12 Busbars13 Plug-in busbar voltage transformers
SF6
1
2
3
4
5
68
7
9
10
11
12
13
Circuit-breaker panel, 1250 A
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
6
Panel variant
Circuit-breaker panel 630A up to 24kV
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
7
Panel variants Circuit-breaker panel
630A / 1250A for all voltages
Cable termination panel 630A / 1250A
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
8
Panel variants Circuit-breaker panel
2500A
Cable termination panel 2500A
Similarly for 1600A 2000A
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
9
Panel variants Sectionalizer / Riser 1250A
Sectionalizer / Riser 2000ASimilarly for 1600A and 2500A
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
10
Panel variants
Switch-disconnector panel with fuses
Up to 24kV
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
Gas-insulated switchgearType ZX0.2
11
Advantages
Partitioned function compartments ► maximum safety
Completely shockproof arrangement
High voltage section totally independent of environmental influences
Maximum availability for the operator
Independence of the environment makes for extremely long system life
Minimum maintenance requirement
Longer life than other system types
© ABB17.02.2015 Gas-insulated switchgear type ZX0.2 |
1
Gas-insulated switchgear Type ZX1.2
ABB AG – Calor Emag Medium Voltage Products
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
2
Medium voltage switchgeartype ZX1.2Single busbar systems
12 kV, …2500 A, …31,5 kA
24 kV, …2500 A, …31,5 kA
36 kV, …2500 A, …31,5 kA
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
3
Rated voltage kV 12 24 36 1)
Rated current of busbars A …2500 …2500 …2500
Rated current of tee-offs A …2500 …2500 …2500
Rated short-circuit breaking current kA …31,5 …31,5 …31,5
Rated short-circuit making current kA 80 80 80
Insulating gas SF62) SF6
2) SF62)
Width a mm 600 / 800 3) 4) 600 / 800 4)
Height b mm 2100Depth c mm 1400-1900 5)
Height of Cable fixing point mm 1250
1) Higher values as per international standards on request2) Insulating gas: sulphur hexafluoride (SF6) 3) Double feeder panel up to 25 kA, 2 x 630 A4) Rated feeder current above 1250 A5) Depending on quantity of cables per phase
with a 500mm deep LVcompartment
ac
b
With IAC classificationAFLR 31.5 kA 1sAFL 31.5 kA 1s
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
4
1 Density sensor2 Circuit-breaker operating mechanism3 Multifunction Protection and
Switchgear Control unit4 Three position disconnector operating mechanism5 Three position disconnector6 Busbar7 Pressure relief disk8 Pressure relief duct (optional)9 Ring type current transformer
10 Cable plug11 Cable socket12 Measuring sockets for capacitive voltage
indicator system13 Test socket14 Circuit-breaker
SF6
Feeder 1250 A
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
5
Bay Control Unit
Modern solution of a conventional switchgear control in ZX
Integral control, indication and annunciation unit
Conventional control without active components
Control via conventional push- buttons and key operated local / remote switch
Operation of a switchgear panel without multi-functional protection-and control-unit
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
6
Feeder Sectionalizer Riser Busbar metering
Single lines of switchgear variants (SBB)
Cable connection
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
7
1 Plug-in voltage transformer2 Disconnecting device for voltage transformers3 Density sensor4 Circuit-breaker operating mechanism5 Multifunction Protection and Switchgear Control unit6 Three position disconnector operating mechanism7 Three position disconnector8 Busbar9 Pressure relief disk
10 Pressure relief duct12 Cable socket13 Measuring sockets for capacitive voltage indicator system14 Test socket15 Circuit-breaker16 Combined current and voltage sensor
or current transformer17 Plasma diverter
SF6
Feeder 2000 A
234
5
6
78
9
1
9
17
16
15141312
11
10
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
8
1 Pressure sensor (temperature-compensated) 2 Multifunction Protection and
Switchgear Control unit 3 Circuit-breaker operating mechanism4 Circuit-breake5 Three position disconnector6 Three position disconnector
operating mechanism7 Busbars8 Pressure relief disk9 Pressure relief duct
10 Current transformer or Rogowski coil11 Inner cone cable plug12 Inner cone cable bushing13 Measuring sockets for capacitive
voltage indicator system 14 Test socket15 Plasma diverter
SF6
Double feeder panel up to 24 kV630 A for each feeder
2
6
7
3
1
4
5
2
89
10
111213
14
158
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
9
Bus sectionalizer 2000 A
with option
Integrated voltage metering
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
10
Bus riser 2000 A
with option
Integrated voltage metering
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
11
Plug-in componentsDummy plug
Test plug
Surge arrestor
Voltage transformer
BB plug-in system
Cable plug
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |
Gas-insulated switchgearType ZX1.2
12
Advantages
Partitioned function compartments ► maximum safety
Completely shockproof enclosures
High voltage section totally independent of environmental influences
No effect of site altitude on dielectric strength
Maximum availability for the operator
Independence of the environment makes for extremely long system life
Minimum maintenance requirement
Longer life than other system types
© ABB17.02.2015 Gas-insulated switchgear type ZX1.2 |