abb t&d divisione sace t.m.s. -01.05.15 - ohb outdoor sulphur hexafluoride circuit-breaker...

22
ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

Upload: alexandra-alfrey

Post on 16-Dec-2015

246 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

AB

B T

&D

Div

isio

ne S

ace

T.M

.S.

-01.

05.1

5 -

OHBOutdoorsulphur Hexafluoride circuit-Breaker

1-2002

Page 2: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

2

OHB outdoor circuit-breaker

Fields of application outdoor installations

control and protection of distribution lines

control and protection of distribution substations

control and protection of transformers

control and protection of capacitor banks

Page 3: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

3

OHB outdoor circuit-breaker

Electrical characteristics Rated voltage 24 36 kV

Withstand voltage (1 min.) 70 (60) 95 (80) kV dry (wet)

Impulse withstand voltage 150 200 kV

Rated normal current at 40°C 1250 / 2500 A

Rated frequency 50 / 60 Hz

Rated breaking capacity 25 / 31.5 kA

Making capacity 63 / 80 kA

Operating temperature -30 . . . . + 40 °C

Page 4: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

4

OHB outdoor circuit-breaker

Standards

IEC 60056 (tested in compliance with the prescriptions of Amendment 3, table XII, list 1 in order to ensure suitability for overhead lines with rapid re-closing cycle)

IEC 60694

Page 5: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

5

OHB outdoor circuit-breaker

Development, production, quality control according to :

ISO 14001 STDs as for Environmental Management System

ISO 9001 STDs as for Quality Assurance System

Page 6: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

6

OHB outdoor circuit-breaker

Features Three Phase Circuit Breaker

The same arcing chamber of HD4 MV indoor c.b. series

HD4 arcing chamber housed in a hollow porcelain cylinder

Ceramic insulators assembled by means of flanges with terminals

Pole cap, flanges, sump in anodized alluminium alloy

Pole ”sealed for life” pressure system

Pole cover with safety valve

Terminal for connection as NEMA 4 form

Page 7: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

7

OHB outdoor circuit-breaker

Features ESH spring charged operating mechanism (the same actuator

of the whole the HD4 series)

Mechanical anti-pumping device to prevent re-closing due to both electrical and mechanical controls

Complete range of accessories

Wide range of power supply voltages of the electrical accessories

Two-levels pressure-switch

Cabinet housing all the actuator, the control devices, the operating shafts and lever, the transmission, the poles linkage

Page 8: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

8

OHB outdoor circuit-breaker

Features Cabinet supporting the three pole assemblies

Cabinet and cabinet supporting structure made of hot galvanised steel sheet

Weather proof cabinet

Tight door with window for status c.b. inspection without opening the cabinet door

Case door handle suitable for three padlocks

Anti-condensation heater and heating elements for low temperature

Page 9: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

9

OHB outdoor circuit-breaker

Features CT brackets (on request)

”Closed”, ”Open”, ”Spring charged/discharged”, ”SF6 low pressure” signalling lamps (on request)

Particularly sturdy construction

Simple structure requiring minimal preparation of the site

Mounting arrangements Cabinet supported by telescopic supports with adjustable height

from 2916 up to 3676 mm (structure in compliance with the prescription of BS 7354 STDs)

Cabinet at ground level

Page 10: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

10

OHB outdoor circuit-breaker

SF6 interrupter ”Autopuffer” technique based on compression and self-blast

technique

Low operating energy thanks to the ”autopuffer” technique

Minimal maintenance

Life in excess of 10,000 mechanical operations

Separation between main and arcing contacts ensuring no wear of the main contacts

Life in excess of 10,000 electrical operations at rated current

Page 11: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

11

OHB outdoor circuit-breaker

SF6 interrupter Low filling pressure respect to a pure puffer technique

Arcing-chamber common to HD4 series (tested arcing-chamber)

Pole assembly / ceramic insulators similar to the previous SFE series (tested solution)

Monitoring of the quenching media ”SF6” thanks to the pressure switch

Page 12: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

12

OHB outdoor circuit-breaker

1 Terminal2 Insulating enclosure3 Blasting nozzle4 Moving arcing contact5 Moving contact6 Fixed arcing contact7 Fixed contact8 Insulating tie-rod9 Cap with bursting valve

Page 13: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

13

OHB outdoor circuit-breaker

Breaking technique

M.V. quenching technique based on proven advantages of SF6 ”auto-puffer” H.V. circuit-breaker well-known, tested and used in the major industrialized countries

State-of-the-art SF6 breaking technology

Page 14: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

14

OHB outdoor circuit-breaker

Autopuffer quenching technique : interruption process

Opening of the main contacts

Opening of the arcing contacts

OpenClose

I I I

Page 15: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

15

OHB outdoor circuit-breaker

The circuit-breaker is closed

The current flows from the upper (fixed) terminal to the moving part through the main contacts.

I Upper terminal

Main contacts

Arcing contacts

Moving part

Nozzle

Page 16: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

16

OHB outdoor circuit-breaker

Opening of the main contacts.

The moving part goes down thus separating the main contacts. There is no arc striking as the current keeps flowing from the upper terminal to the moving parts through the arcing contacts. During the downstroke, the moving part exert a pressure on the gas housed in the lower chamber; the pressure increase generated in the lower chamber opens the connection valve of the upper chamber. The compressed gas flows from the lower to the upper chamber thus taking both enclosures at the same pressure level.

I

Page 17: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

17

OHB outdoor circuit-breaker

Notes:

1) no leakage from the nozzle as it is blocked by the fixed arcing contact

2) no leakage from the cylinder of the moving arcing contact as it is blocked by the fixed arcing contact

3) the upper chamber is connected to the moving mechanism and its volume remains the same during the downstroke (dead volume)

4) the only changing volume is the one of the lower chamber, which decreases during the downstroke of the moving contact

5) this puffer is designed to avoid chopping currents by means of a “dead volume” higher than the compressed volume. As the gas flows towards the upper chamber, the pressure level is equal to the ratio between the dead volume and the lower chamber volume.

Page 18: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

18

OHB outdoor circuit-breaker

Opening of the arcing contacts

The current keeps flowing due to the arc generated between the fixed and moving contacts. The gas cannot leak either from the nozzle as the hole is blocked by the fixed contact or from the inside of the moving contact because of the arc clogging effect.

I

Page 19: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

19

OHB outdoor circuit-breaker

The breaking chamber undergoes the following process:

at low currents: as the current hits the natural zero and the arc is quenched, the gas flows from the dead volume to the inside of the moving contact. The low pressure guarantees the absence of chopping currents and the small quantity of gas involved is sufficient to restore the dielectric strenght between the two contacts by avoiding, at the same time, the re-strike of the transient recovery voltage.

Page 20: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

20

OHB outdoor circuit-breaker

At higher short circuit currents: the pressure wave of the arc propagates like a supersonic wave, increasing the gas pressure which closes the valve between the two chambers. From this moment on, the device starts working as a pure “self-blast”, the gas overheating and the molecular dissociation due to the high temperature increase the pressure in the dead volume. Said pressure is proportional to the arc and the resulting gas flow guarantees the quenching at the first passage through zero natural current.

Page 21: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

21

OHB outdoor circuit-breaker

Circuit-breaker in the open position

The arc is quenched; the lower chamber reaches its minimum volume and its maximum pressure level, kept by the valve locked by the supersonic wave. As the self-generated pressure of the dead volume decreases, due to the outflow of the gas through the moving contact, the valve re-opens. From now on, a new jet of fresh gas flows in and makes the temperature of the contacts sink. At the same time, the gas flows through the nozzle, free from the fixed arcing contact. The “cleaning” of the arcing chamber by means of fresh gas makes the device suitable for another reclosing and the interruption up to the maximum breaking capacity.

Page 22: ABB T&D Divisione Sace T.M.S. -01.05.15 - OHB Outdoor sulphur Hexafluoride circuit-Breaker 1-2002

© A

BB

T&

D D

ivis

ione

Sac

e T

.M.S

. -

22