absorption refrigeration systems

Upload: adedire-fisayo

Post on 13-Apr-2018

259 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/21/2019 Absorption Refrigeration Systems

    1/33

    Note: The source of the technical material in this volume is the Professional

    Engineering Development Program (PEDP) of Engineering Services.

    Warning: The material contained in this document was developed for Saudi

    Aramco and is intended for the exclusive use of Saudi Aramcos

    employees. Any material contained in this document which is notalready in the public domain may not be copied, reproduced, sold, given,

    or disclosed to third parties, or otherwise used in whole, or in part,

    without the written permission of the Vice President, Engineering

    Services, Saudi Aramco.

    Chapter : Process For additional information on this subject, contact

    File Reference: CHE21003 R.A. Al-Husseini on 874-2692

    Engineering EncyclopediaSaudi Aramco DeskTop Standards

    Absorption Refrigeration Systems

  • 7/21/2019 Absorption Refrigeration Systems

    2/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards

    CONTENTS PAGES

    OPERATION OF ABSORPTION REFRIGERATION SYSTEMS ..............................................................1

    General Operation of Absorption Refrigeration Systems ................................................................1Operation of Aqua-Ammonia Systems............................................................................................3

    Operation of Lithium Bromide Systems .................................................................................6

    SELECTING APPROPRIATE ABSORPTION SYSTEMS, GIVEN PROCESS

    REQUIREMENTS ..........................................................................................................................8

    Advantages, Features, and Capacities..............................................................................................8

    Aqua-Ammonia .................................................................................................................8

    Lithium Bromide ...............................................................................................................9

    Sizing Calculations..........................................................................................................................10

    Aqua-Ammonia .................................................................................................................10

    Sample Problem.................................................................................................................11

    Lithium Bromide ...............................................................................................................18

    WORK AID.....................................................................................................................................27

    GLOSSARY....................................................................................................................................28

    ADDENDUM..................................................................................................................................29

  • 7/21/2019 Absorption Refrigeration Systems

    3/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards

    LIST OF FIGURES

    Figure 1. Absorption Refrigeration System.......................................................................................1

    Figure 2. Ammonia-Water Single-Stage Absorption Refrigeration System ......................................4

    Figure 3. Lithium Bromide-Water Single-Stage Absorption Refrigeration System ..........................6

    Figure 4. Enthalpy-Concentration Diagram for Ammonia-Water Solution.......................................12

    Figure 5. Enthalpy Values.................................................................................................................15

    Figure 6. Enthalpy-Concentration Diagram for Lithium Bromide-Water Solutions .........................22

    Figure 7. Enthalpy Values Summary For This Particular Lithium Bromide System.........................23

    Figure 8. Typical Values for Li Br Systems......................................................................................25

    Figure 9. Refrigerant Temperature Enthalpy of Lithium Bromide Solutions ....................................26

  • 7/21/2019 Absorption Refrigeration Systems

    4/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 1

    Operation of Absorption Refrigeration Systems

    This section discusses the operation of absorption refrigeration systems in general and the operation of the

    following absorption refrigeration systems, specifically:

    Aqua-ammonia systems

    Water-lithium bromide systems

    General Operation of Absorption Refrigeration Systems

    Absorption refrigeration systems convert heat into cooling power. Figure 1 is a diagram of a basic absorption

    refrigeration system.

    Figure 1. Absorption Refrigeration System

  • 7/21/2019 Absorption Refrigeration Systems

    5/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 2

    In Step 1, hot liquid refrigerant is expanded into a low-pressure, low-temperature liquid and vapor in the

    evaporator. The expansion of the refrigerant cools the refrigerant due to the heat of vaporization. The cold

    refrigerant provides the cooling power.

    In Step 2, the cold, low-pressure refrigerant vapor is converted to a liquid in solution while the low-pressure ismaintained. This conversion occurs when the refrigerant is miscible with the solution base (absorbent) and

    when there is a high affinity between the refrigerant molecules and the absorbent molecules. Thermal energy

    due to the heat of condensation, sensible heats, and heat of dilution is generated in this process. This thermal

    energy must be removed with minimal heating of the refrigerant-absorbent mixture.

    In Step 3, the refrigerant-absorbent mixture is pressurized.

    In Step 4, the refrigerant-absorbent mixture passes through a heat exchanger where the mixture is heated.

    In Step 5, the refrigerant-absorbent mixture undergoes distillation and separates the refrigerant from the

    absorbent. If the pure absorbent material is nonvolatile, a simple still is adequate. If the pure absorbent

    material is volatile, fractional distillation is required. It is critical that the refrigerant that is obtained in this step

    be free of absorbent. The refrigerant from this step is a hot, high-pressure vapor. The absorbent obtained inthis step may contain significant amounts of refrigerant.

    In Step 6, the hot, high-pressure refrigerant vapor passes into a condenser. The condenser cools the vapor

    sufficiently to convert the vapor to a liquid.

    The hot absorbent from Step 5 is transferred through the heat exchanger in Step 4 to heat the refrigerant-

    absorbent mixture, and at the same time, to cool the regenerated absorbent. The regenerated absorbent is then

    supplied as the absorbent for Step 2.

    Critical characteristics of the refrigerant-absorbent pair are as follows:

    The refrigerant and the absorbent should not form a solid over the range of composition and

    temperature to which they may be subjected.

    The refrigerant should be much more volatile than the absorbent.

  • 7/21/2019 Absorption Refrigeration Systems

    6/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 3

    The absorbent should have a strong affinity for the refrigerant under the conditions in which the

    absorption takes place.

    The operating pressures should be moderate. The operating pressures are largely determined by

    the refrigerant.

    The refrigerant, the absorbent, and the mixture should all be chemically stable. They are subjected

    to severe conditions over years of service.

    The refrigerant, the absorbent, and the mixture should be non- corrosive. Corrosion inhibitors

    should be used as necessary.

    The fluids should be nontoxic and nonflammable.

    The refrigerant's latent heat should be high. High latent heats allows the circulation rate of the

    refrigerant and absorbent to be kept to a minimum.

    The fluids should have good transport properties (viscosity, surface tension, thermal diffusivity,

    and mass diffusivity).

    No known refrigerant-absorbent pair has all of the critical characteristics that are listed. Two commonly used

    pairs are ammonia-water and water-lithium bromide. In the following section, the operations of these

    refrigerant-absorbent pairs are discussed. Critical characteristics are discussed in a later section.

    Operation of Aqua-Ammonia Systems

    Figure 2 illustrates the flow of an ammonia-water absorption refrigeration system. In this type of system, water

    is the absorbent, ammonia is the refrigerant, and ammonia-water is the refrigerant-absorbent mixture. The

    following description refers to the circled numbers in Figure 2 to identify specific points in the process. The

    discussion references these points as the steps in the process are described.

  • 7/21/2019 Absorption Refrigeration Systems

    7/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 4

    Figure 2. Ammonia-Water Single-Stage Absorption

    Refrigeration System

  • 7/21/2019 Absorption Refrigeration Systems

    8/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 5

    Point 1 to 2

    Hot water leaves the generator. This water is cooled in the heat exchanger by the incoming ammonia-water

    (4A). The cold water is then sent to the absorber.

    Point 2 to 3

    In the absorber, the cold water absorbs low-pressure ammonia that comes from the evaporator. The ammonia-

    water then enters the strong aqua (SA) tank.

    Point 3 to 4

    The ammonia-water from the (SA) is pumped to the generator system through the heat exchanger. In the heat

    exchanger, the ammonia-water is heated by the water that was produced at point 1.

    Point 4 to 5

    The hot ammonia-water from the heat exchanger enters the distillation tower and, through the tower, the

    generator system. In the tower and generator system, the ammonia is separated from the water. The hot water

    then leaves the generator at point 1.

    Point 5 to 6

    The gaseous ammonia leaves the tower and enters the condenser where the gas is converted to liquid ammonia.

    Point 6 to 7

    The liquid ammonia is expanded in the evaporator, where the liquid is converted into cold liquid and gaseous

    ammonia. The cold liquid vaporizes and cools the evaporator. The cold, gaseous ammonia is then transferred

    to the absorber. In the absorber, the cold, gaseous ammonia is absorbed by the water.

    Point 8

    Upsets in the tower or changes in evaporator operation could cause the concentration of water in the liquid

    ammonia to increase. The periodic spillover connection allows the return of accumulated water to the system.

  • 7/21/2019 Absorption Refrigeration Systems

    9/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 6

    Operation of Lithium Bromide Systems

    Figure 3 illustrates the flow of a lithium bromide-water absorption refrigeration system. In this type of system,

    lithium bromide is the absorbent, water is the refrigerant, and lithium bromide-water is the refrigerant-absorbent

    mixture. The following description refers to the circled numbers in Figure 3 to identify specific points in the

    process. The discussion references these points as the steps in the process are described.

    Figure 3. Lithium Bromide-Water Single-Stage Absorption Refrigeration System

  • 7/21/2019 Absorption Refrigeration Systems

    10/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 7

    Point 1 to 2

    Hot lithium bromide leaves the generator. This lithium bromide is cooled in the heat exchanger by the

    incoming lithium bromide-water. The cold lithium bromide is then sent to the absorber.

    Point 2 to 4

    In the absorber, cold lithium bromide absorbs the low-pressure water vapor that comes from the evaporator.

    Point 4 to 5

    The cool, lithium bromide-water is pumped from the absorber to the generator through the heat exchanger. In

    the heat exchanger, the lithium bromide-water is heated by the lithium bromide that was produced at point 1.

    Point 5 to 1

    Hot lithium bromide-water from the heat exchanger enters the generator. In the generator, heat is added todistill the water. Hot lithium bromide leaves the generator at point 1.

    Path 6 to 7

    Hot, high-pressure water vapor (6) condenses (7).

    Point 7 to 8

    The hot water expands in the evaporator. The expansion vaporizes the water, which becomes the evaporator.

    The cold, low-pressure water vapor is absorbed by the solution in the absorber .

  • 7/21/2019 Absorption Refrigeration Systems

    11/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 8

    Selecting Appropriate Absorption Systems, Given Process Requirements

    This section compares and contrasts aqua-ammonia and lithium bromide-absorption systems through a

    discussion of the following:

    Advantages, features, and capacities

    Sizing calculations

    Advantages, Features, and Capacities

    Absorption refrigeration equipment has the following advantages:

    The system can be powered with waste, low-level heat

    There are no expensive compressors

    They are quiet

    Absorption refrigeration equipment is classified by how it is fired and whether it has a single-stage or two-stagegenerator. Units that use steam or hot fluid heat sources are indirect fired. Units that use a flame heat source

    are direct fired. Units that use hot waste gases as a heat source are indirect fired, but are often referred to as

    heat-recovery units. Units with two-stage generators are called dual-effect or double-effect units.

    Aqua-Ammonia

    The ammonia-water pair (aqua-ammonia absorption system) meets most of the ideal requirements for an

    absorption refrigeration system. However, the volatility ratio is too low; high operating pressures are required;

    and ammonia is an ASHRAE 15-1978 Safety Code Group 2 fluid, restricting its indoor use.

    The low volatility ratio means that it is difficult to completely separate the ammonia from the water and

    requires a compromise in the refrigeration system. There are two possible solutions. In the first solution, the

    refrigerant will have water vapor present as it passes through the condenser and evaporator, which restricts therefrigerant pathway which can freeze at 0C (32F). In the second solution, the water that serves as an

    absorbent will have a significant amount of ammonia already absorbed and will consequently perform as a less

    efficient absorber. Because water is present throughout the system, ammonia-water absorption should not be

    used for applications near or below 0C (32F).

  • 7/21/2019 Absorption Refrigeration Systems

    12/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 9

    The high operating pressures increase the cost of the refrigeration equipment and also increase the inherent

    dangers associated with the equipment. The condenser pressures are around 2068 kPa (300 psia) and the

    evaporator pressures are around 483 kPa (70 psia).

    Ammonia is an ASHRAE 15-1978 Safety Code Group 2 fluid because it can cause serious injury to people atconcentrations of 0.5 to 1.0 percent for durations of exposure over one half hour. Therefore, the use of an aqua-

    ammonia refrigeration cycle in an enclosed space, especially in a space routinely inhabited, is discouraged.

    Direct-fired, air-cooled ammonia-water liquid chillers are available in 3- to 5-ton (10- to 18-kW) capacities.

    Lithium Bromide

    The water-lithium bromide pair (lithium bromide-absorption system) meets most of the ideal requirements for

    an absorption refrigeration system. However, the pair has the following disadvantages:

    The refrigerant (water) freezes at 0C (32F)

    The water-lithium bromide mixture tends to form solids

    Lithium bromide solutions have a high viscosity

    The fact that water freezes at 0C (32F) means that a lithium bromide-absorption system cannot be used for

    applications requiring refrigeration near or below 0C (32F).

    The tendency of the water-lithium bromide mixture to form solids means that the equipment must be designed

    to allow a partially crystallized solution to flow, especially from the generator, through the heat exchanger and

    into the absorber. It may be necessary to provide a mechanism for removing crystals from the solution, re-

    dissolving them, and returning the reconstituted solution to the system. Because the crystallization of the

    solution occurs most readily when the solution is air-cooled, the absorber should be water cooled.

    Small lithium bromide units of 3- to 30-ton (10- to 105-kW) capacity are available as indirect- or direct-fired,liquid chiller, chiller-heater, or air-conditioning equipment. Indirect-fired liquid chillers are available in

    capacities of 50 to 1500 tons (175 to 5275 kW).

  • 7/21/2019 Absorption Refrigeration Systems

    13/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 10

    Sizing Calculations

    The following material demonstrates sizing calculations for aqua-ammonia and lithium bromide refrigeration

    systems. The objective of this module is to provide only a basic understanding of sizing calculations to help

    determine the correct absorption refrigeration process to use for a given application.

    For absorption refrigeration systems, the following equation determines the refrigerant flow rate:

    RE

    =Q

    E

    hv

    hl( ) (EQN A)

    where: R E = Mass (weight) flow of refrigerant from the evaporator

    QE = Heat load at the evaporator

    hv = Enthalpy of refrigerant vapor from the evaporator

    hl = Enthalpy of refrigerant liquid from the condenser

    Aqua-Ammonia

    The following material, including the sample calculation, is extracted from the 1989 ASHRAE Fundamentals

    Handbook. In many cases, calculations include values with greater precision than that obtainable from charts

    included in this module.

    For aqua-ammonia absorption refrigeration systems, the following equation provides the solution flow rate per

    unit refrigerant rate (see Figure 2):

    WFSA(X) WFSG(X 1) = 1 (EQN B)

    where: WFSA = Mass fraction of ammonia in solution coming from the absorber

    WFSG = Mass fraction of ammonia in solution coming from the generator

    X = Mass of solution from the absorber per unit mass of refrigerant flow

    X-1 = Mass of solution from the generator per unit mass of refrigerant

    flow

  • 7/21/2019 Absorption Refrigeration Systems

    14/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 11

    Sample Problem

    The sample calculation is performed for a large aqua-ammonia absorption refrigeration plant with the following

    conditions:

    Refrigeration load, 1758.5 kW (500 tons)

    Evaporator temperature, 5.0C (41.1F)

    Evaporator pressure, 517 kPa (75 psia)

    Absorber pressure, 507 kPa (73.5 psia)

    Strong aqua solution (absorbent-refrigerant mixture) temperature, 41C (105F)

    Condenser temperature, 38C (100F)

    Condenser and tower pressure, 1461 kPa (211.9 psia)

    Concentrate split (WFSG- WFSA), 6% by weight Cooling tower water temperature, 29.4C (85F)

    Assume a 3% increase in refrigerant flow due to heat gains in equipment

    Figure 4 provides the enthalpy-concentration diagram for ammonia-water solution.

  • 7/21/2019 Absorption Refrigeration Systems

    15/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 12

    Source: ASHRAE 1989 Fundamentals Handbook (IP Edition) , Atlanta, GA, American Society of Heating,

    Refrigerating, and Air Conditioning Engineers, Inc., 1989, p. 17.69, figure 33.

    Figure 4. Enthalpy-Concentration Diagram for Ammonia-

    Water Solution

    From Figure 4 and the given conditions of 507 kPa (73.5 psia) and 41C (105F) at the absorber, the strong

    aqua (SA) solution has an ammonia concentration of 49% by mass.

  • 7/21/2019 Absorption Refrigeration Systems

    16/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 13

    A 6% to 8% concentration increase across the absorber allows sufficient flow and adequate liquid wetting of

    plain horizontal tubes % up to 25 mm (1 in) in diameter. The difference between the concentration of ammonia

    in solution that enters the absorber and the concentration of ammonia in solution that exits the absorber is

    referred to as the concentration split. Concentration splits of 6% to 8% ensure reasonable maximum liquid

    flows for cost effective exchangers and towers, and a practical minimum temperature of heat source for thegenerator. Large splits reduce the flow rate, efficiency, and cost effectiveness of absorbers and exchangers and

    raise the required temperature of the heat source.

    For comparison purposes, the calculations will be shown for two splits: 6% and 30%.

    With a 6% concentration split, there is a 43% ammonia concentration by mass in the absorbent returned from

    the generator to the absorber via the heat exchanger.

    Using Equation B, the solution flow rates for a 6% split are the following:

    0.49X 0.43(X1) = 1

    0.06X + 0.43 = 1

    0.06X = 0.57X = 9.5 lb SA/lb refrigerant

    X1 = 8.5 lb WA/lb refrigerant

    Given the condenser and tower pressure of 1461 kPa (211.9 psia) Figure 4 can be used to determine the

    equilibrium to minimal temperature for the 49% ammonia solution that will enter the heat exchanger. Figure 4

    can also be used to determine the equilibrium temperature for the 43% ammonia solution that will leave the

    generator as absorbent for the 6% split.

    With a 30% concentration split, there is a 19% ammonia concentration by mass in the absorbent returned from

    the generator to the absorber via the heat exchanger.

  • 7/21/2019 Absorption Refrigeration Systems

    17/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 14

    Using Equation B the solution flow rates for a 30% split are the following:

    0.49X-0.19(X-1) = 1

    0.30X+0,19 = 1

    0.30X = 0.81 X = 2.7 lb SA/lb refrigerant

    X-1 = 1.7 lb WA/lb refrigerant

    As with the 6% split, Figure 4 can be used to determine the equilibrium temperature of the 19% ammonia

    solution that leaves the generator as absorbent for the 30% split.

    For the 49% ammonia solution, the equilibrium temperature for the tower and generator is 80.5C (176.9F).

    For the 6% split, the 43% concentration ammonia-water leaves the tower and generator at a temperature of

    90.5C (194.9F). For the 30% split, the 19% concentration ammonia-water leaves the tower and generator at a

    temperature of 144.4C (291.9F).

  • 7/21/2019 Absorption Refrigeration Systems

    18/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 15

    Enthalpy values for the ammonia-water from Figure 4 are as presented in Figure 5.

    6% SPLIT 30% SPLIT

    ENTHALPY kJ/kg Btu/lb kJ/kg Btu/lb

    hl of (1)* WA 166.0 71.4 508.4 218.7

    hlof (4)* 112.3 48.3 112.3 48.3

    hl of (3)* SA -65.8 -28.3 -65.8 -28.3

    *Numbers in parentheses refer to the circled numbers and corresponding point in the

    refrigeration system shown in Figure 2.

    Figure 5. Enthalpy Values

    The enthalpy at point (2) in Figure 2 in the refrigeration system is determined by mass enthalpy flow rate

    balance. This calculation is as follows:

    For 6% split (43% ammonia-water):

    71.4 Btu/lb 9. 5 48.3 Btu / lb 28.3 Btu/ lb( )

    8.5= 14. 21 Btu/ l b

    For 30% split (19% ammonia-water):

    218.7 Btu/ lb 2.7 48.3 Btu/lb 28.3 Btu/lb( )1.7

    = 97.04 Btu/lb

  • 7/21/2019 Absorption Refrigeration Systems

    19/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 16

    At these concentrations, Figure 4 indicates the following temperatures for solution entering the absorber (Point

    2):

    For 6% split: 47.8C (118.0F)

    For 30% split: 83.1C (181.6F)

    For ammonia-water mixtures at 49% SA, feed conditions of 174F, tower pressure of 211.9 psia, and a vapor

    product at 99.95% ammonia, the internal reflux rate is .167 lb/lb refrigerant (1.15 times the minimum reflux).

    These values, while specific for the conditions stated, should be adequate for checking a proposal since the

    vapor product should always be about the same. For exact calculations, the tower should be calculated through

    use of computer programs such as "Process."

    Use Figure 4 to calculate the refrigerant flow rate and condenser heat level as follows:

    Tower Top

    (Point 5) saturated vapor at 211.9 psia at 99.9% purity, hv=

    (Figure 2) read T = 110F hv= 569 Btu/lb

    Condenser Outlet

    (Point 6) saturated liquid at 100F and 210 psia

    (Figure 2) read hl= 60 Btu/lb

    Evaporator Outlet

    (Point 7) saturated vapor at 41.1F and 75 psia

    (Figure 2) read hv= 548 Btu/lb

    H across evaporator = 548 60 = 488 Btu/lb

    Refrigerant flow rate (assuming 3% for heat gain through insulation):

    1.03 x 500 Tons x12000 Btu/hr

    Ton x

    lb

    488 Btu = 12664 lb/hr

  • 7/21/2019 Absorption Refrigeration Systems

    20/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 17

    Generator Heat Load:

    Heat Out 6% Split (Btu/hr) 30% Split (Btu/hr)

    (Point 6) Ql 12,664 x 60 = 759,840

    (Condenser) Qc 12,664 x (569 60) = 6,445,976

    (Reflux) Qr .167 x 12,664 x (569 60) = 1,076,478

    Sub Total Heat Out:8,282,294 8,282,294

    (Point 1) QWA 8.5 x 12,664 x 71.4 = 7,685,782 1.7 x 12,664 x 218.7 = 4,708,349

    Total Heat Out: 15,968,076 12,990,643

    Heat In

    (Feed) Qf 9.5 x 12,664 x 48.3 = 5,810,876 2.7 x 12,664 x 48.3 = 1,651,512

    Generator Heat

    by Difference: 10,157,200 11,339,131

    Absorber Load:

    Heat In 6% Split (Btu/hr) 30% Split (Btu/hr)

    (Point 7) 12,664 x 548 = 6,939,872 12,664 x 548 = 6,939,872

    (Point 2) 8.5 x 12,664 x (-14.21) = -1,529,621 1.7 x 12,664 x 97.04 = 2,089,155

    Sub Total Heat In:5,410,251 9,029,027

    Heat Out

    (Point 3) 9.5 x 12,664 x (-28.3) = -3,404,716 2.7 x 12,664 x (-28.3) = 967,656

    Qa Absorber Load

    by Difference: 8,814,967 9,996,683

  • 7/21/2019 Absorption Refrigeration Systems

    21/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 18

    Heat Balance:

    Heat In 6% Split (Btu/hr) 30% Split (Btu/hr)

    Evaporator 12,664 x (548 60) = 6,180,032 12,664 x (548 60) = 6,180,032

    Generator 10,157,200 11,339,131

    16,337,232 17,519,163

    Heat Out

    Condenser 6,445,976 6,445,976

    Reflux Coil 1,076,478 1,076,478

    Absorber 8,814,967 9,996,683

    16,337,421 17,519,137

    Coefficient of Performance (COP)

    6,180,032 (1.03 x 10,157,200)

    =.591

    6,180,032 (1.03 x 11,339,131) =.529

    The Coefficient of Performance (COP) for absorption refrigeration is the amount of cooling derived from the

    system divided by the amount of heat required to separate the refrigerant from the absorbent.

    Lithium Bromide

    The following material, including the sample calculation, is extracted from the 1989 ASHRAE Fundamentals

    Handbook. In many cases, greater precision is obtained through use of calculations than through use of the

    charts in this module.

  • 7/21/2019 Absorption Refrigeration Systems

    22/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 19

    For lithium bromide-absorption refrigeration systems, the following equation provides the solution flow rate per

    unit refrigerant rate:

    1 WFSA

    ( ) X( ) 1 WFSG( ) X 1( ) = 1 (EQN C)

    where: WFSA = Mass fraction of lithium bromide in solution coming from the absorber

    WFSG = Mass fraction of lithium bromide in solution coming from the generator

    X = Mass of solution from the absorber per unit mass of refrigerant flow

    X-1 = Mass of solution from the generator per unit mass of refrigerant flow

    The sample calculation is performed for a large lithium bromide-absorption refrigeration plant with the

    following conditions (single-digit numbers in parentheses refer to circled numbers in Figure 3):

    Refrigeration load, 1758 kW (500 tons)

    Evaporator temperature (8), 5.0C (41.1F)

    Absorber equilibrium temperature (3), 42C (107.2F)

    Actual solution temperature (4), 38C (100.9F)

    Solution temperature (5), 76.8C (170.3F)

    Solution temperature (1), 98.7C (209.6F)

    Solution temperature (2), 53.4C (128.1F)

    Refrigerant vapor temperature (6), 93.3C (200F)

    Refrigerant temperature (7), 43.3C (110F)

    Refrigerant spillover rate (9), 2.5% of (8)

    Concentration of solutions: WFSAis 0.595 and WFSGis 0.646

    Chilled water temperature, 12.2-6.7C (54-44F)

    Cooling water temperature entering, 29.4C (85F)

    Assume no inerts present

    Cooling water tower flow rate, 408 m3/hr (1800 gpm)

  • 7/21/2019 Absorption Refrigeration Systems

    23/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 20

    For the given values for WFSAand WFSG, X can be calculated using Eqn. C as follows:

    (1 0.595)X (1 0.646)(X 1)= 1

    0.405X (0.354)(X 1)= 1

    0.051X + 0.354 = 1

    0.051X = 0.646

    X = 12.67 lb solution from

    absorber/ lb refrigerant

    To calculate the amount of coolant flow required to provide the 500 tons of refrigeration, the enthalpy change

    of the coolant as it passes through the evaporator is needed. The refrigerant enters the evaporator as a liquid at

    110F and leaves the evaporator as a gas at 41.1F.

    Enthalpy Evaporator Vapor (8) = 1,079.80 Btu/lb

    Enthalpy of Liquid From Condenser (7) = -77.94

    Difference H = 1,001.86 Btu/lb

    Use standard steam tables for saturated vapor at 41.1F

    Refrigerant Flow (including 2.5% spillover) =

    1.025 x500 tons

    1,001.86x

    12,000 Btu/ hr

    tonx

    hr

    60 min= 102.3 lb/min

    Solution Flow Rate From Absorber =

    12.67 lb solution/lb refrigerant x 102.3 lb/min = 1,296.14 lb/min dilute solution

    Concentrated Solution From Generator = 1,296.14

    -102.30 lb/min refrigerant

    1,193.84 lb/min conc. solution

  • 7/21/2019 Absorption Refrigeration Systems

    24/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 21

    Enthalpy of Liquid Spillover (9) =9.15 Btu/lb

    Use standard steam tables for saturated vapor at 41.1F

    Enthalpy of Generator Bottoms From Exchanger (2) = 71.70 Btu/lbUse Figure 6 at concentrations of 64.6% and temperature of 121.1F

    Enthalpy of Absorber Bottoms (4) = 47.20 Btu/lb

    Use Figure 6 at concentrations of 59.5% and temperature of 100.9F

    Enthalpy of Feed to Generator (5) = 79.00 Btu/lb

    Use Figure 6 at concentrations of 59.5% and temperature of 170.3F

    Enthalpy of Liquid From Generator (1) = 107.00 Btu/lb

    Use Figure 6 at concentrations of 64.6% and temperature of 209.6F

    Enthalpy of Generator Overhead (6) = 1,150.30 Btu/lb

    The approximate pressure of the generator overhead is equal to 65.9 mm

    (1.27 psia) (the saturation pressure of water at the condenser outlet with a temperature of 110F). The enthalpy

    of the generator overhead is the vapor enthalpy of steam at 200F and 1.27 psia.

  • 7/21/2019 Absorption Refrigeration Systems

    25/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 22

    Source: ASHRAE 1989 Fundamentals Handbook (IP Edition) , Atlanta, GA, American Society of Heating,Refrigerating, and Air Conditioning Engineers, Inc., 1989, p. 17.71, Figure 34.

    Figure 6. Enthalpy-Concentration Diagram for Lithium Bromide-

    Water Solutions

  • 7/21/2019 Absorption Refrigeration Systems

    26/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 23

    Enthalpy values are summarized in Figure 7.

    ENTHALPY kJ/kg Btu/lb

    hvof (8)* 2,509.9 1,079.8

    hlof (7)* 181.2 77.94hlof (9)* 21.3 9.15

    hlof (2)* 166.7 71.7

    hlof (4)* 109.7 47.2

    hlof (5)* 183.6 79.0

    hlof (1)* 248.7 107.0

    hlof (6)* 2,673.8 1,150.3

    *Numbers in parenthesis refer to circled points in flow diagram, Figure 2.

    Figure 7. Enthalpy Values Summary For This Particular Lithium

    Bromide System

    Material and heat balance the system:

    Absorber:

    Heat In Calculation

    Solution

    (Btu/min)

    (Point 2) 1,193.84 lb/min conc. solution x 71.7 85,598.3

    (Point 8) 102.3 1.025 lb/min refrig. vapor x 1,079.8 Btu/lb 107,769.3

    (Point 9) (102.3 1.025) x (.025) refig. liq. x 9.15 Btu/lb 22.8

    193,390.4

    Heat Out

    (Point 4) 1,296.14 dilute solution lb/hr x 47.2 61,177.8

    Absorber Load by Difference: 132,212.6

  • 7/21/2019 Absorption Refrigeration Systems

    27/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 24

    Generator:

    HeatOut

    Calculation

    Solution

    (Btu/min)

    (Point 1) 1,193.84 conc. solution lb/hr x 107 127,741

    (Point 6) 102.3 refrigerant lb/hr x 1,150.3 117,676

    245,417

    Heat In

    (Point 5) 1,296.14 x 79 102,395

    Generator Load by Difference: 143,022

    Condenser:

    Heat In Calculation

    Solution

    (Btu/min)

    (Point 6) 102.3 x 1,150.3 117,676

    Heat Out

    (Point 7) 102.3 x 77.94 7,973

    Condenser Load by Difference: 109,703

    Evaporator:

    500 tons x12,000 Btu/ hr

    tonx

    hr60 min

    = 100,000 Btu min

    Overall Heat Balance:

    Heat In Btu/min

    Evaporator Load 100,000

    Generator Load 143,022

    243,022

    Heat Out

    Absorber Load 132,213

    Condenser Load 109,703

    241,916

  • 7/21/2019 Absorption Refrigeration Systems

    28/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 25

    The two totals should be the same. However, there are small differences in reading enthalpy values. The

    overall balance is within .46% and is considered complete. The coefficient of performance (COP) is calculated

    as follows:

    COP = Evaporator LoadGenerator Load

    = 100,000143,022

    = .699

    Consider a 2% loss to surroundings: the effective COP is .699 x .98 = .685.

    The steam load to the generator can be calculated knowing the steam/ condensate properties and the heat load

    of 143,022 Btu/min.

    The cooling water rate can be calculated given the water inlet and allowable temperature use with the duty of

    109,703 Btu/min.

    Warmer cooling water will lower the COP since the generator pressure/ temperature will change, which will

    change the concentration of Li Br that can be achieved. Similarly, cooler steam temperatures will lower COPfor the same reason. Cooling water temperatures and steam temperatures can be traded within limits to

    maintain the COP.

    Typical Values for Li Br Systems

    Single Stage Double Effect

    Leaving chilled water temp. 6.7C (44F) 6.7C (44F)

    Chilled water differential 5.5C (10F) 5.5C (10F)

    Entering condenser water temp. 29.4C (85F) 29.4C (85F)

    Steam pressure at control valve inlet

    (gage pressure, dry and saturated)

    62-83 kPa

    (9-12 psig)

    296-896 kPa

    (43-130 psig)

    Exchanger fouling factor 90 mm2k/w

    (.0005 hr ft2F/Btu)

    90 mm2k/w

    (.0005 hr ft2F/Btu)

    Cooling water rate .065 L/s per kw

    (3.6 gpm/ton)

    .054 L/s per kw

    (3.6 gpm/ton)

    Cooling water temp. rise 9C (16F) 8C (15F)

    Steam rate 1.5 kw/kw

    (18.5 lb/hr per ton)

    .43 g/s per kw

    (12 lb/hr per ton)

    Source: ASHRAE 1989 Fundamentals Handbook (IP Edition), Atlanta, GA, American Society of Heating, Refrigerating,

    and Air Conditioning Engineers, Inc., 1989, p. 13.7, Table 1 & 2.

    Figure 8. Typical Values for Li Br Systems

  • 7/21/2019 Absorption Refrigeration Systems

    29/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 26

    Refrigerant Temperature (t ' = F) and Enthalpy (h = Btu/lb) of Lithium Bromide Solutions

    Percent Li Br

    Temp.(t= F)

    0 10 20 30 40 45 50 55 60 65 70

    80t'

    h

    80.0

    48.0

    78.2

    39.2

    75.6

    31.8

    70.5

    25.6

    60.9

    21.6

    53.5

    21.2

    42.1

    23.0

    28.6

    28.7

    13.8

    38.9

    #-0.2

    #52.7

    #-11.6

    #67.1

    100t'

    h

    100.0

    68.0

    98.1

    56.6

    95.3

    47.0

    89.9

    38.7

    79.6

    33.2

    71.8

    32.1

    60.0

    33.2

    46.1

    38.2

    30.9

    47.8

    #16.2

    #61.1

    #3.8

    #75.1

    120t'

    h

    120.0

    87.9

    117.9

    73.6

    114.9

    61.7

    109.2

    51.7

    98.3

    44.7

    90.1

    43.0

    77.9

    43.6

    63.6

    48.0

    48.1

    56.9

    32.7

    69.4

    #19.1

    #83.0

    140t'

    h

    140.0

    107.9

    137.8

    91.0

    134.6

    77.0

    128.5

    65.1

    117.1

    56.5

    108.5

    54.1

    95.8

    54.1

    81.2

    57.9

    65.2

    66.1

    49.1

    78.0

    #34.4

    #91.1

    160t'

    h

    160.0

    127.9

    157.7

    108.2

    154.3

    92.0

    147.9

    78.2

    135.8

    68.1

    126.8

    65.1

    113.8

    64.7

    98.7

    67.9

    82.3

    75.4

    65.6

    86.6

    #49.7

    #99.2

    180t'

    h

    180.0

    147.9

    177.5

    125.4

    173.9

    107.9

    167.2

    91.9

    154.5

    80.4

    145.1

    76.6

    131.7

    75.3

    116.2

    77.7

    99.5

    84.6

    82.0

    95.1

    #65.1

    #107.2

    200t'

    h

    200.0

    168.0

    197.4

    143.4

    193.6

    123.3

    186.5

    105.3

    173.3

    92.1

    163.5

    87.4

    149.6

    85.9

    133.7

    87.8

    116.6

    94.1

    98.5

    104.0

    #80.4

    #115.6

    220t'

    h

    220.0

    188.1

    217.2

    160.7

    213.3

    138.2

    205.8

    119.0

    192.0

    104.1

    181.8

    99.0

    167.5

    96.5

    151.3

    97.8

    133.7

    103.3

    114.9

    112.5

    95.7

    123.6

    240t'

    h

    *240.0

    *208.3

    *237.1

    *178.4

    232.9

    154.0

    225.2

    132.6

    210.7

    116.0

    200.2

    110.3

    185.4

    107.1

    168.8

    107.7

    150.9

    112.5

    131.4

    121.1

    111.0

    131.6

    260t'

    h

    *260.0

    *228.6

    *256.9

    *195.7

    *252.6

    *169.1

    *244.5

    *146.2

    229.4

    128.1

    218.5

    121.6

    203.3

    117.6

    186.3

    117.6

    168.0

    121.6

    147.9

    129.5

    126.4

    139.5

    280t'

    h

    *280.0

    *249.1

    *276.8

    *213.8

    *272.3

    *185.1

    *263.8

    *159.7

    *248.2

    *140.0

    *236.8

    *132.8

    221.2

    128.1

    203.9

    127.5

    185.1

    130.6

    164.3

    137.9

    141.7

    147.6

    300t'

    h

    *300.0

    *269.6

    *396.7

    *231.6

    *291.9

    *200.7

    *283.1

    *173.5

    *266.9

    *152.1

    *255.2

    *144.1

    *239.2

    *138.9

    221.4

    137.3

    202.3

    139.8

    180.8

    146.5

    157.0

    155.5

    320t'

    h

    *320.0

    *290.3

    *316.5

    *249.7

    *311.6

    *216.3

    *302.5

    *187.2

    *285.6

    *164.2

    *273.5

    *155.3

    *257.1

    *149.5

    *238.9

    *147.1

    219.4

    148.8

    197.2

    154.9

    172.4

    163.4

    340t'

    h

    *340.0

    *311.1

    *336.4

    *267.9

    *331.3

    *232.1

    *321.8

    *201.0

    *304.4

    *176.1

    *291.9

    *166.6

    *275.0

    *160.1

    *256.4

    *157.0

    *236.5

    *158.0

    213.7

    163.5

    187.7

    171.0

    360t'

    h

    *360.0

    *332.2

    *356.2

    *286.1

    *350.9

    *248.0

    *341.1

    *214.9

    *323.1

    *188.2

    *310.2

    *178.0

    *292.9

    *170.6

    *274.0

    *166.8

    *253.7

    *167.0

    230.1

    171.9

    203.0

    178.3

    *Extensions of data above 235F are well above the original data and should be used with care.

    Source: ASHRAE 1989 Fundamentals Handbook (IP Edition) , Atlanta, GA, American Society of Heating, Refrigerating, and

    Air Conditioning Engineers, Inc., 1989, p. 17.70.

    Figure 9. Refrigerant Temperature Enthalpy of Lithium Bromide

    Solutions

  • 7/21/2019 Absorption Refrigeration Systems

    30/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 27

    Work Aid 1: Procedure for Sele cting Appropriate Absorption systems,

    Given Process Requirements

    1. Decide if the refrigeration system must provide cooling to a temperature at or below the freezing point of

    water (0C or 32F). Do not use an ammonia-water or lithium bromide-water system.

    2. If the refrigeration system is to be installed inside an enclosed structure, and especially if it is to be

    installed inside an inhabited structure, select a lithium bromide system.

    3. If Step 1 or Step 2 does not force a choice, select the system with the best economy. Obtain the

    investment and utility requirements from the vendor. Use utility costs specific for the location, and

    calculate the operating cost for each proposal. Check the vendor's utility requirements using the methods

    given in the sample problems. Choose the most economical system.

  • 7/21/2019 Absorption Refrigeration Systems

    31/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 28

    GLOSSARY

    absorbent A material which, in contact with a liquid or gas, extracts one or more

    components for which it has an affinity.

    absorption refrigeration Refrigeration in which cooling is effected by expansion of a liquid

    refrigerant into a gas and absorption of the gas by absorbent; the

    refrigerant is reused after separation from the absorbent.

    affinity The ability of an absorbent to easily suck in (absorb) the refrigerant.

    aqua-ammonia system A system that uses a combination of ammonia and water. The ammonia

    functions as the refrigerant, and the water as the absorbent.

    COP Coefficient of Performance. The amount of cooling derived from the

    absorption refrigeration system, divided by the amount of heat required

    to separate the refrigerant from the absorbent.

    direct-fired Refrigeration units that use a flame as their heat source.

    double-effect

    (dual-effect)

    Absorption refrigeration units with two-stage generators.

    heat-recovery Refrigeration units that are indirect-fired and use hot waste gases.

    indirect-fired Refrigeration units that use steam or hot fluid heat as their heat source.

    miscible The refrigerant is capable of being completely mixed with the absorbent

    and forms a single phase.

    lithium bromide system A system that uses a combination of lithium bromide and water. Thewater functions as the refrigerant, and the lithium bromide as the

    absorbent.

    refrigerant A substance that releases or absorbs a large latent heat when it undergoes

    a change in phase (liquid-to-gas or gas-to-liquid).

    spillover Movement of high water concentration liquid ammonia to the absorber

    from the bottom of the evaporator.

  • 7/21/2019 Absorption Refrigeration Systems

    32/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    Saudi Aramco DeskTop Standards 29

    ADDENDUM

    ADDENDUM A: EQUATIONS USED IN ChE 210.03

    RE =QE

    hv hl( ) (EQN A)

    where: R E = Mass (weight) flow of refrigerant from the evaporator

    QE = Heat load at the evaporator

    hv = Enthalpy of refrigerant vapor from the evaporator

    hl = Enthalpy of refrigerant liquid from the condenser

    WFSA(X) WFSG(X 1) = 1 (EQN B)

    where: WFSA = Mass fraction of ammonia in solution coming from the absorber

    WFSG = Mass fraction of ammonia in solution coming from the generator

    X = Mass of solution from the absorber per unit mass of refrigerant flow

    X-1 = Mass of solution from the generator per unit mass of refrigerant flow

    1 WFSA( ) X( ) 1 WFSG( ) X 1( ) = 1 (EQN C)

    where: WFSA = Mass fraction of lithium bromide in solution coming from the absorber

    WFSG = Mass fraction of lithium bromide in solution coming from the generator

    X = Mass of solution from the absorber per unit mass of refrigerant flow

    X-1 = Mass of solution from the generator per unit mass of refrigerant flow

  • 7/21/2019 Absorption Refrigeration Systems

    33/33

    Engineering Encyclopedia Process

    Absorption Refrigeration Systems

    ADDENDUM B: SYMBOLS USED IN ChE 210.03

    hv = Enthalpy of refrigerant vapor

    hl = Enthalpy of refrigerant liquid

    QE = Heat load at the evaporator

    RE = Mass (weight) flow of refrigerant from the evaporator

    WFSA = Mass fraction in solution coming from the absorber

    WFSG = Mass fraction in solution coming from the generator

    X = Mass of solution from the absorber per unit mass of refrigerant flow

    X1 = Mass of solution from the generator per unit mass of refrigerant flow