acceptance testing of fire protection systems 101

117
Acceptance Testing

Upload: hahanh

Post on 11-Dec-2016

218 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Acceptance Testing of Fire Protection Systems 101

Acceptance Testing

Page 2: Acceptance Testing of Fire Protection Systems 101

Acceptance Testing of Fire Protection Systems 101

• Touch on all types of Fire Sprinkler of systems• Fire Pumps and Standpipes• Requirements for Acceptance Testing per NFPA

and the State Fire Marshal• Industry Jargon and Common terminology• State Rules- Texas Insurance Code Chapter 6003

& 28 TAC SS 34.700• Information in these slides comes from NFPA

Standards 13, 14 and 20

Page 3: Acceptance Testing of Fire Protection Systems 101

Defining Terms• “Authority Having Jurisdiction”• Listed and Approved• “Shall” vs. “Should”• Hydrostatic Testing And Cover• Add and Relocates (Remodels) vs. New

System installs• Main Drain Test

Page 4: Acceptance Testing of Fire Protection Systems 101

• Control Valve Testing• Tagging Requirements• System Type- Wet, Dry,

Preaction and Deluge with specific differences and required tests for each

• Specific Application System- ESFR, Control Mode, Residential, Double Interlock, etc

Page 5: Acceptance Testing of Fire Protection Systems 101

Authority Having Jurisdiction (AHJ)

3.2.2* “An organization, office or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure”

Page 6: Acceptance Testing of Fire Protection Systems 101

Examples:• Fire Chief, Fire Marshal• Labor Department• Health Department- TDADS• Building Official, Electrical

Inspector, Plumbing Inspector• Insurance Organizations and their

Representatives• Commanding Officer on Base

Page 7: Acceptance Testing of Fire Protection Systems 101

…essentially…

Anyone with a vested interest in the system performing as intended

Page 8: Acceptance Testing of Fire Protection Systems 101

Listed

3.2.2* “Equipment, materials, or services included in a list published by an organization that is acceptable to the authority having jurisdiction”….

Page 9: Acceptance Testing of Fire Protection Systems 101

Approved3.2.1 “Acceptable to the authority

having jurisdiction”

All materials and methods for installation are to conform to Chapter 6 of NFPA 13- 2007 or the individual product listings and approvals. When in doubt……..

Approved Materials

Page 10: Acceptance Testing of Fire Protection Systems 101

…Make the installing contractor prove it to your satisfaction!!!!

• If it looks incorrect, it probably is• Be wary of new products, have

contractor provide cut sheets when in doubt

• Good review with thorough walk through at hydro at end of job

Page 11: Acceptance Testing of Fire Protection Systems 101

• Your interpretation of the codes and standards is to be met or proven incorrect- codes/ standards are in writing- not inferred

• Sometimes corners are cut by unscrupulous contractors

• Some poor installs are mistakes or “human error” - BUT….

Page 12: Acceptance Testing of Fire Protection Systems 101

Report repeat offenders to the

State Fire Marshal’s office!!!

Page 13: Acceptance Testing of Fire Protection Systems 101

REMEMBER…• You are the last line of defense to

ensure the end user gets what they expect and paid for!!! These are your customers, you are their expert!

• Poor installs fail annual inspections and cost the owner money later for repairs

Page 14: Acceptance Testing of Fire Protection Systems 101

Shall3.2.4 “Indicates a mandatory

requirement.”

Should3.2.5 “Indicates a recommendation

or that which advised but not required.”

Page 15: Acceptance Testing of Fire Protection Systems 101

System Acceptance

• Acceptance Testing of systems is contained in Chapter 24 of NFPA 13-2007 Edition

• All required tests are listed, but required extra heads and some paperwork is not.

Page 16: Acceptance Testing of Fire Protection Systems 101

Hydrostatic Test

• Section 24.2.1- “All piping and attached appurtenances subjected to system working pressure shall be hydrostatically tested at 200 psi (13.8 bar) and shall maintain that pressure without loss for two hours”

Page 17: Acceptance Testing of Fire Protection Systems 101

• Section 24.2.1.2- Portions of systems normally subjected to working pressures in excess of 150 psi (10.4 bar) shall be tested as described in 24.2.1.1 at a pressure of 50 psi (3.5 bar) in excess of working pressure

Page 18: Acceptance Testing of Fire Protection Systems 101

Things to watch at Hydro• Need to know expected pump

churn pressure and expected system working pressure, are PRV’s required?

• Hydrostatic test pressure is taken at the bottom of the system, not the top (Section 24.2.1.8)

Page 19: Acceptance Testing of Fire Protection Systems 101

• Know the limits of the materials- pressure limitations of fittings and sprinkler heads

• If there is freeze potential, an interim pneumatic air test at 40 psi can be conducted for 24 hours per 24.2.2. This does not remove or replace the requirement for a hydrostatic test.

Page 20: Acceptance Testing of Fire Protection Systems 101

• This test is referred to as a “Hydro Test” or “Cover Inspection”

• All systems require this type of test- Sprinkler, Standpipe, Pump

• In new construction the pipe should not be covered up during the test

• A procedure for removing “test blanks” must be in place

Page 21: Acceptance Testing of Fire Protection Systems 101

• Retrofits are typically covered up. These are existing buildings and not all areas are accessible. Use your own judgment.

• Walk systems during the two hour test, look for leaks. Small leaks are not cause for concern.

• Excessive water leakage and pressure drop are cause for failure and re-test of system

Page 22: Acceptance Testing of Fire Protection Systems 101

Hydro Test Procedure• Contractor should have system

pumped up above 200 psi or 50 above working pressure, prior to your arrival to remove air pockets

• Note Pressure on gauge upon arrival.

• Walk system- look for leaks.

Page 23: Acceptance Testing of Fire Protection Systems 101

• While walking system, note areas that are in need of repair or changes required in the system to installing contractor.

• At end of two hour period, note pressure (loss if any). Have Contractor drain system to zero the gauge out in your presence.

Page 24: Acceptance Testing of Fire Protection Systems 101

Things to Keep in Mind• FDC piping is often overlooked- Needs

to be tested @ 150psi after repair/ replacement- Sec 24.2.1.10

• Temperature changes affect system pressure during hydro.

• Trapped air in the system takes time to escape, if the system has not been pumped up for some time then air will escape.

Page 25: Acceptance Testing of Fire Protection Systems 101

Add and Relocates• 24.2.1.4- “Modifications affecting

20 or fewer sprinklers shall not require testing in excess of system working pressure”

Page 26: Acceptance Testing of Fire Protection Systems 101

• Per Section 24.2.1.5- Modifications above 20 sprinklers, isolate the affected portion of the system and hydro

• Per Section 24.2.1.6- Modifications that cannot be isolated (i.e.. Relocated drops) shall not require tested in excess of system working pressure

Page 27: Acceptance Testing of Fire Protection Systems 101

Main Drain Test• 24.2.3.4.1 “The main drain valve

shall be opened and remain open until system pressure stabilizes”

• 24.2.3.4.2 “The static and residual pressures shall be recorded on the contractor’s material and test certificate”

• Use the bottom gauge

Page 28: Acceptance Testing of Fire Protection Systems 101

• Often overlooked• Required on State “white tags”• Provides baseline water supply

test information to measure water supply deterioration in subsequent NFPA 25 Inspections.

• This is required on all systems! The importance cannot be stressed enough!

Page 29: Acceptance Testing of Fire Protection Systems 101

Size of main drainsTable 8.16.2.4.2-Drain Size_________

Riser or Main Size Size of Drain

ConnectionUp to 2 in. 3⁄4 in. or larger21⁄2 in., 3 in., 31⁄2 in. 11⁄4 in. or larger4 in. and larger 2 in. only

No test orifices on main drains!!!! Need fully open for Main Drain Test. Listed Test and drain assemblies are acceptable if capable of full flow.

Page 30: Acceptance Testing of Fire Protection Systems 101

Operational Tests• Referred to as a “Final”• While performing this test, an

inspection should be performed. Things to look for:– Loaded or painted sprinkler heads– Adequate coverage of all spaces– Missing pieces or incorrect install– Tamper and flow switch operation– Fire Alarm System should be on “Test”

Page 31: Acceptance Testing of Fire Protection Systems 101

Walk the space- Check head coverage

• Light Hazard– 225 Sq Ft– Max. 15’ X 15’

• Ordinary Hazard– 130 Sq Ft– Max. 15 ft X 8’-8”

Page 32: Acceptance Testing of Fire Protection Systems 101

• Extra Hazard– 100 Sq Ft– Max. 10’ X 10’ or 12 X 8’-4”

• Storage, ESFR, Control Mode– Look up each individual section-

these change often– Request the sprinkler cut sheet from

the Contractor- these are specific application and may have some special requirements

Page 33: Acceptance Testing of Fire Protection Systems 101

Obstructions• Depending on the type of head

and the obstruction• Refer to Chapter 8 in NFPA 13-

’07. • All types of heads are broken

down individually

Page 34: Acceptance Testing of Fire Protection Systems 101
Page 35: Acceptance Testing of Fire Protection Systems 101

Alarm Initiating Devices

Page 36: Acceptance Testing of Fire Protection Systems 101

Testing Alarm Switches• Inspector’s test connection should

have at least 1 inch pipe connected to a corrosion resistant orifice equal to the size of the smallest orifice on the system.

• Open ITC all the way, alarm should sound in less than 5 minutes

Page 37: Acceptance Testing of Fire Protection Systems 101

• If bell goes off too quick, have contractor adjust delay on alarm device to account for water hammer in city water to avoid nuisance alarms.

• Ensure cover is on WF switch after test is performed

• Call the monitoring company- verify signals are correct for the space/ bldg

Page 38: Acceptance Testing of Fire Protection Systems 101

Valve Tamper Switches

Page 39: Acceptance Testing of Fire Protection Systems 101

Testing Tamper Switches

8.16.1.1.2.1- “Valves on connections to water supplies, sectional control valves, and other valves in supply pipes to sprinklers and other fixed water based fire suppression systems shall be supervised by one of the following:”

Page 40: Acceptance Testing of Fire Protection Systems 101

(1)Central station, proprietary, or remote station signaling at a constantly attended point

(2)Local signaling service that will cause the sounding of an audible signal at a constantly attended point

(3)Valves locked in the correct position(4)Valves in fenced enclosures under

the owner’s control

Page 41: Acceptance Testing of Fire Protection Systems 101

Testing Tampers• 24.2.3.5.1 “All control valves

shall be fully closed and opened under system water pressure to ensure proper operation”

• Check the valve operation• Check Tamper operation and

signal to monitoring company

Page 42: Acceptance Testing of Fire Protection Systems 101

24.2.4- Pressure Reducing Valves

Page 43: Acceptance Testing of Fire Protection Systems 101

Common Misinterpretation

• PRV’s should be a Pressure Reducing Valve- NOT Restricting or Relief Valve

• True PRV’s Reduce pressure under both Flow and Static Conditions

• NFPA 14-’07 Sec. 3.3.16.4 • NFPA 13-’07 Sec. 8.16.1.2.1

Page 44: Acceptance Testing of Fire Protection Systems 101

Where Required• Sprinkler-When working pressure

exceeds 175 psi unless all downstream components are rated for the higher pressure

• Standpipe-For Fire Hose Valves where pressure exceeds 175 psi on 2-1/2” FHV’s pressure shall be limited to 100 psi- 1-1/2” valves can be of regulating type

Page 45: Acceptance Testing of Fire Protection Systems 101
Page 46: Acceptance Testing of Fire Protection Systems 101

PRV Requirements-Fire Sprinkler

• 8.16.1.2.2- Pressure gauges shall be on the inlet and outlet sides of each pressure reducing valve

• 8.16.1.2.3- A relief valve of not less than ½” shall be provided on the discharge side set to operate at a pressure not exceeding 175 psi.

Page 47: Acceptance Testing of Fire Protection Systems 101

• 8.16.1.2.4- A listed indicating valve shall be provided on the inlet side of each PRV, unless the PRV meets the listing requirements for use as an indicating valve.

• 8.16.1.2.5- Means shall be provided downstream of all PRV’s for flow tests at sprinkler demand

Page 48: Acceptance Testing of Fire Protection Systems 101

Acceptance Testing PRV’s

• 24.2.4.1- Each pressure-reducing valve shall be tested upon completion of installation to insure proper operation under flow and no-flow conditions.

• 24.2.4.2- Testing shall verify device regulates outlet at maximum and normal conditions

Page 49: Acceptance Testing of Fire Protection Systems 101

• 24.2.4.3- The results of the flow test of each PRV shall be recorded on the contractor’s material and test certificate

• 24.2.4.4- The results shall include the static and residual inlet pressures, static and residual outlet pressures and the flow rate

Page 50: Acceptance Testing of Fire Protection Systems 101

• Ask for PRV Testing Logs to show work was completed

• NFPA 14- 7.2 requires 1-1/2” hose valves residual pressure limited to 100 psi and 2-1/2” hose valves static and residual pressure limited to 100 psi where pressure exceeds 175 psi

Standpipe Hose Valve PRV’s- NFPA 14-’07

11.5.4

Page 51: Acceptance Testing of Fire Protection Systems 101

Backflow Prevention Assemblies-8.17.4.6

• A.8.17.4.6- Where backflow prevention devices are installed, they should be in an accessible location to provide service and maintenance

Page 52: Acceptance Testing of Fire Protection Systems 101

• 8.17.4.6.1- Means shall be provided downstream of all backflow prevention valves for flow tests at system demands

• A.8.17.4.6.1 describes the describes the methods available- essentially ensuring the backflow will not restrict the system demand

Page 53: Acceptance Testing of Fire Protection Systems 101

Backflow Prevention Assemblies

Section 23.1.8 references AWWA M14, Recommended Practice for Backflow Prevention and Cross

Connection Control and the public Health AHJ requirements

Where are they Required???

Page 54: Acceptance Testing of Fire Protection Systems 101

Backflow Prevention Acceptance Testing-

24.2.5• 24.2.5.1- The backflow prevention

assembly shall be forward flow tested to ensure proper operation.

• 24.2.5.2- The minimum flow rate shall be the system demand, including hose stream …

Page 55: Acceptance Testing of Fire Protection Systems 101

• A copy of the state or local test report performed by a TCEQ approved tester should be attached to the riser

• An approved inspection by the local Health AHJ should be provided prior to final.

Page 56: Acceptance Testing of Fire Protection Systems 101

Circulating Closed Loop Systems

• These are covered in 24.3. • Requires certification of pressure

ratings for auxiliary devices and proof of pressure test in all modes of operation

• Discharge tests to be per 6.9.1- the five minute requirement

Page 57: Acceptance Testing of Fire Protection Systems 101

Wet Pipe System

For Heated Buildings Commercial Industrial Residential Hospitals Educational RetailMost Common Sprinkler SystemEasiest to Maintain and OperateRequires the Least Amount of Testing

Page 58: Acceptance Testing of Fire Protection Systems 101

Wet System

Page 59: Acceptance Testing of Fire Protection Systems 101

Wet System Tests and Requirements

• Hydrostatic and Cover• Walkthrough and Final

– Operational (Alarms, Tamper, Main Drain Test)

– Confirm Code compliance– Ensure correct number of spare heads

are left on site per NFPA 13-2007 Section 6.2.9- Dry heads not required. Sprinkler Wrench is.

Page 60: Acceptance Testing of Fire Protection Systems 101

• New systems to have White Tag and Blue ITM Tag

• All additions over 20 heads are to have a new white tag added

• Hydraulic Placard and General Information Sign

• PRV test tags on each PRV• Backflow certification and Inspection

by Plumbing Dept

Wet System Riser Reqt’s

Page 61: Acceptance Testing of Fire Protection Systems 101

Dry Pipe System

For Non-Heated Buildings Commercial Industrial Parking Garages Building Exteriors

Page 62: Acceptance Testing of Fire Protection Systems 101

Dry Pipe System

Page 63: Acceptance Testing of Fire Protection Systems 101

Dry System Tests and Requirements -24.2.2

• Hydrostatic and Cover• Walkthrough and Final

– Operational (Alarms, Tamper, Main Drain Test)

– Confirm Code compliance– Ensure correct number of spare heads

are left on site per NFPA 13-2007 Section 6.2.9- Dry heads not required. Sprinkler Wrench is.

Page 64: Acceptance Testing of Fire Protection Systems 101

• In addition to 200 psi hydrostatic test- an air leakage test is required

• 40 psi of air for 24 hours- any leakage in excess of 1-1/2 psi shall be corrected

Dry Systems Also Require

Page 65: Acceptance Testing of Fire Protection Systems 101

• 24.2.3.2 covers operational test • Trip test of valve and any quick

opening devices- time how long it takes for water to be discharged from the inspector’s test connection.

• Verify it is per 7.2.3.6 and record it on the Contractor’s Material and Test Certificate

System Operational Test

Page 66: Acceptance Testing of Fire Protection Systems 101

Water Delivery per NFPA 13- 2007

Table 7.2.3.6.1 Dry System Water Delivery

Hazard Number of Most Remote Sprinklers

Initially Open

Maximum Time of Water Delivery

Residential 1 15 seconds Light 1 60 seconds Ordinary I 2 50 seconds Ordinary II 2 50 seconds Extra I 4 45 seconds Extra II 4 45 seconds High piled 4 40 seconds

Page 67: Acceptance Testing of Fire Protection Systems 101

• 7.2.6.2.2- The air supply shall have a capacity capable of restoring normal air pressure in the system within 30 minutes

• A.7.2.6.2.20- When a single compressor serves multiple systems, the 30 minute fill time is based in the largest system

Air Compressor Testing

Page 68: Acceptance Testing of Fire Protection Systems 101

• New systems to have White Tag and Blue ITM Tag

• All additions over 20 heads are to have a new white tag added

• Hydraulic Placard and General Information Sign

• PRV test tags on each PRV• Backflow certification and Inspection

by Plumbing Dept

Dry System Riser Reqt’s

Page 69: Acceptance Testing of Fire Protection Systems 101

Pre Action System

For Environmentally Sensitive Areas Computer Rooms Surgical Suites Tele-Data Switch Rooms Fine Art Storage Rooms

Page 70: Acceptance Testing of Fire Protection Systems 101

Pre Action System

Page 71: Acceptance Testing of Fire Protection Systems 101

Preaction Requirements -24.2.3.3

• Hydrostatic and Cover• Walkthrough and Final

– Operational (Alarms, Tamper, Main Drain Test)

– Confirm Code compliance– Ensure correct number of spare heads

are left on site per NFPA 13-2007 Section 6.2.9- Dry heads not required. Sprinkler Wrench is.

Page 72: Acceptance Testing of Fire Protection Systems 101

• Test the preaction valve operation in accordance with the manufacturer’s instructions- ask for literature if there is any questions on operation

• Test manual and remote control activation- this can be electric, pneumatic or a combination

Preaction Systems Also Require

Page 73: Acceptance Testing of Fire Protection Systems 101

• Is the piping supervised? Sec. 7.3.2.4 requires supervision to ensure system integrity.

• If supervisory air or nitrogen is used- it needs to conform to 7.2.6 for dry systems…– 30 minute refill requirement.

• Also needs to maintain a minimum supervisory pressure of 7 psi.

Page 74: Acceptance Testing of Fire Protection Systems 101

• New systems to have White Tag and Blue ITM Tag

• All additions over 20 heads are to have a new white tag added

• Hydraulic Placard and General Information Sign

• PRV test tags on each PRV• Backflow certification and Inspection

by Plumbing Dept

Preaction Riser Reqt’s

Page 75: Acceptance Testing of Fire Protection Systems 101

Deluge System

For Highly Flammable Areas Aircraft Hangers Solvent Processing Dynamite Plants

Page 76: Acceptance Testing of Fire Protection Systems 101

Deluge System

Page 77: Acceptance Testing of Fire Protection Systems 101

Deluge System Requirements -24.2.3.3

• Hydrostatic and Cover• Walkthrough and Final

– Operational (Alarms, Tamper, Main Drain Test)

– Confirm Code compliance– Ensure correct number of spare heads

are left on site per NFPA 13-2007 Section 6.2.9- Dry heads not required. Sprinkler Wrench is.

Page 78: Acceptance Testing of Fire Protection Systems 101

• Test the deluge valve operation in accordance with the manufacturer’s instructions- ask for literature if there is any questions on operation

• Test manual and remote control activation- this can be electric, pneumatic or hydraulic

Deluge Systems Also Require

Page 79: Acceptance Testing of Fire Protection Systems 101

• Flow Testing of the system to ensure hydraulic performance. Calibrated gauges are to be used at different points on the system

• These gauge readings are to be compared to the hydraulic calculations

• Detection devices are to be automatically supervised

Page 80: Acceptance Testing of Fire Protection Systems 101

• New systems to have White Tag and Blue ITM Tag

• All additions over 20 heads are to have a new white tag added

• Hydraulic Placard and General Information Sign

• PRV test tags on each prv• Backflow certification and Inspection

by Plumbing Dept

Deluge Riser Reqt’s

Page 81: Acceptance Testing of Fire Protection Systems 101

Standpipe System

For Multi-levelBuildings Per AHJ

Page 82: Acceptance Testing of Fire Protection Systems 101

Stand Pipe System

Page 83: Acceptance Testing of Fire Protection Systems 101

Standpipe System Tests and Requirements

• Hydrostatic and Cover• Walkthrough and Final

– Operational (Alarms, Tamper, Main Drain Test)

– Confirm Code compliance and hose thread compatibility

– Flow test through roof manifold testing approved water source- fire pump, FD pumper truck, etc.

Page 84: Acceptance Testing of Fire Protection Systems 101

• PRV tests. Ask for test log• Main Drain flow tests- record on

material test certificate• Dry and semi automatic shall be

trip tested to deliver 250 GPM at the hydraulically most remote hose connection within 3 minutes

• Air testing applies per dry systems in NFPA 13

Page 85: Acceptance Testing of Fire Protection Systems 101

• Open and close each valve manually- make sure hose caps are on prior to testing

• Check for proper signage

Page 86: Acceptance Testing of Fire Protection Systems 101

Fire Pump

Page 87: Acceptance Testing of Fire Protection Systems 101
Page 88: Acceptance Testing of Fire Protection Systems 101

Fire Pump Tests and Requirements

• Per NFPA 20- 2007 Edition Chapter 14

• Piping to be hydrostatically tested per NFPA 13 req’s

• All piping sizes to be verified per table 5.25 (a) by rated pump flow

Page 89: Acceptance Testing of Fire Protection Systems 101
Page 90: Acceptance Testing of Fire Protection Systems 101

• All factory supplier representatives are to be in attendance during field acceptance tests- AHJ should be notified

• As a minimum, proof of the initial startup and field acceptance test report should be provided at Fire Marshal final

Page 91: Acceptance Testing of Fire Protection Systems 101

• A copy of the certified pump test characteristic curve shall be available for comparison of the field acceptance test.

• Compare the curves to ensure the pump meets it’s factory specs.

Page 92: Acceptance Testing of Fire Protection Systems 101

• Pump shall be run at minimum, rated and peak loads

• How is this determined??• Minimum is 0 GPM or churn• Rated is the rating of the pump

– i.e.. 1000 GPM pump needs to be tested at 1000 GPM

• Maximum is 150 % of pump rating- a 1000 GPM rated pump is capable of 1500 GPM flow

Page 93: Acceptance Testing of Fire Protection Systems 101

• Per NFPA 14- 2007, Section 6.2.1- Pumps shall furnish not less than 150 percent of rated capacity at not less than 65 percent of total rated head.

• 6.2.2- The shutoff head shall not exceed 140 percent of rated head for any type of pump.

Page 94: Acceptance Testing of Fire Protection Systems 101

Example 1- Pump is rated for 750 GPM @ 100 psi

150 percent of load-1.5 X 750 =1125

65 percent of total rated head-.65 X 100= 65 psi

Pump should provide 65 psi MINIMUM at 1125 GPM

Page 95: Acceptance Testing of Fire Protection Systems 101

Example 2- Maximum Shutoff100 psi Fire pump

Maximum Shutoff Head-1.4 X 100 psi= 140 psi

Pump shutoff pressure should not be over 140 psi.

Page 96: Acceptance Testing of Fire Protection Systems 101

Keep in mind that is the Fire Pump shutoff pressure- the jockey of maintenance pump will add 10 more psi to the working pressure

of the system

Page 97: Acceptance Testing of Fire Protection Systems 101
Page 98: Acceptance Testing of Fire Protection Systems 101
Page 99: Acceptance Testing of Fire Protection Systems 101
Page 100: Acceptance Testing of Fire Protection Systems 101
Page 101: Acceptance Testing of Fire Protection Systems 101

• Test fire alarm signals in Fire Pump control panel– Pump Run– A/C Power Fail– Phase Reversal

– Normal power and alternate power

Page 102: Acceptance Testing of Fire Protection Systems 101

State Requirements

• What does 28 TAC §§ 34.700 – The Fire Sprinkler Rules require for new systems and system modifications?

Page 103: Acceptance Testing of Fire Protection Systems 101

• White Original Installation Tag

Page 104: Acceptance Testing of Fire Protection Systems 101

• To be affixed to riser after new install or scheduled testing and maintenance.

• To remain on riser for the life of the system- provides baseline water flow information for subsequent inspections.

• Work for this tag to be filled out by licensed RME-G or RME-I.

Page 105: Acceptance Testing of Fire Protection Systems 101

• Blue Inspection Testing and Maintenance Tag

Page 106: Acceptance Testing of Fire Protection Systems 101

• To be affixed to riser after new install or scheduled testing and maintenance.

• To remain on riser for minimum of five years- only to be removed by employee of authorized firm

• Work for this tag to be filled out by licensed RME-G or RME-I.

Page 107: Acceptance Testing of Fire Protection Systems 101

• Blue Service Tag

Page 108: Acceptance Testing of Fire Protection Systems 101

• To be affixed to riser after every service performed

• To remain on riser for minimum of five years- only to be removed by employee of authorized firm

• Work for this tag to be filled out by Installer- license not needed

• If anything is found to be impaired, a yellow or red tag need to be affixed as well.

Page 109: Acceptance Testing of Fire Protection Systems 101

Contractor’s Material and Test Certificates

• Ensure these are filled out in their entirety and affixed to the riser in a protective sheath. The owner will want these at a later date.

Page 110: Acceptance Testing of Fire Protection Systems 101
Page 111: Acceptance Testing of Fire Protection Systems 101
Page 112: Acceptance Testing of Fire Protection Systems 101
Page 113: Acceptance Testing of Fire Protection Systems 101
Page 114: Acceptance Testing of Fire Protection Systems 101

Hydraulic Placard

• Used in future work on system• Often lost over the years• Should be metal and permanently

marked per NFPA 13- 07

Page 115: Acceptance Testing of Fire Protection Systems 101
Page 116: Acceptance Testing of Fire Protection Systems 101

Design Criteria

• NFPA Codes: 13, 13R, 13D, 14, 20, 22, 24, 25 & 101 • UBC • IBC • IFC• Local AHJ’s• Other Jurisdictions – Architect, Engineer & Owner• Insurance Underwriter

Page 117: Acceptance Testing of Fire Protection Systems 101

Post Construction Inspections and Maintenance

• Required per NFPA 25 and all Local Jurisdictions• Texas requires Licensed Inspectors • Identify changes in

• Occupancy and use• Ceiling and finishes (i.e.. Painted and loaded heads)• Added building features(Decks, Canopies, Clouds)

• Ensure system operation • Find system deficiencies and repair them in a timely manner