The Powerful Difference Accessories Fuse Blocks MODEL NUMBERS ME-125F ME-200F ME-300F ME-400F WORKS WITH ME-125F and ME-200 only MM Series MM-AE Series MMS Series MM-E Series ME-300F and ME-400F only ME Series MS Series MS-AE Series RD Series RD-E Series DC Load Disconnect MODEL NUMBERS ME-DCLD The DC Load Disconnect is a pigtail adapter designed to automatically turn off the inverter via a 12 volt DC disconnect switch. Fuse Selection Conductor Gauge Current Capacity Recommended Fuse Rating 4 AWG 125 125 1/0 AWG 200 200 2/0 AWG 290 300 3/0 AWG 310 300 4/0 AWG 360 400 WORKS WITH ME Series MS Series MS-AE Series RD Series RD-E Series Conduit Box MODEL NUMBERS ME-CB WORKS WITH ME Series MS Series MS-AE Series RD Series RD-E Series The ME-CB conduit box is designed to work with Magnum ME, MS, and RD Series Inverter/Chargers. It provides an enclosure for AC and/or DC wiring and has knockouts for ½”, ¾”, 1”, and 2” trade-size conduit. The ME- CB adds just over 5” (13 cm) to the length of the inverter. Protection against costly damage: The ME-125F, ME- 200F, ME-300F, and ME-400F protect the battery bank, inverter, and cables from damage caused by short circuits and overloads. Complete kit in one package: Magnum Energy fuses include a Slow-Blow high current fuse, a mounting block, and protective cover.

Upload: hoangtuyen

Post on 15-Mar-2018

217 views

Category:

Documents


1 download

TRANSCRIPT

The Powerful Difference

Accessories

Fuse BlocksMODEL NUMBERS

ME-125FME-200FME-300FME-400F

WORKS WITH

ME-125F and ME-200 onlyMM SeriesMM-AE SeriesMMS SeriesMM-E Series

ME-300F and ME-400F onlyME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series

DC Load DisconnectMODEL NUMBERS

ME-DCLD

The DC Load Disconnect is a pigtail adapter designed to automatically turn off the inverter via a 12 volt DC disconnect switch.

Fuse Selection

Conductor Gauge Current Capacity Recommended Fuse Rating4 AWG 125 125

1/0 AWG 200 2002/0 AWG 290 3003/0 AWG 310 3004/0 AWG 360 400

WORKS WITH

ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series

Conduit BoxMODEL NUMBERS

ME-CB

WORKS WITH

ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series

The ME-CB conduit box is designed to work with Magnum ME, MS, and RD Series Inverter/Chargers. It provides an enclosure for AC and/or DC wiring and has knockouts for ½”, ¾”, 1”, and 2” trade-size conduit. The ME-CB adds just over 5” (13 cm) to the length of the inverter.

Protection against costly damage: The ME-125F, ME-200F, ME-300F, and ME-400F protect the battery bank, inverter, and cables from damage caused by short circuits and overloads.

Complete kit in one package: Magnum Energy fuses include a Slow-Blow high current fuse, a mounting block, and protective cover.

The Powerful Difference

Authorized Magnum Dealer

Magnum Energy, Inc.1111 80th Street SW, Suite 250Everett, Washington 98203 USA

Phone: 425-353-8833Fax: 425-353-8390Web: www.magnumenergy.comTesting for specifications at 25° CSpecifications subject to change without notice.

June 2008, Rev D Part #64-0011

STACKING CABLE

240 VOLTS

INVE

RTE

R 1

INVE

RTE

R 2

L1 / 120 VOLTS L2 / 120 VOLTS

The Series Stacking Cable Kit allows two inverters to be stacked together to achieve 120/240 VAC output. Series stacking is commonly used for well pumps, tools, motors, and other 240 VAC appliances. The kit includes communication cable, two 2/0 battery cables, and battery lug covers.

Series Stacking Cable KitMODEL NUMBERS

ME-SSI

WORKS WITH

MS4024

Remote Switch Adapter

MODEL NUMBERS

ME-RSA (use SPST switch)

ME-RSA-M (use momentary switch)

The Remote Switch Adapter is a pigtail adapter designed to provide a simple on/off remote switch.

Accessories

WORKS WITH

ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series

Ignition Switch LockoutMODEL NUMBERS

ME-ISW

The Ignition Switch Lockout is a pigtail adapter designed to automatically turn off the inverter via a vehicle ignition switch.

WORKS WITH

ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series

Carling Tech: Magnetic Circuit Breaker

Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers

Back to Hydraulic/Magnetic Circuit Breakers

Hydraulic/Magnetic Circuit Breaker

F-Series

F-Series PDF eLibrary

The F-Series hydraulic/magnetic high amperage circuit breakers are designed to handle high current applications in extremely hot and/or cold locations. Due to its time-proven hydraulic/magnetic design, the F-Series load sensing mechanism is insensitive to changes in ambient or enclosure temperature, providing a consistent trip point over temperatures ranging from -40°C to +85°C.In addition, the F-Series

circuit breakers come with a choice of overload time delays, making them ideal for critical applications having inductive loads.

Series PDF eLibrary F-Series Cir. Breaker PDF (1.2 MB) Cir. Breaker Time Delays for F-

Series PDF (2.3 MB) Cir. Breaker Accessories PDF (49.5

KB)

Certifications UL489 Listed, CUL Certified, UL489A Listed (Telecom), TUV

Number of Poles 1-3 polesAvailable Delays Short, Medium, Long DCMaximum Current and Voltage Ratings

100 - 700 amps @ 125VDC

Maximum Interrupting Capacity

50,000 amps @ 125VDC

Auxiliary Switch Ratings 10.1A @ 250VAC 0.1A @ 125VAC (gold contacts) 5A @ 30VDC 1.0A @ 65VDC 0.5A @ 80VDC

Available Circuits Series, Series with Parallel Pole, Series with Auxiliary/Alarm Switch

Actuator Style Handle (1 per pole)Terminal Options Back Connected Style:

3/8 - 16 Stud 3/8 - 16 Screw Line & Load 3/8 - 16 Short Stud Front Connected Style: Box Wire Connector w/pressure plate 3/8 - 16 Screw Line & Load

Mounting Method Rear Mounted or Front Panel Mounted

English •• Chinese

Circuit Protection

Hydraulic/Magnetic Circuit Breakers

Thermal Circuit Breakers

Equipment Leakage Circuit Breakers

All Circuit Breakers

View All Products

Easily and automatically configure catalog numbers

Guides you to the appropriate switch or circuit breaker product series.

Search by:Part Number

Distributor Stock

List Price

Quick and easy product PDF's resourcing in the eLibrary.

Learn More

News

FAQs

Glossary

Home Site Map

©2009 Carling Technologies

Created by PixelMEDIA, Inc.

http://magnetic-circuit-breakers.carlingtech.com/magnetic-circuit-breaker__80.asp (1 of 2) [10/22/2009 9:45:30 AM]

Carling Tech: Magnetic Circuit Breaker

Value Added Custom actuator colors Non-standard current ratings Metering Shunt and more

http://magnetic-circuit-breakers.carlingtech.com/magnetic-circuit-breaker__80.asp (2 of 2) [10/22/2009 9:45:30 AM]

Littelfuse.com © 2013 Littelfuse POWR-GARD® Products

POWR-GARD® Fuse Datasheet

Rev:4-D-0524131 of 4

.06 (1.52) .14 (3.56)

.04 (1.02)

.02 (.51)

1.53 (38.86)

.50 (12.7).12 (3.05)

MOUNTING HOLE

DETAIL

.406 (10.31).12 (3.05) .28

(7.11)

1.5 (38.1)

.406 (10.31)

SPF SerieS Solar FUSeS1000 VDC • 1-30 A

SpecificationsVoltage Rating 1000 VDCAmperage Rating 1, 2, 3, 3.5, 4, 5, 6, 8, 10, 12, 15, 20, 25, 30Max. Interrupting Rating 20 kATime Constant ≤ 2msMaterial Body: Melamine Caps: Copper AlloyApprovals UL 2579 Listed (File: E339112) IEC 60269-6 (1-25 A) VDE Certified (No. 40033098)* see specifications on pg. 2 CSA Certified (File: 029862_0_000)Environmental RoHS CompliantCountry of Origin Mexico

DescriptionThe SPF Solar Protection Fuse series has been specifically designed for the protection of photovoltaic (PV) systems. This family of Midget style fuses (10 x 38 mm) can safely protect PV modules and conductors from reverse- overcurrent conditions.

As PV systems have grown in size, so have the corresponding voltage requirements. This increase in system voltage has typically been intended to minimize power loss associated with long conductor runs. Standard circuit protection devices are not designed to completely protect photovoltaic panels. However, the SPF series is UL Listed to safely interrupt faulted circuits up to this demanding voltage level.

Littelfuse offers 14 ampere ratings to match specific requirements in a variety of applications.

Features/Benefits• MeetsUL,IECandVDEphotovoltaicstandards• UL2579Listed1000VDCmaximum• 1-30Aratingsavailable• 20,000AInterruptingRating• BothPCBmountanddead-frontholderoptionsavailable

Applications• Inverters• Combiner boxes• Battery charge controllers

Recommended Fuse HoldersLPHV 1000 VDC POWR-Safe Series

Web ResourcesDownloadable CAD drawings and other technical information: Littelfuse.com/spf

Dimensions Inches (mm)

SerieS amP Package QUantity

moUnting method

catalog nUmber

ordering nUmber

SPF 2 10 FeRRuLe SPF002 0SPF002.TSPF 3.5 10 FeRRuLe SPF03.5 0SPF03.5TSPF 30 100 PCB TABS SPF030R 0SPF030.HXR

Ferrule Version PCB Version

look for this logo to indicate products that are used in solar applications. Visit our website Littelfuse.com/solar for the latest updates on approvals, certifications, and new products.

Part Numbering System0SPF xxxx H XR

Package Quantity

Series Mounting Options

Amp Code

T=10H=100

Blank=FerruleXR=PCB

RefertoAmpCodeColumninElectricalSpecificationsTable

Littelfuse.com © 2013 Littelfuse POWR-GARD® Products

POWR-GARD® Fuse Datasheet

Rev:4-D-0524132 of 4

SPF SerieS Solar FUSeS

Electrical Specifications Ferrule Version

Electrical Specifications PCB Version

amPe

rage

amP code

ordering nUmber UPc

Voltage interrUPting rating nom cold

reSiStance (ohm)

WattS loSS at 100% rated cUrrent (W)

WattS loSS at 80% rated cUrrent (W)

total clearing i2t (a2 s) 10 ka

total clearing i2t (a2 s) 20 ka

agency aPProValS

dc ac dc Ul Vde cSa

1 001. 0SPF001.T 07945816907 1000 – 20 kA 0.394 0.602 0.410 0.554 0.554 • •

2 002. 0SPF002.T 07945816910 1000 – 20 kA 0.237 1.586 0.851 1.175 4.755 • • •

3 003. 0SPF003.T 07945816913 1000 – 20 kA 0.11 1.504 0.824 5.007 7.882 • • •

3.5 03.5 0SPF03.5T 07945880087 1000 – 20 kA 0.07787 1.365 0.778 11.297 11.297 • •

4 004. 0SPF004.T 07945816916 1000 – 20 kA 0.06127 1.491 0.839 23.031 23.031 • • •

5 005. 0SPF005.T 07945816919 1000 – 20 kA 0.04086 1.465 0.859 42.600 42.600 • • •

6 006. 0SPF006.T 07945816922 1000 – 20 kA 0.0281 1.348 0.769 76.270 80.254 • • •

8 008. 0SPF008.T 07945816925 1000 – 20 kA 0.0178 1.610 0.914 193.323 198.960 • • •

10 010. 0SPF010.T 07945816928 1000 – 20 kA 0.0125 1.760 1.000 395.556 401.208 • • •

12 012. 0SPF012.T 07945816931 1000 – 20 kA 0.00993 1.965 1.109 599.198 641.940 • • •

15 015. 0SPF015.T 07945816934 1000 – 20 kA 0.00799 2.282 1.382 457.740 504.770 • • •

20 020. 0SPF020.T 07945816937 1000 – 20 kA 0.0045 2.810 1.574 1173.990 1312.850 • • •

25 025. 0SPF025.T 07945817595 1000 – 20 kA 0.00353 2.981 1.745 1937.430 2371.140 • • •

30 030. 0SPF030.T 07945817598 1000 – 20 kA 0.00284 3.923 2.125 2209.480 2678.750 • •

amPe

rage

amP code

ordering nUmber UPc

Voltage interrUPting rating nom cold

reSiStance (ohm)

WattS loSS at 100% rated cUrrent (W)

WattS loSS at 80% rated cUrrent (W)

total clearing i2t (a2 s) 10 ka

total clearing i2t (a2 s) 20 ka

agency aPProValS

dc ac dc Ul cSa

1 001. 0SPF001.HXR 07945816909 1000 – 20 kA 0.394 0.602 0.410 0.554 0.554 • •

2 002. 0SPF002.HXR 07945816912 1000 – 20 kA 0.237 1.586 0.851 1.175 4.755 • •

3 003. 0SPF003.HXR 07945816915 1000 – 20 kA 0.11 1.504 0.824 5.007 7.882 • •

3.5 03.5 0SPF03.5HXR 07945880089 1000 – 20kA 0.07787 1.365 0.778 11.297 11.297 • •

4 004. 0SPF004.HXR 07945816918 1000 – 20 kA 0.06127 1.491 0.839 23.031 23.031 • •

5 005. 0SPF005.HXR 07945816921 1000 – 20 kA 0.04086 1.465 0.859 42.600 42.600 • •

6 006. 0SPF006.HXR 07945816924 1000 – 20 kA 0.0281 1.348 0.769 76.270 80.254 • •

8 008. 0SPF008.HXR 07945816927 1000 – 20 kA 0.0178 1.610 0.914 193.323 198.960 • •

10 010. 0SPF010.HXR 07945816930 1000 – 20 kA 0.0125 1.760 1.000 395.556 401.208 • •

12 012. 0SPF012.HXR 07945816933 1000 – 20 kA 0.00993 1.965 1.109 599.198 641.940 • •

15 015. 0SPF015.HXR 07945816936 1000 – 20 kA 0.00799 2.282 1.382 457.740 504.770 • •

20 020. 0SPF020.HXR 07945817594 1000 – 20 kA 0.0045 2.810 1.574 1173.990 1312.850 • •

25 025. 0SPF025.HXR 07945817597 1000 – 20 kA 0.00353 2.981 1.745 1937.430 2371.140 • •

30 030. 0SPF030.HXR 07945817600 1000 – 20 kA 0.00284 3.923 2.125 2209.480 2678.750 • •

Littelfuse.com © 2013 Littelfuse POWR-GARD® Products

POWR-GARD® Fuse Datasheet

Rev:4-D-0524133 of 4

SPF SerieS Solar FUSeS

amPerage rating

oPening time (minUteS)

100% of amp rating per Ul

113% of amp rating per iec

135% of amp rating per Ul

145% of amp rating per iec

200% of amp rating per Ul

1-30TemperatureStabilization

60 Min 60 Max 60 Max 4 Max

WaVe Parameter lead Free recommendation

PReHeAT: (Typical Industry Recommendation)

TeMPeRATuRe MInIMuM: 130˚ C

TeMPeRATuRe MAXIMuM: —

PRe-HeAT TIMe 75 Seconds Maximum

SOLDeR POT TeMPeRATuRe 280˚ C Maximum

SOLDeR DWeLL TIMe 270˚ C for 8 Seconds Maximum

COMPLeTe CYCLe TIMe 250 Seconds Maximum

Recommended Process Parameters Soldering Parameters

-60°C -40°C -20°C 0°C 20°C 40°C 60°C 80°C 100°C 120°C 140°C-76°F -40°F -4°F 32°F 68°F 104°F 140°F 176°F 212°F 248°F 284°F

AMBIENT TEMPERATURE

60

40

20

0

PERC

ENT

OF

UPR

ATIN

G

0

20

40

60

PERCENT O

F DO

WN

RATING

Temperature Derating Curve (Temperature of Air Immediately Surrounding Fuse)

Electrical Specification – Agency Requirements

Littelfuse.com © 2013 Littelfuse POWR-GARD® Products

POWR-GARD® Fuse Datasheet

Rev:4-D-0524134 of 4

- THIS DATA GENERATED IN EXCEL -

1000900800700600500

400

300

200

1009080706050

40

30

20

1098765

4

3

2

10.90.80.70.60.5

0.4

0.3

0.2

0.10.090.080.070.060.05

0.04

0.03

0.02

0.01

1000900800700600500

400

300

200

1009080706050

40

30

20

1098765

4

3

2

10.90.80.70.60.5

0.4

0.3

0.2

0.10.090.080.070.060.05

0.04

0.03

0.02

0.01

1000900800700600500

400

300

200

1009080706050403020109876543210.90.80.70.60.5

0.4

0.3

0.2

0.1

1000900800700600500

400

300

200

1009080706050403020109876543210.90.80.70.60.5

0.4

0.3

0.2

0.1

CURRENT IN AMPERES

TIM

E IN

SEC

ON

DS

- 1A

- 2A

- 3A

- 6A

- 8A

- 10A

- 12A

- 4A

- 5A

- 3.5A

BASIS FOR DATA:

TEST VOLTAGE: 1000V TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER:

DRAWN BY:DATE:REVISION:DRAWING NO.: SHEET TIME CURRENT CHARACTERISTIC CURVES

LITTELFUSE, INC. CHICAGO, IL. USA

LLL

3/15/10

D2 OF 3

FCC01-SPF

SPF 1A - 30A

SPF SerieS Solar FUSeS

- THIS DATA GENERATED IN EXCEL -

1000 900 800 700 600 500 400

300

200

100 90 80 70 60 50 40

30

20

10 9 8 7 6 5 4

3

2

1 0.9 0.8 0.7 0.6 0.5 0.4

0.3

0.2

0.1 0.09 0.08 0.07 0.06 0.05 0.04

0.03

0.02

0.01

1000 900 800 700 600 500 400

300

200

100 90 80 70 60 50 40

30

20

10 9 8 7 6 5 4

3

2

1 0.9 0.8 0.7 0.6 0.5 0.4

0.3

0.2

0.1 0.09 0.08 0.07 0.06 0.05 0.04

0.03

0.02

0.01

1000 900 800 700 600 500 400

300

200

100 90 80 70 60 50 40

30

20

10 9 8 7 6 5 4 3 2 1 0.9 0.8 0.7 0.6 0.5 0.4

0.3

0.2

0.1

1000 900 800 700 600 500 400

300

200

100 90 80 70 60 50 40

30

20

10 9 8 7 6 5 4 3 2 1 0.9 0.8 0.7 0.6 0.5 0.4

0.3

0.2

0.1

CURRENT IN AMPERES

TIM

E IN

SEC

ON

DS

- 15A

- 20A

- 25A

- 30A

BASIS FOR DATA:

TEST VOLTAGE: 1000V TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER:

DRAWN BY:DATE:REVISION:DRAWING NO.: SHEET TIME CURRENT CHARACTERISTIC CURVES

LITTELFUSE, INC. CHICAGO, IL. USA

LLL

3/15/10

D3 OF 3

FCC01-SPF

SPF 1A - 30A

Time Current Curve (1-12 A)

Time Current Curve (15-30 A)

ME-125F and ME-200F Instruction Sheet

PN: 64-0053 Rev A

Magnum Energy, Inc.2211 West Casino Rd.

Everett, WA USA 98204www.magnumenergy.com

IntroductionThe Magnum Energy ANL Fuse/Fuse Block is designed to provide code com-pliant overcurrent protection for DC systems up to 32-volts. It protects the battery bank, inverter, and cables from damage caused by short circuits and overloads. The ANL fuse cartridge delivers instantaneous protection in the event of a short circuit, as well as a time delay to allow the momentary current surges that are common in inverter applications. Magnum small fuse blocks are available in 125 and 200 amp models. Our ANL fuse holder is molded from glass-fi lled nylon, has an insulating cover, and includes two black rub-ber terminal insulators to protect conductive areas from accidental shorts.The ANL fuses are rated for 32-volt DC systems (48-volts maximum) and are an economical alternative to the Class-T fuses. These fuses have a clear window that provides open-fuse indication; and, have a durable Polyethersul-fone body and riveted construction to offer superior service life in heavy-duty applications.Fuse selection is based upon the size of the conductor between the battery and the load. Keep in mind that the conductor’s current carrying capability is affected by: the length of the cable between the battery and the load, and the conductor’s wire type and temperature rating. Refer to the Table 1 for assistance in selecting a fuse.

InstallationThe battery, fuse block, and inverter should be located as close together as possible – without being in the same enclosure. Batteries can produce explosive gasses that may be ignited by the fuse. For code compliance, locate the fuse within 18” (45 cm) of the battery, and with at least 6” (15 cm) clearance from other equipment on each end. When changing the fuse, it may be energized by the battery; allow additional clearance if grounded metal surfaces (such as the inverter’s chassis) are nearby.Attach the fuse block base to a secure surface using the appropriate hardware (refer to Figure 1). Make the connections to the fuse block fi rst (see Figure 2 for proper hardware stacking), then to the battery, and fi nally to the inverter. Place the rubber terminal insulators on the battery cables before securing the cable lugs to the fuse posts.NOTE: The fuse should not be installed in the grounded conductor.Torque the Hex nuts to ~150 inch-pounds (16.9 N-m). The lock washers provided must be installed to ensure a quality and long lasting connection.Check the cables for correct polarity with a voltmeter before making the fi nal connections to the inverter.

WARNING: Failure to comply with torque specifi cations may result in damage and premature failure of the product. Failures caused by not adhering to the proper torque specifi cations are not covered by warranty.

WARNING: Before replacing a fuse, ensure all AC/DC power sources are de-energized (i.e., breakers opened, fuses removed) to prevent accidental shock.

ME-125F and ME-200F Instruction Sheet

© 2011 Magnum Energy, Inc.

Conductor Gauge Current Capacity* Recommended Fuse

#1 AWG/42.39 mm² 190 200**

#4 AWG/21.14 mm² 125 125

* - Current capacity based on 75° C cable rating in free air @ 30° C (86° F).** - The next larger standard size overcurrent device may be used if the de-rated cable ampacity falls between the standard overcurrent devices found in the NEC.

~5.00" (12.7 cm)~4.50" (11.43 cm)

1.25" (3.17 cm)

.75" (1.9 cm)

5/16 – 18 bolt w/ Hex nut (x2)Requires 9/16" wrench

Figure 1, Small Fuse Block Dimensions

WARNING: During installation, incorrect stacking of the fuse block hardware can create a highly resistive connection that generates heat. DO NOT place anything (i.e., washers) between the fuse and either battery cable lug as this can cause the fuse to overheat and blow open, resulting in a partial melting of the fuse holder and cover. Before stacking, refer to Figure 2.

Figure 2, Small Fuse Block Hardware Stacking

Fuse

Battery Cable Lugs

Flat Washers

Lock WashersHex Nuts

Table 1, Fuse Selection

low voltage

QY-SERIES-DATAPR 2015

Data SheetPage 1 of 8

• DC Circuit Breaker• Hydraulic-Magnetic technology• 100% rating capability, independent of ambient temperature • VDE and CCC approved, CE certified• UL listed (UL 489 A)• Ratings 0.1 to 63 A (1 & 2 pole), 3 pole parallel

(150 A maximum), 4 pole parallel (200 A maximum)• Optional Auxiliary Switch / Trip Alarm - factory fitted

(6.5 mm wide)• Optional Shunt Trip (no approvals)• Wide range of time delays and operating currents• Precision tripping characteristics• Ultra compact – 13 mm wide module• Trip indication with mid-trip handle • Reset immediately after overload• DIN mount product in grey shells• Dual mount product in black shells• 80 V DC devices are reverse feedable• 125 / 250 / 600 V DC devices are polarity sensitive• Suitable to use for electrical isolation

QY - Series Miniature Circuit Breakers

DIN mount(grey body)

Features Applications• DC branch circuit protection (UL 489A, IEC / EN 60947-2)• Telecom / datacom equipment• UPS equipment• Alternative energy equipment• Battery protection & switching• Telecommunication DC power distribution• Railway signalling equipment

• Auxiliary Switch (DIN and Dual Mount)• Auxiliary Switch + Trip Alarm (Dual Mount only)• Trip Alarm (Dual Mount only)• Handle lock• Surface mounting clips• Busbar• 57 mm Escutcheon blank (Dual Mount only)• 57 mm Safety blank (Dual Mount only)

Optional Accessories Auxiliary Switch, Trip Alarm & Combo:Features• AC and DC voltages• UL 489 listed (Auxiliary Switch: 6 A 250 V AC,

0.5 A 80 V DC)• IEC 60947-5-1 approved (Auxiliary Switch: 6 A 240 V AC,

0.5 A 110 V DC; Trip Alarm: 6 A 240 V AC, 0.5 A 110 V DC)• Factory fitted• Attached to right hand side of Circuit Breaker• Compact 6.5 mm width

Dual mount(black body)

Dual mount + Auxiliary(black body)

Dual mountparallel

(black body)

Dual mountseries

(black body)

QY-SERIES-DATAPR 2015

Data SheetPage 2 of 8

low voltage

QY - Series Miniature Circuit Breakers

Breaker QY Wire Size mm² (IEC) Wire Gauge (UL) Torque (IEC) Torque (UL) Comments

1 Pole & 2 Pole 0.75 - 35 mm² 18 – 2 – AWG 2.5 Nm 20 in-lb Pozidriv #2Combi head

2 Pole Parallel 50 mm² 14 – 1/0 – AWG 3.2 Nm 28 in-lb Bridge Terminal3 Pole Parallel 95 mm² 14 – 5/0 – AWG 5.6 Nm 50 in-lb Bridge Terminal

4 Pole Parallel 95 mm² 14 – 5/0 – AWG 5.6 Nm 50 in-lb Bridge Terminal

Technical Data

Approvals UL 489A

Number of Poles 1 2 2 parallel

2 parallel

3 parallel

4 parallel 2 series 4 series 1 pole

plug-in

Operating Voltages 80 V DC, 125 V DC 80 V DC 125 V DC

80 / 125 V DC 80 V DC 250 V

DC600 V DC 80 V DC

Minimum Current Rating 0.1 A 0.1 A 30 A 20 A 110 A 200 A 0.1 A 0.1 A 0.1 AMaximum Current Rating 63 A 50 A 100 A 100 A 150 A 200 A 50 A 20 A 50 AInterrupting Capacity 10 kAOperating Temperature Range -40oC to +85oC

Mounting Options DIN Rail, Dual mounting (DIN & Mini), surface mounting clip, plug-in terminalTime Delay Curves 1, 9, U2, U3, OP

Approvals CCCNumber of Poles 1 2 2 parallel 3 parallel 4 parallel 1 pole plug-inOperating Voltages 80 V DCMinimum Current Rating 0.1 A 0.1 A 30 A 110 A 200 A 0.1 AMaximum Current Rating 63 A 50 A 100 A 150 A 200 A 50 AInterrupting Capacity 10 kAOperating Temperature Range -40oC to +85oC

Mounting Options DIN Rail, Dual mounting (DIN & Mini), surface mounting clip, plug-in terminalTime Delay Curves 1, 9, U2, U3, OP

Approvals IEC / EN 60947-2, VDE

Number of Poles 1 2 2 parallel 2 parallel 3 parallel 4 parallel 2 series 1 pole plug-in

Operating Voltages 80 V DC, 125 V DC 80 V DC 125 V DC 80 V DC 250 V DC 80 V DCMinimum Current Rating 0.1 A 0.1 A 60 A 30 A 110 A 200 A 0.1 A 0.1 AMaximum Current Rating 63 A 50 A 100 A 100 A 150 A 200 A 50 A 50 AInterrupting Capacity 10 kAOperating Temperature Range -40oC to +85oC

Mounting Options DIN Rail, Dual mounting (DIN & Mini), surface mounting clip, plug-in terminalTime Delay Curves 1, 9, U2, U3, OP

low voltage

QY-SERIES-DATAPR 2015

Data SheetPage 3 of 8

QY - Series Miniature Circuit Breakers

Example Code: QY---A-3(13)-D-U2-150A-B0-----ZGroup 1 2 3 4 5 6 7 8 9 10 11 12

Requirement QYFrame

Switch /Neutral Auxiliary Triple

pole

13 mm module width

DIN RailMedium

delay curve U2

Current Rating150 A

Voltage80 V DC

No Shunt Trip

Future use

Parallel bridged

(by customer)

Long Code QY - A 3 (13) D U2 150A B0 - - Z

Long Code

Group 1: Frame Type

Code Description Comments QY 13 mm wide Miniature Circuit Breaker UL 489A, IEC / EN 60947-2, VDE, CE, CCC

Group 2:Switch/Neutral

Code Description Comments - Not applicable Overload poles do not have any further coding

Group 3:Auxiliary

Code Description Comments- Not applicable Use this code if no Auxiliary used

A Auxiliary Switch (1 x Aux in 1 module) 6.5 mm module fitted on right-hand side (DIN & Dual Mount)

T Trip Alarm (1 x Trip Alarm in 1 module) 6.5 mm module fitted on right-hand side (Dual Mount only)

AT Auxiliary Switch + Trip Alarm combo (combined in 1 module) 6.5 mm module fitted on right-hand side (Dual Mount only)Group 4: No of Poles

Code Description Comments1 Single pole

2 Double pole

3 Triple pole

4 Four poleGroup 5: Module Width

Code Description Comments (13) 13 mm module width 13 mm per pole

Group 6: Mounting

Code Description Comments D DIN rail mount – 45 mm Escutcheon, grey body DIN mount supplied in grey only

DM Dual mount – 57 mm Escutcheon, black body Dual mount supplied in black onlyGroup 7: Time Delays

Code Description Instantaneous Trip Point (x In) Comments1 Long time delay, high instantaneous trip 10 – 20 Orange handle

9 Long time delay 7 – 12 White handle

U2 Medium time delay 5 – 10 White handle

U3 Short time delay 3 – 5 White handle

OP Instantaneous None White handleGroup 8: Current Ratings

Code / Description Comments

0.1, 0.2, 0.3, 0.5, 1, 2, 3, 4, 5, 6, 7, 8 ,9, 10, 12, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63, 70, 80, 90, 100, 120, 125, 150, 200 A

Ratings available vary depending on certification, bridging configuration and voltage. (See comments in Group 9)

* Other ratings are available as special orders. Check availability.Group 9: Voltage

(see diagram on page 7)

Code Voltage Description Comments

B0 80 V DC Not polarity sensitive 0.1 - 63 A 1 pole, 0.1 - 50 A 2 pole, 60 - 100 A 2 pole parallel (80 V DC), 30 - 100 A 2 pole parallel (125 V DC), 110 - 150 A 3 pole parallel, 200 A 4 pole parallel(ratings available vary depending on certification)B1 125 V DC Polarity sensitive. Positive bottom.

B2 250 V DC2 poles in series bridged (2 x 125 V)

Positive = pole 1 bottom0.1 - 50 A 2 pole series bridged at the top (by customer)

pole 1 (-) to pole 2 (+)

B3 250 V DC 2 poles in series bridged (2 x 125 V)Positive = pole 1 bottom

0.1 - 50 A 2 pole series bridged at the top (factory fitted)pole 1 (-) to pole 2 (+)

B4 600 V DC 4 poles in series bridged (4 x 125 V)Positive = pole 1 bottom

0.1 - 20 A 4 pole series bridged (factory fitted)As per wiring diagram printed on unit

T1 125 V DC Polarity sensitive. Positive top.0.1 - 63 A 1 pole, 0.1 - 50 A 2 pole, 30 - 100 A 2 pole parallel,

110 - 150 A 3 pole parallel, 200 A 4 pole parallel

T2 250 V DC 2 poles in series bridged (2 x 125 V)Positive = pole 1 top

0.1 - 50 A 2 pole series bridged at the bottom (by customer)pole 1 (-) to pole 2 (+)

T3 250 V DC2 poles in series bridged (2 x 125 V)

Positive = pole 1 top0.1 - 50 A 2 pole series bridged at the bottom (factory fitted)

pole 1 (-) to pole 2 (+)

T4 600 V DC 4 poles in series bridged (4 x 125 V)Positive = pole 1 top

0.1 - 20 A 4 pole series bridged (factory fitted)As per wiring diagram printed on unit

Continues on page 4

QY-SERIES-DATAPR 2015

Data SheetPage 4 of 8

low voltage

105

130

150

1500

15

00

200

300

400

500

2000

2500

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE 9

Minimum

Maximum

Time Delay Curves

QY - Series Miniature Circuit Breakers

Group 10:Shunt Trip

(not certified, only offered as special order)

Code Description Comments- Not applicable Use this code if no Shunt Trip is used

V0 100 – 480 V Fly leads (approximately 60 mm long)

V5 100 – 480 V Internally connected

Other voltages are available as special orders. Check availability.Group 11 Code For future use (-)Group 12: Special Termination

Code Description Comments- Not applicable Use this code if no special terminations are used

P Plug-in

Z Bridged unit (bridge to be fitted by customer)

ZL Bridged unit (factory fitted)

Long Code continues

105

130

150

1500

15

00

200

300

400

500

2000

2500

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE 1

Minimum

Maximum

For options not listed, please contact CBI for assistance

QY-SERIES-DATAPR 2015

low voltage

Data SheetPage 5 of 8

105

130

150

1500

15

00

200

300

400

500

2000

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE U3

Minimum

Maximum

Time Delay Curves

QY - Series Miniature Circuit Breakers

105

130

150

1500

15

00

200

300

400

500

2000

2500

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE U2

Minimum

Maximum

QY-SERIES-DATAPR 2015

Data SheetPage 6 of 8

low voltage

105

130

150

1500

15

00

200

300

400

500

2000

2500

3000

4000

5000

0.001

0.01

0.1

1

10

100

1000

10000

100000

100

1000

Trip

ping

Tim

e (S

econ

ds)

% Rated Current

OPERATING CHARACTERISTICS

CURVE OP

Minimum

Maximum

Internal Resistance vs Current Rating

Time Delay Curves

QY - Series Miniature Circuit Breakers

0 5 10 15 20 25 30 35 40 45 50 55 60 650.1

1

10

100

1,000

10,000Q-Range resistance values

Amp rating

Resis

tanc

e (m

Ω)

Minimum

Maximum

* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which is available on request.

low voltage

QY-SERIES-DATAPR 2015

Data SheetPage 7 of 8

11.7[0.461]

18.0[0.709]

37.8[1.5900]

18.0[0.709]

35.5[1.400]

57.0

[2.2

44]

TEST BUTTON(on Trip Alarm only)

AUXILIARY/ TRIP ALARM (AT)

CONNECTING TERMINALS DETAIL (COMMON TO ALL)

Q-A

UX

RoHS

AUXI

LIAR

Y SW

ITCH

TRIP

ALA

RM S

WIT

CH

EN/IE

C 60

947-

5-1

110

VDC

: 0,5

A24

0 VA

C : 6

A

15

18

16

11

12

14

Uim

p =

2.5

kVIc

w

= 0

.1kA

UTIL

. CAT

. AC1

2/DC

12PO

LLUT

ION

DEG

REE

3

110

VDC

: 0,5

A24

0 VA

C : 6

AS

A00

5438

DE

V

All dimensions in mm [ inch ]Tolerance ± 0.2 unless otherwise specified

Typical outline for an Auxiliary module attached to a Dual mount single pole Circuit Breaker

141211

151816

Circuit Diagram when the Circuit Breaker is in the “OFF” position

Trip Alarm Switch

15

16

18

Auxiliary Switch

11

12

14

97.2

[3.8

27]

69.8[2.750]

6.5[0.256]

6.0[0.236]

0.8[0.0315]

1.42.80

[0.110]

6.8

[0.2

70]

2.3

[0.0

90]

0.5

[0.0

20]

45°

0.055][

19.3 ± 0.3[0.760 ± 0.012]

NC

NO

C

C

NC

NO

Typical outline of Auxiliary Switch / Trip Alarm

QY - Series Miniature Circuit Breakers

Auxiliary available (6.5 mm module width) to match the unit to which it is attached.

Available types as listed in Group 3:

• Type T - Trip Alarm as shown in outline drawings (fitted on a Dual mount product)

• Type AT - Auxiliary Switch + Trip Alarm (as shown)• Type A - Auxiliary Switch

Polarity identification

Pole 1 (Positive Bottom)

Pole 1 (Positive Top)

Positive Bottom

Positive Top

Polarity Marking

Bottom (Load side)

Wire link or busbar

Series Bridged Parallel Bridged

Top (Line side)

4 Poles 2 Poles 1 Pole 1 Pole

+ - + - - - + -

- + - + + + - +

Diagram identifying the polarity of 125 V DC products in reference to Group 9 on page 3. Devices are shown viewed from the front. Series devices (standard) - each pole is opposite polarity from the next pole on the left (bridged “-” to “+”). Parallel devices - each pole has the same polarity (bridged “+” to “+”, “-” to “-”).

A member of the Group

AUSTRALIACBI-electric: Australia90 Fairbank Road Clayton SouthMelbourne Victoria 3169 AustraliaTel: +61 3 9590 3500Fax: +61 3 9551 1051Email: [email protected]: www.cbi-electric.com.au

SOUTH AFRICACBI-electric: low voltageTripswitch Drive ElandsfonteinGauteng 1401 South AfricaTel: +27 11 928 2000Fax: + 27 11 392 2354Email: [email protected]: www.cbi-lowvoltage.co.za

USACBI-electric: North America35 E. Uwchlan Ave Suite 328Exton PA 19341 USATel: +1 610 524 9949Fax: +1 610 524 9945E-mail: [email protected]: www.cbibreakers.com

QY-SERIES-DATAPR 2015

Data SheetPage 8 of 8

low voltage

Please review our Customer Terms and Conditions on www.cbi-lowvoltage.co.zaAll rights reserved. Unless otherwise indicated, all materials on these pages are copyrighted by CBI (Pty) Ltd. No part of these pages, either text or image may be used for any purpose other than personal use. Therefore, reproduction, modification, storage in a retrieval system or retransmission, in any form or by any means, electronic, mechanical or otherwise, for reasons other than personal use, is strictly prohibited without prior written permission. CBI (Pty) Ltd reserves the right to alter any details of this document without notice and while every effort is made to ensure the accuracy of the content, no warranty is given as to accuracy of this document and no responsibility will be accepted for error or misinterpretation and any resulting loss.

1.53639.0

2.04852.0

(Ref

)

(Ref

)(R

ef)

(Ref

)

(Ref

)

(Ref

)(R

ef)

154.

2

6.07

1

5.59

1

142.

0

2.80

1

71.23.82

7

97.22.24

4

57.0

3.24

4

82.4

157.

1

6.18

6

154.

2

6.07

1

5.59

1

142.

0

157.

1

6.18

6

2.80

3

71.2

3.82

7

97.21.77

2

45.03.24

4

82.4

2.512

63.8

1.732

44.0

0.732

18.6

0.197

5.0

0.732

18.62.362

60.0

2.681

68.1

0.772

19.62.400

61.0

2.720

69.1

2.551

64.8

1.772

45.0

0.197

5.0

0.772

19.6

0.512

13.0

1.024

26.0

0.512

13.0

0.512

13.0

1.024

26.0

0.512

13.0

1.02426.0

1.53639.0

2.04852.0

1.02426.0

Maximum cable 50 mm2 Maximum cable

95 mm2Maximum cable

95 mm2

Maximum cable 50 mm2 Maximum cable

95 mm2Maximum cable

95 mm2

(Ref

)

All dimensions in mm [ inch ]Tolerance ± 0.2 [ 0.008 ] unless otherwise specified

All dimensions in mm [ inch ]Tolerance ± 0.2 [ 0.008 ] unless otherwise specified

QY - Series Miniature Circuit Breakers

Outline Dimensions: Dual mount

Outline Dimensions: DIN mount

Plug-in terminal dimensions available on request

H 2

USCC & USM 24, 48 & 600 VOLT/ULTRASAFETM FUSEHOLDERS

ä 600VAC, 30AMin. voltage to operateindicator light:90VAC[Less than 0.7 mAleakage current at 600V]

ä Special Indicator for 24VDC, 30A

ä Special Indicator for 48VDC, 30A

ä Short Circuit Current Rating: Class CC 200kA, Midget Fuse 100kA

ä 800VAC, 1000VDC30A ratings on USM without indicators

Ratings

ULTRASAFE MODULAR FUSE HOLDERS

Ferraz Shawmut ULTRASAFETM modular 24, 48 and600 volt Fuse Holders introduce a new level ofsafety for Class CC (USCC) and Midget 1-1/2" x13/32" (USM) as well as DC rated fuses up to 30amperes. ULTRASAFEholders qualify as “finger safe”under IEC and DIN standards to an IP20 grade of protection, including fuse changing (with the flick ofa finger). ULTRASAFE holders are available in 1, 2, 3or 4 poles, with or without blown-fuse indicators ineach pole. AC indicators are orange and DC arered. The multi-pole units can also be made up byordering pin-tie handles for field assembly. ULTRASAFE holders save up to 15% mountingspace and any combination can be snapped onto35mm DIN rail for extra savings in panel buildingtime. ULTRASAFE holders with Class CC fuses chosen for Type “2” protection give one of the safestprotection packages in the industry. Ultrasafe bodymaterial is tough and durable polyamide, withexceptional insulating properties.

ä All Ultrasafe Fuse Holdersmeet the requirements of UL512

ä UL ListedClass CCGuide IZLT, File E52283

ä UL Recognized ComponentMidget Guide IZLT2, File E52283

ä CSA CertifiedClass CC & MidgetC22.2, Class 6225File 32169

ä IEC 269 690VAC, 32AMidget version only.

Approvals

APPLICATIONS:

ä All circuits up to 600 volts for motors, control circuits, transformers, etc.

ä Non-load disconnectä 12, 24 and 48 volt

DC circuits

HIGHLIGHTS:

ä Finger Safeä Optional Indicator Lightsä DIN Rail Mountä Compact Footprintä Quick, Easy Fuse Change

RECOMMENDED FUSE USAGE

USCC . . . . . . . . . . . . . . . .use with ATDR*, ATMR, ATQR

USM . . . . . . . . . . . . . . . . .use with ATQ, ATM*, A6Y-2B, A25Z-2,TRM, OTM, A13X-2, GFN, GGU, A60Q-2

* Recommended for DC Applications DCT

Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]

H

H 3

USCC & USM 24, 48 & 600 VOLT/ULTRASAFETM FUSEHOLDERS

Dimensions

DIMENSION mm In

A 17.5 0.69B 35.0 1.38C 52.5 2.07D 70.0 2.76

E 78.0 3.07F 2.5 0.10G 78.0 3.07H 59.0 2.32

I 42.5 1.67J 5.0 0.20K 45.0 1.77

For use with Class CC Fuses

CATALOG NO. DESCRIPTION

USCC1 1 poleUSCC1I 1 pole with indicatorUSCC2 2 poleUSCC2I 2 pole with indicatorsUSCC3 3 poleUSCC3I 3 pole with indicatorsUSCC3IN 3 pole with indicators and a 4th neutral poleUSCC3N 3 pole with a 4th neutral poleUSCC4 4 poleUSCC4I 4 pole with indicators

For use with Midget (1-1/2” x 13/32”) Fuses

USM1 1 poleUSM1I 1 pole with indicatorUSM2 2 poleUSM2I 2 pole with indicatorsUSM3 3 poleUSM3I 3 pole with indicatorsUSM3IN 3 pole with indicators and a 4th neutral poleUSM3N 3 pole with a 4th neutral poleUSM4 4 poleUSM4I 4 pole with indicators

Accessories

USPTH2 Pin-tie handle for 2 polesUSPTH3 Pin-tie handle for 3 polesUSPTH4 Pin-tie handle for 4 poles

Neutral Link PoleUSN 1 Pole with Integral Neutral Link

Terminal screws: Phillips/slot headSuggested screw torque: 14.75 in-lbs.Connector type: Pressure plateWire range: #6 to #14 (solid/stranded Cu)Load-break disconnect: No

PART INDICATOR OPERATING LEAKAGENUMBER TYPE VOLTAGE CURRENT

USM1I-DC24 LED 12 to 24 VDC 10mA max.(@24vdc)USM1I-DC24P LED 20 to 24 VDC 1mA max.(@24vdc)USM1I-DC48 LED 35 to 48 VDC 10mA max.(@48vdc)USCC1I-DC24 LED 12 to 24 VDC 10mA max.(@24vdc)USCC1I-DC48 LED 35 to 48 VDC 10mA max.(@48vdc)

Special Indicator Options For use with Low Voltage DC Rated Class CC & Midget Fuses

Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]