The Powerful Difference
Accessories
Fuse BlocksMODEL NUMBERS
ME-125FME-200FME-300FME-400F
WORKS WITH
ME-125F and ME-200 onlyMM SeriesMM-AE SeriesMMS SeriesMM-E Series
ME-300F and ME-400F onlyME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series
DC Load DisconnectMODEL NUMBERS
ME-DCLD
The DC Load Disconnect is a pigtail adapter designed to automatically turn off the inverter via a 12 volt DC disconnect switch.
Fuse Selection
Conductor Gauge Current Capacity Recommended Fuse Rating4 AWG 125 125
1/0 AWG 200 2002/0 AWG 290 3003/0 AWG 310 3004/0 AWG 360 400
WORKS WITH
ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series
Conduit BoxMODEL NUMBERS
ME-CB
WORKS WITH
ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series
The ME-CB conduit box is designed to work with Magnum ME, MS, and RD Series Inverter/Chargers. It provides an enclosure for AC and/or DC wiring and has knockouts for ½”, ¾”, 1”, and 2” trade-size conduit. The ME-CB adds just over 5” (13 cm) to the length of the inverter.
Protection against costly damage: The ME-125F, ME-200F, ME-300F, and ME-400F protect the battery bank, inverter, and cables from damage caused by short circuits and overloads.
Complete kit in one package: Magnum Energy fuses include a Slow-Blow high current fuse, a mounting block, and protective cover.
The Powerful Difference
Authorized Magnum Dealer
Magnum Energy, Inc.1111 80th Street SW, Suite 250Everett, Washington 98203 USA
Phone: 425-353-8833Fax: 425-353-8390Web: www.magnumenergy.comTesting for specifications at 25° CSpecifications subject to change without notice.
June 2008, Rev D Part #64-0011
STACKING CABLE
240 VOLTS
INVE
RTE
R 1
INVE
RTE
R 2
L1 / 120 VOLTS L2 / 120 VOLTS
The Series Stacking Cable Kit allows two inverters to be stacked together to achieve 120/240 VAC output. Series stacking is commonly used for well pumps, tools, motors, and other 240 VAC appliances. The kit includes communication cable, two 2/0 battery cables, and battery lug covers.
Series Stacking Cable KitMODEL NUMBERS
ME-SSI
WORKS WITH
MS4024
Remote Switch Adapter
MODEL NUMBERS
ME-RSA (use SPST switch)
ME-RSA-M (use momentary switch)
The Remote Switch Adapter is a pigtail adapter designed to provide a simple on/off remote switch.
Accessories
WORKS WITH
ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series
Ignition Switch LockoutMODEL NUMBERS
ME-ISW
The Ignition Switch Lockout is a pigtail adapter designed to automatically turn off the inverter via a vehicle ignition switch.
WORKS WITH
ME SeriesMS SeriesMS-AE SeriesRD SeriesRD-E Series
Carling Tech: Magnetic Circuit Breaker
Products :: Circuit Protection :: Hydraulic/Magnetic Circuit Breakers
Back to Hydraulic/Magnetic Circuit Breakers
Hydraulic/Magnetic Circuit Breaker
F-Series
F-Series PDF eLibrary
The F-Series hydraulic/magnetic high amperage circuit breakers are designed to handle high current applications in extremely hot and/or cold locations. Due to its time-proven hydraulic/magnetic design, the F-Series load sensing mechanism is insensitive to changes in ambient or enclosure temperature, providing a consistent trip point over temperatures ranging from -40°C to +85°C.In addition, the F-Series
circuit breakers come with a choice of overload time delays, making them ideal for critical applications having inductive loads.
Series PDF eLibrary F-Series Cir. Breaker PDF (1.2 MB) Cir. Breaker Time Delays for F-
Series PDF (2.3 MB) Cir. Breaker Accessories PDF (49.5
KB)
Certifications UL489 Listed, CUL Certified, UL489A Listed (Telecom), TUV
Number of Poles 1-3 polesAvailable Delays Short, Medium, Long DCMaximum Current and Voltage Ratings
100 - 700 amps @ 125VDC
Maximum Interrupting Capacity
50,000 amps @ 125VDC
Auxiliary Switch Ratings 10.1A @ 250VAC 0.1A @ 125VAC (gold contacts) 5A @ 30VDC 1.0A @ 65VDC 0.5A @ 80VDC
Available Circuits Series, Series with Parallel Pole, Series with Auxiliary/Alarm Switch
Actuator Style Handle (1 per pole)Terminal Options Back Connected Style:
3/8 - 16 Stud 3/8 - 16 Screw Line & Load 3/8 - 16 Short Stud Front Connected Style: Box Wire Connector w/pressure plate 3/8 - 16 Screw Line & Load
Mounting Method Rear Mounted or Front Panel Mounted
English •• Chinese
Circuit Protection
Hydraulic/Magnetic Circuit Breakers
Thermal Circuit Breakers
Equipment Leakage Circuit Breakers
All Circuit Breakers
View All Products
Easily and automatically configure catalog numbers
Guides you to the appropriate switch or circuit breaker product series.
Search by:Part Number
Distributor Stock
List Price
Quick and easy product PDF's resourcing in the eLibrary.
Learn More
News
FAQs
Glossary
Home Site Map
©2009 Carling Technologies
Created by PixelMEDIA, Inc.
http://magnetic-circuit-breakers.carlingtech.com/magnetic-circuit-breaker__80.asp (1 of 2) [10/22/2009 9:45:30 AM]
Carling Tech: Magnetic Circuit Breaker
Value Added Custom actuator colors Non-standard current ratings Metering Shunt and more
http://magnetic-circuit-breakers.carlingtech.com/magnetic-circuit-breaker__80.asp (2 of 2) [10/22/2009 9:45:30 AM]
Littelfuse.com © 2013 Littelfuse POWR-GARD® Products
POWR-GARD® Fuse Datasheet
Rev:4-D-0524131 of 4
.06 (1.52) .14 (3.56)
.04 (1.02)
.02 (.51)
1.53 (38.86)
.50 (12.7).12 (3.05)
MOUNTING HOLE
DETAIL
.406 (10.31).12 (3.05) .28
(7.11)
1.5 (38.1)
.406 (10.31)
SPF SerieS Solar FUSeS1000 VDC • 1-30 A
SpecificationsVoltage Rating 1000 VDCAmperage Rating 1, 2, 3, 3.5, 4, 5, 6, 8, 10, 12, 15, 20, 25, 30Max. Interrupting Rating 20 kATime Constant ≤ 2msMaterial Body: Melamine Caps: Copper AlloyApprovals UL 2579 Listed (File: E339112) IEC 60269-6 (1-25 A) VDE Certified (No. 40033098)* see specifications on pg. 2 CSA Certified (File: 029862_0_000)Environmental RoHS CompliantCountry of Origin Mexico
DescriptionThe SPF Solar Protection Fuse series has been specifically designed for the protection of photovoltaic (PV) systems. This family of Midget style fuses (10 x 38 mm) can safely protect PV modules and conductors from reverse- overcurrent conditions.
As PV systems have grown in size, so have the corresponding voltage requirements. This increase in system voltage has typically been intended to minimize power loss associated with long conductor runs. Standard circuit protection devices are not designed to completely protect photovoltaic panels. However, the SPF series is UL Listed to safely interrupt faulted circuits up to this demanding voltage level.
Littelfuse offers 14 ampere ratings to match specific requirements in a variety of applications.
Features/Benefits• MeetsUL,IECandVDEphotovoltaicstandards• UL2579Listed1000VDCmaximum• 1-30Aratingsavailable• 20,000AInterruptingRating• BothPCBmountanddead-frontholderoptionsavailable
Applications• Inverters• Combiner boxes• Battery charge controllers
Recommended Fuse HoldersLPHV 1000 VDC POWR-Safe Series
Web ResourcesDownloadable CAD drawings and other technical information: Littelfuse.com/spf
Dimensions Inches (mm)
SerieS amP Package QUantity
moUnting method
catalog nUmber
ordering nUmber
SPF 2 10 FeRRuLe SPF002 0SPF002.TSPF 3.5 10 FeRRuLe SPF03.5 0SPF03.5TSPF 30 100 PCB TABS SPF030R 0SPF030.HXR
Ferrule Version PCB Version
look for this logo to indicate products that are used in solar applications. Visit our website Littelfuse.com/solar for the latest updates on approvals, certifications, and new products.
Part Numbering System0SPF xxxx H XR
Package Quantity
Series Mounting Options
Amp Code
T=10H=100
Blank=FerruleXR=PCB
RefertoAmpCodeColumninElectricalSpecificationsTable
Littelfuse.com © 2013 Littelfuse POWR-GARD® Products
POWR-GARD® Fuse Datasheet
Rev:4-D-0524132 of 4
SPF SerieS Solar FUSeS
Electrical Specifications Ferrule Version
Electrical Specifications PCB Version
amPe
rage
amP code
ordering nUmber UPc
Voltage interrUPting rating nom cold
reSiStance (ohm)
WattS loSS at 100% rated cUrrent (W)
WattS loSS at 80% rated cUrrent (W)
total clearing i2t (a2 s) 10 ka
total clearing i2t (a2 s) 20 ka
agency aPProValS
dc ac dc Ul Vde cSa
1 001. 0SPF001.T 07945816907 1000 – 20 kA 0.394 0.602 0.410 0.554 0.554 • •
2 002. 0SPF002.T 07945816910 1000 – 20 kA 0.237 1.586 0.851 1.175 4.755 • • •
3 003. 0SPF003.T 07945816913 1000 – 20 kA 0.11 1.504 0.824 5.007 7.882 • • •
3.5 03.5 0SPF03.5T 07945880087 1000 – 20 kA 0.07787 1.365 0.778 11.297 11.297 • •
4 004. 0SPF004.T 07945816916 1000 – 20 kA 0.06127 1.491 0.839 23.031 23.031 • • •
5 005. 0SPF005.T 07945816919 1000 – 20 kA 0.04086 1.465 0.859 42.600 42.600 • • •
6 006. 0SPF006.T 07945816922 1000 – 20 kA 0.0281 1.348 0.769 76.270 80.254 • • •
8 008. 0SPF008.T 07945816925 1000 – 20 kA 0.0178 1.610 0.914 193.323 198.960 • • •
10 010. 0SPF010.T 07945816928 1000 – 20 kA 0.0125 1.760 1.000 395.556 401.208 • • •
12 012. 0SPF012.T 07945816931 1000 – 20 kA 0.00993 1.965 1.109 599.198 641.940 • • •
15 015. 0SPF015.T 07945816934 1000 – 20 kA 0.00799 2.282 1.382 457.740 504.770 • • •
20 020. 0SPF020.T 07945816937 1000 – 20 kA 0.0045 2.810 1.574 1173.990 1312.850 • • •
25 025. 0SPF025.T 07945817595 1000 – 20 kA 0.00353 2.981 1.745 1937.430 2371.140 • • •
30 030. 0SPF030.T 07945817598 1000 – 20 kA 0.00284 3.923 2.125 2209.480 2678.750 • •
amPe
rage
amP code
ordering nUmber UPc
Voltage interrUPting rating nom cold
reSiStance (ohm)
WattS loSS at 100% rated cUrrent (W)
WattS loSS at 80% rated cUrrent (W)
total clearing i2t (a2 s) 10 ka
total clearing i2t (a2 s) 20 ka
agency aPProValS
dc ac dc Ul cSa
1 001. 0SPF001.HXR 07945816909 1000 – 20 kA 0.394 0.602 0.410 0.554 0.554 • •
2 002. 0SPF002.HXR 07945816912 1000 – 20 kA 0.237 1.586 0.851 1.175 4.755 • •
3 003. 0SPF003.HXR 07945816915 1000 – 20 kA 0.11 1.504 0.824 5.007 7.882 • •
3.5 03.5 0SPF03.5HXR 07945880089 1000 – 20kA 0.07787 1.365 0.778 11.297 11.297 • •
4 004. 0SPF004.HXR 07945816918 1000 – 20 kA 0.06127 1.491 0.839 23.031 23.031 • •
5 005. 0SPF005.HXR 07945816921 1000 – 20 kA 0.04086 1.465 0.859 42.600 42.600 • •
6 006. 0SPF006.HXR 07945816924 1000 – 20 kA 0.0281 1.348 0.769 76.270 80.254 • •
8 008. 0SPF008.HXR 07945816927 1000 – 20 kA 0.0178 1.610 0.914 193.323 198.960 • •
10 010. 0SPF010.HXR 07945816930 1000 – 20 kA 0.0125 1.760 1.000 395.556 401.208 • •
12 012. 0SPF012.HXR 07945816933 1000 – 20 kA 0.00993 1.965 1.109 599.198 641.940 • •
15 015. 0SPF015.HXR 07945816936 1000 – 20 kA 0.00799 2.282 1.382 457.740 504.770 • •
20 020. 0SPF020.HXR 07945817594 1000 – 20 kA 0.0045 2.810 1.574 1173.990 1312.850 • •
25 025. 0SPF025.HXR 07945817597 1000 – 20 kA 0.00353 2.981 1.745 1937.430 2371.140 • •
30 030. 0SPF030.HXR 07945817600 1000 – 20 kA 0.00284 3.923 2.125 2209.480 2678.750 • •
Littelfuse.com © 2013 Littelfuse POWR-GARD® Products
POWR-GARD® Fuse Datasheet
Rev:4-D-0524133 of 4
SPF SerieS Solar FUSeS
amPerage rating
oPening time (minUteS)
100% of amp rating per Ul
113% of amp rating per iec
135% of amp rating per Ul
145% of amp rating per iec
200% of amp rating per Ul
1-30TemperatureStabilization
60 Min 60 Max 60 Max 4 Max
WaVe Parameter lead Free recommendation
PReHeAT: (Typical Industry Recommendation)
TeMPeRATuRe MInIMuM: 130˚ C
TeMPeRATuRe MAXIMuM: —
PRe-HeAT TIMe 75 Seconds Maximum
SOLDeR POT TeMPeRATuRe 280˚ C Maximum
SOLDeR DWeLL TIMe 270˚ C for 8 Seconds Maximum
COMPLeTe CYCLe TIMe 250 Seconds Maximum
Recommended Process Parameters Soldering Parameters
-60°C -40°C -20°C 0°C 20°C 40°C 60°C 80°C 100°C 120°C 140°C-76°F -40°F -4°F 32°F 68°F 104°F 140°F 176°F 212°F 248°F 284°F
AMBIENT TEMPERATURE
60
40
20
0
PERC
ENT
OF
UPR
ATIN
G
0
20
40
60
PERCENT O
F DO
WN
RATING
Temperature Derating Curve (Temperature of Air Immediately Surrounding Fuse)
Electrical Specification – Agency Requirements
Littelfuse.com © 2013 Littelfuse POWR-GARD® Products
POWR-GARD® Fuse Datasheet
Rev:4-D-0524134 of 4
- THIS DATA GENERATED IN EXCEL -
1000900800700600500
400
300
200
1009080706050
40
30
20
1098765
4
3
2
10.90.80.70.60.5
0.4
0.3
0.2
0.10.090.080.070.060.05
0.04
0.03
0.02
0.01
1000900800700600500
400
300
200
1009080706050
40
30
20
1098765
4
3
2
10.90.80.70.60.5
0.4
0.3
0.2
0.10.090.080.070.060.05
0.04
0.03
0.02
0.01
1000900800700600500
400
300
200
1009080706050403020109876543210.90.80.70.60.5
0.4
0.3
0.2
0.1
1000900800700600500
400
300
200
1009080706050403020109876543210.90.80.70.60.5
0.4
0.3
0.2
0.1
CURRENT IN AMPERES
TIM
E IN
SEC
ON
DS
- 1A
- 2A
- 3A
- 6A
- 8A
- 10A
- 12A
- 4A
- 5A
- 3.5A
BASIS FOR DATA:
TEST VOLTAGE: 1000V TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER:
DRAWN BY:DATE:REVISION:DRAWING NO.: SHEET TIME CURRENT CHARACTERISTIC CURVES
LITTELFUSE, INC. CHICAGO, IL. USA
LLL
3/15/10
D2 OF 3
FCC01-SPF
SPF 1A - 30A
SPF SerieS Solar FUSeS
- THIS DATA GENERATED IN EXCEL -
1000 900 800 700 600 500 400
300
200
100 90 80 70 60 50 40
30
20
10 9 8 7 6 5 4
3
2
1 0.9 0.8 0.7 0.6 0.5 0.4
0.3
0.2
0.1 0.09 0.08 0.07 0.06 0.05 0.04
0.03
0.02
0.01
1000 900 800 700 600 500 400
300
200
100 90 80 70 60 50 40
30
20
10 9 8 7 6 5 4
3
2
1 0.9 0.8 0.7 0.6 0.5 0.4
0.3
0.2
0.1 0.09 0.08 0.07 0.06 0.05 0.04
0.03
0.02
0.01
1000 900 800 700 600 500 400
300
200
100 90 80 70 60 50 40
30
20
10 9 8 7 6 5 4 3 2 1 0.9 0.8 0.7 0.6 0.5 0.4
0.3
0.2
0.1
1000 900 800 700 600 500 400
300
200
100 90 80 70 60 50 40
30
20
10 9 8 7 6 5 4 3 2 1 0.9 0.8 0.7 0.6 0.5 0.4
0.3
0.2
0.1
CURRENT IN AMPERES
TIM
E IN
SEC
ON
DS
- 15A
- 20A
- 25A
- 30A
BASIS FOR DATA:
TEST VOLTAGE: 1000V TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER:
DRAWN BY:DATE:REVISION:DRAWING NO.: SHEET TIME CURRENT CHARACTERISTIC CURVES
LITTELFUSE, INC. CHICAGO, IL. USA
LLL
3/15/10
D3 OF 3
FCC01-SPF
SPF 1A - 30A
Time Current Curve (1-12 A)
Time Current Curve (15-30 A)
ME-125F and ME-200F Instruction Sheet
PN: 64-0053 Rev A
Magnum Energy, Inc.2211 West Casino Rd.
Everett, WA USA 98204www.magnumenergy.com
IntroductionThe Magnum Energy ANL Fuse/Fuse Block is designed to provide code com-pliant overcurrent protection for DC systems up to 32-volts. It protects the battery bank, inverter, and cables from damage caused by short circuits and overloads. The ANL fuse cartridge delivers instantaneous protection in the event of a short circuit, as well as a time delay to allow the momentary current surges that are common in inverter applications. Magnum small fuse blocks are available in 125 and 200 amp models. Our ANL fuse holder is molded from glass-fi lled nylon, has an insulating cover, and includes two black rub-ber terminal insulators to protect conductive areas from accidental shorts.The ANL fuses are rated for 32-volt DC systems (48-volts maximum) and are an economical alternative to the Class-T fuses. These fuses have a clear window that provides open-fuse indication; and, have a durable Polyethersul-fone body and riveted construction to offer superior service life in heavy-duty applications.Fuse selection is based upon the size of the conductor between the battery and the load. Keep in mind that the conductor’s current carrying capability is affected by: the length of the cable between the battery and the load, and the conductor’s wire type and temperature rating. Refer to the Table 1 for assistance in selecting a fuse.
InstallationThe battery, fuse block, and inverter should be located as close together as possible – without being in the same enclosure. Batteries can produce explosive gasses that may be ignited by the fuse. For code compliance, locate the fuse within 18” (45 cm) of the battery, and with at least 6” (15 cm) clearance from other equipment on each end. When changing the fuse, it may be energized by the battery; allow additional clearance if grounded metal surfaces (such as the inverter’s chassis) are nearby.Attach the fuse block base to a secure surface using the appropriate hardware (refer to Figure 1). Make the connections to the fuse block fi rst (see Figure 2 for proper hardware stacking), then to the battery, and fi nally to the inverter. Place the rubber terminal insulators on the battery cables before securing the cable lugs to the fuse posts.NOTE: The fuse should not be installed in the grounded conductor.Torque the Hex nuts to ~150 inch-pounds (16.9 N-m). The lock washers provided must be installed to ensure a quality and long lasting connection.Check the cables for correct polarity with a voltmeter before making the fi nal connections to the inverter.
WARNING: Failure to comply with torque specifi cations may result in damage and premature failure of the product. Failures caused by not adhering to the proper torque specifi cations are not covered by warranty.
WARNING: Before replacing a fuse, ensure all AC/DC power sources are de-energized (i.e., breakers opened, fuses removed) to prevent accidental shock.
ME-125F and ME-200F Instruction Sheet
© 2011 Magnum Energy, Inc.
Conductor Gauge Current Capacity* Recommended Fuse
#1 AWG/42.39 mm² 190 200**
#4 AWG/21.14 mm² 125 125
* - Current capacity based on 75° C cable rating in free air @ 30° C (86° F).** - The next larger standard size overcurrent device may be used if the de-rated cable ampacity falls between the standard overcurrent devices found in the NEC.
~5.00" (12.7 cm)~4.50" (11.43 cm)
1.25" (3.17 cm)
.75" (1.9 cm)
5/16 – 18 bolt w/ Hex nut (x2)Requires 9/16" wrench
Figure 1, Small Fuse Block Dimensions
WARNING: During installation, incorrect stacking of the fuse block hardware can create a highly resistive connection that generates heat. DO NOT place anything (i.e., washers) between the fuse and either battery cable lug as this can cause the fuse to overheat and blow open, resulting in a partial melting of the fuse holder and cover. Before stacking, refer to Figure 2.
Figure 2, Small Fuse Block Hardware Stacking
Fuse
Battery Cable Lugs
Flat Washers
Lock WashersHex Nuts
Table 1, Fuse Selection
low voltage
QY-SERIES-DATAPR 2015
Data SheetPage 1 of 8
• DC Circuit Breaker• Hydraulic-Magnetic technology• 100% rating capability, independent of ambient temperature • VDE and CCC approved, CE certified• UL listed (UL 489 A)• Ratings 0.1 to 63 A (1 & 2 pole), 3 pole parallel
(150 A maximum), 4 pole parallel (200 A maximum)• Optional Auxiliary Switch / Trip Alarm - factory fitted
(6.5 mm wide)• Optional Shunt Trip (no approvals)• Wide range of time delays and operating currents• Precision tripping characteristics• Ultra compact – 13 mm wide module• Trip indication with mid-trip handle • Reset immediately after overload• DIN mount product in grey shells• Dual mount product in black shells• 80 V DC devices are reverse feedable• 125 / 250 / 600 V DC devices are polarity sensitive• Suitable to use for electrical isolation
QY - Series Miniature Circuit Breakers
DIN mount(grey body)
Features Applications• DC branch circuit protection (UL 489A, IEC / EN 60947-2)• Telecom / datacom equipment• UPS equipment• Alternative energy equipment• Battery protection & switching• Telecommunication DC power distribution• Railway signalling equipment
• Auxiliary Switch (DIN and Dual Mount)• Auxiliary Switch + Trip Alarm (Dual Mount only)• Trip Alarm (Dual Mount only)• Handle lock• Surface mounting clips• Busbar• 57 mm Escutcheon blank (Dual Mount only)• 57 mm Safety blank (Dual Mount only)
Optional Accessories Auxiliary Switch, Trip Alarm & Combo:Features• AC and DC voltages• UL 489 listed (Auxiliary Switch: 6 A 250 V AC,
0.5 A 80 V DC)• IEC 60947-5-1 approved (Auxiliary Switch: 6 A 240 V AC,
0.5 A 110 V DC; Trip Alarm: 6 A 240 V AC, 0.5 A 110 V DC)• Factory fitted• Attached to right hand side of Circuit Breaker• Compact 6.5 mm width
Dual mount(black body)
Dual mount + Auxiliary(black body)
Dual mountparallel
(black body)
Dual mountseries
(black body)
QY-SERIES-DATAPR 2015
Data SheetPage 2 of 8
low voltage
QY - Series Miniature Circuit Breakers
Breaker QY Wire Size mm² (IEC) Wire Gauge (UL) Torque (IEC) Torque (UL) Comments
1 Pole & 2 Pole 0.75 - 35 mm² 18 – 2 – AWG 2.5 Nm 20 in-lb Pozidriv #2Combi head
2 Pole Parallel 50 mm² 14 – 1/0 – AWG 3.2 Nm 28 in-lb Bridge Terminal3 Pole Parallel 95 mm² 14 – 5/0 – AWG 5.6 Nm 50 in-lb Bridge Terminal
4 Pole Parallel 95 mm² 14 – 5/0 – AWG 5.6 Nm 50 in-lb Bridge Terminal
Technical Data
Approvals UL 489A
Number of Poles 1 2 2 parallel
2 parallel
3 parallel
4 parallel 2 series 4 series 1 pole
plug-in
Operating Voltages 80 V DC, 125 V DC 80 V DC 125 V DC
80 / 125 V DC 80 V DC 250 V
DC600 V DC 80 V DC
Minimum Current Rating 0.1 A 0.1 A 30 A 20 A 110 A 200 A 0.1 A 0.1 A 0.1 AMaximum Current Rating 63 A 50 A 100 A 100 A 150 A 200 A 50 A 20 A 50 AInterrupting Capacity 10 kAOperating Temperature Range -40oC to +85oC
Mounting Options DIN Rail, Dual mounting (DIN & Mini), surface mounting clip, plug-in terminalTime Delay Curves 1, 9, U2, U3, OP
Approvals CCCNumber of Poles 1 2 2 parallel 3 parallel 4 parallel 1 pole plug-inOperating Voltages 80 V DCMinimum Current Rating 0.1 A 0.1 A 30 A 110 A 200 A 0.1 AMaximum Current Rating 63 A 50 A 100 A 150 A 200 A 50 AInterrupting Capacity 10 kAOperating Temperature Range -40oC to +85oC
Mounting Options DIN Rail, Dual mounting (DIN & Mini), surface mounting clip, plug-in terminalTime Delay Curves 1, 9, U2, U3, OP
Approvals IEC / EN 60947-2, VDE
Number of Poles 1 2 2 parallel 2 parallel 3 parallel 4 parallel 2 series 1 pole plug-in
Operating Voltages 80 V DC, 125 V DC 80 V DC 125 V DC 80 V DC 250 V DC 80 V DCMinimum Current Rating 0.1 A 0.1 A 60 A 30 A 110 A 200 A 0.1 A 0.1 AMaximum Current Rating 63 A 50 A 100 A 100 A 150 A 200 A 50 A 50 AInterrupting Capacity 10 kAOperating Temperature Range -40oC to +85oC
Mounting Options DIN Rail, Dual mounting (DIN & Mini), surface mounting clip, plug-in terminalTime Delay Curves 1, 9, U2, U3, OP
low voltage
QY-SERIES-DATAPR 2015
Data SheetPage 3 of 8
QY - Series Miniature Circuit Breakers
Example Code: QY---A-3(13)-D-U2-150A-B0-----ZGroup 1 2 3 4 5 6 7 8 9 10 11 12
Requirement QYFrame
Switch /Neutral Auxiliary Triple
pole
13 mm module width
DIN RailMedium
delay curve U2
Current Rating150 A
Voltage80 V DC
No Shunt Trip
Future use
Parallel bridged
(by customer)
Long Code QY - A 3 (13) D U2 150A B0 - - Z
Long Code
Group 1: Frame Type
Code Description Comments QY 13 mm wide Miniature Circuit Breaker UL 489A, IEC / EN 60947-2, VDE, CE, CCC
Group 2:Switch/Neutral
Code Description Comments - Not applicable Overload poles do not have any further coding
Group 3:Auxiliary
Code Description Comments- Not applicable Use this code if no Auxiliary used
A Auxiliary Switch (1 x Aux in 1 module) 6.5 mm module fitted on right-hand side (DIN & Dual Mount)
T Trip Alarm (1 x Trip Alarm in 1 module) 6.5 mm module fitted on right-hand side (Dual Mount only)
AT Auxiliary Switch + Trip Alarm combo (combined in 1 module) 6.5 mm module fitted on right-hand side (Dual Mount only)Group 4: No of Poles
Code Description Comments1 Single pole
2 Double pole
3 Triple pole
4 Four poleGroup 5: Module Width
Code Description Comments (13) 13 mm module width 13 mm per pole
Group 6: Mounting
Code Description Comments D DIN rail mount – 45 mm Escutcheon, grey body DIN mount supplied in grey only
DM Dual mount – 57 mm Escutcheon, black body Dual mount supplied in black onlyGroup 7: Time Delays
Code Description Instantaneous Trip Point (x In) Comments1 Long time delay, high instantaneous trip 10 – 20 Orange handle
9 Long time delay 7 – 12 White handle
U2 Medium time delay 5 – 10 White handle
U3 Short time delay 3 – 5 White handle
OP Instantaneous None White handleGroup 8: Current Ratings
Code / Description Comments
0.1, 0.2, 0.3, 0.5, 1, 2, 3, 4, 5, 6, 7, 8 ,9, 10, 12, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63, 70, 80, 90, 100, 120, 125, 150, 200 A
Ratings available vary depending on certification, bridging configuration and voltage. (See comments in Group 9)
* Other ratings are available as special orders. Check availability.Group 9: Voltage
(see diagram on page 7)
Code Voltage Description Comments
B0 80 V DC Not polarity sensitive 0.1 - 63 A 1 pole, 0.1 - 50 A 2 pole, 60 - 100 A 2 pole parallel (80 V DC), 30 - 100 A 2 pole parallel (125 V DC), 110 - 150 A 3 pole parallel, 200 A 4 pole parallel(ratings available vary depending on certification)B1 125 V DC Polarity sensitive. Positive bottom.
B2 250 V DC2 poles in series bridged (2 x 125 V)
Positive = pole 1 bottom0.1 - 50 A 2 pole series bridged at the top (by customer)
pole 1 (-) to pole 2 (+)
B3 250 V DC 2 poles in series bridged (2 x 125 V)Positive = pole 1 bottom
0.1 - 50 A 2 pole series bridged at the top (factory fitted)pole 1 (-) to pole 2 (+)
B4 600 V DC 4 poles in series bridged (4 x 125 V)Positive = pole 1 bottom
0.1 - 20 A 4 pole series bridged (factory fitted)As per wiring diagram printed on unit
T1 125 V DC Polarity sensitive. Positive top.0.1 - 63 A 1 pole, 0.1 - 50 A 2 pole, 30 - 100 A 2 pole parallel,
110 - 150 A 3 pole parallel, 200 A 4 pole parallel
T2 250 V DC 2 poles in series bridged (2 x 125 V)Positive = pole 1 top
0.1 - 50 A 2 pole series bridged at the bottom (by customer)pole 1 (-) to pole 2 (+)
T3 250 V DC2 poles in series bridged (2 x 125 V)
Positive = pole 1 top0.1 - 50 A 2 pole series bridged at the bottom (factory fitted)
pole 1 (-) to pole 2 (+)
T4 600 V DC 4 poles in series bridged (4 x 125 V)Positive = pole 1 top
0.1 - 20 A 4 pole series bridged (factory fitted)As per wiring diagram printed on unit
Continues on page 4
QY-SERIES-DATAPR 2015
Data SheetPage 4 of 8
low voltage
105
130
150
1500
15
00
200
300
400
500
2000
2500
3000
4000
5000
0.001
0.01
0.1
1
10
100
1000
10000
100000
100
1000
Trip
ping
Tim
e (S
econ
ds)
% Rated Current
OPERATING CHARACTERISTICS
CURVE 9
Minimum
Maximum
Time Delay Curves
QY - Series Miniature Circuit Breakers
Group 10:Shunt Trip
(not certified, only offered as special order)
Code Description Comments- Not applicable Use this code if no Shunt Trip is used
V0 100 – 480 V Fly leads (approximately 60 mm long)
V5 100 – 480 V Internally connected
Other voltages are available as special orders. Check availability.Group 11 Code For future use (-)Group 12: Special Termination
Code Description Comments- Not applicable Use this code if no special terminations are used
P Plug-in
Z Bridged unit (bridge to be fitted by customer)
ZL Bridged unit (factory fitted)
Long Code continues
105
130
150
1500
15
00
200
300
400
500
2000
2500
3000
4000
5000
0.001
0.01
0.1
1
10
100
1000
10000
100000
100
1000
Trip
ping
Tim
e (S
econ
ds)
% Rated Current
OPERATING CHARACTERISTICS
CURVE 1
Minimum
Maximum
For options not listed, please contact CBI for assistance
QY-SERIES-DATAPR 2015
low voltage
Data SheetPage 5 of 8
105
130
150
1500
15
00
200
300
400
500
2000
3000
4000
5000
0.001
0.01
0.1
1
10
100
1000
10000
100000
100
1000
Trip
ping
Tim
e (S
econ
ds)
% Rated Current
OPERATING CHARACTERISTICS
CURVE U3
Minimum
Maximum
Time Delay Curves
QY - Series Miniature Circuit Breakers
105
130
150
1500
15
00
200
300
400
500
2000
2500
3000
4000
5000
0.001
0.01
0.1
1
10
100
1000
10000
100000
100
1000
Trip
ping
Tim
e (S
econ
ds)
% Rated Current
OPERATING CHARACTERISTICS
CURVE U2
Minimum
Maximum
QY-SERIES-DATAPR 2015
Data SheetPage 6 of 8
low voltage
105
130
150
1500
15
00
200
300
400
500
2000
2500
3000
4000
5000
0.001
0.01
0.1
1
10
100
1000
10000
100000
100
1000
Trip
ping
Tim
e (S
econ
ds)
% Rated Current
OPERATING CHARACTERISTICS
CURVE OP
Minimum
Maximum
Internal Resistance vs Current Rating
Time Delay Curves
QY - Series Miniature Circuit Breakers
0 5 10 15 20 25 30 35 40 45 50 55 60 650.1
1
10
100
1,000
10,000Q-Range resistance values
Amp rating
Resis
tanc
e (m
Ω)
Minimum
Maximum
* The published time delay curves are generated at 30oC ambient temperature with the Circuit Breaker mounted in the up-right position. The “must hold”, “must trip” and “instantaneous trip” current values are not affected by temperature, although delay time for the other operating current values may have to be adjusted using the temperature compensation curve which is available on request.
low voltage
QY-SERIES-DATAPR 2015
Data SheetPage 7 of 8
11.7[0.461]
18.0[0.709]
37.8[1.5900]
18.0[0.709]
35.5[1.400]
57.0
[2.2
44]
TEST BUTTON(on Trip Alarm only)
AUXILIARY/ TRIP ALARM (AT)
CONNECTING TERMINALS DETAIL (COMMON TO ALL)
Q-A
UX
RoHS
AUXI
LIAR
Y SW
ITCH
TRIP
ALA
RM S
WIT
CH
EN/IE
C 60
947-
5-1
110
VDC
: 0,5
A24
0 VA
C : 6
A
15
18
16
11
12
14
Uim
p =
2.5
kVIc
w
= 0
.1kA
UTIL
. CAT
. AC1
2/DC
12PO
LLUT
ION
DEG
REE
3
110
VDC
: 0,5
A24
0 VA
C : 6
AS
A00
5438
DE
V
All dimensions in mm [ inch ]Tolerance ± 0.2 unless otherwise specified
Typical outline for an Auxiliary module attached to a Dual mount single pole Circuit Breaker
141211
151816
Circuit Diagram when the Circuit Breaker is in the “OFF” position
Trip Alarm Switch
15
16
18
Auxiliary Switch
11
12
14
97.2
[3.8
27]
69.8[2.750]
6.5[0.256]
6.0[0.236]
0.8[0.0315]
1.42.80
[0.110]
6.8
[0.2
70]
2.3
[0.0
90]
0.5
[0.0
20]
45°
0.055][
19.3 ± 0.3[0.760 ± 0.012]
NC
NO
C
C
NC
NO
Typical outline of Auxiliary Switch / Trip Alarm
QY - Series Miniature Circuit Breakers
Auxiliary available (6.5 mm module width) to match the unit to which it is attached.
Available types as listed in Group 3:
• Type T - Trip Alarm as shown in outline drawings (fitted on a Dual mount product)
• Type AT - Auxiliary Switch + Trip Alarm (as shown)• Type A - Auxiliary Switch
Polarity identification
Pole 1 (Positive Bottom)
Pole 1 (Positive Top)
Positive Bottom
Positive Top
Polarity Marking
Bottom (Load side)
Wire link or busbar
Series Bridged Parallel Bridged
Top (Line side)
4 Poles 2 Poles 1 Pole 1 Pole
+ - + - - - + -
- + - + + + - +
Diagram identifying the polarity of 125 V DC products in reference to Group 9 on page 3. Devices are shown viewed from the front. Series devices (standard) - each pole is opposite polarity from the next pole on the left (bridged “-” to “+”). Parallel devices - each pole has the same polarity (bridged “+” to “+”, “-” to “-”).
A member of the Group
AUSTRALIACBI-electric: Australia90 Fairbank Road Clayton SouthMelbourne Victoria 3169 AustraliaTel: +61 3 9590 3500Fax: +61 3 9551 1051Email: [email protected]: www.cbi-electric.com.au
SOUTH AFRICACBI-electric: low voltageTripswitch Drive ElandsfonteinGauteng 1401 South AfricaTel: +27 11 928 2000Fax: + 27 11 392 2354Email: [email protected]: www.cbi-lowvoltage.co.za
USACBI-electric: North America35 E. Uwchlan Ave Suite 328Exton PA 19341 USATel: +1 610 524 9949Fax: +1 610 524 9945E-mail: [email protected]: www.cbibreakers.com
QY-SERIES-DATAPR 2015
Data SheetPage 8 of 8
low voltage
Please review our Customer Terms and Conditions on www.cbi-lowvoltage.co.zaAll rights reserved. Unless otherwise indicated, all materials on these pages are copyrighted by CBI (Pty) Ltd. No part of these pages, either text or image may be used for any purpose other than personal use. Therefore, reproduction, modification, storage in a retrieval system or retransmission, in any form or by any means, electronic, mechanical or otherwise, for reasons other than personal use, is strictly prohibited without prior written permission. CBI (Pty) Ltd reserves the right to alter any details of this document without notice and while every effort is made to ensure the accuracy of the content, no warranty is given as to accuracy of this document and no responsibility will be accepted for error or misinterpretation and any resulting loss.
1.53639.0
2.04852.0
(Ref
)
(Ref
)(R
ef)
(Ref
)
(Ref
)
(Ref
)(R
ef)
154.
2
6.07
1
5.59
1
142.
0
2.80
1
71.23.82
7
97.22.24
4
57.0
3.24
4
82.4
157.
1
6.18
6
154.
2
6.07
1
5.59
1
142.
0
157.
1
6.18
6
2.80
3
71.2
3.82
7
97.21.77
2
45.03.24
4
82.4
2.512
63.8
1.732
44.0
0.732
18.6
0.197
5.0
0.732
18.62.362
60.0
2.681
68.1
0.772
19.62.400
61.0
2.720
69.1
2.551
64.8
1.772
45.0
0.197
5.0
0.772
19.6
0.512
13.0
1.024
26.0
0.512
13.0
0.512
13.0
1.024
26.0
0.512
13.0
1.02426.0
1.53639.0
2.04852.0
1.02426.0
Maximum cable 50 mm2 Maximum cable
95 mm2Maximum cable
95 mm2
Maximum cable 50 mm2 Maximum cable
95 mm2Maximum cable
95 mm2
(Ref
)
All dimensions in mm [ inch ]Tolerance ± 0.2 [ 0.008 ] unless otherwise specified
All dimensions in mm [ inch ]Tolerance ± 0.2 [ 0.008 ] unless otherwise specified
QY - Series Miniature Circuit Breakers
Outline Dimensions: Dual mount
Outline Dimensions: DIN mount
Plug-in terminal dimensions available on request
H 2
USCC & USM 24, 48 & 600 VOLT/ULTRASAFETM FUSEHOLDERS
ä 600VAC, 30AMin. voltage to operateindicator light:90VAC[Less than 0.7 mAleakage current at 600V]
ä Special Indicator for 24VDC, 30A
ä Special Indicator for 48VDC, 30A
ä Short Circuit Current Rating: Class CC 200kA, Midget Fuse 100kA
ä 800VAC, 1000VDC30A ratings on USM without indicators
Ratings
ULTRASAFE MODULAR FUSE HOLDERS
Ferraz Shawmut ULTRASAFETM modular 24, 48 and600 volt Fuse Holders introduce a new level ofsafety for Class CC (USCC) and Midget 1-1/2" x13/32" (USM) as well as DC rated fuses up to 30amperes. ULTRASAFEholders qualify as “finger safe”under IEC and DIN standards to an IP20 grade of protection, including fuse changing (with the flick ofa finger). ULTRASAFE holders are available in 1, 2, 3or 4 poles, with or without blown-fuse indicators ineach pole. AC indicators are orange and DC arered. The multi-pole units can also be made up byordering pin-tie handles for field assembly. ULTRASAFE holders save up to 15% mountingspace and any combination can be snapped onto35mm DIN rail for extra savings in panel buildingtime. ULTRASAFE holders with Class CC fuses chosen for Type “2” protection give one of the safestprotection packages in the industry. Ultrasafe bodymaterial is tough and durable polyamide, withexceptional insulating properties.
ä All Ultrasafe Fuse Holdersmeet the requirements of UL512
ä UL ListedClass CCGuide IZLT, File E52283
ä UL Recognized ComponentMidget Guide IZLT2, File E52283
ä CSA CertifiedClass CC & MidgetC22.2, Class 6225File 32169
ä IEC 269 690VAC, 32AMidget version only.
Approvals
APPLICATIONS:
ä All circuits up to 600 volts for motors, control circuits, transformers, etc.
ä Non-load disconnectä 12, 24 and 48 volt
DC circuits
HIGHLIGHTS:
ä Finger Safeä Optional Indicator Lightsä DIN Rail Mountä Compact Footprintä Quick, Easy Fuse Change
RECOMMENDED FUSE USAGE
USCC . . . . . . . . . . . . . . . .use with ATDR*, ATMR, ATQR
USM . . . . . . . . . . . . . . . . .use with ATQ, ATM*, A6Y-2B, A25Z-2,TRM, OTM, A13X-2, GFN, GGU, A60Q-2
* Recommended for DC Applications DCT
Gross Automation (877) 268-3700 · www.ferrazshawmutsales.com · [email protected]
H
H 3
USCC & USM 24, 48 & 600 VOLT/ULTRASAFETM FUSEHOLDERS
Dimensions
DIMENSION mm In
A 17.5 0.69B 35.0 1.38C 52.5 2.07D 70.0 2.76
E 78.0 3.07F 2.5 0.10G 78.0 3.07H 59.0 2.32
I 42.5 1.67J 5.0 0.20K 45.0 1.77
For use with Class CC Fuses
CATALOG NO. DESCRIPTION
USCC1 1 poleUSCC1I 1 pole with indicatorUSCC2 2 poleUSCC2I 2 pole with indicatorsUSCC3 3 poleUSCC3I 3 pole with indicatorsUSCC3IN 3 pole with indicators and a 4th neutral poleUSCC3N 3 pole with a 4th neutral poleUSCC4 4 poleUSCC4I 4 pole with indicators
For use with Midget (1-1/2” x 13/32”) Fuses
USM1 1 poleUSM1I 1 pole with indicatorUSM2 2 poleUSM2I 2 pole with indicatorsUSM3 3 poleUSM3I 3 pole with indicatorsUSM3IN 3 pole with indicators and a 4th neutral poleUSM3N 3 pole with a 4th neutral poleUSM4 4 poleUSM4I 4 pole with indicators
Accessories
USPTH2 Pin-tie handle for 2 polesUSPTH3 Pin-tie handle for 3 polesUSPTH4 Pin-tie handle for 4 poles
Neutral Link PoleUSN 1 Pole with Integral Neutral Link
Terminal screws: Phillips/slot headSuggested screw torque: 14.75 in-lbs.Connector type: Pressure plateWire range: #6 to #14 (solid/stranded Cu)Load-break disconnect: No
PART INDICATOR OPERATING LEAKAGENUMBER TYPE VOLTAGE CURRENT
USM1I-DC24 LED 12 to 24 VDC 10mA max.(@24vdc)USM1I-DC24P LED 20 to 24 VDC 1mA max.(@24vdc)USM1I-DC48 LED 35 to 48 VDC 10mA max.(@48vdc)USCC1I-DC24 LED 12 to 24 VDC 10mA max.(@24vdc)USCC1I-DC48 LED 35 to 48 VDC 10mA max.(@48vdc)
Special Indicator Options For use with Low Voltage DC Rated Class CC & Midget Fuses