acoustic cabinet fans cab series - innovating … · acoustic cabinet fans ... cab-200 328 430 365...

4
CAB Acoustic cabinet fans Low noise level Acoustic cabinet fans manufactured from heavy gauge galvanised steel sheet and inter- nally lined with 50 mm thickness of fireproof acoustic insulation (M0). Fan cover supplied with “quick-fix” fixings to enable fast remov- al and fitting, and a tight close. All models incorporate single phase direct-drive forward curved centrifugal fan. All cabinets can be installed outdoors as standard. Available, depending upon the model, with single motors in 2 or 4 poles. Motors From CAB-125 to 250N, all motors are IP44, Class B, with ball bearings and thermal protection. From CAB-315 to 400, all motors are IP55, Class F, with ball bearings and thermal protection. Electrical supply: Single phase 230V-50Hz. Speed controllable using voltage regulation. Acoustic insulation of 50 mm thickness fireproof fibreglass (M0) with a high resistance coating reducing the noise level significantly Cabinet air tightness All models incorporate inlet and discharge circular duct connection flanges with integrated rubber air seal IP55 remote terminal box To ease installation and connection to external controls Easy to install Easy maintenance “Quick fix” fixings to enable a fast and easy maintenance All models are supplied with four mounting feet to facilitate any ceiling, wall or floor mounting installation ACOUSTIC CABINET FANS CAB Series A P P L I C A T I O N S Workshops Commercial Premises Offices Restaurants and cafes INSTALLATION IN ANY POSITION Can be mounted in vertical, horizontal or inverted position.

Upload: phungnga

Post on 22-May-2018

223 views

Category:

Documents


3 download

TRANSCRIPT

CA

BA

cous

tic

cab

inet

fan

s

Low noise level

Acoustic cabinet fans manufactured from

heavy gauge galvanised steel sheet and inter-

nally lined with 50 mm thickness of fireproof

acoustic insulation (M0). Fan cover supplied

with “quick-fix” fixings to enable fast remov-

al and fitting, and a tight close. All models

incorporate single phase direct-drive forward

curved centrifugal fan. All cabinets can be installed

outdoors as standard.

Available, depending upon the model, with

single motors in 2 or 4 poles.

Motors

From CAB-125 to 250N, all motors are IP44, Class

B, with ball bearings and thermal protection.

From CAB-315 to 400, all motors are IP55, Class

F, with ball bearings and thermal protection.

Electrical supply:

Single phase 230V-50Hz.

Speed controllable using voltage regulation.

Acoustic insulation of 50 mm

thickness fireproof fibreglass

(M0) with a high resistance

coating reducing the noise

level significantly

Cabinet airtightness

All models incorporate inlet

and discharge circular duct

connection flanges with

integrated rubber air seal

IP55remote terminal box

To ease installation and

connection to external controls

Easy to installEasy maintenance

“Quick fix” fixings to enable a

fast and easy maintenance

All models are supplied with four

mounting feet to facilitate any

ceiling, wall or floor mounting

installation

ACOUSTIC CABINET FANS

CAB Series

A P P L I C A T I O N S

Workshops Commercial Premises

Offices Restaurants and cafes

INSTALLATION IN ANY POSITION

Can be mounted in vertical, horizontal or inverted position.

CA

BA

cous

tic

cab

inet

fan

s

Technical characteristics

Sound power spectrum in dB(A) at 2/3 of Qmax:

Acoustic characteristics

Dimensions (mm)

Model A B C Ø D E F G

CAB-125 273 388 395 125 125 162 505

CAB-160 273 388 395 160 143 162 505

CAB-200 328 430 365 200 216 210 475

CAB-250 383 525 450 250 263 237 560

CAB-315 443 600 505 315 301 264 615

CAB-355 513 660 600 355 331 292 710

CAB-400 513 660 600 400 331 292 710

Before installation check that the product electrical characteristics listed on the data plate label (Voltage, power, frequency etc) match those of the intended electrical supply.

Model Fan size Speed

(r.p.m.)

Max.abs.power

(W)

Max.abs.current at 230V

(A)

Max. airflow

(m3/h)

Sound pressure level ** Weight

(kg)

Speed controller

Outlet Inlet Radiated*

CAB-125 140/059 1600 48 0,2 240 46 33 29 16 REB-1N

CAB-160 140/059 2350 100 0,4 390 54 40 35 18 REB-1N

CAB-200 133/126 2000 180 0,7 695 55 45 37 22 REB-1N

CAB-250 180/184 1250 200 0,8 1250 57 41 33 25 REB-1N

CAB-250N 146/180 2200 350 1,5 1140 62 45 38 27 REB-2,5N

CAB-315 180/240 1400 500 2,8 2100 63 50 37 33 REB-5

CAB-315N 240/180 1400 780 3,24 2600 70 53 48 33 REB-5

CAB-355 240/240 1400 1100 4,6 3150 68 53 44 35 REB-5

CAB-400 240/240 1400 1100 4,6 3500 70 56 44 35 REB-5*Fan ducted on both inlet and outlet sides. ** Curves measured at 2/3 of Qmax.

Model 63 125 250 500 1000 2000 4000 8000

CAB-125Outlet 35 46 44 50 59 54 50 44Inlet 41 46 36 36 37 35 32 29Radiated 41 41 25 27 26 25 22 20

CAB-160Outlet 38 55 55 60 65 65 60 56Inlet 42 53 44 43 40 43 43 39Radiated 38 49 36 35 32 31 30 30

CAB-200Outlet 37 53 54 60 67 64 61 57Inlet 46 56 50 52 50 49 45 40Radiated 31 51 41 36 40 37 31 27

CAB-250Outlet 49 54 55 62 69 66 62 57Inlet 48 51 49 47 48 46 41 36Radiated 41 44 39 37 39 35 30 26

CAB-250NOutlet 51 59 60 67 71 74 69 64Inlet 52 54 52 51 48 54 49 42Radiated 41 47 44 43 44 47 41 33

CAB-315Outlet 48 60 62 67 73 73 70 66Inlet 55 54 58 54 58 59 52 45Radiated 40 46 47 41 44 43 37 34

CAB-315NOutlet 54 65 69 76 80 78 76 72Inlet 57 59 59 55 60 61 58 52Radiated 55 52 54 51 56 55 55 49

CAB-355Outlet 64 67 68 72 78 76 74 68Inlet 55 62 60 55 59 60 58 49Radiated 44 54 53 49 50 46 42 37

CAB-400Outlet 59 63 68 75 81 79 77 70Inlet 60 63 61 58 65 65 60 50Radiated 41 52 53 51 52 48 42 36

CA

BA

cous

tic

cab

inet

fan

s

Performance curves

0.00 0.01 0.02 0.03 0.04 0.05 0.06 0.07 m3/s

0 40 80 120 160 200 240 m3/h0

5

10

15

20

25

30

mmcda CAB-125

0

50

100

150

200

250

300

Pa

32

33

34*

0.00 0.02 0.04 0.06 0.08 0.10 0.12 m3/s

0 100 200 300 400 m3/h0

5

10

15

20

25

30

35

mmcda

0

50

100

150

200

250

300

350

PaCAB-160

0.00 0.04 0.08 0.12 0.16 0.20 m3/s

0 100 200 300 400 500 600 700 m3/h0

5

10

15

20

25

30

35

40

45

mmcda

0

50

100

150

200

250

300

350

400

450Pa

CAB-200 a

45

4139

0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7m3/s

0 300 600 900 1200 1500 1800 2100 2400 m3/h0

5

10

15

20

25

30

35

40

45

mmcda

0

50

100

150

200

250

300

350

400

450Pa

CAB-315

52

50

48

315N

315

56

53

51

53

53

57

5056

54

– Q = Air volume in, m3/hr and m3/s.– Ps = Static pressure in mmWG and Pa.– Dry air at 20ºC and 760 mmHg.– Performance data in accordance with ISO 5801 and AMCA 210-99 Standards.

* Sound pressure at 1,5 m, at the inlet.

Pa mmWG

Pa mmWGPs

Q

Q

Q

Q

Q

Q

PsPa mmWG

Ps

Ps

Ps

Ps

Pa mmWG

Pa mmWGPa mmWG

CA

BA

cous

tic

cab

inet

fan

s

Electrical accessories

REB-1N, REB-1NE,REB-2,5N, REB-2,5NE,REB-5 Electronic, singlephase speedcontrollers.

RMB-1,5,RMB-3,5,RMB-8Auto transformersingle phasespeed controllers.

Mounting accessories

MFLFiltration boxes

MBEElectric heater batteries

SILSound attenuators.

TG-K330Duct temperaturesensorTG-R530Room temperaturesensor.

PULSERSingle phase/threephase electricalheater batterycontroller.

TTC-2000 TTC-2000 + TTS-1 Three phase electrical heater battery controller.The TTC-2000 needs an external temperature sensor to control the battery (TG-K300 or TG-R530).

On/OffIP55 Switch

APCDischarge protection guards for direct connec-tion to the inlet-outlet flange (please see pages Mounting Accessories).

KSE-45Flexible supports Rubber anti-vibration mounts to reduce vibration and noise transmission to the installation. (1KSE = set of 4 supports per bag).

CARCircular back draft shutters.

Model A B D E F

MFL-100 200 200 100 160 196

MFL-125 200 200 125 160 196

MFL-160 200 200 160 154 196

MFL-200 243 244 200 154 202

MFL-250 293 294 250 154 206

MFL-315 342 343 315 154 206

MFL-355 447 448 355 154 254

MFL-400 447 448 400 154 254

MBE battery model

Battery power (W)

Batteries supply

Minimum airflow (m3/s)

Controller type

MBE-100/04B 400 1/230 50 PULSER

MBE-125/12B 1200 1/230 70 PULSER

MBE-160/21B 2100 1/230 110 PULSER

MBE-200/50T 5000 2/400 170 PULSER

MBE-250/60T 6000 2/400 270 PULSER

MBE-315/90T 9000 3/400 420 TTC-2000

MBE-355/90T 9000 3/400 420 TTC-2000

MBE-400/120T 12000 3/400 420 TTC-2000

B

A

Ø D

E F

ACOPEL F400Circular flexible connector.