Plug-in and filter Options
ABB industrial drives,
ACS800
Welcome to the ABB industrial drives, ACS800 plug-in and filter options training module.
If you need help navigating this module, please click the Help button in the top right corner. To view the presenter notes as text, please click the Notes button in the bottom right corner.
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
2-
Help
Objectives
After completing this module, you will be able to
� Recognize the plug-in options
� List the functions of plug-in options
� List the filter options
After completing this module, you will be able to
• recognize the plug-in options,
• list the functions of plug-in options, and
• list the filter options.
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
3-
Help
Plug-in options
� Used to provide additional connections between the drive and other devices
– Fieldbus
– Pulse encoder
– Extended I/O
� Software-dependent
Plug-in options are used when additional connections like fieldbus, pulse encoder or extended I/O are needed between the drive and other devices.
The number of the available plug-in options in the ACS800 series is software-dependent.
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
4-
Help
Slot 1 (Upper)– Digital I/O extension (RDIO)
– Analogue I/O extension (RAIO)
– Pulse encoder interface (RTAC)
– Fieldbus interface
Slot 2 (Middle)– Digital I/O extension (RDIO)
– Analogue I/O extension (RAIO)
– Pulse encoder interface (RTAC)
Slot 3 (Lower)– DDCS link (RDCO)
Option Slot Allocation
There are three option slots in the RMIO (motor control and I/O) board. It has two slots for the bigger option modules and one for the RDCO (DDCS channel) module.
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
5-
Help
Mounting
� Two I/O options can be mounted onto a drive
� Snap on to the skeleton covering the RMIO-01 or to the AIMA extension board
Node numbering 0…15 via switch
Board grounding to chassis with locking screws
Terminals for the outside connections
Indication LEDs in the option module
Connection via parallel bus connector to the RMIO or to the AIMA extension board
Two I/O option modules can be mounted onto a drive.
The mounting procedure is the same for all ACS800 drives. The modules are snapped on to the skeleton covering the RMIO-01 or AIMA board.
Each module type has different LED and terminal structures.
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
6-
Help
~=
1 2X11
~=
1 2X12
~=
3 4 X21 1 2 3 X22 1 2 3
DI1 DI2 DI3 RO1 RO2
X10 Address Data RXD/TXD +5V +24V
IOCC-2B ASIC
DI1ON
DI2ON
DI3ON
WD/INIT
NODEADDRESS
0..15
RDIO-01 Block Diagram
Three isolated digital input channels· Divided into two groups: DI1 and DI2 & DI3· 2.5 kV isolation voltage between groups· Each input suitable for AC and DC signals· HW filter time selection via DIP switch for each channel
Two change-over type output relays
Node address selection via rotary switch· Address range: 0..15
Four diagnostic LEDs· 'ON' indication for each input channel· Module status indication
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
7-
Help
1 2X1 3 4 X2
AI1 AI2 AO1
X10 Address Data RXD/TXD +5V +24V
IOCC-2B ASIC
WD/INIT
NODEADDRESS
AD
��������
��� ���
1 25 6
SHLD
RC
5 6
SHLD
RC
AO2
AD
3 4
==
==
� ��� ����
� ��� ����
+24V
AD
0..15
RAIO-01 Block Diagram
Two isolated analogue input channels· 3-pole DIP switch per input channel for selection of:
-Input signal polarity: Unipolar (12 bit), Bipolar (11 bit)-Input signal range: 0..20mA, 0..10V or 0..2V
· 1.5 kV isolation voltage towards supply and analogue outputs
Two isolated analogue output channels· Output signal range: 0..20mA (12 bit)· 1.5 kV isolation voltage towards supply and analogue inputs
Node address selection via rotary switch· Address range: 0..15
One diagnostic LED for module status indication
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
8-
Help
1 2X2 3 4
CH A CH B
X10 Address Data RXD/TXD +5V +24V
IOCC-2B ASIC
CHAON
CHBON
WD/INIT
NODEADDRESS
16..31
5 6
CH Z
==
1 2 3 4 5 6X1
RC
+24V
+15V
+VO
UT
-VO
UT
SH
LD
EX
T
RTAC-01 Block Diagram
Three isolated differential input channels· Two input channels with 90°phase shift · One zero pulse input channel
Encoder interface· Supporting differential and single-ended connection-push-pull, open collector, open emitter· Supply for 24VDC and 15VDC encoders
Node address selection via rotary switch· Address range: 16..31
Three diagnostic LEDs· 'ON' indication for input channel A and B· Module status indication
Maximum Encoder Cable Lenghts· Differential push-pull: 300m· Single-ended push-pull: 200m· Open collector/emitter: 100m
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
9-
Help
X10 Address Data RXD/TXD +5V
DPRAM
==
1 2 nX1
RC+5V
CONFIG.
IND.
MCU
FBUS CTRL
RAM
FLASH
FIELDBUS CONNECTOR
Fieldbus Block Diagram
A different type of fieldbus module is used for different fieldbus systems.
The connection principle and data transfer protocol between the drive and fieldbus module is the same for each fieldbus system.
Fieldbus types:- DeviceNet- Lonworks- Interbus-S- Profibus DB- CanOpen- Modbus- ModbusPlus- Ethernet- ControlNet
�
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
10-
Help
Channel 0 for Fieldbus adapters
RDCO channels
Channel 1 for NDIO, NAIO, NTAC
Channel 2 for NTAC/ Master Follower
Channel 3 for PC Tools
Four fiber optic channels
Four fiber optic DDCS link channels are available in the optional RDCO module providing interfaces for PC tools, pulse encoders, master/followers, and I/O and Fieldbus adapters.
The N-type options which in ACS600 used, require in the ACS 800 the option board RDCO which is connected to the Slot 3.The RDCO option boards is fully compatible with the previous generation option modules: NDIO, NAIO, NTAC, NPBA, NMBA....
Three module versions are available RDCO-01, RDCO-02, RDCO-03.
���
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
11-
Help
AIMA-01 I/O module adapter� For connecting I/O extension modules
– 3 slots for RDIO, RAIO and RTAC
– Connected to I/O channel CH1 of RMIO
When more than the two standard option slots are needed for an application, the AIMA-01 I/O module adapter can be used as an extension unit.
It includes three I/O slots for digital and analogue I/O extension modules (RDIO, RAIO) and pulse encoders (RTAC). The AIMA is connected to channel 1 (CH1) of the RMIO board.
��
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
12-
Help
I/O Extension with AIMA
AIMA
RD
IOR
DIO
RAIO
CH1
Here is an example of connecting an AIMA module to the ACS800.
��
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
13-
Help
NDIO-02
TXD
DI GITAL I /O
X2R2CMR2NO R1NC R1CMR1NOR2NC
RXD
X1DI1BDI1A DI2A DI 2B +24V 0V
EXTENSION
12345678
1 2 3 4 5 6 7 8
X2
X1
NDIO-02
TXD
DI GITAL I /O
X2R2CMR2NO R1NC R1CMR1NOR2NC
RXD
X1DI1BDI1A DI2 A DI 2B +24V 0V
EXTENSIO N
12345678
1 2 3 4 5 6 7 8
X2
X1
I/O Extension with N-type modules
Here is an example of I/O extension connections with ACS600 option modules. This solution can be used when an ACS600 is replaced with an ACS800.
��
©C
opyr
ight
12/
28/2
010
AB
B.
All
right
s re
serv
ed. -
14-
Help
EMC
du/dt
SineACS800
ACS800InternalRFI-Boards
Linefilter
ACS800-01ACS800-02/ACS800-07
Commonmode
InternalRFI-Boards
Cabinet
du/dt filters are not needed if a sine filter is used
ACS800-02/ACS800-07
Filters
EMC
Four different filter types are used with the ACS800: EMC, du/dt, Common mode and Sine filters.
� �
Thank you for your attention. You may now go ahead and move on to the next unit.