Woodward 1724 Electrically Powered Governor Systems FEATURES 24V operation Isochronous control (8290 speed control) Accepts load sharing accessories No mechanical drive Gain and stability adjustments tailored to engine characteristics EPG CONTROL SPECIFICATIONS 24 Volt Control 24 Vdc (20 Vdc minimum to 32 Vdc maximum) 95 watts maximum power consumption. A battery charger must be capable of at least five amps when the governor is energized. Stability and Gain These adjustments set the speed control’s response to match the individual prime mover characteristics. Slow and fast response settings are provided with the dual-dynamics controller. Rated Speed A 25-turn internal potentiometer sets rated speed. A factory-installed external potentiometer allows ± 5% adjustment of rated speed. Idle Speed Factory set at 100% of rated. An optional 50 Kpotentiometer can be connected to set the idle speed between 25 percent and 100 percent of rated. Steady State Speed Band The control typically maintains ±1/4 of one percent of rated speed. Ambient Temperature Range -40° C to 75° C (-40° F to 167° F) Construction The control box is constructed of cast aluminum and weighs about 1 pound (0.5 kg).* * The 1724 actuator weighs about 16.8 pounds (7.6 kg). ACTUATOR SPECIFICATIONS Output Shaft 0.375”-36 SAE serrated shaft on each end Ambient Temperature Range -40° C to 93° C (-40° F to 200° F) Construction Aluminum and steel parts. All internal parts treated for corrosion resistance. Not painted. Work Output Maximum work capacity over full governor travel of 35° is 1.7 ft-lbs. Internal return springs provide operating force in the decrease-fuel direction. Additional external spring must not be used. Full Governor Travel Full Prime Mover Travel No Load Full Load Prime Mover Stop Prime Mover Stop A D B C A 0 100% A – Overtravel to ensure prime mover stops are reached B – No-Load to Full-Load travel – normally 2/3 of full governor travel is recommended C – Travel required to accelerate the prime mover D – Travel required to decelerate or shut down prime mover

Upload: alexander-colmenares-rincon

Post on 16-Nov-2015

19 views

Category:

Documents


9 download

DESCRIPTION

actuador

TRANSCRIPT

  • Woodward 1724Electrically PoweredGovernor Systems

    FEATURESn 24V operation

    n Isochronous control (8290 speed control)

    n Accepts load sharing accessories

    n No mechanical drive

    n Gain and stability adjustments tailoredto engine characteristics

    EPG CONTROL SPECIFICATIONS

    24 Volt Control24 Vdc (20 Vdc minimum to 32 Vdc maximum) 95 watts maximum power consumption. Abattery charger must be capable of at least fiveamps when the governor is energized.

    Stability and GainThese adjustments set the speed controlsresponse to match the individual prime movercharacteristics. Slow and fast response settingsare provided with the dual-dynamics controller.

    Rated SpeedA 25-turn internal potentiometer sets ratedspeed. A factory-installed external potentiometerallows 5% adjustment of rated speed.

    Idle SpeedFactory set at 100% of rated. An optional 50 Kpotentiometer can be connected to set the idlespeed between 25 percent and 100 percent ofrated.

    Steady State Speed BandThe control typically maintains 1/4 of onepercent of rated speed.

    Ambient Temperature Range-40 C to 75 C (-40 F to 167 F)

    ConstructionThe control box is constructed of cast aluminumand weighs about 1 pound (0.5 kg).*

    * The 1724 actuator weighs about 16.8 pounds (7.6 kg).

    ACTUATOR SPECIFICATIONS

    Output Shaft0.375-36 SAE serrated shaft on each end

    Ambient Temperature Range-40 C to 93 C (-40 F to 200 F)

    ConstructionAluminum and steel parts. All internal partstreated for corrosion resistance. Not painted.

    Work OutputMaximum work capacity over full governortravel of 35 is 1.7 ft-lbs. Internal return springsprovide operating force in the decrease-fueldirection. Additional external spring must notbe used.

    FullGovernor Travel

    Full PrimeMover Travel

    NoLoad

    Full Load

    PrimeMover Stop

    Prime MoverStop

    AD B C

    A

    0 100%

    A Overtravel to ensure prime mover stops are reached

    B No-Load to Full-Load travel normally 2/3 of full governor travel is recommended

    C Travel required to accelerate the prime mover

    D Travel required to decelerate or shut down prime mover

  • WIRING DIAGRAM FOR8290 SPEED CONTROL

    1724 WOODWARD EPG SYSTEMS

    Shielded wires to be twisted pairs or twisted 3 conductor.Grounded at one end only.

    No. 12 AWG or 14 AWG stranded wire. Must be as short as possible. (See max. length in chart.)

    See text for voltage.

    Open for minimum fuel.

    For positive ground systems, switch and fuse to be located in series with battery () and terminal 2. Positive terminal becomes chassis ground. Leads from battery to terminals 1 and 2 must be direct and not pass through distribution points.Use 10 A fuse and switch.

    Approximate speed change with trim potentiometer: 2.5% using a 1k ohm potentiometer 5.0% using a 2k ohm potentiometer

    Approximately one second ramp time per 50 UF.Capacitor specification: 200 UF maximum. 15 WVDC minimum. Less than 30 UA DC leakage current over temperature range.

    Idle range approximately 25% to 100% of rated using 50kpotentiometer. For fixed idle speed, calculate the value of the resistor:

    R = 17 Kohm

    Jumper if idle speed is not used.

    Use a 10 amp fuse (3 AG or GBB type)

    Polarity not important

    Connections to load sensor when used in load sharing application

    1

    2

    3

    4

    5

    6

    7

    9

    10

    11

    8

    rated speedidle speed -1 )(

    EPGSpeed ControlAccel/Decel Ramp

    Capacitor (Optional) 7

    1 2 3 4 5 6 7 8 9 10 11 122

    3

    4

    10

    5

    2

    5 9

    6

    8

    1

    Magnetic Pickup

    Co

    m

    Auxiliary Input

    (Jumper If Not Used)

    Speed Trim Jumper If Not Used

    IdleOpenRatedClosed

    EPGActuator

    Battery

    +

    CW

    Optional

    IdleOpenRatedClosed

    SpeedTrim orJumper

    Magnetic Pickup

    Actuator24VBattery

    AuxInput

    ++ 1 2 3 4 5 6 7 8 9 10 11 12

    StartFuel Limit

    Gain Stability RatedSpeed

    EPG Speed Control

    82431091618 GA

    11

    Output Shaft.375 36 (inch) Serr.(See note)

    DIMENSIONAL DRAWINGS

    146.0(5.75)

    114.0(4.49)

    64.4 (2.54)63.6 (2.50)

    125.0(4.92)

    119.5 (4.7)116.5 (4.59)

    .250 20 (inch) thd. minimum mountingscrew thread engagement should be 9.5 mm (.37 in).Torque screws to 9 11.3 Nm (80 100 lb-in).

    Note:Nominal 35 output shaft rotationUse as much of 35 as possible not less than 21.Make sure fuel control provides min. and max. fuelflow requirements.

    82300A49

    #8 32 (inch) Binding Head ScrewTerminal (2)

    Materials and specifications are subject to change without notice. The International System of Units (SI) is used in this publication.

    LEHX7048 1997 Caterpillar Inc. Printed in U.S.A.All rights reserved.

    Additional information reference: SENR6430-01,Service manual, 524 & 1724 Electrically PoweredGovernor Systems.