2810 Duniven Circle Amarillo, Texas 806/358-7069 ADDENDUM NO. FOUR DATE: December 17, 2019 FROM: Lavin Architects TO: Plan Holders of Record PROJECT: Toot’ N Totum 7909 E. I-40 Amarillo, Texas 79118 This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated November 27, 2019. Work not specifically deleted, modified, changed or altered by the Addendum should remain in effect as part of the Contract Documents. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject Bidder to disqualification. ON THE DRAWINGS: Sheet C3.3 1. Clarification of “Cat Scale” scope of work. Coordinate with Cat Scale installers to verify scope of work. For bidding purposes use civil points “Scale 4057”, “Scale 4058”, “Scale 4059”, and “Scale 4060” on sheet C3.3 as your construction limits. Sheet C5.1 See attached sheet C5.1 for revised details. Sheet C7.1 See attached sheet C7.1 for revised details Sheet A1.2 1. Provide alternate price to demolish the existing chain link fence at west and north side of trucker parking and provide new fence as per note 37. 2. The dog park, playground, curbing, turf, fall protection, fence, etc. will be by owner. GC scope to be concrete sidewalks, patio concrete, and installing the owner furnished outdoor furniture. 3. Provide additional concrete sidewalk from existing accessible ramp to new sidewalk. Sidewalk to have no greater slope than 5% in direction of travel and no cross slope greater than 2%. See attached drawing. 4. Delete 12” x 12” drains at the diesel canopy (note 38). Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior Elevation 15/A6.2. 2. Add “Door buzzer on exterior doors with an on/off switch located at Cashier 102 and Trucker Cashier 124. Verify with owner exact location of the switches” Sheet A2.2 1. See attached floor plan for raised platform at Cashier 102. 2. Equipment Schedule #74 change to Bobrick B-169-2436. See A6.2-R & electrical addendum #4 for quantities. 3. Equipment Schedule #75 change to Bobrick B-169-3040. See A6.2-R & electrical addendum #4 for quantities. Sheet A2.4 1. Wall Schedule Clarification. All interior walls (stud, gyp. bd., insulation) to deck. At exposed areas all walls to be scribed inside of flutes at deck.

Upload: others

Post on 28-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior

2810 Duniven Circle Amarillo, Texas 806/358-7069

ADDENDUM NO. FOUR

DATE: December 17, 2019 FROM: Lavin Architects TO: Plan Holders of Record PROJECT: Toot’ N Totum

7909 E. I-40 Amarillo, Texas 79118

This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents dated November 27, 2019. Work not specifically deleted, modified, changed or altered by the Addendum should remain in effect as part of the Contract Documents. Acknowledge receipt of this Addendum in the space provided on the Bid Form. Failure to do so may subject Bidder to disqualification. ON THE DRAWINGS: Sheet C3.3 1. Clarification of “Cat Scale” scope of work. Coordinate with Cat Scale installers to verify scope of

work. For bidding purposes use civil points “Scale 4057”, “Scale 4058”, “Scale 4059”, and “Scale 4060” on sheet C3.3 as your construction limits.

Sheet C5.1 See attached sheet C5.1 for revised details. Sheet C7.1 See attached sheet C7.1 for revised details Sheet A1.2 1. Provide alternate price to demolish the existing chain link fence at west and north side of trucker

parking and provide new fence as per note 37. 2. The dog park, playground, curbing, turf, fall protection, fence, etc. will be by owner. GC scope to

be concrete sidewalks, patio concrete, and installing the owner furnished outdoor furniture. 3. Provide additional concrete sidewalk from existing accessible ramp to new sidewalk. Sidewalk to

have no greater slope than 5% in direction of travel and no cross slope greater than 2%. See attached drawing.

4. Delete 12” x 12” drains at the diesel canopy (note 38). Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior Elevation 15/A6.2. 2. Add “Door buzzer on exterior doors with an on/off switch located at Cashier 102 and Trucker

Cashier 124. Verify with owner exact location of the switches” Sheet A2.2 1. See attached floor plan for raised platform at Cashier 102. 2. Equipment Schedule #74 change to Bobrick B-169-2436. See A6.2-R & electrical addendum #4 for

quantities. 3. Equipment Schedule #75 change to Bobrick B-169-3040. See A6.2-R & electrical addendum #4 for

quantities. Sheet A2.4 1. Wall Schedule Clarification. All interior walls (stud, gyp. bd., insulation) to deck. At exposed areas

all walls to be scribed inside of flutes at deck.

Page 2: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior

2810 Duniven Circle Amarillo, Texas 806/358-7069

ADDENDUM NO. FOUR

Sheet A2.5 1. Omit Room Finish Schedule Notes 3 & 7 where “Silikal” is to be provided. Sheet A3.1 1. Spandrel panel to be bronze to match the glazing. 2. Doors 127C, 128C, 138D, 145A & 145H to be 3’-0” wide in lieu of 2’-10” wide to meet TAS & ADA. Sheet A4.1 1. Exterior elevations to be “Scale 1/8” = 1’-0” in lieu of 1/4” = 1’-0”. Sheet A5.1 1. Delete note that states “Smooth form finish at exterior grade beam 12” below brick pocket”.

Grade Beams can be Earth formed. Sheet A6.2 1. See attached reissued sheet for revised restroom layout & interior elevations. Sheet A6.4 1. Ensure the faucet lever is within 17” of the face of counter for detail 15/A6.4 to meet TAS & ADA. Sheet A8.1 1. See attached reissued sheet with revised lighting layouts in restrooms. Sheet S5.04 1. See attached revised detail #4 Civil 1. See attached sheet. Structural 1. See attached sheet. Mechanical 1. See attached sheet. Electrical 1. See attached sheet. END OF ADDENDUM NO. 1

Page 3: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior
Page 4: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior
Page 5: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior
Page 6: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior
Page 7: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior
Page 8: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior

T.O.S. EL.-SEE ARCH'L

B.O.S. EL.-SEE PLAN

T.O.S. EL.-SEE PLAN

JOIST UPLIFTBRIDGING ASREQ'D. BY JOISTSUPPLIER

MASONRY,EIFS OR MTL. PANEL -SEE ARCH'L

L3x3x1/4 CONT.

C.F.S. STUD W/ DEFLECTION TRACK @ TOP (NOT BY JQ)

STL. BEAM -SEE PLAN

STL. JOIST -SEE PLAN

HSS3x3x3/16 @ 32" O.C.

1'-6

"2'-2

1/2

"

PL. 1/4"x12" CONT. W/ 3/4"Ø HOLES @ 32" O.C.

SE

E P

LA

N

SEE ARCH'L

AWNING BY OTHERS-SEE ARCH'L

STL. ROOF DECK -SEE STRUCTL. NOTES

HSS3x3x1/4 AT EA VERT. W/ 1/2" CAP PLATE. 5/8"Ø THREADED STUD TO SHOP WELD TO CAP PLATE

TYP.

TYP.

SEE FOR ATTACHMENT AT ENDS TO COLUMN

14/S5.02

FOR ADDN'L INFO.SEE 7/S5.03

4

4

JQ ENGINEERING, LLP1204 BROADWAY, SUITE 204806.392.9180

LUBBOCK, TEXAS 79401

TBPE FIRM F-1294

JQENG.COM

PROJECT NO:

REF.

CLIENT

PROJECT

REV. DATE SHEET

shaping the built environment

BRIAN J. ROBERTSON

108844

12/17/2019

Toot 'N Totum, 7909 E. I-40, Amarillo, TX

Lavin Associates, Inc.

12/17/19 SSK-01ADDENDUM #4S5.043190114

SCALE: 3/4" = 1'-0"4 SECTION AT CANOPY

Page 9: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior

Page 1 of 1

Brown Consulting Engineers, Inc.

3505 Olsen • Suite 110 (806) 354-0141

Amarillo, Texas 79109 Fax: (806) 354-0142

December 16, 2019 BCE, Inc. Project #21927

Memo to: Richard Sims, Lavin Associates, Inc.

From: Seth A. McClellan, P.E.

Subject: A New Building for Toot ‘N’ Totum Addendum #4 Please forward the following addendum to the contractor for inclusion in the project.

PLUMBING Item 1: Specification Section 15410: Add the following paragraph:

2.20 COMPRESSED AIR PIPING

A. Steel Pipe: ASTM A53 Schedule 40 black. 1. Fittings: ASME B16.3, malleable iron, or ASTM A234/A234M, forged steel

welding type. 2. Joints: NFPA 54, threaded

2.21 COMPRESSED AIR BALL VALVES

A. Manufacturers: 1. Nibco Model T-585-70-66 2. Milwaukee #BA-400S

B. Construction, 2 inches and smaller: MSS SP-110, Class 150, 600 psi CWP, bronze, two piece body, stainless steel, full port, teflon seats and stuffing box ring, blow-out proof stainless steel stem, lever handle threaded ends.

End of Addendum #4

December 16, 2019 Texas Registered Engineering Firm F-683

Page 10: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior

P. O. Box 3800

121 S. Bonham

Amarillo, TX 79116

806.372.2904

fax 806.371.0424

[email protected]

Daniel McCracken, P.E. Michael Ferry, Electrical Designer

Ryan Miller

Lavin Architects

Amarillo, Tx

12/17/2019

Re: Toot-N-Totum Lakeside Electrical Addendum #4

Dear Ryan;

Please note the following electrical items for Toot-N-Totum Lakeside Electrical Addendum #4:

1. Add power and sleeves for a CAT Scale. See the attached SK1.

2. Change the 2x2 troffers in certain restrooms to recessed downlights

and add combination Type M1 and M2 mirror lights over the

vanities where shown. See the attached SK1. The Type M1 mirror

lights are Bobrick B169-2436 mirrors. Type M2 Mirror Lights are

Bobrick B169-3040. Connect the Type M1 and M2 lights to the rest

of the lighting in the room.

3. Pole base detail on Sheet E-0.0. The rod ties shall be every 12” the

entire height of the pole base.

4. Install flush single gang junction boxes at every exterior camera

location. Heights of cameras will vary based on the locations.

Cameras for drive up locations will be 4 feet. Verify all heights. Stub a ¾” conduit to accessible

ceiling.

5. For cameras in door mullions, feed down the mullion with Cat 5e cable to a height of 5’ and

penetrate the mullion with the cable.

6. Sheet E-2.0 – Keyed Note 25 – Add a 2” conduit in the floor from the TV rack to the IT room.

7. Add Item 49 to the C-Store Equipment Schedule for Cameras.

Sincerely,

Spectrum Engineering

Page 11: ADDENDUM NO. FOUR · 2019-12-17 · Sheet A1.3 1. Refer to detail 6/A1.3 for sidewalks. Sheet A2.1 1. Interior Elevations for Corridor 139 & Corridor 143 to be similar to Interior

CAT

PICK-U

PW

IND

OW

KEEP CLEAR

KEEP CLEAR

JJJ

J

JJ

SPSP

SP

SP

SP

SP

SP

SP

M

M

M

M

M

M

MM

M

M M

MM

OS

OS

M M

M M

M

SP

OS

G-37,39

G-38,40

G-41,43

G-42,44

AA29

AA29 AA29

AA28 AA28

HA-6,8

HB-6,8

2-#12, 1-#12 G THE ENTIRE LENGTH OF THE CIRCUIT

2-#8, 1-#10 G

2-#8, 1-#10 G

2-#8, 1-#10 G

2-#8, 1-#10 G

DRIVE UP SIGN

8

8

23

24

11

G2-5,7 G2-6,82-#8, 1-#10 G2-#8, 1-#10 G

15

3

14

26

26 26 26 26 26 26 26 26 26 26

2626

27

27 27

27

27

26

TWO 1-1/2" C EMPTY, ONE 1" CONDUIT WITH 9-#10, ONE-1" CONDUIT WITH 7-#10 FROM PANEL LA2 TO THE CAT SCALE. SEE KEYED NOTE 28

TWO 1-1/2" EMPTY FROM FUEL DESK TO CAT SCALE

11

28

28

28

1

28. POWER AND SLEEVES FOR CAT SCALES. INSTALL TWO 1-1/2" CONDUITS FROM THE FUEL DESK AND TWO 1-1/2" CONDUITS FROM PANEL LA2 FOR CAT SCALE INSTALLER LOW VOLTAGE CONDUITS. INSTALL 8-#10 STRANDED, 1-#10 STRANDED GROUND IN 1" CONDUIT FROM FOUR 20/1 CIRCUIT BREAKERS (USED FROM THE SPARES) IN PANEL LA2 FOR SCALE POWER. FEED THE FUEL DESK EQUIPMENT WITH 3-#10 FROM A CIRCUIT BREAKER IN PANEL LA. INSTALL 6-#10, 1-#10 GROUND IN ANOTHER 1" FOR THE SIGN, INTERCOM, AND CAMERA LOCATED AT THE SCALE.

SITE PLAN KEYED NOTES ADDENDUM 4

KL8 KL8

KL8KL8

KL8 KL8

KL1

KL1

KL1EM

KL1EM

KL1

KL1

KL1

KL1

KL1

KL8 KL8

KL8

KL8

KL8

KL1 KL1

KL1

AL30

AL30EM

AL30

AL30EM

AL30

AL30EMAL30EM

AL30

AL30

AL30

AL30

KL1

KL1KL1KL1

KL1

KL1

KL1

KL1

KL1

KL1

KL1

KL1

KL1

KL1EM KL1KL1

KL1 KL1

KL1 KL1

KL1EMKL1KL1

LA-36

KL1 KL1 KL1

KL1

1313

13

13

KL1

KL1

KL1

KL1 KL1

KL1 KL1

KL1

KL1

KL1KL1

1

1

M1

M1

M1

M1

M1 M1 M1

M2

KL1

KL1

KL1

KL1

KL1 KL1

KL1

KL1

KL1 KL1KL1

13

13

KL1

KL1

KL1

KL1 KL1

KL1

KL1

KL1

KL1

KL1 KL1

KL1 KL1

1

M2

M1 M1 M1

KL1

O

N

DANIEL G. McCRACKEN

52857EO R

O

G

I

I

F

SE

S

S T A

RP

T E

EDE NIRE

L E N GS T

A

E

TF

SAE X

R

121 South BonhamAmarillo, TX 79106Phone: 806.372.2904Fax: 806.371.0424

Email: [email protected]

SPECTRUM ENGINEERING

Scale

Project numberDateDrawn byChecked by

EXPIRES 12/31/2019THE SEAL APPEARING ON THIS

DOCUMENTWAS AUTHORIZED BY

DANIEL G. MCCRACKEN P.E. ON 12/16/2019

REVISION 1 - 12/16/20191

As indicated

12/1

7/20

19 9

:14:

50 A

M

SK-1ADDENDUM 4

2013-24TOOT-N-TOTUM

Addendum 412/16/2019AuthorChecker

1" = 40'-0"1 Site Plan Addendum 4

1/8" = 1'-0"3 Addendum 4 Lighting N

1/8" = 1'-0"4 Addendum 4 Lighting S