administrative bulletin draft outline · web view... where applicable. the test method shall be in...

32

Click here to load reader

Upload: lyngoc

Post on 14-Jul-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

DRAFT-16, R1, by JC

ADMINISTRATIVE BULLETIN

NO. AB-047 :

DATE :

SUBJECT : Fire and Life Safety

TITLE : Smoke Control Systems: Minimum Requirements for Design, Submittals, Special Inspection and Final Acceptance Testing

PURPOSE : This Administrative Bulletin outlines the minimum requirements for design, submittals, inspection and testing of smoke control systems in the City and County of San Francisco. This Administrative Bulletin applies to new smoke control systems as well as changes to existing systems. It does not apply to periodic operational testing of accepted smoke control systems. DBI format requires Purpose and Discussion as shown. Consider relocating this to Discussion below and adding Purpose language here.

REFERENCES : 2007 California Building Code- Section 909, Smoke Control Systems- Section 1704.1, Special Inspections, General- Section 1704.14, Special inspection for smoke control

2007 San Francisco Building Code- Section 106A.3.4, Architect or engineer of record- Section 106A.3.5, Inspection and observation program

DBI Administrative Bulletins- AB-005, Procedures for approval of Local Equivalencies- AB-028, Pre-application and Pre-addendum Plan Review Procedures

SFFD Administrative Bulletins- 2.01, Fire Alarm Submittals- 2.04, Fire Sprinkler submittals

DISCUSSION : later

6/22/2009 Page 1

Page 2: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

TABLE OF CONTENTS

1.0 GENERAL

2.0 QUALIFICATIONS

3.0 RESPONSIBILITIES

4.0 DESIGN FUNDAMENTALS

5.0 NEW SMOKE CONTROL SYSTEMS

6.0 DESIGN CHANGES TO EXISTING SMOKE CONTROL SYSTEMS

7.0 SPECIAL INSPECTION AND TESTING OF SMOKE CONTROL SYSTEMS

8.0 SPECIAL INSPECTION AND TESTING REQUIREMENTS

9.0 REFERENCE PUBLICATIONS

10.0 ATTACHMENTS

1.0 GENERAL

1.1 Definitions. See latest editions of the CBC, CFC, NFPA 92A and NFPA 92B.

1.2 Methods of Smoke Control. See CBC/CFC Section 902 and referenced publications.

1.3 Alternate Methods of Smoke Control1.3.1 Equivalent/Alternate methods shall be pre-approved by DBI/SFFD. Examples of alternate

methods include natural ventilation (not applicable to smokeproof enclosures) and garage CO exhaust systems. Additional justification and analyses, including documentation and calculations, are required to show the alternate method provides equivalent life-safety to prescribed methods.

2.0 QUALIFICATIONS

2.1 Smoke Control System Designers2.1.1 The architect-of-record and engineers-of-record shall be licensed in the State of California.

2.1.2 If a smoke control consultant is engaged, this person shall be experienced in smoke control system design and shall be a fire protection engineer or mechanical engineer licensed in the State of California.

2.1.3 Where peer review is required by DBI/SFFD, the reviewer shall be approved by DBI/SFFD.

2.2 Special Inspection Agency2.2.1 The special inspector shall be a qualified person who shall demonstrate competence, to the

satisfaction of DBI and SFFD, for inspection and testing of the smoke control systems [CBC 1704.14.1].

6/22/2009 Page 2

Page 3: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

2.2.2 Special inspection agencies for smoke control shall have expertise in fire protection engineering, mechanical engineering and certification as air balancers [CBC/CFC 909.18.8.2].

2.2.3 Testing agencies that measure HVAC performance (TAB agencies) shall be certified by the Associated Air Balance Council (AABC) or the National Environmental Balancing Bureau (NEBB).

2.2.4 Testing agencies that measure smoke barrier leakage by door fan systems shall be certified by the testing equipment manufacturer.

3.0 RESPONSIBILITIES

3.1 Project Owner or Owner’s Representative3.1.1 Contract project design professionals.

3.1.2 Contract the smoke control consultant. Previously Smoke Control Report author. Recommend renaming to use consistent terminology throughout.

3.1.3 Contract peer reviewer, where required by DBI/SFFD.

3.1.4 Contract Special Inspection Agency for smoke control (Special Inspector and testing agencies).

3.1.5 Coordinate document submittals including:~.1 Requests for alternate materials and methods.~.2 Preliminary Smoke Control Report.~.3 Final Smoke Control Report, including amendments.~.4 Special Inspection Program.~.5 Special Inspection and Testing Final Report.

3.1.6 Coordinate plan submittals including:~.1 Site plan.~.2 Architectural plans, including smoke barrier plans.~.3 Mechanical, electrical, and plumbing plans.~.4 Fire alarm shop drawings, including Control Diagrams and smoke control panel layout.~.5 Fire sprinkler shop drawings.

3.1.7 Maintain copies of the approved Smoke Control Report, Special Inspection Program, and Special Inspection and Testing Final Report at an approved location in the building.

3.2 Design Professionals3.2.1 Architect-of-Record

~.1 Architectural design in accordance with code requirements and the Smoke Control Report.~.2 Review plans by others to verify the smoke control system design is coordinated.~.3 Stamp, sign and date the Smoke Control Report, Special Inspection Program and Special

Inspection and Testing Final Report when satisfied that the design intent has been achieved.

3.2.2 Engineers-of-Record~.1 Mechanical and electrical design in accordance with code requirements and the Smoke

Control Report.~.2 Review plans by others including deferred submittals to verify the smoke control system

design is coordinated.

6/22/2009 Page 3

Page 4: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

~.3 Stamp, sign and date the Smoke Control Report, Special Inspection Program and Special Inspection and Testing Final Report when satisfied that the design intent has been achieved.

3.3 Smoke Control Consultant3.3.1 Establish the smoke control system design basis.

3.3.2 Prepare the Preliminary Smoke Control Report in accordance with the architectural concept.

3.3.3 Prepare the Final Smoke Control Report, including amendments.

3.3.4 Establish the pass/fail criteria for smoke control system testing.

3.3.5 Prepare the Special Inspection Program.

3.3.4 Communicate with the peer reviewer (where applicable), DBI, and SFFD throughout the design phase.

3.4 Contractor3.4.1 Provide access to ductwork, piping, wiring, etc., prior to concealment for special inspection.

3.4.2 Identify and mark all smoke control components.

3.4.3 Pre-test all equipment and systems prior to testing by the Special Inspection Agency.

3.5 Special Inspection Agency Reorganized to be consistent with code requirement for Special Inspection Agency

3.5.1 Special Inspector~.1 Prepare the Special Inspection and Testing Final Report.~.2 Inspect and document all architectural features affecting smoke control design.~.3 Witness testing and document all elements of the smoke control system.~.4 Submit Letter of Completion to the Designers-of-Record.

3.5.2 Testing Agencies~.1 Perform all required testing with properly calibrated instruments.~.2 Document all testing and provide results to the Special Inspector.

3.7 Department of Building Inspection3.7.1 Review plans and submittals.

3.7.2 Mandate peer review (in conjunction with SFFD) where deemed necessary.

3.7.3 Perform field inspections.

3.7.4 Review the Special Inspection and Testing Final Report.

3.7.5 Provide Certificate of Final Completion when work is complete.

3.7.6 Custodian of records (microfilm).

3.8 Fire Department3.8.1 Review plans and submittals.

6/22/2009 Page 4

Page 5: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

3.8.2 Mandate peer review (in conjunction with DBI) where deemed necessary.

3.8.3 Approve the Preliminary and Final Smoke Control Reports

3.8.4 Approve the Special Inspection Program.

3.8.5 Authorize fabrication of the Firefighters’ Smoke Control Panel after review and approval.

3.8.6 Perform field inspections.

3.8.7 Communicate deficiencies and required corrections with Plan Check, field inspectors, design professionals and Special Inspector.

3.8.8 Approve the Special Inspection and Testing Final Report.

3.8.9 Witness final acceptance testing.

3.8.10 Provide approval documentation when work is complete.

4.0 DESIGN FUNDAMENTALS

4.1 Pressurization Method4.1.1 Typically used in high-rise buildings to contain and manage the smoke from fires. Added to be

consistent with sections below

4.1.2 Pressurization calculations shall be based on prescribed leakage area ratios [CBC/CFC 909.5]. Leakage area ratios per the architectural specifications may be used on a case-by-case basis where more restrictive and approved by SFFD. Edited

4.1.3 The minimum pressure difference across a smoke barrier in fully sprinklered buildings shall be 0.05-inch water gauge [CBC/CFC 909.6.1]. The minimum pressure difference across a smoke barrier in buildings that are not fully sprinklered shall be at least two times the maximum calculated pressure difference produced by the design fire [CBC/CFC 909.6.1]. Edited

4.1.4 The maximum air pressure difference across a smoke barrier shall be determined by required door-opening or closing forces [CBC/CFC 909.6.2]. The calculated force to set a side-hinged, swinging door in motion shall be determined by CBC/CFC Equation 9-1. These hand calculations may be required for selected doors to verify computer calculations. Relocated and edited – was part of 4.1.5 below

4.1.5 All buildings shall be analyzed using a network model that is valid for the application, e.g. CONTAM. State all variables used/required in the calculations and where additional modifiers are available and used in the calculations, e.g., wind tunnel data. Edited

4.1.6 Base calculations input data on 1 percent wind speeds and dry bulb temperatures of 99.6 and 0.4 percent (in accordance with 2006 NFPA 92A A4.8 and based on Klote & Mike’s Principals of Smoke Management, 2002 edition equation 5.37.) Include prevailing winds, summer and winter, and all other wind directions considered critical to demonstrate wind effects. Current wind data shall be obtained from a nationally recognized authority, e.g. ASHRAE, and included in the report. Use of site specific wind data is recommended. Not reviewed

4.1.7 For verification of commissioning and testing data provide design calculations for the temperature(s) and wind condition(s) experienced during the testing. Recommend deleting. Not required by code. Would this be in the Special Inspection and Testing Final Report?

6/22/2009 Page 5

Page 6: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

4.1.8 All exterior openings and non-smoke management fans in smoke control zones and sub-zones that are operable in smoke control mode shall be included in the analysis in their normal position, e.g., windows, doors, scavenger fans, z-ducts and vents.

4.1.9 Buildings with operable windows and/or doors the analyses shall performed with all openings that are fixed in open position and expected to be opened. Needs editing. Should this be the same as 4.2.4 or 4.3.4 below?

4.2 Airflow Method4.2.1 Typically used in tunnels or spaces connected to large volume spaces to manage the flow of

smoke from fires.

4.2.2 Where the space geometry is a simple (no obstructions, simple air supply, symmetrical construction), the analysis may be based on NFPA 92B algebraic calculations. Edited

4.2.3 Where the space geometry is not simple (obstructions, multiple air supplies, asymmetric construction) or where tenability is used as design criteria, CFD analysis is required. Edited

4.2.4 All openings in smoke control zones that are operable shall be included in the analysis, e.g. windows, doors, and vents. Separate design scenarios for each zone with open and closed openings shall be included.

4.3 Exhaust Method4.3.1 Typically used atriums to exhaust the smoke from fires.

4.3.2 Where the space geometry is a simple (no obstructions, simple air supply, symmetrical construction), the analysis may be based on NFPA 92B algebraic calculations. Edited

4.3.3 Where the space geometry is not simple (obstructions, multiple air supplies, asymmetric construction) or where tenability is used as design criteria, CFD analysis is required. Edited

4.3.4 All exterior openings and non-smoke management fans in smoke control zones and sub-zones that are operable in smoke control mode shall be included in the analysis, e.g. windows, doors, scavenger fans and vents.

4.4 Smokeproof Towers4.4.1 Required for all exit enclosures in high-rise buildings and underground buildings

[CBC 1020.1.7]. New – added to be consistent with sections above.

4.4.1 Stairway pressurization systems shall include 2,500 cfm additional airflow per stairway for a barometric relief vent located at the top of the stairway [NFPA 92A 2.3.2.2.2 (a)]; Not required by code or NFPA 92A

4.4.2 If the barometric vent is not provided pressure testing will be performed with the fire-floor stairway entrance, or vestibule, and egress passage way doors open and minimum pressure differentials [NFPA 92A 5.3.4.3.] Not consistent with code or current NFPA 92A

4.4.3 Stairway air-injection points shall be equally distributed with and shall not be located at the top level (adjacent to the barometric relief vent) Not consistent with code or current NFPA 92A

4.4.2 If the stairway is greater than 50-feet in height provide computer analysis. Code reference?

6/22/2009 Page 6

Page 7: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

4.4.3 Stairway pressurization systems shall be dedicated. Code reference?

4.4.4 Transfer grills (used in vestibules) are not acceptable except for pressurization of large stairway transfer passageways. Code reference?

4.5 Natural Ventilation4.5.1 Designs that utilize natural ventilation (not applicable to 909.20.3; Smoke proof enclosures) in

whole or part of the smoke management system will require CFD or physical (scale) model analysis.

4.5.2 The affect of outdoor wind, temperature, design fire size, and the surrounding structures are especially important in the design of natural ventilation smoke control. Multiple design scenarios that reflect a complete range of operating conditions are required to demonstrate the validity of the smoke control systems’ function.

4.5.3 Wind speeds shall range from zero to the 1 percent annual extreme. Include prevailing winds, summer and winter, and a minimum of 4 other wind directions considered critical to demonstrate wind affect at the required wind speeds. Current wind data shall be obtained from a nationally recognized authority, e.g. ASHRAE, and included in the report.

4.5.4 Ambient temperature used in calculations shall range from low to high annual extremes, dry bulb temperatures of 99.6 and 0.4 percent, as reported by the most current data obtained from a nationally recognized authority, e.g. ASHRAE [909.8.]

4.5.5 For verification of commissioning and testing data provide design calculations for the temperature(s) and wind condition(s) experienced during the testing.

4.5.6 All openings in smoke control zones that are operable shall be included in the analysis, e.g. windows, doors, and vents. Separate design scenarios for each zone with open and openings closed shall be included.

4.6 Tenability and Egress Analyses4.6.1 Tenability criteria shall be established based documented studies. Items to be included, but not

limited to, determining tenability criteria are the following: temperature and humidity, visibility (KS=3, light reflecting), toxicity assessment of combustion products and FED.

4.6.2 Egress Analysis~.1 Timed egress analyses shall be based on CBC 909.4.6 (where duration of system is less

than 20-minutes) based on documented methods as provided in the listed references. Agree?

~.2 Calculation of Available Safe Egress Time (ASET) and Required Safe Egress Time (RSET) with a minimum safety factor of two (2).

~.3 ASET and RESET shall be calculated in phases/time segments: ignition-detection, detection-alarm, alarm-perception, perception-interpretation, interpretation-action, action-movement, and tenability limit only for ASET.

~.4 Occupancy loads shall be determined by the CBC or actual occupant load, whichever is greater.

~.5 Consideration shall be made for handicapped and disabled occupants by reduction of travel speeds and flow rates. Yes but without specifics and buy-in from the disabled community, this could be very controversial

6/22/2009 Page 7

Page 8: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

~.6 Duration of the smoke management system operation shall be the code required minimum or the maximum RESET, whichever is greater. Seems to allow relaxation of code based on complicated analysis that rests on arbitrary assumptions

5.0 NEW SMOKE CONTROL SYSTEMS

5.1 General5.1.1 Submit two copies of the Preliminary Smoke Control Report with the site permit drawings (for

site permit projects) or with schematic drawings (for all other projects).

5.1.2 Submit two copies of the Final Smoke Control Report with permit drawings.

5.1.3 Submit two copies of the Special Inspection Program [SFBC 106A.3.5] with permit drawings.

5.1.4 One copy or reviewed reports will be returned to the submitter when approved by DBI/SFFD.

5.1.5 Reports shall be in booklet format, bound (e.g. spiral bind), with 8 ½” x 11” sheets.

5.1.6 Submittals of final reports shall be accompanied by two sets of CD-Rs in slim plastic “jewel cases” with fixed label indicating the permit application number, project name and address, report title, revision number, and date, as well as all included files. Each CD-R shall include a complete copy of the final report in PDF format as well as all supporting material, diagrams, calculations, appendices and data files.

5.1.7 If a report is revised after approval by DBI/SFFD, the revised report shall be resubmitted with all required items from the original submittal as well as the revised plans showing applicable changes.

5.1.8 Construction documents shall include sufficient information and detail to adequately describe the design and properly facilitate installation.

5.2 Smoke Control Report5.2.1 Cover Page. Show the permit application number, project name and address, report title,

revision number, and date as well as the author’s name and company.

5.2.2 Signature Page. Include the completed signature page; see Attachment 1.

5.2.3 Table of Contents. New

5.2.4 Introduction. Renamed and revised~.1 Provide a general description of the building and its uses.~.2 Include the building height, number of stories, basement levels, and gross floor areas.~.3 Identify all members of the design team and include contact information. New~.4 Identify all applicable codes and standards including editions.

5.2.5 Building Features. Renamed~.1 Identify the types of occupancies, type(s) of construction and ratings of fire resistive

elements.~.2 Provide a general description of the exiting plan. New~.3 Identify the architectural features that affect smoke control such as size and geometry of

atriums, location of fire/smoke barriers, fire-safeing, make-up air openings, operable windows and vents, floor and wall openings, door closers, ceiling heights, shafts used as

6/22/2009 Page 8

Page 9: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

ducts, types and heights of surrounding structures/buildings, and location of the Fire Command Center if any.

~.4 Identify the type, location and quantity of flammable/combustible fuels, as well as the locations of hazardous/toxic materials, if any.

~.5 Identify the elevators for firefighters emergency response use.

5.2.6 Mechanical Systems.~.1 Provide a general description of the HVAC and ventilation systems where used for smoke

control.~.2 Include the types of systems and areas served (zoning), design objectives and basic

operation, major equipment, and the types/classes and actuating temperatures of fire/smoke dampers.

~.3 Indicate where fire dampers are provided with increased operating temperature actuating devices (not more than 286OF) due to smoke control [CBC 716.3.1.1].

~.4 Indicate where fire/smoke dampers are not provided at shafts due to smoke control [CBC 716.2.1; 716.5.3, #1.3, #4].

~.5 Indicate where fire/smoke dampers are not provided at shafts due to 22-inch sub-ducts and continuously operating exhaust fans [CBC 716.5.3, #1.1, #2.2, #2.3].

5.2.7 Power Supply Systems.~.1 Provide a general description of the primary and secondary sources of power for the smoke

control systems.~.2 Identify the types of systems (emergency or standby) and equipment served, locations of

major equipment (including the secondary power source, transfer switches, normal power transformers and switchgear), and routing of the normal and standby power distribution systems [CBC 909.11]. Note that secondary power is usually required for scavenger fans.

~.3 Identify the required duration of operation [CBC 909.4.6].~.4 Address the need for uninterruptible power supplies and power surge protectors

[CBC 909.11.1].

5.2.8 Fire Suppression Systems.~.1 Provide a general description of the fire suppression system(s).~.2 Identify the types of systems and areas served (zoning), major equipment, design criteria

and basic operation.

5.2.9 Fire Alarm System and Firefighters’ Smoke Control Panel.~.1 Provide a general description of the fire alarm system and firefighters’ smoke control

panel. If the building management system (BMS) is interconnected with the smoke control/management system, provide an overview narrative of the BMS system.

~.2 Identify the smoke control components that must be monitored for proper operation (supervised end-to-end) and the method of supervision [CBC 909.12].

~.3 Confirm that the fire detection and control systems are UL listed in category UUKL, including the BMS system where used for smoke control [CBC 909.12].

~.4 Damper supervision and control at the Firefighters Control Panel is required for all active-passive zone boundaries, e.g. corridor to residential units, group control and interlocking on fans with dampers is allowed. The minimum acceptable supervision and control required will indicate proper damper operation and fault condition for smoke control operation i.e. open and closed. These dampers shall be included in the UUKL Self-Test and fail-safe in the closed position.

6/22/2009 Page 9

Page 10: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

~.5 Fan supervision and control at the Firefighters Control Panel is required for all fans used in the smoke control system [CBC 909.16.] Supervision and control of additional fans may be required in cases where an alternate/equivalent method is approved, e.g. where garage CO exhaust is utilized for smoke control, and use of supply fans are necessary for adequate smoke exhausting.

5.2.10 Smoke Control Systems.~.1 Provide a general description of the smoke control system(s).~.2 Identify the types of systems, design objectives, zoning, major equipment, basic operation

and activation sequences.~.3 Provide a detailed description of each smoke control zone including the occupancy; fire

suppression and fire alarm systems, including specific design criteria required by the smoke control system; construction type, ratings and leakage values; door and window types, ratings, leakage values, and closing methods; operable and fixed exterior openings; expected fire size/loads, combustible materials; means of egress; method(s) of smoke control; analyses methods, with referenced equations for hand calculations, name and version of software; design scenarios addressed, including specific weather data used for each scenario; summary of results including but not limited to tenability, timed egress, i.e. ASET vs. RESET; sprinkler type and activation times; activation methods.

~.4 For smoke control systems using the passive method, identify the total leakage area for typical smoke barriers [CBC 909.5.1].

~.5 Address the probable temperatures to which fans, dampers and ducts may be exposed in a fire [CBC 909.10].

~.6 Identify smoke zone openings which must be open or closed for proper operation, such as doors, windows, dampers and louvers; identify smoke zone openings that are supervised in the open and/or closed positions.

~.7 For dedicated smoke control systems, identify the system components tested weekly by the automatic self-test feature [CBC 909.12; UL 864, 49.7].

5.2.11 Rational Analysis. New section~.1 Provide a general description of each rational analysis scenario including the design fire.~.2 Identify the analytical methods used. For example, algebraic equations, zone modeling

(CFAST), or CFD modeling (FDS) are often used for atria and other large spaces. Network modeling (CONTAM) is often used for pressurized smoke zones, pressurized stairs and passive smoke zones.

~.3 Address the stack effect, temperature effect of the fire, wind effect, HVAC system effects, climate, and duration of operation [CBC 909.4].

~.4 Address the fuel characteristics (toxicity, particulate yield, and growth rate), fuel spacing and configurations (radiant heat), heat-release assumptions (HRR), and sprinkler effectiveness assumptions [CBC 909.9].

~.5 Address the floor-to-floor variations in building leakage, elevator piston effect, and system activation. For single car elevator shafts, provide calculations to show the smoke control system is not overcome by the piston effect.

~.6 For smoke control systems using the exhaust method, specify the maximum ceiling jet temperatures and time lag expected before sprinkler activation. Provide supporting calculations. Edited

~.7 Justify all assumptions and performance-based approaches.

6/22/2009 Page 10

Page 11: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

5.2.12 Appendices. New section~.1 Include copies of all pre-application agreements and approved alternate means of

protection.~.2 Include reference drawings.~.3 Include Smoke Zone Diagrams; show the location of all active and passive smoke zones.~.4 Include Smoke Control Functional Diagrams; show the input/output operations by zone.~.5 Include calculations where appropriate.

5.3 Special Inspection Program5.3.1 Cover Page. Show the permit application number, project name and address, report title,

revision number, and date as well as the author’s name and company.

5.3.2 Signature Page. Include the completed signature page; see Attachment 1.

5.3.3 Scope. ~.1 Identify portions of the work that require smoke control special inspection and testing.~.2 Establish the pass/fail test criteria for individual components and systems.

5.3.4 Inspections.~.1 Provide an overview of special inspection methods and approach.~.2 Provide samples of special inspection documentation.

5.3.5 Testing.~.1 Provide an overview of testing methods and approach.~.2 Provide samples of testing documentation.~.3 Address leak testing of residential units. Test one unit per floor, or 10% of total units,

whichever is greater.~.4 Address cold/hot smoke visualization testing where required by SFFD. Identify proposed

test methods.

5.4 Architectural Permit Drawings5.4.1 Include the following compliance statement on the architectural drawings cover sheet:

“COMPANY NAME has reviewed these drawings for compliance with the Smoke Control Report. As the author of the Smoke Control Report for this project, it is my professional opinion that these drawings comply with the Smoke Control Report.” Revised

The compliance statement must be signed and wet-stamped by the Smoke Control Report author. Revised

5.4.2 As part of the architectural drawings provide smoke barrier drawings showing the location of all smoke zones: delineate each zone as passive or active and provide a zone designation for each active zone. Additionally, show occupancies of each smoke zone and all openings required e.g. doors required to open for make-up air. The zones and designations used in the architectural drawings shall correspond to zones and designations used in the smoke control report.

5.4.3 Provide sufficient detail in the drawings to support engineering calculations, e.g. leakage values for walls, ceilings, and doors; locations and heights of surrounding buildings; sizes and locations of make-up air openings; and smoke-barrier wall construction details.

6/22/2009 Page 11

Page 12: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

5.5 Mechanical Permit Drawings5.5.1 Include the following compliance statement on the mechanical drawings cover sheet:

“COMPANY NAME has reviewed these drawings for compliance with the Smoke Control Report. As the author of the Smoke Control Report for this project, it is my professional opinion that these drawings comply with the Smoke Control Report.” Revised

The compliance statement must be signed and wet-stamped by the Smoke Control Report author. Revised

5.5.2 Show the location of all smoke zones, including passive smoke zones.

5.5.3 Provide a schematic riser diagram of the smoke control/management systems.

5.5.4 Provide a narrative summary and sequence of operations of the smoke control/management system operation.

5.5.5 Identify the major mechanical components used for smoke control in appropriate schedules. Include fans, drivers, variable frequency drives (VFDs) and their locations, and louver and damper operators. Indicate the minimum service factor for fan motors (1.15) and the minimum number of fan belts for belt-driven fans, and temperature rating of fans and ducts [CBC 909.10.5].

5.5.6 Identify the ducts and shafts used for smoke control in the schematic riser diagrams and plan drawings. Indicate the minimum test pressure for ducts and shafts used for smoke control (1.5 times the maximum design pressure) [CBC 909.10.2]. All shafts shall be sheet metal lined, unless an alternate method is approved [CMC 602].

5.5.7 For smoke control systems with variable frequency drives (VFDs), locate the VFDs outside the smoke zone they serve. Alternatively, protect VFDs within the smoke zone they serve from smoke and heat so they are capable of continued operation after detection of fire for at least 20 minutes or the time set by the required safe exiting time (2.0 times RSET), whichever is greater [CBC 909.4.6]. VFDs shall not serve more than one end device unless listed for smoke control service.

5.5.8 For air-moving systems greater than 2,000 cfm, identify where automatic shutoffs are not provided due to smoke control [CMC 609 #4].

5.5.9 Prerequisites for a mechanical permit issuance: Approved architectural, approved Smoke Control Report, and an approved Special Inspection Program.

5.6 Electrical Permit Drawings5.6.1 Include the following compliance statement on the electrical drawings cover sheet.

“COMPANY NAME has reviewed these drawings for compliance with the Smoke Control Report. As the author of the Smoke Control Report for this project, it is my professional opinion that these drawings comply with the Smoke Control Report.” Revised

The compliance statement must be signed and wet-stamped by the Smoke Control Report author. Revised

5.6.2 Identify the major electrical components used for smoke control, including standby (or emergency) power source, transfer switches, and control system(s).

6/22/2009 Page 12

Page 13: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

5.6.3 Provide load calculations for the standby/emergency power source.

5.6.4 Show the layout of the standby generator room (or other secondary power source). The standby generator and its transfer switches shall be in a separate room from the normal power transformers and switchgear [CBC 909.11, 909.11.1].

5.6.5 Show the routing and fire rating of the normal and standby power distribution systems. The normal and standby power systems shall be routed independently [CBC 909.11].

5.6.6 Show the locations of the fire alarm control panel (FACP), firefighters’ smoke control panel (FSCP) and fire alarm annunciator(s).

5.6.7 Provide a 1-line diagram showing feeder conductor sizes, overcurrent protection sizes, ampacity calculations, and the connected loads on each feeder supplied by the standby (or emergency) power source [CEC 215-5, 310, 700-5, 701-6].

5.6.8 For high-rise buildings, show the layout of the Fire Command Center (Central Control Station). See CBC 403.7, 403.8, and 911, for required equipment and furnishings.

5.6.9 For buildings with passive smoke zones, connect the motor operators for smoke dampers to the building power panel and emergency/standby power – not the tenant space power panels.

5.7 Sprinkler System Permit Drawings5.7.1 Sprinkler system submittals shall be in accordance with SFFD Administrative Bulletin

AB 2.04, Fire Sprinkler Submittals.

5.7.2 Include the following compliance statement on the sprinkler shop drawings cover sheet.

“COMPANY NAME has reviewed these drawings for compliance with the Smoke Control Report. As the author of the Smoke Control Report for this project, it is my professional opinion that these drawings comply with the Smoke Control Report.” Revised

The compliance statement must be signed and wet-stamped by the Smoke Control Report author. Revised

5.7.3 Provide separate sprinkler zones for atriums and non-atrium spaces [CBC 909.12.3].

5.7.4 Provide separate sprinkler zones for malls and tenant spaces [CBC 402.8, 909.12.3]

5.8 Fire Alarm System Permit Drawings5.8.1 Fire alarm submittals shall be in accordance with SFFD Administrative Bulletin AB 2.01, Fire

Alarm Submittals.

5.8.2 Include the following compliance statement on the fire alarm shop drawings cover sheet.

“COMPANY NAME has reviewed these drawings for compliance with the Smoke Control Report. As the author of the Smoke Control Report for this project, it is my professional opinion that these drawings comply with the Smoke Control Report.” Revised

The compliance statement must be signed and wet-stamped by the Smoke Control Report author. Revised

5.8.3 For atriums/atria show the simplified fire alarm/smoke control matrix per the Smoke Control Report.

6/22/2009 Page 13

Page 14: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

5.8.4 Provide a detailed fire alarm/smoke control matrix.~.1 Show every fire alarm/smoke control system input in a column on the left. Include every

initiating device by address. Inputs may be combined with prior approval. Include manual operation of control switches for fans and dampers where the switch controls multiple outputs.

~.2 Show every fire alarm/smoke control system output in a row across the top. Include every notification appliance by zone, every fan and damper (or group of dampers) by identifier, every monitored device by identifier and every other event that must occur for proper operation of the smoke control system. Outputs may be combined with prior approval.

~.3 Show automatic fan shutoffs per CMC 609 where required or provided.~.4 Show supervised conditions for required smoke control components such as fan power

disconnect, pressure differentials, switches, fans not full speed, and doors/windows/dampers open or closed.

~.5 Alarm, supervisory and trouble signals shall be transmitted to an approved supervising station in accordance with NFPA 72 [CBC 907.14].

5.8.5 Provide a full scale color drawing of the firefighters’ smoke control panel (FSCP) for review and approval prior to fabrication [CBC 909.2.]

~.1 Show individual control switches for fans and dampers or multiple dampers with identical actions, and automatic closing/opening doors required for smoke control [909.16.2.]

~.2 Show status indicators for all smoke control equipment by pilot lamp-type indicators as follows:

GREEN: Fans, dampers and other operating equipment are in their ON or OPEN status. Provide a green light to indicate Smoke Control Mode and another for Manual Mode.RED: Fans, dampers and other operating equipment are in their OFF or CLOSED status.YELLOW: Fans, dampers and other operating equipment are in a fault status.WHITE: Fans, dampers and other operating equipment are in their normal status (use of the white light on panels will be reviewed on a case by case basis and designed to what makes the most sense without creating confusion.)

~.3 Provide a legend or matrix either on the panel or separately mounted showing the configuration of fans, dampers and doors in normal status mode and smoke control status mode.

~.4 Alternate designs of the firefighters’ smoke control panel may be approved on a case-by-case basis by SFFD.

5.8.6 Include a reference copy of the approved mechanical plans.

5.8.7 Smoke control systems shall have an automatic weekly self-test feature. The self-test feature shall automatically command activation of each associated function(s). An audible and visual trouble signal shall be annunciated at the FSCP identifying any function that fails to operate within the required time period [CBC 909.12, 907; UL 864, 49.7].

6.0 DESIGN CHANGES TO EXISTING SMOKE CONTROL SYSTEMS

6.1 Smoke Control Systems Designed Per the 1995, 1998, and 2001 CBC/SFBC6.1.1 Comply with the requirements of new smoke control systems for the modified portions of the

system except as noted otherwise in this section.

6/22/2009 Page 14

Page 15: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

6.1.2 Where modifications of existing smoke control systems are made and the original approved reports are not available, provide a new Smoke Control Report, Special Inspection Program, and Special Inspection and Testing Final Report.

6.1.3 Where modifications of existing smoke control systems are minor, DBI/SFFD may waive requirements for new reports or amendments to the original approved reports on a case-by-case basis. Minor modifications do not include new FSDs, smoke barriers/walls, new fire alarm system, changes in use/occupancy, replacement of equipment (except in-kind), or like changes to the building and its systems.

6.1.4 Where work is done to a building with a smoke control system provide on plans a narrative of the smoke control/management system(s) operation and a matrix of fire/smoke damper operations for normal and smoke control modes of the smoke management system(s). Needs editing

6.1.5 Where building renovations do not affect the design or operation of existing smoke control systems, provide the following non-infringement statement on the permit drawings:

“COMPANY NAMES have reviewed these drawings for non-infringement with the existing smoke control system design. As the Designers-of-Record for this project, it is our professional opinion that these drawings do not affect the design or operation of the existing smoke control system design.” Revised

The non-infringement statement must be signed and wet-stamped.by the Architect-of-record and Engineers-of-Record. Revised

6.2 Smoke Control Systems Designed Per the 1992 CBC/SFBC or Earlier6.2.1 Where building renovations affect the design or operation of existing smoke control systems,

provide a smoke control narrative on the permit drawings that describes the building renovations and modifications to the existing smoke control systems.

6.2.2 Where work is done to a building with a smoke control system provide on plans a narrative of the smoke control/management system(s) operation and a matrix of fire/smoke damper operations for normal and smoke control modes of the smoke management system(s). Needs editing

6.2.3 Where building renovations do not affect the design or operation of existing smoke control systems, provide the following non-infringement statement on the permit drawings:

“COMPANY NAMES have reviewed these drawings for non-infringement with the existing smoke control system design. As the Designers-of-Record for this project, it is our professional opinion that these drawings do not affect the design or operation of the existing smoke control system design.” Revised

The non-infringement statement must be signed and wet-stamped.by the Architect-of-record and Engineers-of-Record. Revised

7.0 SPECIAL INSPECTION AND TESTING OF SMOKE CONTROL SYSTEMS

7.1 General

6/22/2009 Page 15

Page 16: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

7.1.1 Submit two copies of the Special Inspection and Testing Final Report [CBC/CFC 909.18.8] upon completion of special inspection. One copy will be returned to the submitter when approved by DBI/SFFD.

7.1.2 Reports shall be in booklet format, bound (e.g. spiral bind), with 8 ½” x 11” sheets.

7.1.3 Submittals of final reports shall be accompanied by two sets of CD-Rs in slim plastic “jewel cases” with fixed label indicating the permit application number, project name and address, report title, revision number, and date, as well as all included files. Each CD-R shall include a complete copy of the final report in PDF format as well as all supporting material, diagrams, calculations, appendices and data files.

7.1.4 If the report is revised after approval by DBI/SFFD, the revised report shall be resubmitted with all required items from the original submittal.

7.2 Special Inspection and Testing Final Report7.2.1 Cover Page. Show the permit application number, project name and address, report title,

revision number, and date as well as the author’s name and company.

7.2.2 Signature Page. Include the completed signature page; see Attachment 1.

7.2.3 Table of Contents.

7.2.4 Special Inspection and Testing Overview.

7.2.5 Conclusions and Recommendations.

7.2.6 Appendices.

~.1 Include the completed Attachment 2, Smoke Control System Special Inspection and Testing Summary Checklist.

~.2 A copy of the Report shall be provided to the SFFD inspector.

7.3 Inspection and Testing Close-out Procedures7.3.1 When the Special Inspector determines that the smoke control system is complete and

operating properly, then he/she shall write a Letter of Completion documenting the system status to the Designers-of-Record, with copies to the DBI and SFFD inspectors.

7.3.2 The Letter of Completion is required to schedule final inspection by DBI/SFFD.

7.3.3 Satisfactory completion of final inspection of the smoke control system by DBI/SFD inspectors is a prerequisite for TCO.

7.3.4 Approval of the Special Inspection and Testing Final Report by DBI/SFFD is a prerequisite for Final Occupancy.

8.0 SPECIAL INSPECTION AND TESTING REQUIREMENTS

8.1 General8.1.1 This section provides specific requirements and clarifications for the inspection and testing of

new smoke control systems. These requirements are in addition to those specified in CBC Section 909.

6/22/2009 Page 16

Page 17: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

8.1.2 Projects involving modifications to existing smoke control systems shall employ only those requirements listed below applicable to the project.

8.2 Inspection and Testing Requirements8.2.1 The Special Inspector shall inspect and test to the following approved documents:

~.1 Smoke Control Report.~.2 Architectural plans, with emphasis on smoke barrier plans.~.3 Mechanical plans.~.4 Electrical plans.~.5 Fire sprinkler shop drawings, with focus on zoning and special design criteria required for

smoke control design.~.6 Fire alarm shop drawings, with the detailed smoke control sequence of operations matrix

and the approved Firefighter’s Smoke Control Panel configuration.

8.2.2 Witness duct and shaft leakage testing, where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition, 1993. Leakage testing shall be performed prior to the installation of dampers, but with all laterals installed. The test pressure and allowable leakage shall be in accordance with CBC, 909.10.2.Testing shall be performed during erection of ductwork and prior to concealment.

8.2.3 Witness leakage testing of dwelling units, where applicable. Leakage testing shall be accomplished using a calibrated door-fan test rig. Test pressure shall be approximately 0.05 in. WG or greater as determined by design. Measured leakage shall be compared to compartment leakage determined by calculation using allowable barrier leakage area ratios in CBC, 909.5 or architectural specification as applicable.

8.2.4 Witness airflow testing, where applicable.

8.2.5 Visually inspect representative portions of the installed perimeter fire-stop to verify installation per its Listing and/or engineering judgment.

8.2.6 Visually inspect the Firefighter’s Smoke Control Panel (FSCP) and verify:~.1 The configuration is consistent with approved fire alarm drawings.~.2 The panel graphic is representative of the building smoke control system.~.3 Indicator lights meet San Francisco requirements:

GREEN: Fan ON or Damper OPEN.RED: Fan OFF or Damper CLOSED.YELLOW: Damper/Fan FAULT or Loss of Power.WHITE: Fans, dampers and other operating equipment are in their normal status (use of the white light on panels will be reviewed on a case by case basis and designed to what makes the most sense without creating confusion.)

8.2.7 Verify that loss-of-power to each smoke control fan causes an immediate illumination of the associated FAULT light on the FSCP.

8.2.8 Verify that fire alarm control/monitor modules are within 3 feet of HVAC equipment used for smoke control OR that the wiring between is supervised.

8.2.9 Verify that the open/closed position of each FSD is monitored. Grouped FSDs with independent motors and jackshafts require the blades of each FSD to be monitored.

8.2.10 Verify that all VFD control panels are removed or the HOA on each VFD is password-protected.

6/22/2009 Page 17

Page 18: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

8.2.11 Pressure testing shall be performed with the building in the following condition:~.1 The building and all smoke control equipment are connected to permanent power.~.2 Windows and exterior doors are CLOSED.~.3 Sub-ducted exhaust systems (toilet, kitchen and dryer) are ON at fire-event speeds.~.4 Dampers and fans that shut down during a fire event are CLOSED/OFF.

8.2.12 Verify proper operation of the smoke control system under standby power by (as a minimum) confirming that current and voltage under normal and standby power are equivalent.

8.2.13 Current switches shall be adjusted after the building has been verified to be properly balanced. Adjustment shall be verified to indicate a no-belt condition, where appropriate.

8.2.14 The weekly fire alarm self-test shall be observed and the following verified:~.1 A written report is produced. The report must clearly indicate a “start” of the test and an

“end.” The report must clearly indicate any failures, but need not specify the component that fails.

~.2 The test shall cycle those components required for proper operation of the smoke control system as identified in the smoke control report.

~.3 Any failure during the self-test shall place a “TROUBLE” on the fire alarm control panel and notify Central Station.

~.4 Any alarm shall interrupt the self-test.

8.2.15 Verify that equipment labels and documentation are in order.~.1 Fans and dampers used for smoke control are field labeled consistent with the control

drawings (approved fire alarm drawings) and the Firefighter’s Smoke Control Panel (FSCP). Fan labels shall be red phenolic with 1” white lettering. Where the fan and the local disconnect/control panel are not immediately adjacent, both shall be labeled.

~.2 Required documentation shall be available in an approved location (Fire Control Room for high-rise buildings). This includes: a) As-built fire alarm (control) shop drawings, b) Smoke control event matrix (typically in the approved fire alarm shop drawings), c) approved Smoke Control Report, d) approved Special Inspection Program, e) approved Special Inspection and Testing Final Report, d) weekly fire alarm self-test reports, e) final commissioning report (same as appr’d Special Inspection and Testing Final Rrt?).

9.0 REFERENCED PUBLICATIONS

9.1 International Code Council (ICC)Guide to Smoke Control in the 2006 IBC, Dr. John H. Klote, PE and Douglas H. Evans, P.E., 2007, ICC.

9.2 National Fire Protection Association (NFPA)NFPA 92A, Smoke-Control Systems Utilizing Barriers and Pressure DifferencesNFPA 92B, Smoke Management Systems in Malls, Atria and Large Spaces

9.3 American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE)ASHRAE Guideline 5-1994, Commissioning Smoke Management Systems.

9.4 Sheet Metal and Air Conditioning Contractors’ National Association (SMACNA)HVAC Systems – Testing, Adjusting, and Balancing, Third Edition, 2002.HVAC Air Duct Leakage Test Manual, First Edition, 1985.

6/22/2009 Page 18

Page 19: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

DRAFT-16, R1, by JC

AB-047 Attachment 1Signature Page

Prepared by:

_________________________ _________ ______________________ ________Preparer License # Company Date

Reviewed and approved by:

_________________________ ________ ______________________ ________Owner’s Representative License # Company Date

Reviewed and approved by:

I have reviewed this report and confirm, to the best of my knowledge, the smoke control system design is in compliance with applicable codes and standards and this report.

_________________________ _________ ______________________ ________Architect-of-Record License # Company Date

_________________________ _________ ______________________ ________Mechanical Engineer-of-Record License # Company Date

_________________________ _________ ______________________ ________Electrical Engineer-of-Record License # Company Date

Instructions: Complete this form (stamp, sign, and date) and include in the Smoke Control Report, Special Inspection Program, and Special Inspection and Testing Final Report

6/22/2009 Page 19

Page 20: Administrative Bulletin Draft Outline · Web view... where applicable. The test method shall be in accordance with SMACNA, HVAC Systems Testing, Adjusting and Balancing, Second Edition,

2007 SAN FRANCISCO BUILDING CODE AB-047

DRAFT-16, R1, by JC

AB-047 Attachment 2Smoke Control System Special Inspection and Testing Summary Checklist

Project:

Special Inspector:

Date:

1. Inspect Installed System for Compliance with Design Yes No NAa. Substantially complies with CBC/CFC 909b. Substantially complies with approved drawingsc. Substantially complies with approved Smoke Control Report

2. Inspect Installed Components for Compliance with Code Requirementsa. Fans [909.10.5]b. Ducts and dampers [909.10.2, 909.10.4, 716]c. Power [909.11]d. Detection and control [909.12]e. Control air tubing [909.13]f. Marking and identification [909.14]g. Control Diagrams [909.15]h. Firefighters’ smoke control panel [909.16]

3. Test Components and System for Compliance with Code Requirementsa. Smoke barriers – pressure differential tests comply [909.5.1, 909.18.6]b. Fans – motor running tests comply [909.10.5]c. Ducts – pressure and flow tests comply [909.10.5, 909.18.2]d. Dampers – proper operation [909.18.3]e. Power transfer within 60 seconds [909.11]f. Control air tubing – pressure tests comply [909.13.3]g. Detection devices – proper operation [909.18.1]h. Firefighters’ smoke control panel – proper operation [909.18.7]i. Component response times comply [909.17]j. Smoke control system – proper operation for each zone [909.18.7]

Instructions: Complete this form and include in the Special Inspection and Testing Final Report. The report may be rejected for “No” or “NA” answers without acceptable explanation.

6/22/2009 Page 20