advanced trailing edge blowing concepts for fan noise control: experimental validation · 2020. 9....

138
Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation Christopher W. Halasz Master of Science in Mechanical Engineering Ricardo Burdisso, Chair Wing Ng Marty Johnson 20 June 2005 Blacksburg, VA Keywords: Fan Noise Reduction, Interaction Noise, Turbofan Engine Copyright 2005, Christopher W. Halasz Thesis submitted to the faculty of the Virginia Polytechnic Institute and State University in partial fulfillment of the requirements for the degree of

Upload: others

Post on 01-Mar-2021

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

Advanced Trailing Edge Blowing Concepts for Fan Noise Control:

Experimental Validation

Christopher W. Halasz

Master of Science

in

Mechanical Engineering

Ricardo Burdisso, Chair

Wing Ng

Marty Johnson

20 June 2005

Blacksburg, VA

Keywords: Fan Noise Reduction, Interaction Noise, Turbofan Engine

Copyright 2005, Christopher W. Halasz

Thesis submitted to the faculty of the

Virginia Polytechnic Institute and State

University in partial fulfillment of the

requirements for the degree of

Page 2: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

Advanced Trailing Edge Blowing Concepts for Fan Noise Control:

Experimental Validation

Christopher W. Halasz

(ABSTRACT)

This thesis documents trailing edge blowing research performed to reduce rotor / stator

interaction noise in turbofan engines. The existing technique of filling every velocity deficit

requires a large amount of air and is therefore impractical. The purpose of this research is to

investigate new blowing configurations in order to achieve noise reduction with lesser amounts

of air. Using the new configurations air is not injected into every fan blade, but is instead varied

circumferentially. For example, blowing air may be applied to alternating fan blades. This type

of blowing configuration both reduces the amount of air used and changes the spectral shape of

the tonal interaction noise. The original tones at the blade passing frequency and its harmonics

are reduced and new tones are introduced between them. This change in the tonal spectral shape

increases the performance of acoustic liners used in conjunction with trailing edge blowing. This

thesis presents numerical predictions performed to estimate the sound power reductions due to

these concepts, as well as experimental results taken on the ANCF rig at NASA Glenn for

validation purposes. The results show that the new concepts are successful in increasing the

efficiency of trailing edge blowing.

Page 3: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

iii

Acknowledgements:

First I would like to thank my advisor Ricardo Burdisso for all of his advice and support

throughout this research. Many thanks are also extended to Wing Ng and Marty Johnson for

making this work possible as my committee members.

I am thankful to all the members of the Vibration and Acoustics Laboratory (VAL). Especially

David Arntz, whose initial work in this area paved the way for my own, and Diego de la Riva for

all of his help and teaching.

I would like to acknowledge the work of Daniel Sutliff and the staff at NASA Glenn's AAPL

facility for conducting the experimental testing. I am grateful to NASA for providing funding for

this research under STTR Contract NAS3-03077.

Finally, I thank Matt Langford and the staff at Techsburg, Inc. for their contributions.

Page 4: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

iv

Table of Contents

Chapter 1 : Introduction .................................................................................................................. 1

1.1: Aircraft Noise Problem........................................................................................................ 1

1.2: Characterization and Measurement of Aircraft Noise ......................................................... 2

1.3: Aircraft Noise Sources......................................................................................................... 4

1.4: Rotor / Stator Interaction Noise ........................................................................................... 5

1.5: Trailing Edge Blowing and Previous Work......................................................................... 6

1.6: Thesis Objectives and Organization .................................................................................... 8

Chapter 2 : Advanced Trailing Edge Blowing Concept ................................................................. 9

Chapter 3 : Experimental Setup .................................................................................................... 14

3.1: ANCF Rig .......................................................................................................................... 14

3.2: TEB Fan Blades ................................................................................................................. 16

3.3: In-Duct Velocity Instrumentation and Data Reduction ..................................................... 17

3.4: In-Duct Acoustic Instrumentation and Data Reduction..................................................... 20

3.5: Far-field Acoustic Instrumentation and Data Reduction ................................................... 25

3.6: Experimental Test Configurations ..................................................................................... 27

3.6.1: First Test Entry ........................................................................................................... 27

3.6.2: Second Test Entry....................................................................................................... 29

Chapter 4 : Experimental Results ................................................................................................. 31

4.1: Hotwire Results (First Test Entry)..................................................................................... 31

4.2: Rotating Rake Results (First Test Entry)........................................................................... 35

4.2.1 Rake Results - No TEB Configuration ........................................................................ 35

4.2.2 Rake Results - Full TEB Configuration....................................................................... 37

4.2.3 Rake Results - ATEB 1x1 Configuration .................................................................... 39

4.2.4 Rake Results - ATEB 2x2 Configuration .................................................................... 41

4.3 Far-Field Results (First Test Entry) .................................................................................... 45

4.3.1: Configurations using 0 Vanes..................................................................................... 45

4.3.2: Configurations using the Inlet Duct and 14 Vanes ..................................................... 46

4.3.3: Configurations using the Aft Duct and 14 Vanes ....................................................... 51

4.3.4: Configurations using the Inlet Duct and 28 Vanes ..................................................... 55

4.3.5: Configurations using the Aft Duct and 28 Vanes ....................................................... 58

Page 5: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

v

4.4 Hotwire Results (Second Test Entry) ................................................................................. 61

4.5 Far-Field Results (Second Test Entry)................................................................................ 64

4.5.1: Configurations using the Inlet Duct (Second Test Entry)........................................... 64

4.5.2: Configurations using the Aft Duct (Second Test Entry)............................................. 66

Chapter 5 : Acoustic Liner Performance with ATEB................................................................... 69

5.1: Numerical Codes................................................................................................................ 69

5.1.1: "V072" Rotor Wake / Stator Interaction Code ........................................................... 69

5.1.2: Eversman Finite Element Radiation Code.................................................................. 70

5.2: Proof of Concept - Acoustic Liner Performance ............................................................... 72

5.2.1: Liner Performance - Configurations with Inlet Duct and 14 Vanes........................... 73

5.2.2: Liner Performance - Configurations with Inlet Duct and 28 Vanes........................... 76

Chapter 6 : Conclusions ................................................................................................................ 80

References..................................................................................................................................... 82

Appendix A: Rake Data (First Test Entry) ................................................................................... 85

Appendix B: First Test Entry Far-Field Results ......................................................................... 113

Appendix C: Second Test Entry Far-Field Results..................................................................... 119

Appendix D: Initial Numerical Predictions ................................................................................ 123

Appendix E: Validation of Eversman Code Accuracy ............................................................... 128

Vita.............................................................................................................................................. 129

Page 6: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

vi

List of Figures

Figure 1.1: Noise Level Certifications............................................................................................ 2

Figure 1.2: EPNL Measurement Locations. ................................................................................... 4

Figure 1.3: Turbofan Engine Noise Sources................................................................................... 5

Figure 1.4: Fan Blades and Wakes. ................................................................................................ 6

Figure 2.1: Fan, Wakes, and Interaction Noise with No TEB. ....................................................... 9

Figure 2.2: Fan, Wakes, and Interaction Noise with Full TEB..................................................... 10

Figure 2.3: Fan, Wakes, and Interaction Noise with ATEB 1x1. ................................................. 11

Figure 2.4: Interaction Spectra (a) without ATEB and (b) with ATEB, in comparison with liner

attenuation curves. ........................................................................................................................ 13

Figure 3.1: (a) Photograph and (b) Cross-Sectional Diagram of ANCF Rig................................ 15

Figure 3.2: Predicted (a) Inlet and (b) Aft Liner Impedances....................................................... 16

Figure 3.3: Fan Blades used in (a) Test Entry I and (b) Test Entry II. ......................................... 17

Figure 3.4: Velocity Triangle and Notation.................................................................................. 18

Figure 3.5: Upwash Velocity Definition....................................................................................... 19

Figure 3.6: ANCF Aft Duct with Rotating Rake Microphone Array. .......................................... 20

Figure 3.7: Far-Field Microphone Array Geometry. .................................................................... 26

Figure 3.8: Photograph of ANCF and Far-Field Microphone Arrays. ......................................... 26

Figure 4.1: Upwash Velocity Contours for (a) No TEB, (b) Full TEB 1.1%, (c) Full TEB 1.5%,

(d) Full TEB 1.8%, and (e) ATEB 1x1 0.9%................................................................................ 34

Figure 4.2: Rake Data for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall] at (a) 1xBPF, (b)

2xBPF, (c) 3xBPF......................................................................................................................... 36

Figure 4.3: Rake Data for [Inlet Duct, 14 Vanes, Full TEB 1.5%,Hardwall] at (a)

1xBPF,(b)2xBPF,(c) 3xBPF. ........................................................................................................ 38

Figure 4.4: Rake Data for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall] at (a) 0.5xBPF, (b)

1xBPF, (c) 1.5xBPF, (d) 2xBPF, (e) 2.5xBPF, and (f) 3xBPF..................................................... 40

Figure 4.5: Rake Data for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall] at (a) 0.25xBPF,

(b) 0.5xBPF, (c) 0.75xBPF, (d) 1xBPF, (e) 1.25xBPF, and (f) 1.5xBPF..................................... 43

Figure 4.6: Rake Data for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall] at (a) 1.75xBPF,

(b) 2xBPF, (c) 2.25xBPF, (d) 2.5xBPF, (e) 2.75xBPF, and (f) 3xBPF........................................ 44

Page 7: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

vii

Figure 4.7: 0-Vane Sound Power Spectra for (a) [Inlet Duct, 0 Vanes, No TEB 0%, Hardwall]

and (b) [Aft Duct, 0 Vanes, No TEB 0%, Hardwall] (dB ref. 10-12 W/m2). ................................. 46

Figure 4.8: Power Spectrum for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall]. ....................... 47

Figure 4.9: Power vs. Blowing Rate for the Configurations [Inlet Duct, 14 Vanes].................... 48

Figure 4.10: Power Spectra for (a) [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall], (b) [Inlet

Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall], and (c) [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%,

Hardwall]. ..................................................................................................................................... 50

Figure 4.11: Original and New Tones' Power for (a) [Inlet Duct, 14 Vanes, ATEB 1x1,

Hardwall] and (b) [Inlet Duct, 14 Vanes, ATEB 2x2, Hardwall]................................................. 51

Figure 4.12: Power Spectrum for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall]. ....................... 52

Figure 4.13: Power vs. Blowing Rate for the Configurations [Aft Duct, 14 Vanes].................... 52

Figure 4.14: Power Spectra for (a) [Aft Duct, 14 Vanes, Full TEB 1.5%, Hardwall], (b) [Aft

Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall], and (c) [Aft Duct, 14 Vanes, ATEB 2x2 0.9%,

Hardwall]. ..................................................................................................................................... 54

Figure 4.15: Original and New Tones' Power for (a) [Aft Duct, 14 Vanes, ATEB 1x1, Hardwall]

and (b) [Aft Duct, 14 Vanes, ATEB 2x2, Hardwall]. ................................................................... 55

Figure 4.16: [Inlet Duct, 28 Vanes, No TEB 0%, Hardwall]........................................................ 55

Figure 4.17: Power vs. Blowing Rate for the Configurations [Inlet Duct, 28 Vanes].................. 56

Figure 4.18: Power Spectra for (a) [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall] and (b)

[Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]. .................................................................... 57

Figure 4.19: Original and New Tones' Power for (a) [Inlet Duct, 28 Vanes, ATEB 1x1,

Hardwall] and (b) [Inlet Duct, 28 Vanes, ATEB 2x2, Hardwall]................................................. 58

Figure 4.20: Power Spectrum for [Aft Duct, 28 Vanes, No TEB 0%, Hardwall]. ....................... 59

Figure 4.21: Power vs. Blowing Rate for the Configurations [Aft Duct, 28 Vanes].................... 59

Figure 4.22: Power Spectra for (a) [Aft Duct, 28 Vanes, ATEB 1x1 0.8%, Hardwall] and (b) [Aft

Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]............................................................................... 60

Figure 4.23: Original and New Tones' Power for (a) [Aft Duct, 28 Vanes, ATEB 1x1, Hardwall]

and (b) [Aft Duct, 28 Vanes, ATEB 2x2, Hardwall]. ................................................................... 61

Figure 4.24: Upwash Velocities for (a) No TEB, (b) Full TEB 0.65%, and (c) Full TEB 0.65%

Partial Span ................................................................................................................................... 63

Figure 4.25: Power Spectrum for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall, (2nd Entry)].. 64

Page 8: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

viii

Figure 4.26: Power vs. Blowing Rate for the Configurations [Inlet Duct, 14 Vanes, (2nd Entry)].

....................................................................................................................................................... 65

Figure 4.27: Power Spectra for (a) [Inlet Duct, 14 Vanes, Full TEB 0.65%, Hardwall, (2nd

Entry)] and (b) [Inlet Duct, 14 Vanes, ATEB 1x1 0.43%, Hardwall, (2nd Entry)]...................... 66

Figure 4.28: Power Spectrum for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall, (2nd Entry)].... 67

Figure 4.29: Power vs Blowing Rate for the Configurations [Aft Duct, 14 Vanes,(2nd Entry)]. 67

Figure 4.30: Power Spectra for (a) [Aft Duct, 14 Vanes, Full TEB 0.65%, Hardwall, (2nd Entry)]

and (b) [Aft Duct, 14 Vanes, ATEB 1x1 0.43%, Hardwall, (2nd Entry)]. ................................... 68

Figure 5.1: Eversman Code (a) Inlet Mesh and (b) Aft Mesh. ..................................................... 71

Figure 5.2: Procedure for Predicting Optimum Liner Attenuations ............................................. 73

Figure 5.3: [Inlet Duct, 14 Vanes] Liner Reductions for (a) No TEB, (b) Full TEB, (c) ATEB

1x1, (d) ATEB 2x2. ...................................................................................................................... 75

Figure 5.4: [Inlet Duct, 14 Vanes] Sound Power Reductions from Wake-Filling and from Liner

Attenuation.................................................................................................................................... 76

Figure 5.5: [Inlet Duct, 28 Vanes] Liner Attenuations for (a) No TEB, (b) ATEB 1x1, and (c)

ATEB 2x2. .................................................................................................................................... 77

Figure 5.6: [Inlet Duct, 28 Vanes] Sound Power Reductions from Wake-Filling and from Liner

Attenuation.................................................................................................................................... 78

Page 9: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

ix

List of Tables

Table 3.1: Predicted Circumferential Modes for No TEB / Full TEB Configurations................. 22

Table 3.2: Predicted Circumferential Modes for ATEB 1x1 Configurations............................... 22

Table 3.3: Predicted Circumferential Modes for ATEB 2x2 Configurations............................... 23

Table 3.4: Propagating Interaction Modes for Configurations with No TEB / Full TEB. ........... 24

Table 3.5: Propagating Interaction Modes for Configurations with ATEB 1x1........................... 24

Table 3.6: Propagating Interaction Modes for Configurations with ATEB 2x2........................... 25

Table 3.7: Rake Data Test Matrix (1st Entry)............................................................................... 28

Table 3.8: Far-Field Data Test Matrix (1st Entry)........................................................................ 29

Table 3.9: Far-Field Data Test Matrix (2nd Entry)....................................................................... 30

Page 10: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

1

Chapter 1 : Introduction

This section introduces the problem of aircraft noise and the measures being taken to

address it. First a statement of the problem is given, followed by a description of how aircraft

noise is quantified and measured. The different types of aircraft noise sources are discussed.

Rotor / stator interaction noise of turbofan engines, the noise generation mechanism targeted by

this research, is explained. The traditional method of reducing interaction noise, called "trailing

edge blowing" (TEB), is outlined and previous work is cited.

1.1: Aircraft Noise Problem

Aircraft noise is a problem because it disturbs the normal activities of nearby

communities. In the United States about 6,000,000 people on 900,000 acres of land are subjected

to aircraft noise. The general quality of life is degraded as conversation, relaxation, and sleep are

made more difficult. Lawsuits are filed for both decreased property values and punitive damages.

Airport proprietors are forced to buy up residential properties nearby and contribute to the

soundproofing of public buildings like schools. In response to public opposition to noise airports

have imposed restrictions on operations. Examples include night time operating restrictions,

exclusion of certain aircraft, a limited number of aircraft operations, and setting noise preferred

runways. Such measures have an effect on commerce, transportation, and air navigation [1].

Old and noisy aircraft are being replaced by newer and quieter models, but at the same

time the volume of air traffic is increasing. In order to control the amount of noise, local and

federal regulations are imposed and made ever stricter. The next step of these regulations, called

"Stage 4," is to take effect in the year 2006. Figure 1.1 illustrates the downward trend in

allowable noise levels. New technology is required to meet stricter standards and provide

aircraft to meet the replacement and growth requirements of the industry [2].

Page 11: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

2

Figure 1.1: Noise Level Certifications.

1.2: Characterization and Measurement of Aircraft Noise

The definition of “aircraft noise” as it is used in this thesis must first be made clear. The

term is used in its capacity describing “community noise,” or more exactly the noise reaching the

ground near airports. This contrasts with its other meaning of “cabin noise,” or the noise

reaching passengers within the aircraft. This thesis and research deal with the issue of aircraft

noise as it relates to communities, not passengers.

When discussing noise it is necessary to have a system of units with which to quantify

measured levels. Noise is, of course, measured as a perturbation of air pressure and is expressed

logarithmically as decibels. However, the measured values in dB do not always give the best

representation of noise as it is experienced by humans. Weighted scales such as dBA are widely

used, but other measures exist specifically to describe aircraft noise. One such measure

quantifies the “annoyance” of each individual flyover. Human response to a single flyover is best

represented in terms of the “Effective Perceived Noise Level” (EPNL) which is used for FAA

certification. The EPNL is a weighting scale that is applied to the measured sound pressure levels

in dB. It considers the frequency content that is audible to humans and emphasizes any pure

tones or “screeches” present in the sound. Furthermore, the EPNL integrates the weighted noise

levels over the flyover time of a passing aircraft. The sensitivity of the unit is such that people

Page 12: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

3

can detect differences of about 5 dB, and differences of 10 dB are described as “twice as loud” or

“half as loud” as the original level.

When considering a person's reaction to multiple flyovers a measure of the cumulative

noise “dose” is needed. This measure is the “Noise Exposure Forecast” (NEF). The NEF at a

point near an airport is calculated by summing the noise energy reaching that point over a 24

hour time period with a penalty applied to nighttime flights. In addition to quantifying the noise

levels for an existing situation the NEF is used to characterize hypothetical scenarios in which a

prediction of a community’s reaction to a proposed change in noise levels is needed. For

example, the number of complaints about a new airport may be predicted by first predicting the

NEF that would result from the facility’s construction. This would require knowledge of the

number and type of each aircraft operating at the airport, their flight paths, and their power

settings.

Next a standardized procedure for taking noise measurements is required. The NEF can

be measured or predicted at any location of interest. The EPNL, however, must be measured at

three specific locations for certification. These locations are called “Sideline,” “Community,”

and “Approach.” The sideline noise is measured 450 m to the side of the runway. The

community noise is measured on takeoff 6500 m down the runway. The approach noise is

measured 2000 m in front of the runway. Figure 1.2 illustrates these locations. The time signals

measured at these locations are called “Perceived Noise Levels with Tonal Weighting” (PNLT),

and are integrated over time to calculate the EPNL. The FAA imposes a maximum allowable

EPNL for each of the three measurement points. The maximum EPNL for a given aircraft is a

function of its weight and number of engines, with larger planes being allowed to make more

noise [3].

Page 13: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

4

Figure 1.2: EPNL Measurement Locations.

1.3: Aircraft Noise Sources

The broadest classifications of aircraft noise are those of airframe and engine noise.

Airframe noise is the non-propulsive noise of an aircraft in flight. Landing gear, flaps, and slats

all contribute to airframe noise and are most used on takeoff and approach when an aircraft is

near the ground. Unsteady flow from wing and tail trailing edge, turbulent flow through or

around flaps and slats, flow past landing gear and other undercarriage elements, fuselage and

wing turbulent boundary layers, and panel vibrations all contribute to airframe noise. Airframe

noise is most significant during approach when the engine noise is low.

Engine noise has been reduced significantly in the past 50 years, first with the transition

from turbojet to turbofan engines and then with evolutionary improvements to turbofan

technology. Switching from the turbojet's small, high-velocity exhaust to the turbofan's large,

low-velocity exhaust drastically reduced the broadband jet noise (roaring, rumbling sound) of

modern aircraft. This noise reduction is achieved because jet noise is an eighth power function of

jet exhaust velocity. With jet noise no longer so dominant the other sources of engine noise have

become significant and noise reduction strategies are needed for all of them.

Page 14: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

5

In addition to jet noise, the noise sources of a turbofan engine are the fan, compressor,

turbine, and combustor. The combustor produces what is called "core noise" which is a

combination of the combustion noise itself and the passing of hot combustion products through

the turbine and exhaust. The core noise level is a function of temperature, pressure, and the

geometry of the flow path. It is broadband and low frequency in nature. The fan, compressor, and

turbine produce "turbomachine noise" that is a function of pressure change, tip speed, flow rate,

turbulence, and wakes. It has both broadband and tonal contents. Figure 1.3 shows the noise

sources of a turbofan engine and their relative contributions at the inlet and exhaust [4].

Figure 1.3: Turbofan Engine Noise Sources.

1.4: Rotor / Stator Interaction Noise

One of the tonal contents of the fan noise is due to "rotor / stator interaction." The fan

blades of a turbofan engine introduce wakes or velocity deficits due to viscous effects (losses)

into the working fluid. These rotating wake deficits propagate downstream where they are cut by

stator vanes. The unsteady surface pressure on the vanes is coupled to duct acoustic modes that

are excited to produce tonal noise at the blade passing frequency (BPF) and its harmonics

(2xBPF, 3xBPF, etc.) [5]. Figure 1.4 shows a blade row and associated wakes. The fluid velocity

becomes unsteady after passing the fan blades.

Page 15: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

6

Figure 1.4: Fan Blades and Wakes.

1.5: Trailing Edge Blowing and Previous Work

Flow control, also referred to as wake management or trailing edge blowing, has proven

to be effective at reducing fan noise by suppressing the unsteady rotor / stator interaction. The

interaction is suppressed by reducing the wakes due to viscous boundary layer effects. This is

accomplished either by removing (suction) low momentum fluid to decrease boundary layer

thickness or by adding (blowing) high momentum fluid to energize low momentum zones (fill

wake deficits). The first tests conducted to validate the use of flow control were performed on

flat plates [6-8]. These tests were important in showing the feasibility of flow control geometries

in affecting steady and unsteady aspects of wakes with their decay and mixing rates, but are not

applicable to modern engines.

The first application of flow control for the reduction of fan noise by Waitz [9] evaluated

the use of mass addition and removal in order to decrease unsteady stator loading and therefore

rotor / stator interaction in a 2D setting. The two flow control concepts studied were boundary

layer suction and trailing edge blowing, which were investigated using numerical and

experimental techniques. Numerically manipulating Gaussian wakes showed that decreasing

wake depth reduced unsteady stator loading harmonics and therefore acoustic tones. Simulation

concluded that wide, shallow wakes are desired for flow control. Experimental results concluded

Page 16: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

7

that trailing edge blowing was a better flow control mechanism than boundary layer suction.

Trailing edge blowing used less mass flow and passage area to produce better interaction

reductions than those achieved with boundary layer suction. The study was taken another step

forward to test different air injection configurations [10]. The conclusion was that many small

jets aimed at the wake centerline was the best trailing edge blowing design.

A later experiment by Brookfield [11] was performed in a rotating fan stage, taking flow

and acoustic measurements. This test used less than 2% of the fan through-flow mass as trailing

edge blowing air in tip-weighted and midspan-weighted blowing distributions. The results

showed that time-mean relative Mach profiles were smoothed such that 85% reductions in wake

harmonic amplitudes were achieved.

A similar technique of stator trailing edge blowing was used on a 3D test rig to reduce

fan noise produced by rotors passing through wakes shed by upstream stators [12, 13]. Velocity

contours showed good results, giving more pitch-wise uniformity with blowing than without.

Extensive trailing edge blowing work has been performed at the NASA Glenn Research

Center using the Advanced Noise Control Fan rig (ANCF). An experimental proof-of-concept

test by Sutliff [14] was performed to demonstrate reduction of rotor / stator interaction noise

through trailing edge blowing. The blade-to-vane spacing used was one chord. The first three

blade passing frequencies were found to be reduced in power by 5.4 dB, 10.6 dB, and 12.4 dB,

respectively. These reductions were achieved at trailing edge blowing rates of 1.6% to 1.8% of

the total mass flow rate through the fan. In a turbofan engine these percentages would be

multiplied by the bypass ratio to calculate the percentage air bled off the compressor, leading to

an impractical air requirement. Two-component flow velocity and stator vane unsteady surface

pressures were also measured to illustrate the physics behind noise reduction. The effects of

trailing edge blowing on broadband fan noise are also documenter by Sutliff [15].

Page 17: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

8

1.6: Thesis Objectives and Organization

Previous studies have demonstrated trailing edge blowing as an effective flow control

mechanism for the reduction of rotor / stator interaction noise. However, the trailing edge

blowing air must be bled from a compressor stage downstream. Bleeding enough air off of the

compressor to fill all of the wake deficits reduces the performance of the engine and makes

commercial application of TEB impractical.

The goal of this research is to experimentally validate a new way of applying TEB. The

new concept, called "advanced trailing edge blowing" (ATEB), addresses the problem of

excessive air requirements. The validation is performed by first presenting the results of

experimental testing. This describes the behavior of ATEB under hardwall conditions. Then

numerical codes are used to predict the performance of ATEB when used in combination with

acoustic liners.

The new TEB concept is described in Chapter 2 of this thesis. The experimental setup is

described in Chapter 3. The results of two experimental test entries using two different types of

fan blades are given in Chapter 4. Chapter 5 explains the computer codes used to predict liner

performances, and presents the results of using ATEB in combination with optimized acoustic

liners. Conclusions are drawn in Chapter 6, and lists of experimental data are given in the

Appendices.

Page 18: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

9

Chapter 2 : Advanced Trailing Edge Blowing Concept

As discussed in Chapter 1, the root cause of rotor / stator interaction noise is unsteadiness

in the fluid reaching the stator vanes. These unsteady wake deficits are caused by losses incurred

along fan blade surfaces. If no interaction noise control is attempted, every fan blade produces a

wake and these wakes produce interaction noise tones at the blade passing frequency and

harmonics. This baseline configuration is illustrated in Figure 2.1. A fan with 16 blades is shown

(3 blades have been removed for ease of visualization). The blue surface downstream of the

blades represents fluid velocity; there is a ripple downstream of every blade trailing edge

representing the wake due to that blade. The stators (not shown) would be further downstream.

The spectrum shows the interaction noise produced in this situation. Interaction tones are

produced at the blade passing frequency and harmonics (1xBPF, 2xBPF, 3xBPF, etc.)

Figure 2.1: Fan, Wakes, and Interaction Noise with No TEB.

The conventional application of trailing edge blowing requires a large amount of air

because every wake deficit is filled. This configuration of TEB applied to every blade is shown

in Figure 2.2, which shows the same fan as Figure 2.1 except that the wakes are greatly reduced.

With only small amounts of unsteadiness present in the velocity profile only small amounts of

interaction noise are produced. The interaction tones are smaller than they were in the baseline

configuration of Figure 2.2, and would be eliminated completely if the wakes were perfectly

filled. Any remaining interaction noise is, however, present at the same frequencies and modes

as it was with no blowing; only the magnitudes are reduced.

Wakes

Page 19: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

10

Figure 2.2: Fan, Wakes, and Interaction Noise with Full TEB.

Advanced trailing edge blowing differs from conventional (full / every blade) trailing

edge blowing because it does not attempt to fill every wake profile. This partial-blowing

configuration results in an immediate savings of air.

Instead of injecting air on every blade to fill every wake deficit, the application of air is

varied circumferentially to selectively fill wakes. This selective wake filling can be done in any

number of different ways, but numerical predictions have identified two configurations in

particular that are used in this research. The two configurations were chosen because they were

predicted to give the best and the worst noise reductions, respectively. The first configuration

predicted to give the most noise reduction is called "ATEB 1x1" and consists of injecting air into

alternating fan blades. The second configuration predicted to give the worst noise reduction is

called "ATEB 2x2" and consists of injecting air into alternating, adjacent fan blades. That is, air

is injected into two adjacent blades, skipped on the next two, applied on the next two, etc. Both

of these advanced layouts use air on exactly half of the fan blades present, and therefore

theoretically should use half as much air as conventional TEB.

The ATEB 1x1 layout serves as an example in Figure 2.3. For this explanation, it is

assumed that TEB perfectly fills any wake that it is applied to. Therefore, applying the ATEB

All Wakes

Filled

Page 20: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

11

1x1 configurations is, acoustically speaking, equivalent to halving the number of fan blades. The

shape on the interaction noise is changed accordingly. In this case (ATEB 1x1), the acoustic

blade passing frequency is reduced to half of the physical blade passing frequency. The

harmonics are therefore spaced more closely together. This behavior is demonstrated in Figure

2.3, which shows the effects of applying the ATEB 1x1 layout. The illustration of the fan shows

how alternating wakes are filled. The spectrum shows a reduction in the original tones' power

and the introduction of new tones at new interaction frequencies.

New interaction modes are present at the new interaction frequencies, but the modal

structure at the "original" frequencies (1xBPF, 2xBPF, etc) is not changed by the application of

ATEB. Interaction modes are neither added nor removed at these frequencies, as shown in

section 3.4. This has two implications. The first is that any tone that is cut off with no TEB or

full TEB remains cut off when ATEB is applied. For example, fans are often designed to cut off

the 1xBPF tone. This tone will remain cut off when ATEB is applied. The second implication is

that ATEB should always decrease the original tones' power levels. This is because the modal

structure is held constant at the original frequencies while there are less wakes present to drive

noise generation.

Figure 2.3: Fan, Wakes, and Interaction Noise with ATEB 1x1.

Some Wakes

Filled

Page 21: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

12

All of the ATEB layouts are by definition partial-blowing layouts, and as such they do

not achieve as much source-level noise reduction as conventional TEB on every blade. Some of

the velocity deficits are still present and therefore still produce some interaction noise. This

remaining noise is managed with acoustic liners. Acoustic liners used in turbofan engines

typically have high resistances, and are most effective at attenuating broadband noise. The liner

can be tuned to a specific tone at a specific engine power setting by designing the proper liner

cavity depth and having a low resistance. However, the liner becomes less effective for the other

tones and power settings. Thus, the liner is designed to be effective over a broad frequency band

by increasing the liner resistance. Rotor / stator interaction noise is tonal in nature, and the

interaction noise resulting from a fan with no TEB or full TEB has tones only at the BPF and

harmonics. Liner performance on conventional interaction noise is poor because the noise is

strongly tonal in nature but the liners are designed to attenuate broadband noise. When ATEB is

used the spectral shape of the interaction noise is changed. The sound energy is split into more

tones spread out over more frequencies. In addition the distribution of power over radial modes

may be changed even within a particular frequency. The noise from a fan with ATEB is more

"like" broadband noise. Therefore acoustic liner performance is expected to be improved. This

change in liner performance is validated in Chapter 5. Figure 2.4 shows how interaction noise

behaves more like broadband noise when ATEB is used. A standard rotor produces interaction

noise only at the BPF and harmonics, but an ATEB configured rotor produces more interaction

tones. The ATEB interaction spectrum is a better fit for a high resistance liner's attenuation

curve.

Page 22: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

13

Figure 2.4: Interaction Spectra (a) without ATEB and (b) with ATEB, in comparison with liner attenuation

curves.

To summarize the concept, advanced trailing edge blowing leaves some of the wake

deficits unfilled in order to use less air. Because some of the deficits are left unfilled, less source-

level noise reduction is achieved with ATEB than is achieved with TEB. A second effect of

ATEB is to modify the spectral shape of the tonal interaction noise. The modified spectrum

allows acoustic liners to perform better, making up for the lesser amount of source-level

reduction. The end result is that similar overall noise reduction levels are achieved while using

less air. This hypothesis is investigated and demonstrated in this thesis.

Page 23: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

14

Chapter 3 : Experimental Setup

This chapter describes how the experimental portion of the research was performed. It

describes the experimental fan and specialized blades used. The instrumentation to acquire

acoustic as well as flow data is described. Finally, a description of the test configurations

obtained is given. This material is presented so that the experimental results discussed in Chapter

4 can be understood.

3.1: ANCF Rig

The experimental portion of this research was performed in the Aero-Acoustic Propulsion

Laboratory at NASA Glenn Research Center. This facility provides a dome 130 feet in diameter

and 65 feet high with anechoically treated walls. This is the testing environment for the

"Advanced Noise Control Fan" (ANCF) [16]. The ANCF is a test bed specifically designed to

test fan noise reduction concepts and is equipped with far-field and in-duct instrumentation. It is

a 4-foot ducted fan with 16 blades driven by a 125 hp electric motor (at 1800 rpm for these

experiments). The inlet and aft mach numbers were 0.11 and 0.16, respectively. The rig also

includes a row of stator vanes whose number and location can be changed. Either 0, 14, or 28

vanes were used in these experiments. The axial spacing between the rotors and stators was one

half of a blade chord for the configurations discussed here. (A blade chord is about 5"). Inlet and

aft ducts are attached to the fan as 48 inch diameter spool pieces. The centerbody of the rig is 18

inches in diameter at the rotors and stators, widening to 24 inches in diameter at the aft duct exit.

Figure 3.1 shows a photograph of the ANCF in part (a) and a cross-sectional diagram in part (b).

Page 24: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

15

Figure 3.1: (a) Photograph and (b) Cross-Sectional Diagram of ANCF Rig.

Acoustic liners were used on the rig in some configurations, called "softwall." The liners

were used to record data points which were later used to validate numerical predictions of liner

performance. They were not designed to directly demonstrate the performance of ATEB.

The liners were placed on the inlet nacelle as well as on the aft nacelle and aft

centerbody. When in use for softwall configurations, the liners were exposed to the flow through

the duct. When not in use, they were covered with a layer of tape to restore the hardwall

condition. The liners were removed from the rig during a second test entry, i.e. only hardwall

condition tested.

All of the liners used were linear, single degree of freedom liners. They were produced

by Goodrich as contributions to a previous project using the ANCF. The liners are 16 inches long

in the axial direction and are made of a wire mesh bonded to a perforated plate. They are

constructed in two identical halves such that they can be placed in the ducts to provide a nearly

seamless liner without discontinuities. The inlet liner has a normalized resistance of 1.7 pc and a

core depth of 0.85 inches, where pc is the free-field acoustic impedance in air. The aft liners have

normalized resistances of 1.0 pc and core depths of 1.0 inches. Figure 3.2 shows predicted inlet

and aft normalized impedances.

Page 25: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

16

Figure 3.2: Predicted (a) Inlet and (b) Aft Liner Impedances.

3.2: TEB Fan Blades

Two test entries were performed on the ANCF during the course of this research. The

first was conducted from August to September 2004 and the second in March 2005. Two

different sets of fan blades were used for these two test entries. Both had internal flow passages

to direct air supplied at the hub into the working fluid.

The first type of blade is designed to inject air through a long slot in the trailing edge.

This results in a blunt trailing edge that causes vortex shedding if the blade is used with no

blowing air. For cases in which TEB was not desired these slots were sealed with an insert (plug)

that restored the blades' usual sharp trailing edge. A photograph of this type of blade is seen in

Figure 3.3A.

The blades used in the second test entry have the same external geometry as the first set,

with the difference being found in the method of TEB air injection. These fan blades use discrete

jets on the suction and pressure surfaces of the blade to inject the air. A photograph of these

blades can be seen in Figure 3.3B. The second set of blades was designed by Techsburg to

Page 26: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

17

achieve wake-filling with less air, leading to more efficient noise reduction. This design is

discussed in a recent publication by Langford [17].

In a real engine the source of the blowing air would be a compressor bleed. In this rig the

source was an external, positive displacement blower. The mass flow rate was calculated by

measuring the temperature and pressure of the air supplied by the blower. The amount of air used

is expressed as a percentage of the total mass flow rate through the rig. (The total mass flow rate

is 125 lbm/s when the rig is operated at 1800 rpm.)

Figure 3.3: Fan Blades used in (a) Test Entry I and (b) Test Entry II.

3.3: In-Duct Velocity Instrumentation and Data Reduction

One of the three data types taken on the ANCF was in-duct fluid velocity. This data was

taken to examine the wake deficits responsible for interaction noise. The data can be used to tell

whether or not an application of TEB was successful in eliminating velocity deficits and

unsteadiness. The data can also be used as an input to one of the computer codes discussed in

Chapter 5.

A two component (axial and tangential) hotwire probe was used transduce axial velocity

and tangential flow angle at the stator vanes' axial location. For the experiments in the first test

entry, data were recorded at 80 tangential locations spanning two blade widths or 45 degrees, and

Page 27: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

18

15 radial locations ranging from 10 to 23.5 inches from the centerline in increments of 1 inch.

(The hub radius of the blades is 9 inches and the tip radius of the blades is 24 inches.) For the

second test entry hotwire experiments, data were taken at 40 tangential locations spanning one

blade width or 22.5 degrees. The one blade width was sufficient because no ATEB layouts were

used and all wakes were theoretically the same. The full span measurements in the second test

entry used the same radial locations as those in the first test entry. Some measurements were

taken at a greater resolution over a smaller portion of the blade span. These measurements were

taken at radial locations ranging from 18 to 20 inches from the centerline in increments of 0.1

inch.

The velocity profile in the axial and tangential directions can be completely specified by

the axial velocity, tangential flow angle, radial location, and tangential blade speed. (The radial

velocity of the fluid is assumed to be zero.) A velocity triangle is shown below in Figure 3.4,

where "U" is the tangential blade velocity, "C" is the absolute velocity, "Cz" is the axial absolute

velocity, "W" is the relative velocity between the fluid and the rotor, and "a" is the tangential

angle between the axial direction and the absolute flow. The direction of vector W is set by the

direction fluid leaves the rotors. The direction of vector C is the direction required to enter the

stators.

Figure 3.4: Velocity Triangle and Notation.

Page 28: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

19

A useful way to describe the wake profiles is with "upwash velocities." The upwash

velocity is the component of the absolute velocity perpendicular to the stator vane surface.

Fluctuations in this component are responsible for noise generation. Figure 3.5 shows the

upwash velocity using two velocity triangles. One triangle represents the freestream velocity,

with no losses caused by the fan blades. The other triangle represents the velocity in a wake.

Losses incurred along the fan blade surface reduce the relative velocity in the wake. This causes

the absolute velocity to change as well, because the blade speed is constant and the triangle must

be closed. Therefore the absolute velocity vector and its upwash component fluctuate between

the freestream and wake conditions. For on-design operation the freestream absolute velocity is

parallel to the stator vanes (to enter without separation) and the upwash velocity is equivalent to

the velocity component perpendicular to the direction of mean flow. The upwash velocity is

calculated at each radius as

Upwash Velocity = Cz*sin(amean-a) (3.1)

where amean is the average tangential flow angle at that radius.

Figure 3.5: Upwash Velocity Definition.

Page 29: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

20

3.4: In-Duct Acoustic Instrumentation and Data Reduction

The in-duct microphone instrumentation consists of rotating-rake microphone arrays at

both the inlet and aft ducts. The inlet rotating rake is located between the last hardwall spool

piece and the duct lip. The aft rake is located just at the duct opening. Figure 3.6 shows a

photograph of the aft duct of the rig with the rake array installed. This data was taken to describe

the modal structure inside the rig. It was also used as an input to numerical codes used to make

predictions in Chapter 5.

The rake array rotates at 1% of the speed of the fan while measurements are being taken,

positioning the microphones at different spatial locations in the duct. When post-processed these

data describe modal behavior, giving complex pressures and powers for each mode measured.

The post-processing decomposition was run at multiples of 0.25xBPF from 0.25xBPF to 3xBPF.

The multiples of 0.25xBPF correspond to the expected interaction tones using the ATEB 2x2

configuration. Measured circumferential modes range from -14 to +14 and measured radial

modes range from 0 to 5.

Figure 3.6: ANCF Aft Duct with Rotating Rake Microphone Array.

Page 30: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

21

The circumferential interaction modes "m" present in the rig are calculated using the

number of blades "B", the number of vanes "V", the BPF harmonic "N", and the set of integers

k=[0, +-1, +-2, …] using

m = (N*B) + (k*V) (3.2)

For configurations with no TEB or Full TEB, the use of this equation is straightforward

and gives the predicted circumferential interaction modes shown in Table 3.1. This table lists the

circumferential interaction modes "m" for the first three BPFs, for configurations with 14 and 28

vanes. The modes (-14 < m < 14) are of special interest because they lie within the

experimentally measured range. For ATEB 1x1 configurations, the number of blades must be

halved (because some are made acoustically "invisible" by the application of TEB) and the

number of blade passing frequencies under consideration must be doubled to examine the same

frequency range. These predictions are shown in Table 3.2. For ATEB 2x2 configurations, the

number of blades is quartered and the number of blade passing frequencies is quadrupled. These

predictions are shown in Table 3.3.

It is important to note that the circumferential interaction modes at the 1xBPF, 2xBPF,

and 3xBPF are unchanged by the application of ATEB. No interaction modes are added or

removed at these frequencies. This is demonstrated in the sample calculations below. First the

circumferential interaction modes for the 1xBPF of a configuration with 14 Vanes and no TEB

are calculated as

m = (1*16) + ([-2,-1,0,1,2])*14) = [-12,2,16,30,44] (3.3)

where N=1 to denote the 1xBPF tone, B=16 to denote 16 blades present, k=[-2,-1,0,1,2] to

consider five different interaction modes, and V=14 to denote 14 vanes present. Next the

circumferential interation modes for the 1xBPF of a configuration with 14 vanes and ATEB 1x1

are calculated as

m = (2*8) + ([-2,-1,0,1,2]*14) = [-12,2,16,30,44] (3.4)

Page 31: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

22

where N=2 to denote the 1xBPF tone. (Every other fan blade is made acousically invisible by

ATEB, halving the effective acoustic blade passing frequency. Therefore the harmonic must be

doubled to examine the frequency corresponding to the no TEB 1xBPF.) The variable B=8

denotes 8 wakes. There are 16 blades present, but only the 8 of them allowed to produce wakes

are acoustically relevant. The variables k and V remain unchanged from the no TEB calculation.

When ATEB 1x1 is applied the variable N is doubled while the variable B is halved, and

therefore the same interaction modes are predicted as were predicted without ATEB.

Table 3.1: Predicted Circumferential Modes for No TEB / Full TEB Configurations.

Table 3.2: Predicted Circumferential Modes for ATEB 1x1 Configurations.

1xBPF 2xBPF 3xBPF 1xBPF 2xBPF 3xBPF-54 -38 -22 -124 -108 -92-40 -24 -8 -96 -80 -64-26 -10 6 -68 -52 -36-12 4 20 -40 -24 -8

2 18 34 -12 4 2016 32 48 16 32 48

No TEB & Full TEB - 14 Vanes No TEB & Full TEB - 28 Vanes

0.5xBPF 1xBPF 1.5xBPF 2xBPF 2.5xBPF 3xBPF-62 -54 -46 -38 -30 -22-48 -40 -32 -24 -16 -8-34 -26 -18 -10 -2 6-20 -12 -4 4 12 20

-6 2 10 18 26 348 16 24 32 40 48

22 30 38 46 54 62

0.5xBPF 1xBPF 1.5xBPF 2xBPF 2.5xBPF 3xBPF-76 -68 -60 -52 -44 -36-48 -40 -32 -24 -16 -8-20 -12 -4 4 12 20

8 16 24 32 40 4836 44 52 60 68 76

ATEB 1x1 - 14 Vanes

ATEB 1x1 - 28 Vanes

Page 32: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

23

Table 3.3: Predicted Circumferential Modes for ATEB 2x2 Configurations.

Within each of these circumferential modes are radial modes that may or may not

propagate out of the duct. To determine whether or not a mode will propagate, it is necessary to

compute the mode axial wavenumber [18]. To this end, the free-field acoustic wave number is

given by

k0 = (2*pi*f) / c (3.5)

where f is frequency in Hz and c is the speed of sound in m/s. The flow Mach number "M" and

the mode eigenvalue "kmn" are also required, where "m" is the circumferential mode number and

"n" is the radial mode number. The eigenvalues used were calculated for the hardwall condition

[18]. A mode will propagate if the condition

ko > kmn * sqrt(1-M2) (3.6)

0.25xBPF 0.5xBPF 0.75xBPF 1xBPF 1.25xBPF 1.5xBPF-38 -34 -30 -26 -22 -18-24 -20 -16 -12 -8 -4-10 -6 -2 2 6 10

4 8 12 16 20 2418 22 26 30 34 38

1.75xBPF 2xBPF 2.25xBPF 2.5xBPF 2.75xBPF 3xBPF-42 -38 -34 -30 -26 -22-28 -24 -20 -16 -12 -8-14 -10 -6 -2 2 6

0 4 8 12 16 2014 18 22 26 30 3428 32 36 40 44 48

0.25xBPF 0.5xBPF 0.75xBPF 1xBPF 1.25xBPF 1.5xBPF-52 -48 -44 -40 -36 -32-24 -20 -16 -12 -8 -4

4 8 12 16 20 2432 36 40 44 48 52

1.75xBPF 2xBPF 2.25xBPF 2.5xBPF 2.75xBPF 3xBPF-56 -52 -48 -44 -40 -38-28 -24 -20 -16 -12 -8

0 4 8 12 16 2028 32 36 40 44 48

ATEB 2x2 - 14 Vanes

ATEB 2x2 - 28 Vanes

Page 33: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

24

is met.

The propagating interaction modes are therefore first a function of which circumferential

interaction modes exist in the duct, and then of which radial modes propagate out of the duct.

These calculations were performed to identify the propagating interaction modes in the ANCF.

The circumferential modes within the bounds (-14 < m <14) are taken from Tables 3.1 through

3.3. The propagating radial modes within each of these circumferential modes are identified

using the condition of Equation 3.4. Tables 3.4 through 3.6 list the propagating interaction modes

for no TEB / full TEB, ATEB 1x1, and ATEB 2x2 configurations, respectively.

Table 3.4: Propagating Interaction Modes for Configurations with No TEB / Full TEB.

Table 3.5: Propagating Interaction Modes for Configurations with ATEB 1x1.

1xBPF 2xBPF 3xBPF 1xBPF 2xBPF 3xBPF(2,0) (4,0) (-8,0) (none) (4,0) (-8,0)

(4,1) (-8,1) (4,1) (-8,1)(6,0)(6,1)(6,2)

No TEB & Full TEB - 14 Vanes No TEB & Full TEB - 28 Vanes

0.5xBPF 1xBPF 1.5xBPF 2xBPF 2.5xBPF 3xBPF(none) (2,0) (-4,0) (4,0) (-2,0) (-8,0)

(4,1) (-2,1) (-8,1)(-2,2) (6,0)(-2,3) (6,1)

(6,2)

0.5xBPF 1xBPF 1.5xBPF 2xBPF 2.5xBPF 3xBPF(none) (none) (-4,0) (4,0) (none) (-8,0)

(4,1) (-8,1)

ATEB 1x1 - 14 Vanes

ATEB 1x1 - 28 Vanes

Page 34: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

25

Table 3.6: Propagating Interaction Modes for Configurations with ATEB 2x2.

3.5: Far-field Acoustic Instrumentation and Data Reduction

The far-field instrumentation of the ANCF consists of 30 microphones arranged around

the rig. One array of 15 microphones is centered on the inlet duct and another array of 15

microphones is centered on the aft duct. The inlet microphones are placed 10 feet away from the

center of the inlet duct opening, from 0 degrees in-line with the duct axis to 90 degrees to the

side. The aft microphones are placed 12 feet away from the center of the aft duct opening and are

arranged from 90 degrees to 160 degrees with respect to the duct axis as shown in Figure 3.7.

Figure 3.8 shows a photograph of the rig with the far-field microphone arrays deployed.

0.25xBPF 0.5xBPF 0.75xBPF 1xBPF 1.25xBPF 1.5xBPF(none) (none) (-2,0) (2,0) (none) (-4,0)

1.75xBPF 2xBPF 2.25xBPF 2.5xBPF 2.75xBPF 3xBPF(0,0) (4,0) (-6,0) (-2,0) (2,0) (-8,0)(0,1) (4,1) (-6,1) (-2,1) (2,1) (-8,1)(0,2) (8,0) (-2,2) (2,2) (6,0)

(-2,3) (2,3) (6,1)(6,2)

0.25xBPF 0.5xBPF 0.75xBPF 1xBPF 1.25xBPF 1.5xBPF(none) (none) (none) (none) (none) (-4,0)

1.75xBPF 2xBPF 2.25xBPF 2.5xBPF 2.75xBPF 3xBPF(0,0) (4,0) (8,0) (none) (-12,0) (-8,0)(0,1) (4,1) (-8,1)(0,2)

ATEB 2x2 - 14 Vanes

ATEB 2x2 - 28 Vanes

Page 35: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

26

Figure 3.7: Far-Field Microphone Array Geometry.

Figure 3.8: Photograph of ANCF and Far-Field Microphone Arrays.

The time history measurements of each microphone were used to calculate sound

pressure level spectra. Then the pressure spectra were used to calculate power spectra. To this

end, first each pressure level in decibels was converted into pressure mean-square-value in Pa2.

Then each msv pressure was used to calculate intensity by dividing by pc (characteristic acoustic

impedance). Each intensity was then integrated with area to give sound power.

The interaction tones from these power spectra were used in the far-field data analysis.

Configurations using no TEB or full TEB have interaction tones at multiples of 1xBPF, or 480

Page 36: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

27

Hz. On the other hand, configurations using ATEB 1x1 have interaction tones at multiples of

0.5xBPF (240 Hz) and configurations using ATEB 2x2 have interaction tones at multiples of

0.25xBPF (120 Hz).

Using these two steps (conversion from to power spectra and then selecting relevant

tones) the far-field data are reduced to the form used in Chapter 4. Extensive comparisons are

made to describe the performance of different TEB configurations.

3.6: Experimental Test Configurations

As mentioned above, the experiments were performed in two test entries separated by

several months. Results from these test entries are presented in Chapter 4. This section lists and

describes the configurations run.

3.6.1: First Test Entry

The configurations in the first test entry can be described in terms of five parameters. The

first parameter specifies which duct of the ANCF is being used, either the inlet or the aft. The

second parameter specifies how many stator vanes are used, either 0, 14, or 28. The third

parameter specifies the application of TEB, if any. The possible choices for this parameter are no

TEB, full TEB, ATEB 1x1, and ATEB 2x2. The fourth parameter specifies the amount of air

used for wake-filling. The fifth parameter specifies the duct wall condition, either hardwall or

softwall. The softwall condition indicates that the liner was installed in the duct. For example,

[Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall] denotes a configuration using the inlet duct of

the ANCF, 14 stator vanes, the ATEB 1x1 alternating blowing layout, 0.9% of the mass flow

through the rig, and no liner.

In this test entry, hotwire data were collected for five configurations. One baseline

configuration was run with no TEB (0% air). Three more configurations were run with full TEB

using mass flow rates of 1.1%, 1.5%, and 1.8%. The last configuration was run with the ATEB

Page 37: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

28

1x1 layout using 0.9% air. Note that the duct, vanes, and liner parameters are not applicable to

the hotwire data type.

Rotating rake and far-field data were collected for many configurations as shown in

Tables 3.7 and 3.8, respectively. Each row of the table lists one or more configurations. If one

blowing rate is listed in a row, that row defines one configuration with the five parameters

discussed above. If a row lists multiple blowing rates, it describes multiple configurations that

have the same duct, number of vanes, TEB layout, and liner condition, but different blowing

rates.

Table 3.7: Rake Data Test Matrix (1st Entry).

Duct # Vanes Layout Liner Blowing Rates (%)Inlet 0 No TEB Hardwall 0Inlet 14 No TEB Hardwall 0Inlet 14 No TEB Softwall 0Inlet 14 ATEB 1x1 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Inlet 14 ATEB 1x1 Softwall 0.9Inlet 14 ATEB 2x2 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Inlet 14 ATEB 2x2 Softwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Inlet 14 Full TEB Hardwall 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8Inlet 28 No TEB Hardwall 0Inlet 28 No TEB Softwall 0Inlet 28 ATEB 1x1 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Inlet 28 ATEB 1x1 Softwall 0.9Inlet 28 ATEB 2x2 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Inlet 28 ATEB 2x2 Softwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Aft 0 No TEB Hardwall 0Aft 14 No TEB Hardwall 0Aft 14 No TEB Softwall 0Aft 14 ATEB 1x1 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Aft 14 ATEB 1x1 Softwall 0.9Aft 14 ATEB 2x2 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Aft 14 ATEB 2x2 Softwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Aft 14 Full TEB Hardwall 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8Aft 28 No TEB Hardwall 0Aft 28 No TEB Softwall 0Aft 28 ATEB 2x2 Hardwall 0, 0.55, 0.7, 0.8, 0.9, 1.0Aft 28 ATEB 2x2 Softwall 0, 0.55, 0.7, 0.8, 0.9, 1.0

Page 38: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

29

Table 3.8: Far-Field Data Test Matrix (1st Entry).

Duct # Vanes Layout Liner Blowing Rates (%)Inlet 0 No TEB Hardwall 0Inlet 0 Full TEB Hardwall 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8Inlet 14 No TEB Hardwall 0Inlet 14 No TEB Softwall 0Inlet 14 ATEB 1x1 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Inlet 14 ATEB 1x1 Softwall 0.9Inlet 14 ATEB 2x2 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Inlet 14 ATEB 2x2 Softwall 0.55, 0.7, 0.8, 0.9, 1.0Inlet 14 Full TEB Hardwall 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8Inlet 28 No TEB Hardwall 0Inlet 28 No TEB Softwall 0Inlet 28 ATEB 1x1 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Inlet 28 ATEB 1x1 Softwall 0.9Inlet 28 ATEB 2x2 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Inlet 28 ATEB 2x2 Softwall 0.55, 0.7, 0.8, 0.9, 1.0Aft 0 No TEB Hardwall 0Aft 0 Full TEB Hardwall 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8Aft 14 No TEB Hardwall 0Aft 14 No TEB Softwall 0Aft 14 ATEB 1x1 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Aft 14 ATEB 1x1 Softwall 0.9Aft 14 ATEB 2x2 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Aft 14 ATEB 2x2 Softwall 0.55, 0.7, 0.8, 0.9, 1.0Aft 14 Full TEB Hardwall 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8Aft 28 No TEB Hardwall 0Aft 28 No TEB Softwall 0Aft 28 ATEB 1x1 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Aft 28 ATEB 1x1 Softwall 0.9Aft 28 ATEB 2x2 Hardwall 0.55, 0.7, 0.8, 0.9, 1.0Aft 28 ATEB 2x2 Softwall 0.55, 0.7, 0.8, 0.9, 1.0

3.6.2: Second Test Entry

Hotwire velocity data were taken for a total of six configurations in the second test entry.

The first was a baseline configuration of no blowing. The second was a full TEB configuration at

the optimum blowing rate of 0.65%. The third used the same layout as the second; however, the

data were taken in greater resolution over a smaller portion of the blade span. The last three of

the configurations tested used a blade-to-vane spacing of one rotor chord; to remain focused on

the ATEB concept these results are not presented in this thesis (all experiments presented used a

spacing of one half of a rotor chord).

Page 39: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

30

Far-field data were collected for many configurations as shown in Table 3.9, but the

number of vanes was always 14 and the liner conditions was always hardwall. The ATEB 2x2

layout was not used because of its inferior performance in the first test entry.

Rake data were collected for the second test entry, but are not presented in this thesis

because they lead to the same conclusions as the data from the first test entry. Similar behavior

was seen in both test entries, as shown in a discussion of the far-field data results in Chapter 4.

Therefore the second entry rake data are not needed for this discussion of the ATEB concept.

Table 3.9: Far-Field Data Test Matrix (2nd Entry).

Duct # Vanes Layout Liner Blowing Rates (%)Inlet 14 No TEB Hardwall 0Inlet 14 No TEB Hardwall 0Inlet 14 ATEB 1x1 Hardwall 0.36, 0.41, 0.43, 0.46, 0.48, 0.53, 0.56

Inlet 14 Full TEB Hardwall0.40, 0.50, 0.59, 0.67, 0.74, 0.85, 0.93, 0.96, 0.99, 1.03, 1.08

Inlet 14 Full TEB Hardwall 0.57, 0.75, 0.86, 0.87, 0.96, 1.01Aft 14 No TEB Hardwall 0Aft 14 No TEB Hardwall 0Aft 14 ATEB 1x1 Hardwall 0.36, 0.41, 0.43, 0.46, 0.48, 0.53, 0.56

Aft 14 Full TEB Hardwall0.40, 0.50, 0.59, 0.67, 0.74, 0.85, 0.93, 0.96, 0.99, 1.03, 1.08

Aft 14 Full TEB Hardwall 0.57, 0.75, 0.86, 0.87, 0.96, 1.01

Page 40: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

31

Chapter 4 : Experimental Results

This chapter presents results from the hardwall experiments performed on the ANCF.

Hotwire results are given first, to show how wake deficits were filled by the application of TEB.

Rake data are shown next, to show how ATEB affected the modal structure in the rig. Far-field

data are shown last, to examine the source-level reductions achieved with TEB and ATEB.

4.1: Hotwire Results (First Test Entry)

This section discusses the wake profiles measured by hotwire probe in the first test entry.

The examination is performed to assess how effectively wake-filling was achieved by each

configuration measured.

The hotwire results are presented as upwash velocity contours in Figure 4.1. The units of

upwash velocity are ft/s. A negative value indicates a wake deficit and a positive value indicates

a wake surplus (over-blowing). The ideal value is 0 ft/s, representing no disturbance. Positive or

negative values lead to noise generation. Each contour describes a profile spanning two blade

widths, or 45 tangential degrees (360 degrees divided by 16 blades equals 22.5 degrees per

blade). The profiles extend from a radial location of 10" to 23.5". (The locations of the hub at 9

inches and the tip at 24 inches are shown with arrows on the figure.) The direction of rotation is

from the left to the right as indicated in the plots. The right side of each wake is the pressure side

and the left side is the suction side.

Part (a) of the figure shows an upwash velocity contour for the configuration of no TEB.

No wake-filling is attempted, and therefore two distinct wakes are seen in the contour. The

wakes are 5 degrees wide and exhibit 10 degrees of sweep from hub to tip. The upwash

velocities in the wakes are about -30 ft/s, and are 0 ft/s in the freestream between wakes. Upwash

velocities in addition of those of the wake itself are seen near the tip of the blade. To the left of

each wake is a region of positive upwash velocity and to the right of each wake is a region of

negative upwash velocity. These velocities are generated by counter-rotating vortices. The

vortices are likely synchronized with the rotational speed of the fan, otherwise the averaging

technique employed to record the hotwire data would eliminate the signal. The ANCF includes

rub strips to ensure a tight tip clearance, therefore the vortices are not likely due to leakage from

Page 41: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

32

the pressure to the suction side of the blade. The presence of these vortices is significant because

their respective upwash velocities act as noise sources in the same way as the wakes themselves.

A destructive interference effect may occur because the vortices alternate between positive and

negative upwash velocities in the tangential direction. This is analogous to noise sources out of

phase with one another.

Part (b) shows an upwash velocity contour for the first of the three full TEB

configurations. This configuration uses 1.1% of the mass flow through the rig as blowing air.

The contour plot shows that this configuration was not successful in filling the wake deficits. The

wakes are still present and appear mostly unchanged from the no TEB configuration. Only a

small amount of wake-filling is apparent near the hub, with upwash velocities near -20 ft/s. The

conclusion is that 1.1% air is not enough to achieve effective wake-filling. The tip vortices are

still present, and similar behavior is also seen at the blade hub. Regions of positive upwash

velocity are seen between the wakes at the hub. Tip and hub vortices are seen in all remaining

parts of Figure 4.1.

Part (c) shows an upwash velocity contour for the second of the three full TEB

configurations. This configuration uses 1.5% of the mass flow through the rig as blowing air.

The contour plot clearly shows that upwash velocities have been reduced. The wakes are still

visible, but upwash velocities are now -5 ft/s near the blade tip and -10 ft/s near the blade hub.

The conclusion is that 1.5% air is an appropriate amount to achieve wake-filling, and that

interaction noise should be reduced with this configuration.

Part (d) shows an upwash velocity contour for the third and last full TEB configuration

using 1.8% of the mass flow through the rig as blowing air. Upwash velocities are only -5 ft/s

near the blade hub, but have risen to +15 ft/s near the blade tip. This means that too much air was

injected. The wake deficit became a wake surplus, i.e. over-blowing occurred. The magnitude of

the upwash velocity drives interaction noise, so a wake surplus is a noise generation mechanism

just like a wake deficit. The conclusion is that 1.8% air is excessive and that over-blowing occurs

with an associated increase in noise.

Page 42: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

33

Part (e) shows an upwash velocity contour for the ATEB 1x1 configuration using 0.9%

air. It is clear that this air was applied to the left wake, which has been filled with slight over-

blowing. The right wake is unaffected. It is interesting to note that 1.8% air spread over 16 wakes

did not give the same results as 0.9% air spread over 8 wakes. In the former case, severe over-

blowing occurs. In the latter, only minor over-blowing is seen. This means that the optimum

blowing rate for ATEB 1x1 is not necessarily exactly half of the optimum rate for full TEB.

Taken together, the five parts of Figure 4.1 shows how wake-filling is achieved using

different amounts of air. Too little air leaves the wakes unfilled, while too much air causes

counterproductive over-blowing. Using 0.9% air to fill 8 wakes or 1.5% air to fill 16 wakes are

both shown to be effective solutions. In later sections, far-field data is used to show that these are

often the optimum blowing rates for ATEB and TEB, respectively.

Page 43: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

34

Figure 4.1: Upwash Velocity Contours for (a) No TEB, (b) Full TEB 1.1%, (c) Full TEB 1.5%, (d) Full TEB

1.8%, and (e) ATEB 1x1 0.9%.

Page 44: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

35

4.2: Rotating Rake Results (First Test Entry)

This section presents results for the in-duct rake data measured in the first test entry. This

study is performed because the rake data contains modal information and it is important to show

how ATEB spreads out interaction noise into more modes than conventional TEB. Chapter 3

presented a list of theoretical interaction modes while this section presents experimental

measurements. In addition to its presentation here, rake data is also used in Chapter 5 as an input

to computer codes predicting liner performance.

Not all of the rake data collected in the test entry are presented in this thesis. First, sound

power levels are presented but complex pressures are not. Second, only configurations using no

blowing or optimum blowing rates are presented. Third, only the interaction frequencies relevant

to each configurations are examined. For example, the 1.25xBPF tone is examined for ATEB

2x2 configurations but not for no TEB configurations. The main body of the thesis discusses and

plots data for configurations with the inlet duct and 14 vanes. Appendix A tabulates sound power

levels for these configurations, and also for those with 28 vanes or the aft duct.

4.2.1 Rake Results - No TEB Configuration

From Table 3.4, the only propagating interaction mode for [Inlet Duct, 14 Vanes, No

TEB 0%, Hardwall] at the 1xBPF is (2,0). At the 2xBPF they are the (4,0) and (4,1) modes. At

the 3xBPF they are the (-8,0), (-8,1), (6,0), (6,1), and (6,2) modes. Figure 4.2 (corresponding

with tables A.1 through A.3) shows the modes actually measured in the ANCF rig. Part (a) of

this figure shows the (2,0) mode to be dominant; this agrees with theory because the (2,0) mode

is the only propagating interaction mode at this frequency. Likewise in part (b) the (4,0) mode is

dominant followed by the (4,1) mode - these are also the predicted modes at 2xBPF. At 3xBPF,

part (c) show the (6,0) mode to be dominant followed by the (6,1) mode. These are two of the

predicted modes at this frequency; the (-8,0), (-8,1), and (6,2) modes are either not excited or do

not have enough power to differentiate them from the other, non-interaction modes measured.

These results show agreement between theory and measured results. The dominant modes

measured in the rig are all predicted interaction modes.

Page 45: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

36

Figure 4.2: Rake Data for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall] at (a) 1xBPF, (b) 2xBPF, (c) 3xBPF.

Page 46: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

37

4.2.2 Rake Results - Full TEB Configuration

Figure 4.3 (corresponding with tables A.4 through A.6) shows the measured modal data

for the configuration [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall]. The predicted modes are

the same as for the no TEB configuration described above. Part (a) of the figure shows that the

predicted (2,0) mode is still dominant at the 1xBPF. At the 2xBPF, part (b) shows that the

predicted (4,0) and (4,1) modes are still dominant as well. However, with full TEB the (4,1)

mode has more power than the (4,0). According to part (c) all power levels are low at 3xBPF, but

the predicted (6,0), (6,1), and (6,2) modes are the dominant modes present. The (-8,0) and (-8,1)

modes have power levels less than 60 dB and do not contribute a significant amount of power to

this configuration.

These results are very similar to the results for no TEB. Power levels are lower but the

predicted modes still dominate. Even though the same interaction modes are present as in the no

blowing case, the distribution of power into radial modes can be different. This change is

important because it can affect the performance of liners.

Page 47: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

38

Figure 4.3: Rake Data for [Inlet Duct, 14 Vanes, Full TEB 1.5%,Hardwall] at (a) 1xBPF,(b)2xBPF,(c) 3xBPF.

Page 48: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

39

4.2.3 Rake Results - ATEB 1x1 Configuration

When the ATEB 1x1 configuration is applied, new interaction modes are produced. Table

3.5 shows how the original modal structure at 1xBPF, 2xBPF, and 3xBPF remain unchanged

while new modes are added at other frequencies. When 14 vanes are used, propagating

interaction modes are added at the 1.5xBPF and 2.5xBPF tones. The (-4,0) mode is added at

1.5xBPF and the (-2,0), (-2,1), (-2,2), and (-2,3) modes are added at 2.5xBPF.

Figure 4.4 (corresponding to tables A.7 through A.12) shows the modes measured for the

configuration [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]. No propagating interaction

modes are predicted at 0.5xBPF, and correspondingly part (a) of the figure shows only a few

low-power modes at this frequency. The predicted mode at 1xBPF is (2,0) just as it was in the

previous configurations, and part (b) shows this mode to be dominant. A new interaction mode (-

4,0) is predicted at 1.5xBPF, and part (c) shows this to be the second most dominant mode

measured; the (-3,0) mode is 0.6 dB louder but is not an interaction mode. The presence of this

mode is not clear. At 2xBPF the predicted modes are still (4,0) and (4,1), and these modes are

dominant as shown in part (d). The other new modes due to ATEB 1x1 are predicted at 2.5xBPF

and part (e) illustrates their presence. They would be the dominant 4 modes if not for the (11,0)

mode, which is the most dominant but not a predicted interaction mode. The predicted modes at

3xBPF are unchanged from the previous configurations, and part (f) shows the (6,0) and (6,1)

modes to be dominant.

The modal structure at the original three BPF tones remained unchanged by the

implementation of the ATEB 1x1 blowing layout. The predicted interaction modes are dominant

at these frequencies. The new modes due to ATEB 1x1 were measured and showed a strong

presence, but were not the dominant modes at their respective frequencies. At 1.5xBPF and

2.5xBPF the dominant modes were not predicted interaction modes. The reason for the presence

of dominant non-interaction modes is not clear.

Page 49: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

40

Figure 4.4: Rake Data for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall] at (a) 0.5xBPF, (b) 1xBPF, (c)

1.5xBPF, (d) 2xBPF, (e) 2.5xBPF, and (f) 3xBPF.

Page 50: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

41

4.2.4 Rake Results - ATEB 2x2 Configuration

The ATEB 2x2 configuration leads to new propagating interaction modes at the new

tones. In this case, the new tones take place at 0.25xBPF, 0.5xBPF, 0.75xBPF, and so forth.

However, there are propagating modes at only some of these tones as shown in Table 3.6. The (-

2,0) mode is present at 0.75xBPF; modes (0,0), (0,1), and (0,2) are introduced at 1.75xBPF;

modes (-6,0), (-6,1), and (8,0) are introduced at 2.25xBPF; and modes (2,0), (2,1), (2,2), and

(2,3) are added at 2.75xBPF. The modal structure measured for the configuration [Inlet Duct, 14

Vanes, ATEB 2x2 0.9%, Hardwall] is shown in Figures 4.5 and 4.6.

Figure 4.5 (corresponding to tables A.13 through A.18) shows the measured modal

structure for frequencies up to 1.5xBPF. No propagating interaction modes are predicted at

0.25xBPF, 0.5xBPF, or 1.25xBPF. Parts (a), (b), and (e) of the figure show non-interaction

modes at these frequencies that are small in power compared to the measured interaction modes

of other frequencies. Part (c) shows the dominant mode at 0.75xBPF to be (-2,0), which is the

predicted interaction mode. The predicted mode at 1xBPF is (2,0), and part (d) shows that this

mode is dominant just as it was in all previous configurations. The predicted mode at 1.5xBPF is

(-4,0) and this is the dominant mode present according to part (f).

Figure 4.6 (corresponding to tables A.19 through A.24) shows the measured powers for

modes contained in frequencies from 1.75xBPF to 3xBPF. Part (a) shows the modes at

1.75xBPF. The predicted modes at this frequency are (0,0), (0,1), and (0,2). These are the three

most powerful modes measured. The predicted modes at 2xBPF are (4,0) and (4,1) as they were

in all previous configurations discussed; part (b) shows them to be the two most powerful modes

present. Three new modes are predicted at 2.25xBPF, these are the (-6,0), (-6,1), and (8,0)

modes. Part (c) shows that these are the three most powerful modes measured. As with the

ATEB 1x1 configuration, the modes predicted at 2.5xBPF are (-2,0), (-2,1), (-2,2), and (-2,3).

These are seen in part (d), although the (-2,1) mode shares dominance with the (11,0) mode

which is not an interaction mode. More new modes are predicted at 2.75xBPF, these being the

(2,0), (2,1), (2,2), and (2,3) modes. The (2,0) mode is dominant. Finally, the predicted modes at

3xBPF are again (-8,0), (-8,1), (6,0), (6,1), and (6,2). These are all seen in part (f), with (6,0)

being dominant.

Page 51: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

42

As with the ATEB 1x1 data examined in the previous section, the ATEB 2x2 data also

shows that the modal structure at the original, integer multiples of the BPF is unchanged. The

dominant modes at these frequencies are predicted interaction modes. The interaction modes at

the new tones (0.25xBPF, 0.5xBPF, etc.) are also seen in the rake data. The predicted interaction

modes are not always dominant at these new frequencies.

Results for configurations using the aft duct or 28 vanes are found in Appendix A. All of

the configurations with the inlet duct and 28 vanes exhibit the predicted interaction modes, but

they are not always the dominant modes. Especially at the 3xBPF, unexpected modes are found

in the rake data. Considering those configurations with the aft duct and 14 vanes, the no TEB and

full TEB cases behave as expected. The ATEB 1x1 case, again, shows unexpected modes at

3xBPF. The ATEB 2x2 case shows a strongly dominant unexpected mode at 3xBPF, mode (-

12,0). This is an interaction mode for 28 vanes, but data for all other frequencies agrees with the

14 vane predictions. Finally, the configurations with the aft duct and 28 vanes behave as

expected except for the power found at the 1xBPF which should be cut off.

Page 52: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

43

Figure 4.5: Rake Data for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall] at (a) 0.25xBPF, (b) 0.5xBPF, (c)

0.75xBPF, (d) 1xBPF, (e) 1.25xBPF, and (f) 1.5xBPF.

Page 53: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

44

Figure 4.6: Rake Data for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall] at (a) 1.75xBPF, (b) 2xBPF, (c)

2.25xBPF, (d) 2.5xBPF, (e) 2.75xBPF, and (f) 3xBPF.

Page 54: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

45

4.3 Far-Field Results (First Test Entry)

This section presents hardwall results using far-field data from the first test entry. These

results are important because they describe the source-level noise reductions obtained by TEB

and ATEB. The most relevant results are presented here. First a baseline (no blowing)

configuration is shown, and then the optimum blowing rates are found. The configurations using

the optimum blowing rates are described in more detail. For completeness, the sound power

spectra of all configurations can be found in Appendix B.

4.3.1: Configurations using 0 Vanes

The best that TEB can accomplish is to completely eliminate interaction noise; it cannot

eliminate the tonal noise due to the rotor alone. Thus, the minimum possible sound level can be

quantified by examining configurations with zero stator vanes, i.e. there is no interaction noise

and this represents a lower limit for the configurations with blowing.

Sound power spectra for the configurations [Inlet Duct, 0 Vanes, No TEB 0%, Hardwall]

and [Aft Duct, 0 Vanes, No TEB, Hardwall] are shown in Figure 4.7 parts (a) and (b),

respectively. For the inlet duct, the total tonal power is 94.8 dB and for the aft duct the total tonal

power is 98.4 dB. These values are theoretically the lowest that can be achieved by TEB (not

counting the effects of acoustic liners).

Page 55: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

46

Figure 4.7: 0-Vane Sound Power Spectra for (a) [Inlet Duct, 0 Vanes, No TEB 0%, Hardwall] and (b) [Aft

Duct, 0 Vanes, No TEB 0%, Hardwall] (dB ref. 10-12 W/m2).

4.3.2: Configurations using the Inlet Duct and 14 Vanes

This thesis breaks the remainder of the far-field data into four groups so that meaningful

comparisons can be made. First the group of configurations using the inlet duct and 14 stator

vanes is considered. The baseline case for this group is [Inlet Duct, 14 Vanes, No TEB 0%,

Hardwall]. Figure 4.8 shows a power spectrum for this configuration. The 1xBPF tone is

dominant and each subsequent BPF tone contributes less power until the 8xBPF tone contributes

an insignificant amount (down 30 dB). The total tonal power is 109.2 dB. Therefore, a 14.4 dB

reduction would occur if interaction noise were completely eliminated.

Page 56: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

47

Figure 4.8: Power Spectrum for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall].

The configurations using TEB and ATEB are now discussed. The blowing rate is an

important parameter for such configurations; too little air will not give much noise reduction and

too much air will result in counterproductive over-blowing. It is therefore necessary to identify

the best blowing rates to use with TEB, ATEB 1x1, and ATEB 2x2. The optimum blowing rate

is defined as the blowing rate resulting in the lowest total tonal sound power. The optimum rates

are found by calculating the total tonal powers of configurations with different blowing rates and

comparing them. This is shown in Figure 4.9, which shows sound powers for the TEB, ATEB

1x1, and ATEB 2x2 configurations as functions of the blowing rate. The TEB powers are shown

in blue. At 0% blowing the power is the baseline level of 109.2 dB. As the blowing rate is

increased power falls until a clearly defined optimum rate of 1.5% is reached. The power at this

optimum rate is 101.6 dB (a 7.6 dB reduction). At greater blowing rates the power rises again

due to over-blowing. The ATEB 1x1 powers are shown in green. The optimum blowing rate

using ATEB 1x1 is 0.9%, which results in a power of 104.5 dB (a 4.7 dB reduction). The ATEB

2x2 powers are shown in red, and the optimum blowing rate is also 0.9%, which results in a

power of 106.2 dB (a 3.0 dB reduction). It is interesting to note that the optimum blowing rate

for the ATEB concept seems to be less sensitive than the optimum for the conventional full TEB.

For example, the ATEB 2x2 blowing rate can be reduced to 0.7% and still gives a noise

reduction of 2.7 dB which is virtually the same as the reduction for the 0.9% case.

The important conclusions drawn from this figure is that the ATEB optimum blowing

rate is less than the TEB optimum blowing rate. Advanced TEB uses 60% (or less) as much air

Page 57: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

48

as conventional TEB. In return, ATEB gives a lesser amount of source-level noise reduction. It is

also interesting to note that ATEB 1x1 gives more reduction than ATEB 2x2.

100

102

104

106

108

110

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8

Blowing Rate (%)

So

un

d P

ow

er (

dB

)

ATEB 1x1 Hardwall ATEB 2x2 Hardwall Full TEB Hardwall

Figure 4.9: Power vs. Blowing Rate for the Configurations [Inlet Duct, 14 Vanes].

Now that the optimum blowing rates have been identified, the sound power spectra for

the TEB configuration using 1.5% air, the ATEB 1x1 configuration using 0.9% air, and the

ATEB 2x2 configuration using 0.9% air are considered. These spectra are shown in Figure 4.10.

Part (a) shows the configuration [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall]. Compared to

the no-blowing case, the 1xBPF, 2xBPF, and 3xBPF tones are reduced by 7.0, 7.8, and 11.6 dB,

respectively. Further reductions of 9.8, 6.1, and 1.7 dB, respectively, would be needed to reduce

these tones to the rotor-alone levels. The arrows shown on the figure at each tone note the change

from the no-blowing case. The cross-bars show the minimum rotor-alone levels. Part (b) shows

the configuration [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]. Compared to the no-

blowing case, the 1xBPF, 2xBPF, and 3xBPF tones are reduced by 3.5, 7.7, and 8.4 dB,

respectively. Further reductions of 13.3, 6.2, and 4.9 dB, respectively, would be needed to reduce

these tones to the rotor-alone levels. New tones appear at multiples of 0.5xBPF. Part (c) shows

the configuration [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]. Compared to the no-

blowing case, the 1xBPF, 2xBPF, and 3xBPF tones are reduced by 1.6, 9.7, and 11.5 dB,

Page 58: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

49

respectively. Further reductions of 15.2, 4.2, and 1.8 dB, respectively, would be needed to reduce

these tones to the rotor-alone levels. New tones appear at multiples of 0.25xBPF.

It is also interesting to note that the TEB and ATEB configurations give similar

reductions at the 2xBPF and 3xBPF harmonics. It is only the 1xBPF that is less strongly affected

by ATEB. For example the TEB, ATEB 1x1, and ATEB 2x2 reductions of the 1xBPF are 7.0,

3.5, and 1.6 dB, respectively; TEB gives at least 3.5 dB more reduction at this tone. However,

the reductions at the 2xBPF are 7.8, 7.7, and 9.7 dB, respectively; ATEB gives a similar or even

greater amount of reduction.

Page 59: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

50

Figure 4.10: Power Spectra for (a) [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall], (b) [Inlet Duct, 14

Vanes, ATEB 1x1 0.9%, Hardwall], and (c) [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall].

Another important conclusion drawn from this figure is that the original tones at 1xBPF,

2xBPF, etc. are reduced by ATEB, while new tones are introduced between them. The power

contribution of the new tones is important to the performance of ATEB and is examined in more

detail below. The overall sound power reduction is a tradeoff between the reduced power of the

original tones and the increased power of the new tones. If the new tones are large relative to the

Page 60: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

51

original tones, overall sound power reduction is low. These effects can be seen in Figure 4.11.

The new tones are small compared to the original tones for these configurations. The new tones'

power is at least 6 dB less than the original tones' power at all blowing rates measured, and

therefore the total power is close to the original tones' power. The new tones do not limit ATEB

performance for these configurations.

Figure 4.11: Original and New Tones' Power for (a) [Inlet Duct, 14 Vanes, ATEB 1x1, Hardwall] and (b)

[Inlet Duct, 14 Vanes, ATEB 2x2, Hardwall].

4.3.3: Configurations using the Aft Duct and 14 Vanes

This section performs a similar study on the aft duct of the rig. Figure 4.12 shows the

baseline configuration of [Aft Duct, 14 Vanes, No TEB 0%, Hardwall]. The 1xBPF tone is no

longer dominant as in the inlet. In the aft duct, the 3xBPF tone is the dominant tone. The total

tonal power is 112.1 dB. If TEB could perfectly eliminate all interaction noise, a 13.7 dB

reduction would bring the level to the rotor-alone level of 98.4 dB.

Page 61: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

52

Figure 4.12: Power Spectrum for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall].

The approach described in the previous section is again used to find the optimum blowing

rate for the TEB, ATEB 1x1, and ATEB 2x2 configurations. The results are shown in Figure

4.13. The results are similar to those for the inlet duct. The optimum rate for TEB is 1.5% and

results in an overall power reduction of 7.8 dB. The optimum rates for ATEB 1x1 and ATEB

2x2 are both 0.9% and result in power reductions of 5.8 and 3.4 dB, respectively.

102

104

106

108

110

112

114

0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8

Blowing Rate (%)

So

un

d P

ow

er (

dB

)

ATEB 1x1 Hardwall ATEB 2x2 Hardwall Full TEB Hardwall

Figure 4.13: Power vs. Blowing Rate for the Configurations [Aft Duct, 14 Vanes].

Page 62: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

53

Figure 4.14 shows power spectra for the optimum blowing rate configurations [Aft Duct,

14 Vanes, Full TEB 1.5%, Hardwall], [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall], and

[Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall] in parts (a), (b), and (c), respectively. In all

three parts of this figure the 2xBPF and 3xBPF tones are reduced. However, the 1xBPF tones are

increased by 1.5, 0.5, and 0.2 dB, respectively. These results are surprising because TEB and

ATEB are predicted to reduce the tones at integer multiples of the BPF. No new modes are

introduced at these frequencies and the number of noise-producing wakes is reduced. The modal

rake data provides more details with which to investigate this behavior.

The only propagating interaction mode with 14 vanes at 1xBPF is the mode (2,0) as

shown in Table 3.4. Compared to the no blowing levels, the full TEB, ATEB 1x1, and ATEB

2x2 levels of this mode are reduced by 0.7, 0.5, and 1.9 dB, respectively. (The relevant rake data

are shown in Appendix A tables A.25, A.28, A.32, and A.40.) Therefore the interaction sound

power at 1xBPF is actually decreased according to the rake data. The increased levels seen here

are not due to interaction noise. In fact, the rake data show that the total tonal power levels are

reduced by 0.5, 0.8, and 1.8 dB for full TEB, ATEB 1x1, and ATEB 2x2, respectively. The rake

and far-field data do not agree, and the rake data make more physical sense because the 1xBPF

level should be reduced by TEB and ATEB.

It is also interesting to note that the 0.75xBPF tone is dominant in the ATEB 2x2

configuration of part (c). This is due to the mode (-2,0) being introduced at this frequency by the

implementation of ATEB 2x2, as shown in Table 3.6 and Table A.39.

Even though the 1xBPF tone is increased in power and the new tones dominate the

ATEB 2x2 spectrum, overall power levels are still decreased. This reduction in total tonal power

is due to the large reduction of the originally dominant 3xBPF tone.

Page 63: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

54

Figure 4.14: Power Spectra for (a) [Aft Duct, 14 Vanes, Full TEB 1.5%, Hardwall], (b) [Aft Duct, 14 Vanes,

ATEB 1x1 0.9%, Hardwall], and (c) [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall].

The power due to the original and new tones can be seen in Figure 4.15. The new tones'

power is significant for these configurations, as noted above. At a blowing rate of 1.0%, the new

tones' power is greater than the original tones'. At a 1.0% blowing rate the original tones' power

rises due to over-blowing and the new tones dominate, preventing this from being the optimum

rate.

Page 64: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

55

Figure 4.15: Original and New Tones' Power for (a) [Aft Duct, 14 Vanes, ATEB 1x1, Hardwall] and (b) [Aft

Duct, 14 Vanes, ATEB 2x2, Hardwall].

4.3.4: Configurations using the Inlet Duct and 28 Vanes

This section discusses the configurations using the inlet duct and 28 stator vanes. When

28 vanes are used the 1xBPF is cut off, i.e. all modes are cut-off and can’t propagate. Figure 4.16

shows the baseline configuration [Inlet Duct, 28 Vanes, No TEB 0%, Hardwall]. The 1xBPF is

no longer dominant because it is cut off. The 2xBPF is dominant instead and the total tonal

power is 101.6 dB.

Figure 4.16: [Inlet Duct, 28 Vanes, No TEB 0%, Hardwall].

Page 65: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

56

The approach described in the previous sections is used again to find the optimum

blowing rate for the TEB, ATEB 1x1, and ATEB 2x2 configurations. The results are shown in

Figure 4.17. (There are no experimental data for the full TEB layout with 28 vanes.) The ATEB

1x1 layout has its optimum blowing rate at 0.9% resulting in a reduction of 2.1 dB. The ATEB

2x2 configurations performed especially poorly, with all of the blowing rates actually increasing

the sound power. The lowest of these powers is achieved at a blowing rate of 0.8%, which

increases the power by 0.8 dB. The reason for the power increase is discussed below.

98

100

102

104

106

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

Blowing Rate (%)

So

un

d P

ow

er (

dB

)

ATEB 1x1 Hardwall ATEB 2x2 Hardwall

Figure 4.17: Power vs. Blowing Rate for the Configurations [Inlet Duct, 28 Vanes].

Figure 4.18 shows power spectra for the optimum rate configurations [Inlet Duct, 28

Vanes, ATEB 1x1 0.9%, Hardwall] and [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall] in

parts (a) and (b), respectively. Part (a) shows that the 1xBPF power level is increased by 0.9 dB,

while the 2xBPF and 3xBPF levels are reduced by 4.8 and 2.1 dB, respectively.

It is surprising to see the power of the 1xBPF tone increase when ATEB 1x1 is

implemented. According to Table 3.5 there are no propagating interaction modes at this

frequency when using 28 vanes. Checking the rake data of Appendix A reveals that no single

Page 66: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

57

mode is strongly dominant at the 1xBPF frequency. According to tables A.49 and A.53, the total

tonal power at this frequency decreases by 2.4 dB when ATEB 1x1 is applied. This is also

surprising because the power of the 1xBPF is expected to be unaffected by ATEB because it

contains no interaction modes; this also disagrees with the far-field data.

The power of the 1xBPF tone rises 4.3 dB when ATEB 2x2 is applied, as shown in part

(b) of Figure 4.18. Calculating the change in power level with tables A.49 and A.61 of Appendix

A, applying ATEB 2x2 causes a 1.3 dB decrease in the total tonal power. Therefore the rake and

far-field power change disagrees by 5.6 dB in this case, a serious discrepancy. It seems likely

that some noise source is measured in the far-field but not in the duct. In addition to the unusual

behavior of the 1xBPF tone, the 3xBPF tone also increases when it is expected to decrease. The

cut on interaction modes are the modes (-8,0) and (-8,1) according to Table 3.4. Using the in-

duct rake data of tables A.51 and A.69 in Appendix A, the interaction power and the total tonal

power are reduced by 9.0 and 6.6 dB, respectively, when ATEB 2x2 is applied.

Figure 4.18: Power Spectra for (a) [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall] and (b) [Inlet Duct, 28

Vanes, ATEB 2x2 0.8%, Hardwall].

Page 67: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

58

The power due to the original and new tones can be seen in Figure 4.19. For the ATEB

1x1 configurations, the new tones' power is small at the lesser blowing rates and nearly equal to

the original tones' power at the highest blowing rate of 1.0%. For the ATEB 2x2 configurations,

the new tones' power is about the same as the original tones' at all of the blowing rates. This

explains the poor performance of ATEB 2x2 according to the far-field data; the new tones

contribute too much power for effective overall noise reduction to occur.

Figure 4.19: Original and New Tones' Power for (a) [Inlet Duct, 28 Vanes, ATEB 1x1, Hardwall] and (b)

[Inlet Duct, 28 Vanes, ATEB 2x2, Hardwall].

4.3.5: Configurations using the Aft Duct and 28 Vanes

This section discusses configurations using the aft duct of the rig and 28 vanes. Figure

4.20shows the baseline configuration [Aft Duct, 28 Vanes, No TEB 0%, Hardwall]. The 3xBPF

tone is dominant and the total power is 107.7 dB.

Page 68: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

59

Figure 4.20: Power Spectrum for [Aft Duct, 28 Vanes, No TEB 0%, Hardwall].

The optimum blowing rates are found using the same method as in the above sections,

and shown in Figure 4.21. The optimum blowing rate is 0.8% for both configurations, with

ATEB 1x1 and ATEB 2x2 giving power reductions of 3.4 and 2.0 dB, respectively.

104

104.5

105

105.5

106

106.5

107

107.5

108

108.5

109

0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

Blowing Rate (%)

So

un

d P

ow

er (

dB

)

ATEB 1x1 Hardwall ATEB 2x2 Hardwall

Figure 4.21: Power vs. Blowing Rate for the Configurations [Aft Duct, 28 Vanes].

The power spectra for [Aft Duct, 28 Vanes, ATEB 1x1 0.8%, Hardwall] and [Aft Duct,

28 Vanes, ATEB 2x2 0.8%, Hardwall] are shown in Figure 4.22 parts (a) and (b). Part (a) shows

the spectrum for ATEB 1x1. Compared to the no-blowing case, the 1xBPF, 2xBPF, and 3xBPF

Page 69: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

60

tones are reduced by 4.6, 8.6, and 3.5 dB, respectively. Part (b) shows the spectrum for ATEB

2x2. Compared to the no-blowing case, the 1xBPF, 2xBPF, and 3xBPF tones are reduced by 3.4,

7.2, and 4.4 dB, respectively.

The 1xBPF levels for these configurations are actually lower than the rotor-alone levels.

The rotor-alone level is 95.0 dB, while with 28 vanes the No TEB, ATEB 1x1, and ATEB 2x2

levels are 98.3, 93.7, and 94.9 dB, respectively. As previously mentioned no interaction modes

are cut on at the 1xBPF when 28 vanes are used.

Figure 4.22: Power Spectra for (a) [Aft Duct, 28 Vanes, ATEB 1x1 0.8%, Hardwall] and (b) [Aft Duct, 28

Vanes, ATEB 2x2 0.8%, Hardwall].

The power due to the original and new tones can be seen in Figure 4.23. For the ATEB

1x1 configurations, the new tones' power is small at the lesser blowing rates and greater than the

original tones' power at the high blowing rates. For the ATEB 2x2 configurations, the new tones'

Page 70: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

61

power is about the same as the original tones' at all of the blowing rates measured. This explains

why ATEB 1x1 gives more overall power reduction than ATEB 2x2; the later configuration's

performance is more limited by the new tones.

Figure 4.23: Original and New Tones' Power for (a) [Aft Duct, 28 Vanes, ATEB 1x1, Hardwall] and (b) [Aft

Duct, 28 Vanes, ATEB 2x2, Hardwall].

4.4 Hotwire Results (Second Test Entry)

Hotwire data were also taken in the second test entry. These data are presented here to aid

in the understanding of the sound power reductions shown in section 4.5, and to show

similarities and differences compared to the wakes of the first test entry.

Part (a) of Figure 4.24 shows an upwash velocity contour plot for the no blowing

configuration. The velocity deficit due to the blade is clearly visible, with upwash velocities in

the wake reaching -30 ft/s. Counter-rotating vortices are again seen at the tip, as in the first test

entry. This wake is more tip-weighted than the wakes of the first test entry.

The configuration using full TEB and 0.65% air is shown in part (b). The wake has been

reduced from its no blowing state of part (a), but is still present with upwash velocities reaching

25 ft/s. It is surprising that the 0.65% blowing rate was the optimum rate, because it appears that

Page 71: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

62

more air could better fill in this wake deficit. Tip vortices are visible, and disturbances are also

seen between the wakes at the hub. Two small regions of positive upwash velocity are seen at

radii of approximately 13 and 23 inches, possibly due to localized over-blowing.

Part (c) presents data taken from the same full TEB configuration as part (b), but in

greater resolution over a smaller portion of the blade span. The wake seen in this plot is very

discontinuous. In the wake centerline, regions of wake-filling alternate with regions of velocity

deficit in the radial direction. In addition, small regions of over-blowing are offset from the wake

by a few degrees.

The fan blades used in the second test entry inject air through discrete jets, and these

results show the effects of each jet. The air supplied by the jets has not mixed with the rest of the

wake by the time the wake reaches the stator vanes. The discussion of the far-field results in

section 4.5 shows that noise reduction is achieved regardless of the discontinuous wake-filling

seen here. The wake is partially filled, which is expected to reduce noise. In addition, the

adjacent regions of under- and over-blowing may be responsible for destructive interference

effects similar to those hypothesized for the counter-rotating tip vortices.

Page 72: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

63

Figure 4.24: Upwash Velocities for (a) No TEB, (b) Full TEB 0.65%, and (c) Full TEB 0.65% Partial Span

Page 73: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

64

4.5 Far-Field Results (Second Test Entry)

This section presents far-field results from the second test entry. Compared to the first

test entry, a different method of air injection is used. The method of injection causes the amount

of air required to be reduced, which is the main difference between the first and second test

entries. However, the ATEB concept is independent of the wake-filling method and the same

conclusions are reached as in the first test entry. These results are therefore presented for the

sake of completeness.

The results in this section are presented in a similar form as for the first entry discussed in

section 4.3. However, they are described in less detail because of the results' similarity. The

sound power spectra discussed are listed in Appendix C. This appendix also lists results for

configurations not discussed in the main body of the thesis.

4.5.1: Configurations using the Inlet Duct (Second Test Entry)

The configurations using the inlet duct and 14 vanes are discussed in this section. Figure

4.25 shows the baseline configuration [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall, (2nd

Entry)]. The 1xBPF is dominant and the total tonal power is 110.0 dB.

Figure 4.25: Power Spectrum for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall, (2nd Entry)].

The optimum rate using TEB was 0.65% and resulted in a 5.6 dB power reduction. The

optimum rate using ATEB 1x1 was 0.43% and resulted in a 4.2 dB reduction. This is shown in

Page 74: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

65

Figure 4.26. It is important to note that the ATEB optimum rate is less well defined in the second

test entry than it was in the first test entry. This is because the sound power versus blowing rate

trend line does not form a smooth curve identifying the optimum rate in a "valley." The

experimental apparatus had difficulty in supplying large amounts of air to the ATEB configured

blades. The mass flow rate is set by controlling the blowing air pressure. At maximum system

pressure the mass flow rate was still small because the second entry fan blades have smaller air

passages than the first entry blades.

Figure 4.26: Power vs. Blowing Rate for the Configurations [Inlet Duct, 14 Vanes, (2nd Entry)].

With the optimum rates identified, the power spectra for [Inlet Duct, 14 Vanes, Full TEB

0.65%, Hardwall, (2nd Entry)] and [Inlet Duct, 14 Vanes, ATEB 1x1 0.43%, Hardwall, (2nd

Entry)] are shown in Figure 4.27. Part (a) shows the full TEB configuration using 0.65% air.

Compared to the no-blowing levels the 1xBPF, 2xBPF, and 3xBPF levels are reduced 3.8, 7.4,

and 12.9 dB, respectively. Part (b) shows the ATEB 1x1 configuration using 0.43% air.

Compared to the no-blowing levels the 1xBPF, 2xBPF, and 3xBPF levels are reduced 3.1, 4.5,

and 6.5 dB, respectively. As in the first test entry, the ATEB configuration gives less source-

level reduction while using less air.

Page 75: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

66

Figure 4.27: Power Spectra for (a) [Inlet Duct, 14 Vanes, Full TEB 0.65%, Hardwall, (2nd Entry)] and (b)

[Inlet Duct, 14 Vanes, ATEB 1x1 0.43%, Hardwall, (2nd Entry)].

4.5.2: Configurations using the Aft Duct (Second Test Entry)

This section describes configurations in the second test entry using the aft duct of the rig.

Figure 4.28 shows the baseline configuration [Aft Duct, 14 Vanes, No TEB 0%, Hardwall, (2nd

Entry)]. The 3xBPF is dominant and the total tonal power level is 114.8 dB.

Page 76: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

67

Figure 4.28: Power Spectrum for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall, (2nd Entry)].

Figure 4.29 shows how the optimum rate using TEB was 0.65% (resulting in a 7.0 dB

power reduction) and the optimum rate using ATEB 1x1 rate was 0.43% (resulting in a 3.5 dB

power reduction). These are the same optimum rates found at the inlet duct.

106

107

108

109

110

111

112

113

114

115

116

0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90

Blowing Rate (%)

So

un

d P

ow

er (

dB

)

Full TEB Hardwall ATEB 1x1 Hardwall

Figure 4.29: Power vs Blowing Rate for the Configurations [Aft Duct, 14 Vanes,(2nd Entry)].

With the optimum rates identified, the power spectra for [Inlet Duct, 14 Vanes, Full TEB

0.65%, Hardwall, (2nd Entry)] and [Inlet Duct, 14 Vanes, ATEB 1x1 0.43%, Hardwall, (2nd

Entry)] are shown in Figure 4.30. Part (a) shows the full TEB configuration using 0.65% air.

Page 77: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

68

Compared to the no-blowing levels the 1xBPF, 2xBPF, and 3xBPF levels are reduced 0.6, 10.7,

and 2.0 dB, respectively. Part (b) shows the ATEB 1x1 configuration using 0.43% air. Compared

to the no-blowing levels the 1xBPF, 2xBPF, and 3xBPF levels are reduced 1.9, 6.9, and 5.0 dB,

respectively.

Figure 4.30: Power Spectra for (a) [Aft Duct, 14 Vanes, Full TEB 0.65%, Hardwall, (2nd Entry)] and (b) [Aft

Duct, 14 Vanes, ATEB 1x1 0.43%, Hardwall, (2nd Entry)].

Page 78: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

69

Chapter 5 : Acoustic Liner Performance with ATEB

Prior to the experimental effort, numerical codes were used to predict the performance of

ATEB. In addition, after the experiments were conducted a combination of experimental data

and numerical codes was used to predict the performance of ATEB when combined with

optimized acoustic liners. These predictions were needed because only two liners were tested

experimentally; one type in the inlet duct and one type in the aft duct. These liners were not

optimized for use with an ATEB spectrum and therefore can not demonstrate the potential of the

concept. Predictions were needed to find optimum liners and their attenuations for each

configuration. The codes used are described in this chapter so that the results can be understood.

5.1: Numerical Codes

Two computer codes can be used to model the ATEB concept. The codes and how they

were used are described in the following subsections.

5.1.1: "V072" Rotor Wake / Stator Interaction Code

The "V072" Rotor / Stator interaction code was used to make the initial predictions found

in Appendix D, but was not used in the liner performance modeling of section 5.2. This is

because experimental modal data, once available, was used instead. The measured rake data are

assumed to be more accurate than predictions made with the V072 code. The program is

discussed here to describe the modeling process in its entirety.

The V072 code is a program that predicts the rotor / stator interaction noise produced in

an infinite annular duct of constant cross section [19]. There are two parts to the program. The

first part calculates the wake deficits due to losses on fan blade surfaces. The second part then

calculates the acoustic response when these wakes reach the stator vanes.

In its original version, the V072 program requires the user to supply the geometry and

operating conditions of the turbomachine for which predictions are to be made. Given this

information the program outputs the in-duct acoustic mode complex amplitudes and sound

Page 79: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

70

powers produced by the interaction of the rotor wakes and the stator vanes. This information is

provided for each acoustic mode propagating both upstream and downstream of the fan and each

tone component.

The V072 code has been modified from its original version so that it can be used with

ATEB layouts [20]. The original program did not have the means to use an ATEB profile; the

wake of every blade must be the same. In order to bypass this restriction the program was

modified to allow the input of an arbitrary wake profile. For example, the ATEB 1x1 layout

consists of TEB applied to alternating blades. To run this layout in V072 a wake profile spanning

two fan blades (one with TEB and one without) is constructed and entered into the program.

Since the program considers this to be the wake resulting from one blade, the variable specifying

the number of blades is halved. As far as the code is concerned, 16 single-blade wakes are

equivalent to 8 double-blade wakes. In this way any arbitrary wake profile can be produced and

input to the code. The program also outputs its internally generated wake profile; modifying this

profile and then inputting it back into the code is often a useful technique.

5.1.2: Eversman Finite Element Radiation Code

Once the modal amplitudes at the stator vanes are calculated by the V072 code or are

measured experimentally, they can then used as the inputs to the Eversman code [22]. The

Eversman code calculates how sound propagates out of the duct into the far-field and predicts the

effects of acoustic liners.

The far-field radiation calculation requires that a finite element mesh be produced for the

inlet and aft ducts. This mesh is generated by the Eversman program provided it is supplied with

the required duct geometry. Figure 5.1 parts (a) and (b) show the meshes used for the inlet and

aft ducts, respectively. If acoustic liners are used, their locations are described in terms of the

elements of these meshes and their impedances are described as a function of frequency.

The Eversman code is run once for each propagating circumferential mode in the duct.

All radial modes associated with a particular circumferential mode are analyzed during the same

Page 80: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

71

run. The outputs from the code are the acoustic pressures at each element in the inlet and aft

meshes. These pressures are then used to calculate sound powers in a similar manner to that of

the far-field data discussed in section 3.5.

Figure 5.1: Eversman Code (a) Inlet Mesh and (b) Aft Mesh.

Page 81: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

72

5.2: Proof of Concept - Acoustic Liner Performance

This section presents the procedure for and results of predicting liner performance.

Optimum liners and their attenuations are found. These predictions validate the hypothesis that

ATEB configurations increase liner performance.

The only liners previously discussed (in section 3.1) have been the liners physically

installed in the ANCF inlet and aft ducts. These liners were not designed for use with ATEB, and

therefore do not demonstrate the full potential of the concept. They are used only to validate the

accuracy of the Eversman code in Appendix E.

Figure 5.2 outlines the process used to predict optimized liner performance. The process

begins with experimentally measured in-duct modal data for hardwall (no liner) configurations.

This data is input to the Eversman code and run with no liner present to calculate a hardwall

power. Then the code is supplied with a liner impedance and run again to calculate a softwall

power. The predicted attenuation due to the modeled liner is the difference in power between the

hardwall and softwall cases. This is repeated using a 43 study to find the optimum liner for each

configuration. The liners were assumed to be single degree-of-freedom linear liners with

normalized resistances ranging from 0.5 pc to 2.6 pc. Tuned frequencies ranged from 500 Hz to

4300 Hz. The liner normalized impedance were calculated using

Z = R- I * cot(k * d) (5.1)

where R is resistance, d is core depth, and k is wavenumber. This study was performed for no

TEB configurations, ATEB 1x1 configurations using 0.9% air, ATEB 2x2 configurations using

0.9% air, and full TEB configurations using 1.5% air. These rates are the optimum rates found

using the far-field results in sections 4.3.2 and 4.3.4.

Page 82: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

73

Figure 5.2: Procedure for Predicting Optimum Liner Attenuations

5.2.1: Liner Performance - Configurations with Inlet Duct and 14 Vanes

In this section, acoustic liner performance for configurations using the inlet duct and 14

vanes is modeled. Modal data from the configurations [Inlet Duct, 14 Vanes, No TEB 0%,

Hardwall], [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall], [Inlet Duct, 14 Vanes, ATEB 1x1

0.9%, Hardwall], and [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall] are used as inputs to

the Eversman code. These data are represented in Figures 4.2 through 4.6, but the complex

pressures directly input to the code are not listed in this thesis due to the volume of data and

difficulty in concise presentation.

Results for these configurations are shown in Figure 5.3. Liner attenuation is shown as a

function of resistance and tuned frequency. Tuned frequency is itself a function of core depth,

and specifies the frequency at which the imaginary component of the liner impedance is equal to

zero, i.e. the resonant frequency.

Page 83: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

74

Part (a) shows the liner attenuation when no TEB is used. The maximum attenuation is

6.5 dB for a liner normalized resistance of approximately 1.0 pc and tuned frequency near 900

Hz. When full TEB using 1.5% air is used, Part (b) shows the maximum attenuation to be 8.5

dB. Liner normalized resistance is lower, near 0.7 pc, and tuned frequency is approximately 900

Hz.

Parts (c) and (d) show liner attenuations for the ATEB 1x1 and ATEB 2x2

configurations, respectively. ATEB 1x1 gives a maximum attenuation of 9.8 dB and ATEB 2x2

gives a maximum attenuation of 10.3 dB. Both configurations achieve optimum performance

near normalized resistances of 0.8 pc, whereas the tuned frequency for ATEB 1x1 is near 900Hz

and the tuned frequency for ATEB 2x2 is near 800 Hz.

Comparing these four optimized liner attenuations demonstrates how liner performance is

increased when ATEB is used. The ATEB 1x1 configuration increases liner performance by 3.3

dB relative to the no TEB configuration and 1.3 dB relative to the full TEB configuration. The

ATEB 2x2 configuration increases liner performance by 3.8 dB relative to the no TEB

configuration and 1.8 dB relative to the full TEB configuration. In addition, liner performance is

less sensitive to changes in liner parameters when ATEB is used. High attenuations are achieved

over a greater section of the design space.

Page 84: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

75

Figure 5.3: [Inlet Duct, 14 Vanes] Liner Reductions for (a) No TEB, (b) Full TEB, (c) ATEB 1x1, (d) ATEB

2x2.

The overall sound power reduction achieved with the ATEB concept is due to both the

source-level reduction of wake-filling and the attenuation of liners. Figure 5.4 presents these

results in a format such that it is easy to visualize the two types of reduction. All values in this

figure are results of running the Eversman code with rake data inputs. The "wake-filling"

reductions represent the difference in power between a hardwall configuration with no blowing

and a hardwall configuration with blowing. The "liner" reductions represent the difference in

power between a hardwall and a softwall configuration. Optimized liner results from Figure 5.3

are used.

Page 85: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

76

The "liner alone" configuration provides only 6.5 dB liner attenuation. The full TEB

layout provides the most wake-filling reduction (8.9 dB) and 8.5 dB liner attenuation for a total

power reduction of 17.4 dB. On the other hand, the ATEB 1x1 and 2x2 layouts provide less

wake-filling reduction (4.3 dB and 2.7 dB, respectively) but more reduction from the liner (9.8

dB and 10.3 dB, respectively.) The ATEB configurations give less total reduction (14.1 and 13.0

dB) as compared to that of full TEB (17.4 dB) but at a cost of using only 60% as much air.

0

4.32.7

8.96.5

9.810.3

8.5

0

2

4

6

8

10

12

14

16

18

20

Liner Only ATEB 1-1 ATEB 2-2 TEB

Po

wer

Red

uct

ion

(d

B)

Wake-Filling Reduction Liner Reduction

6.5

14.113.0

17.4

Figure 5.4: [Inlet Duct, 14 Vanes] Sound Power Reductions from Wake-Filling and from Liner Attenuation.

5.2.2: Liner Performance - Configurations with Inlet Duct and 28 Vanes

The same study was performed for configurations using the inlet duct and 28 vanes. The

only difference is that no experimental in-duct modal data is available for the full TEB

configuration. The configurations used as inputs to the code were [Inlet Duct, 28 Vanes, No TEB

0%, Hardwall], [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall], and [Inlet Duct, 28 Vanes,

ATEB 2x2 0.9%, Hardwall].

0.9% Air 1.5% Air

Page 86: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

77

The results of Figure 5.5 show how ATEB increased liner performance relative to the

configuration with no TEB. Part (a) shows the optimized liner reduction with no TEB to be 5.5

dB. This occurs near a normalized resistance of 2.0 pc and a tuned frequency of 1400 Hz. The

best reducing achieved when using ATEB 1x1 is shown by part (b) to be 6.7 dB. The normalized

resistance is near 1.4 pc and the tuned frequency is lower, near 900 Hz. An even greater

optimized liner performance of 7.6 dB is achieved when applying ATEB 2x2, as shown in part

(c). For this configuration the normalized resistance is approximately 1.2 pc and the tuned

frequency is 1000 Hz.

Figure 5.5: [Inlet Duct, 28 Vanes] Liner Attenuations for (a) No TEB, (b) ATEB 1x1, and (c) ATEB 2x2.

Page 87: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

78

Wake-filling and liner reductions are shown together in Figure 5.6. The liner alone gives

5.5 dB power reduction. The ATEB 1x1 configuration gives 2.3 dB reduction from wake-filling

and 6.7 dB reduction from the liner for a total reduction of 9.0 dB. The ATEB 2x2 configuration

raises sound power by 0.6 dB due to wake filling and then reduces it by 7.6 dB with the liner for

a total reduction of 7.0 dB.

0

2.3

-0.6

5.5

6.7

7.6

-2

0

2

4

6

8

10

Liner Only ATEB 1-1 ATEB 2-2 TEB

Po

wer

Red

uct

ion

(d

B)

Wake-Filling Liner

5.5

9.0

7.0

(No Data)

Figure 5.6: [Inlet Duct, 28 Vanes] Sound Power Reductions from Wake-Filling and from Liner Attenuation.

This same method was used to attempt a study of the aft duct, but the author has little

confidence in the results. First, the liner performance was not a function of liner properties; all

liners in the parametric study returned attenuations within 0.2 dB of one another. Second, when

the liner on the ANCF was modeled to compare measured and predicted results the values

strongly disagreed. The author interprets these results as a failure to properly treat the modal data

or Eversman code, and not as evidence against the ATEB concept. The concept is expected to

apply to the aft duct for the same reason it applies to the inlet duct - the spreading of sound

power over a greater number of frequencies and modes makes liners more effective. Using the

Page 88: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

79

aft duct and 14 vanes the liner attenuations with no TEB, full TEB, ATEB 1x1, and ATEB 2x2

were 1.9 dB, 3.7 dB, 4.7 dB, and 9.1 dB, respectively. Using the aft duct and 28 vanes the liner

attenuations with no TEB and ATEB 2x2 were 1.5 dB and 4.7 dB, respectively.

Page 89: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

80

Chapter 6 : Conclusions

Trailing edge blowing (TEB) is a proven technique for reducing rotor / stator interaction

noise, but is made impractical by the amount of air required. A new implementation of TEB was

experimentally validated in this research. The concept "advanced trailing edge blowing" (ATEB)

applies selective wake-filling to achieve noise reduction with less air used. This is possible

because the modified spectral shape of interaction noise from advanced blowing layouts makes

acoustic liners more effective. The interaction noise is spread over more frequencies and modes,

behaving more like broadband noise and better matching liners' attenuation curves. This

compensates for decreased source-level reduction due to leaving some wakes unfilled.

Experiments were performed on the ANCF rig at NASA Glenn Research Center.

Microphone arrays were used in the far-field and in the rig ducts to measure sound pressure

levels. A hotwire probe was used to measure the velocity profile in the duct. Hardwall

configurations using no blowing, TEB, and ATEB were run to compare their noise reduction

capabilities. As expected the conventional TEB configurations gave more noise reduction than

the advanced configurations, but also used more air. Conventional TEB gave an average sound

power reduction of 7.7 dB while using 1.5% of the mass through the rig, and ATEB gave an

average sound power reduction of 3.0 dB while using 0.9% of the mass through the rig.

The performance of ATEB blowing used in combination with acoustic liners was

investigated using experimental data and numerical codes. Experimental data taken by in-duct

microphone arrays described the modal structure of noise inside the rig. This data was used with

the Eversman radiation code to find optimized liners for each blowing layout and their respective

attenuations. It was found that the ATEB configurations had the highest liner attenuations (i.e.

liner performance was increased). The liner attenuations using ATEB were an average of 2.6 dB

higher than the attenuations using no TEB and an average of 1.6 dB greater than the attenuations

using conventional TEB.

The work performed has validated the hypothesis that advanced trailing edge blowing

increases liner performance and can achieve noise reductions comparable to those of

conventional TEB while using less air. The total tonal sound power reduction predicted with

Page 90: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

81

TEB and a liner was 17.4 dB and required 1.5% of the mass flow through the rig. A total

reduction of 14.1 dB was predicted for ATEB and a liner, using only 0.9% air. Advanced

blowing layout make TEB more practical, using only 60% as much air.

The ATEB concept has been demonstrated by this research but issues remain unexplained

and ideas remain unexplored, providing the potential for future work. First, ATEB could be

tested on a high-speed rig or on a real engine. Second, different blowing layouts could be

investigated. For example, using a layout in which air is injected randomly rather than in a

pattern could produce interaction noise spread out over even more tones. This could further

increase acoustic liner performance. With increased liner performance the blowing rate could be

lowered while still providing similar overall noise reductions. Third, the potential for noise

reduction through destructive interference effects could be considered. Regions of positive and

negative upwash velocities may act as out-of-phase noise sources.

Page 91: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

82

References

[1] The Federal Aviation Administration, Office of Environment and Energy,

http://www.faa.gov/programs/en/impact/1976ANAP.

[2] Huff, D., "Technology Development for Aircraft Noise Alleviation," Presented to Hiller

Aviation Museum, NASA Glenn Research Center, Cleveland Ohio, December 2000.

[3] Lord, W., "Aircraft Noise Source Reduction Technology," Airport Noise Symposium,

Palm Springs California, March 2004.

[4] Rushwald, I. , "Continuing Work on Aircraft Noise Reduction," Aircraft Noise

Symposium, San Diego California, February 2002.

[5] Brookfield, J.M., Waitz, I.A., “Trailing Edge Blowing for Reduction of Turbomachinery

Fan Noise,” Journal of Propulsion and Power, Vol. 16, No. 1, pp. 57-64, 2000.

[6] Naumann, R.G., “Control of Wake from a Simulated Blade by Trailing Edge Blowing,”

Master’s Thesis, Lehigh University, Bethlehem, PA, 1992.

[7] Park, W.J., Cimbala, J.M., “The Effect of Jet Injection Geometry on Two-Dimensional

Momentumless Wakes,” Journal of Fluid Mechanics, Vol. 224, pp. 29-47, 1991.

[8] Corcoran, T.E., “Control of Wake from a Simulated Blade by Trailing Edge Blowing,”

Master’s Thesis, Lehigh University, Bethlehem, PA, 1992.

[9] Waitz, I.A., Brookfield, J.M., Sell, J., Hayden, B.J., “Preliminary Assessment of Wake

Management Strategies for Reduction of Turbomachinery Fan Noise,” Journal of

Propulsion and Power, Vol. 12, No.5, pp. 958-66, 1996.

Page 92: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

83

[10] Sell, J., “Cascade Testing to Assess the Effectiveness of Mass Addition/Removal Wake

Management Strategies for Reduction of Rotor-Stator Interaction Noise,” Master’s

Thesis, MIT, Cambridge, MA, 1997.

[11] Brookfield, J.M., Waitz, I.A., Sell, J., “Wake Decay: Effect of Freestream Swirl,” Journal

of Propulsion and Power, Vol. 14, No.2, pp. 215-224, 1998.

[12] Leitch, T.A., Saunders, C.A., Ng, W.F., “Reduction of Unsteady Stator-Rotor Interaction

using Trailing Edge Blowing,” AIAA Paper 99-1952, 1999.

[13] Rao, N.M., Feng, J., Burdisso, R.A., Ng, W.F., “Active Flow control to Reduce Fan

Blade Vibration and Noise,” AIAA Paper 99-1806, 1999.

[14] Sutliff, D., Tweedt, D., Fite, E., and Envia, E., "Low-Speed Fan Noise Reduction with

Trailing Edge Blowing", NASA Glenn Research Center, NASA/TM 2002-

211559,Cleveland, Ohio, May 2002.

[15] Sutliff, D., "Broadband Noise Reduction of a Low-Speed Fan with Trailing Edge

Blowing", NASA Glenn Research Center, AIAA-2005-3028, Cleveland, OH, May 2005.

[16] Heidelberg, L.J., Hall, D.G., Bridges, J.E., and Nallasamy, M., "A Unique Ducted Fan

Test Bed for Active Noise Control and Aeroacoustics Research," NASA TM-107213,

AIAA 96-1740. May 1996.

[17] Langford, M., Minton, C., and Ng, W., "Fan Flow Control for Noise Reduction Part 2:

Investigation of Wake-FillingTechniques", AIAA-2005-3026. Techsburg, Inc.,

Blacksburg, VA, May 2005.

[19] Morse, P. and Ingard, K. Theoretical Acoustics. Princeton: Princeton University Press,

1986. pp. 492-522.

Page 93: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

84

[19] Topol, D.A. and Matthews, D.C., "Rotor Wake / Stator Interaction Noise Prediction

Code, Technical and User's Manual," NASA Contract No. NAS3-25952 Report, April

1993.

[20] Arntz, D., Unpublished report "Advanced Trailing Edge Blowing Investigation",

Virginia Polytechnic Institute and State University, Blacksburg, Virginia, July 2003.

[21] Eversman, W., and Danada, R.L., "Ducted Fan Acoustic Radiation Including the Effects

of Non-Uniform Mean Flow and Acoustic Treatment," AIAA-93-4424, October 1993.

Page 94: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

85

Appendix A: Rake Data (First Test Entry)

This appendix presents tabulated sound power levels for cut-on modes measured with the

rotating rake arrays.

Table A.1: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall] 1xBPF

Table A.2: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall] 2xBPF

Table A.3: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, No TEB 0%, Hardwall] 3xBPF

Page 95: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

86

Table A.4: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall] 1xBPF

Table A.5: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall] 2xBPF

Table A.6: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, Full TEB 1.5%, Hardwall] 3xBPF

Page 96: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

87

Table A.7: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

0.5xBPF

Table A.8: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

1xBPF

Table A.9: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

1.5xBPF

Page 97: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

88

Table A.10: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

2xBPF

Table A.11: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

2.5xBPF

Table A.12: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

3xBPF

Page 98: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

89

Table A.13: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

0.25xBPF

Table A.14: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

0.5xBPF

Table A.15: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

0.75xBPF

Page 99: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

90

Table A.16: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1xBPF

Table A.17: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1.25xBPF

Table A.18: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1.5xBPF

Page 100: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

91

Table A.19: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1.75xBPF

Table A.20: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2xBPF

Table A.21: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2.25xBPF

Page 101: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

92

Table A.22: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2.5xBPF

Table A.23: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2.75xBPF

Table A.24: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

3xBPF

Page 102: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

93

Table A.25: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall] 1xBPF

Table A.26: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall] 2xBPF

Table A.27: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, No TEB 0%, Hardwall] 3xBPF

Page 103: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

94

Table A.28: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, Full TEB 1.5%, Hardwall] 1xBPF

Table A.29: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, Full TEB 1.5%, Hardwall] 2xBPF

Table A.30: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, Full TEB 1.5%, Hardwall] 3xBPF

Page 104: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

95

Table A.31: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

0.5xBPF

Table A.32: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

1xBPF

Table A.33: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

1.5xBPF

Page 105: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

96

Table A.34: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

2xBPF

Table A.35: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

2.5xBPF

Table A.36: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

3xBPF

Page 106: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

97

Table A.37: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

0.25xBPF

Table A.38: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

0.5xBPF

Table A.39: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

0.75xBPF

Page 107: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

98

Table A.40: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1xBPF

Table A.41: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1.25xBPF

Table A.42: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1.5xBPF

Page 108: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

99

Table A.43: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

1.75xBPF

Table A. 441: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2xBPF

Table A.45: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2.25xBPF

Page 109: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

100

Table A.46: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2.5xBPF

Table A.47: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

2.75xBPF

Table A.48: Rake Data Modal Sound Powers (dB) for [Aft Duct, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

3xBPF

Page 110: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

101

Table A.49: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, No TEB 0%, Hardwall] 1xBPF

Table A.50: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, No TEB 0%, Hardwall] 2xBPF

Table A.51: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, No TEB 0%, Hardwall] 3xBPF

Page 111: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

102

Table A.52: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

0.5xBPF

Table A.53: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

1xBPF

Table A.54: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

1.5xBPF

Page 112: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

103

Table A.55: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

2xBPF

Table A.56: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

2.5xBPF

Table A.57: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

3xBPF

Page 113: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

104

Table A.58: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

0.25xBPF

Table A.59: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

0.5xBPF

Table A.60: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

0.75xBPF

Page 114: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

105

Table A.61: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1xBPF

Table A.62: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1.25xBPF

Table A.63: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1.5xBPF

Page 115: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

106

Table A.64: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1.75xBPF

Table A.65: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2xBPF

Table A.66: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall] 2

2.25xBPF

Page 116: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

107

Table A.67: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2.5xBPF

Table A.68: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2.75xBPF

Table A.69: Rake Data Modal Sound Powers (dB) for [Inlet Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

3xBPF

Page 117: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

108

Table A.70: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, No TEB 0%, Hardwall] 1xBPF

Table A.71: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, No TEB 0%, Hardwall] 2xBPF

Table A.72: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, No TEB 0%, Hardwall] 3xBPF

Page 118: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

109

Table A.73: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

0.25xBPF

Table A.74: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

0.5xBPF

Table A.75: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

0.75xBPF

Page 119: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

110

Table A.76: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1xBPF

Table A.77: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1.25xBPF

Table A.78: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1.5xBPF

Page 120: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

111

Table A.79: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

1.75xBPF

Table A.80: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2xBPF

Table A.81: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2.25xBPF

Page 121: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

112

Table A.82: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2.5xBPF

Table A.83: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

2.75xBPF

Table A.84: Rake Data Modal Sound Powers (dB) for [Aft Duct, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

3xBPF

Page 122: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

113

Appendix B: First Test Entry Far-Field Results

This appendix lists all sound power level results for far-field experiments in the first test

entry. Shown in the tables below are the sound power spectra for each configuration. The power

of each interaction frequency is given along with the total power.

Table B.1: Sound Power at Each Interaction Frequency, Configurations using Inlet Duct and No TEB / Full

TEB.

Table B.2: Sound Power at Each Interaction Frequency, Configurations using Aft Duct and No TEB / Full

TEB.

Configuration 1 2 3 4 5 6 7 8 Total[Inlet, 0 Vanes, No TEB, Hardwall] 89.9 89.3 87.6 86.5 80.5 75.6 71.3 72.9 94.8[Inlet, 0 Vanes, Full TEB 1.1%, Hardwall] 90.6 93.3 89.4 95.7 90.1 75.3 72.0 79.4 99.6[Inlet, 0 Vanes, Full TEB 1.2%, Hardwall] 86.5 94.7 86.9 95.9 91.4 80.3 81.8 75.4 99.8[Inlet, 0 Vanes, Full TEB 1.3%, Hardwall] 89.5 91.2 90.4 96.3 93.3 78.1 80.8 73.7 100.0[Inlet, 0 Vanes, Full TEB 1.4%, Hardwall] 88.7 92.5 88.7 95.9 92.0 76.7 75.7 76.0 99.5[Inlet, 0 Vanes, Full TEB 1.5%, Hardwall] 85.9 90.9 92.2 95.4 89.8 78.5 77.4 71.9 98.9[Inlet, 0 Vanes, Full TEB 1.6%, Hardwall] 90.6 90.8 87.1 94.0 90.2 76.5 73.6 76.1 98.2[Inlet, 0 Vanes, Full TEB 1.7%, Hardwall] 89.3 92.4 87.6 94.1 89.5 76.2 73.3 79.1 98.3[Inlet, 0 Vanes, Full TEB 1.8%, Hardwall] 91.0 93.3 87.4 96.1 93.2 75.1 80.5 71.6 100.1[Inlet, 14 Vanes, No TEB, Hardwall] 106.7 103.2 100.9 92.3 88.7 81.0 79.1 75.9 109.2[Inlet, 14 Vanes, Full TEB 1.1%, Hardwall] 102.2 101.2 98.5 91.6 87.6 84.4 76.6 76.5 105.9[Inlet, 14 Vanes, Full TEB 1.2%, Hardwall] 101.2 99.8 97.1 90.5 87.4 84.1 76.3 76.9 104.8[Inlet, 14 Vanes, Full TEB 1.3%, Hardwall] 100.3 98.8 95.0 89.5 86.0 81.5 75.2 73.8 103.6[Inlet, 14 Vanes, Full TEB 1.4%, Hardwall] 99.7 96.5 91.9 89.1 84.2 79.0 73.2 73.0 102.2[Inlet, 14 Vanes, Full TEB 1.5%, Hardwall] 99.7 95.4 89.3 85.8 82.4 76.4 72.6 73.0 101.6[Inlet, 14 Vanes, Full TEB 1.6%, Hardwall] 101.9 95.1 90.9 85.4 79.8 73.6 74.8 70.2 103.1[Inlet, 14 Vanes, Full TEB 1.7%, Hardwall] 103.8 95.1 89.7 90.2 84.6 78.4 77.4 72.5 104.8[Inlet, 14 Vanes, Full TEB 1.8%, Hardwall] 104.7 97.2 93.5 90.5 87.7 79.3 79.4 73.7 105.9[Inlet, 14 Vanes, No TEB, Softwall] 106.6 99.1 92.3 89.4 81.8 76.0 77.2 66.1 107.5[Inlet, 28 Vanes, No TEB, Hardwall] 91.9 97.4 91.4 96.2 90.0 86.8 81.0 80.2 101.6[Inlet, 28 Vanes, No TEB, Softwall] 91.6 92.1 83.5 92.9 85.2 85.3 78.5 72.9 97.8

Blade Passing Frequency

Configuration 1 2 3 4 5 6 7 8 Total[Aft, 0 Vanes, No TEB, Hardwall] 95.0 88.4 93.4 86.8 79.5 81.7 77.4 76.0 98.4[Aft, 0 Vanes, Full TEB 1.1%, Hardwall] 86.4 85.8 91.8 88.0 82.9 81.1 74.6 69.6 95.2[Aft, 0 Vanes, Full TEB 1.2%, Hardwall] 85.3 84.6 90.6 85.3 83.4 82.9 77.3 73.2 94.2[Aft, 0 Vanes, Full TEB 1.3%, Hardwall] 85.0 82.3 92.2 88.1 80.2 83.8 74.8 73.3 95.1[Aft, 0 Vanes, Full TEB 1.4%, Hardwall] 86.2 83.9 91.9 88.5 82.1 82.9 73.5 73.7 95.2[Aft, 0 Vanes, Full TEB 1.5%, Hardwall] 85.0 80.5 90.7 85.2 82.3 83.5 75.9 71.7 93.8[Aft, 0 Vanes, Full TEB 1.6%, Hardwall] 86.6 84.2 92.0 87.5 83.9 81.8 74.3 74.6 95.2[Aft, 0 Vanes, Full TEB 1.7%, Hardwall] 86.3 83.4 91.2 87.7 83.1 81.7 76.2 74.3 94.7[Aft, 0 Vanes, Full TEB 1.8%, Hardwall] 86.4 84.7 92.3 87.8 79.6 82.9 75.9 72.3 95.3[Aft, 14 Vanes, No TEB, Hardwall] 101.4 104.1 110.6 97.4 91.3 89.2 88.4 80.9 112.1[Aft, 14 Vanes, Full TEB 1.1%, Hardwall] 104.5 103.6 107.4 96.6 95.3 88.0 84.5 76.4 110.6[Aft, 14 Vanes, Full TEB 1.2%, Hardwall] 103.9 102.6 105.6 95.6 94.1 87.1 84.3 76.7 109.3[Aft, 14 Vanes, Full TEB 1.3%, Hardwall] 103.8 100.9 103.3 94.4 92.9 85.4 83.1 72.6 108.0[Aft, 14 Vanes, Full TEB 1.4%, Hardwall] 103.7 98.0 98.6 92.3 90.5 82.1 80.6 72.8 106.0[Aft, 14 Vanes, Full TEB 1.5%, Hardwall] 102.9 95.1 94.4 89.7 87.5 81.9 78.2 68.6 104.3[Aft, 14 Vanes, Full TEB 1.6%, Hardwall] 103.3 92.1 95.8 85.2 81.9 82.9 73.3 69.5 104.4[Aft, 14 Vanes, Full TEB 1.7%, Hardwall] 101.3 95.6 102.3 90.3 87.3 87.6 80.3 75.8 105.6[Aft, 14 Vanes, Full TEB 1.8%, Hardwall] 99.7 100.3 106.9 93.1 89.8 90.0 82.3 78.1 108.7[Aft, 14 Vanes, No TEB, Softwall] 100.8 101.0 103.2 93.1 87.1 81.6 77.8 73.3 106.8[Aft, 28 Vanes, No TEB, Hardwall] 98.3 101.4 104.2 97.9 94.0 93.7 89.5 86.0 107.7[Aft, 28 Vanes, No TEB, Softwall] 94.2 95.8 96.4 95.4 88.0 85.6 78.9 81.2 101.9

Blade Passing Frequency

Page 123: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

114

Table B.3: Sound Power at Each Interaction Frequency, Configurations using Inlet Duct and ATEB 1x1.

Table B.4: Sound Power at Each Interaction Frequency, Configurations using Aft Duct and ATEB 1x1.

Configuration 0.5 1 1.5 2 2.5 3 3.5 44.5 5 5.5 6 6.5 7 7.5 8 Total

72.4 105.2 82.6 100.5 87.7 99.6 80.8 88.381.1 86.5 80.8 82.8 78.1 74.8 70.4 69.1 107.570.5 104.7 80.4 98.7 86.4 96.4 80.6 86.480.3 85.0 79.4 80.9 77.0 74.7 67.7 68.7 106.371.2 103.5 80.7 97.1 84.6 94.1 79.8 86.378.6 83.5 78.8 80.5 75.7 74.2 65.9 68.7 105.074.5 103.2 83.1 95.5 83.7 92.5 81.8 87.883.2 80.9 80.2 80.0 77.0 73.7 67.6 69.6 104.576.8 104.1 90.2 92.8 87.4 86.9 86.4 87.686.7 80.7 83.4 80.1 79.6 74.1 69.2 67.8 105.076.2 102.1 83.7 91.4 79.5 85.0 79.1 83.678.9 80.0 74.1 76.3 72.4 74.7 67.6 73.8 102.778.7 93.4 89.1 98.6 85.9 93.2 79.5 94.887.4 88.0 85.8 87.8 82.8 81.9 73.9 73.7 102.679.6 92.5 88.8 96.5 83.3 93.2 81.0 92.684.9 88.6 83.9 86.3 80.4 80.0 72.6 71.9 101.279.6 93.2 90.5 94.6 82.7 90.9 79.2 90.984.5 86.7 82.8 84.2 78.3 77.5 70.0 73.1 100.179.6 92.8 91.1 92.6 83.8 89.3 81.0 89.388.3 86.3 83.8 82.2 78.7 76.6 69.8 73.6 99.580.9 92.2 94.5 92.4 85.4 88.4 82.2 89.590.9 85.9 86.1 82.2 80.3 75.9 72.8 73.5 100.380.8 92.9 90.0 87.9 81.5 82.3 77.6 86.176.9 83.2 81.2 79.9 73.8 73.3 68.0 71.2 97.0

[Inlet, 28 Vanes, ATEB 1x1 0.8%, Hardwall]

[Inlet, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

[Inlet, 28 Vanes, ATEB 1x1 1.0%, Hardwall]

[Inlet, 28 Vanes, ATEB 1x1 0.9%, Softwall]

[Inlet, 14 Vanes, ATEB 1x1 1.0%, Hardwall]

[Inlet, 14 Vanes, ATEB 1x1 0.9%, Softwall]

[Inlet, 28 Vanes, ATEB 1x1 0.55%, Hardwall]

[Inlet, 28 Vanes, ATEB 1x1 0.7%, Hardwall]

[Inlet, 14 Vanes, ATEB 1x1 0.55%, Hardwall]

[Inlet, 14 Vanes, ATEB 1x1 0.7%, Hardwall]

[Inlet, 14 Vanes, ATEB 1x1 0.8%, Hardwall]

[Inlet, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

Blade Passing Frequency

Configuration 0.5 1 1.5 2 2.5 3 3.5 44.5 5 5.5 6 6.5 7 7.5 8 Total

78.8 103.6 88.4 104.1 85.7 109.0 94.4 96.491.5 92.6 84.3 86.7 83.9 77.8 78.5 76.5 111.579.5 102.9 86.1 101.4 88.7 105.8 91.6 93.889.6 91.0 83.1 85.5 83.0 77.4 76.6 72.4 109.080.5 103.3 93.5 98.5 86.6 102.9 90.3 92.389.2 88.2 82.2 84.3 81.0 76.4 74.5 72.5 107.582.8 101.9 98.9 95.6 86.9 99.9 91.1 91.891.6 85.8 83.2 83.3 81.8 78.0 76.4 74.6 106.384.8 100.5 102.7 90.1 91.2 98.2 92.8 90.894.9 85.0 86.9 82.7 84.2 81.4 80.5 75.5 106.783.5 101.9 95.2 91.2 83.4 91.4 77.1 88.478.4 78.1 76.8 77.6 74.8 73.0 74.3 72.1 103.683.6 94.3 89.1 97.6 88.2 104.0 89.5 94.894.7 89.4 89.5 91.4 84.0 81.2 84.0 83.3 106.682.5 93.7 87.4 95.3 89.6 102.6 87.8 91.492.1 87.1 87.7 89.5 79.7 80.5 81.3 80.1 105.081.0 93.7 96.6 92.8 89.2 100.7 87.7 91.192.8 84.6 86.3 87.6 78.7 80.1 79.2 76.3 104.379.1 93.9 102.4 92.8 90.1 99.3 89.5 92.795.3 83.5 87.7 88.0 81.6 81.0 79.8 76.4 106.080.3 94.5 105.5 93.1 93.0 97.5 92.1 93.698.2 84.4 90.0 88.9 84.9 83.2 81.3 76.8 107.984.8 92.0 100.0 87.2 78.0 92.0 81.4 88.286.0 77.5 78.2 78.3 73.8 74.3 71.0 71.8 101.9

[Aft, 28 Vanes, ATEB 1x1 0.8%, Hardwall]

[Aft, 28 Vanes, ATEB 1x1 0.9%, Hardwall]

[Aft, 28 Vanes, ATEB 1x1 1.0%, Hardwall]

[Aft, 28 Vanes, ATEB 1x1 0.9%, Softwall]

[Aft, 14 Vanes, ATEB 1x1 1.0%, Hardwall]

[Aft, 14 Vanes, ATEB 1x1 0.9%, Softwall]

[Aft, 28 Vanes, ATEB 1x1 0.55%, Hardwall]

[Aft, 28 Vanes, ATEB 1x1 0.7%, Hardwall]

[Aft, 14 Vanes, ATEB 1x1 0.55%, Hardwall]

[Aft, 14 Vanes, ATEB 1x1 0.7%, Hardwall]

[Aft, 14 Vanes, ATEB 1x1 0.8%, Hardwall]

[Aft, 14 Vanes, ATEB 1x1 0.9%, Hardwall]

Blade Passing Frequency

Page 124: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

115

Table B.5: Sound Power at Each Interaction Frequency, Configurations using Inlet Duct and ATEB 2x2.

Configuration 0.25 0.5 0.75 1 1.25 1.5 1.75 22.25 2.5 2.75 3 3.25 3.5 3.75 44.25 4.5 4.75 5 5.25 5.5 5.75 66.25 6.5 6.75 7 7.25 7.5 7.75 8 Total

82.7 67.4 91.7 105.6 76.5 79.9 89.6 101.088.5 71.6 88.5 98.6 91.1 75.7 85.8 88.383.6 74.6 82.2 86.9 79.7 70.6 80.4 78.178.1 68.5 76.5 74.8 73.8 64.3 71.7 69.8 108.182.6 70.1 92.9 104.7 73.6 79.0 88.9 97.885.3 73.7 87.4 94.0 87.1 73.2 83.9 88.681.7 75.5 80.0 87.0 77.0 70.0 79.4 76.775.5 67.1 75.3 76.5 71.7 63.3 68.5 71.0 106.579.1 72.0 92.8 104.7 75.6 81.1 89.0 96.485.2 73.2 86.2 93.1 83.8 75.4 81.9 87.978.9 75.9 79.7 85.4 75.2 70.7 78.7 77.973.7 67.0 73.7 78.0 70.3 62.1 65.7 71.4 106.283.9 70.6 93.5 105.1 79.3 81.8 88.9 93.589.0 76.0 85.6 89.4 85.7 71.7 80.3 88.779.7 74.5 77.2 85.8 76.6 70.0 78.6 79.374.1 66.3 74.1 78.3 70.7 62.9 63.5 73.3 106.283.9 71.8 95.6 106.0 82.6 78.1 90.5 94.391.0 71.3 87.0 89.8 90.2 74.5 84.1 88.682.5 74.3 77.6 85.6 79.9 73.1 80.0 82.175.3 69.4 75.5 79.4 71.6 62.8 65.4 74.6 107.381.7 63.8 90.3 104.3 73.7 76.8 84.1 95.979.8 66.3 86.4 88.4 85.4 70.5 78.9 86.578.4 70.1 73.8 80.3 80.1 63.3 74.9 74.172.3 63.8 72.2 72.0 67.6 57.4 66.6 63.5 105.481.8 69.0 90.8 103.5 75.1 75.4 84.0 92.078.4 67.9 84.8 86.8 81.1 69.0 77.6 84.675.9 71.1 73.5 79.9 77.1 64.8 73.6 72.869.9 62.3 70.1 73.9 66.8 58.7 64.3 62.1 104.481.9 67.2 90.3 103.2 76.9 77.5 84.6 89.778.2 69.5 83.1 85.4 77.4 69.8 75.5 84.772.1 70.9 71.8 80.5 73.6 64.8 71.0 75.269.0 61.9 69.1 73.8 65.2 57.5 63.4 66.9 104.081.4 68.0 90.7 103.4 78.5 77.8 85.5 88.679.4 70.3 82.1 84.6 78.5 69.2 77.1 84.774.2 70.8 70.8 78.3 73.6 65.7 71.7 75.168.7 62.8 69.2 74.0 65.2 59.0 61.6 66.3 104.184.8 72.7 93.3 104.2 81.7 74.8 88.2 95.782.4 73.7 84.5 89.9 84.8 71.2 81.8 85.779.1 68.8 74.5 79.9 76.6 67.5 74.4 79.071.3 67.0 71.5 74.9 67.9 59.7 64.3 67.6 105.6

[Inlet, 14 Vanes, ATEB 2x2 0.9%, Softwall]

[Inlet, 14 Vanes, ATEB 2x2 1.0%, Softwall]

[Inlet, 14 Vanes, ATEB 2x2 1.0%, Hardwall]

[Inlet, 14 Vanes, ATEB 2x2 0.55%, Softwall]

[Inlet, 14 Vanes, ATEB 2x2 0.7%, Softwall]

[Inlet, 14 Vanes, ATEB 2x2 0.8%, Softwall]

[Inlet, 14 Vanes, ATEB 2x2 0.55%, Hardwall]

[Inlet, 14 Vanes, ATEB 2x2 0.7%, Hardwall]

[Inlet, 14 Vanes, ATEB 2x2 0.8%, Hardwall]

[Inlet, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

Blade Passing Frequency

Page 125: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

116

Table B. 5: Sound Power at Each Interaction Frequency, Configurations using Inlet Duct and ATEB 2x2

(Continued).

Configuration 0.25 0.5 0.75 1 1.25 1.5 1.75 22.25 2.5 2.75 3 3.25 3.5 3.75 44.25 4.5 4.75 5 5.25 5.5 5.75 66.25 6.5 6.75 7 7.25 7.5 7.75 8 Total

81.6 69.0 82.4 95.3 76.8 75.8 90.5 95.497.9 74.1 84.8 92.8 88.1 77.1 87.9 93.489.1 78.5 91.5 84.9 80.8 74.8 82.0 83.881.2 71.8 79.7 75.9 82.3 71.3 71.7 72.2 103.879.5 69.1 80.5 96.2 77.4 78.1 90.0 94.396.4 73.3 85.5 92.7 86.1 76.2 88.6 92.986.7 78.2 90.1 87.2 79.2 74.5 81.3 81.779.2 71.4 76.7 76.1 80.4 70.3 70.3 72.8 103.279.6 67.3 79.6 96.2 80.6 81.2 90.0 93.495.2 73.9 83.6 91.8 84.9 77.4 86.9 92.083.7 77.3 87.8 86.3 76.5 75.5 79.5 81.077.8 69.9 74.1 76.3 79.1 69.1 66.7 75.8 102.481.0 70.1 76.7 95.8 81.9 84.8 90.5 93.497.7 71.7 81.8 91.4 85.1 76.6 85.3 92.884.0 73.3 86.3 86.0 74.3 74.8 78.1 81.877.7 70.6 73.8 76.5 79.1 68.4 67.6 77.5 102.982.0 67.8 73.6 95.7 83.3 86.1 92.7 97.5

101.7 77.2 85.4 91.0 86.7 78.4 87.8 94.787.2 75.2 84.3 87.7 75.0 74.8 79.6 83.178.2 71.0 75.2 77.5 78.5 70.1 68.9 77.0 105.480.2 69.5 83.2 93.0 69.4 71.3 85.5 92.387.4 71.6 74.5 83.7 82.4 74.5 83.9 90.287.6 70.3 75.3 78.3 81.3 72.2 80.4 80.478.4 73.0 71.3 75.5 78.7 70.5 69.7 69.8 99.080.4 67.6 82.3 92.5 69.7 72.3 85.1 90.885.7 71.2 75.6 83.7 80.7 73.8 81.8 88.883.9 70.2 75.3 80.1 78.6 72.3 78.2 78.075.7 72.1 70.2 76.1 77.2 67.4 67.0 64.5 97.980.5 70.9 81.1 92.8 72.8 75.1 86.0 91.283.3 71.7 75.1 83.6 78.8 73.3 80.7 87.581.6 70.0 72.6 81.5 76.7 72.2 76.6 77.773.7 70.8 68.8 72.9 76.2 65.8 63.7 66.5 97.679.9 68.7 80.1 92.8 76.8 79.0 87.5 93.285.7 71.9 76.0 84.9 79.4 74.2 78.8 86.781.0 67.8 71.9 81.6 75.0 71.7 76.0 75.873.6 68.7 67.4 74.0 74.9 65.4 60.4 69.2 98.379.2 68.0 78.7 93.3 78.7 80.9 90.1 97.388.8 71.5 76.4 86.1 80.6 74.9 81.3 87.983.0 67.6 70.7 83.9 74.9 71.2 78.0 78.376.1 66.1 68.1 74.2 74.8 66.4 63.1 71.7 100.7

[Inlet, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 0.9%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 1.0%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 0.9%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 1.0%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 0.55%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 0.7%, Hardwall]

Blade Passing Frequency

[Inlet, 28 Vanes, ATEB 2x2 0.55%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 0.7%, Hardwall]

[Inlet, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

Page 126: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

117

Table B.6: Sound Power at Each Interaction Frequency, Configurations using Aft Duct and ATEB 2x2.

Configuration 0.25 0.5 0.75 1 1.25 1.5 1.75 22.25 2.5 2.75 3 3.25 3.5 3.75 44.25 4.5 4.75 5 5.25 5.5 5.75 66.25 6.5 6.75 7 7.25 7.5 7.75 8 Total

78.9 69.9 90.8 104.1 80.2 86.2 92.0 102.491.4 81.1 95.3 108.4 91.0 79.7 90.3 95.489.0 80.6 91.6 93.2 83.2 76.3 85.5 84.386.0 72.7 81.1 81.2 80.0 71.1 78.9 74.4 111.280.1 74.6 96.8 103.9 77.6 85.4 89.7 100.191.2 81.2 92.9 105.2 89.3 80.6 88.8 93.886.2 81.6 89.3 90.6 80.0 77.6 83.3 84.083.8 74.5 78.4 82.2 78.5 71.6 76.7 72.2 109.379.1 74.6 99.3 103.6 78.2 87.8 88.1 98.593.9 84.0 91.6 103.8 90.4 81.6 87.1 93.482.7 82.3 87.2 89.1 77.3 77.7 82.1 85.182.8 75.5 76.1 83.0 76.6 72.5 74.2 75.7 108.781.4 72.4 103.0 101.6 79.7 87.6 89.8 97.396.5 80.4 92.3 102.6 92.4 79.5 87.0 94.485.0 81.1 86.5 88.8 77.0 78.2 80.8 87.283.0 74.2 74.1 84.0 76.1 72.1 72.1 76.9 108.783.5 74.8 106.5 100.6 82.5 89.6 94.1 99.399.3 81.3 96.0 105.5 95.7 81.9 90.6 95.488.7 82.0 89.6 90.9 81.1 77.6 84.0 88.983.9 74.9 77.1 86.1 80.3 71.9 74.4 79.7 111.279.2 74.7 90.2 103.1 79.4 84.7 89.0 99.080.4 76.0 79.0 101.2 85.1 73.2 84.1 93.578.3 71.0 81.7 83.4 74.3 70.0 77.6 80.881.6 69.1 76.8 74.6 76.5 64.8 72.3 69.6 106.875.9 77.0 95.3 102.8 77.6 83.5 86.1 96.580.4 76.6 79.0 98.4 83.1 73.0 82.7 91.674.4 71.6 80.6 81.4 73.3 69.3 75.8 81.579.4 68.8 75.6 77.2 75.1 67.9 70.5 69.0 105.773.5 75.4 98.6 102.1 78.0 85.6 85.5 94.384.5 77.8 76.2 96.1 83.5 74.0 81.1 91.575.2 72.3 77.7 81.1 71.5 68.4 73.7 81.678.0 68.6 72.7 74.6 73.2 67.3 67.0 71.3 105.377.0 76.5 101.9 100.8 80.1 85.2 87.9 92.985.5 76.5 76.5 95.4 84.0 68.6 82.7 90.678.7 70.1 76.9 80.8 74.6 69.6 72.3 83.076.6 66.9 68.7 73.7 73.3 66.9 65.4 70.1 105.680.1 77.3 106.0 100.0 84.2 86.8 93.0 94.289.1 76.0 81.4 99.1 87.0 70.9 87.2 91.481.9 72.5 78.2 83.2 78.1 68.5 76.7 84.878.3 68.5 70.9 73.2 74.1 68.9 70.8 73.6 108.3

[Aft, 14 Vanes, ATEB 2x2 1.0%, Softwall]

[Aft, 14 Vanes, ATEB 2x2 0.55%, Hardwall]

[Aft, 14 Vanes, ATEB 2x2 0.7%, Hardwall]

[Aft, 14 Vanes, ATEB 2x2 0.8%, Hardwall]

[Aft, 14 Vanes, ATEB 2x2 0.9%, Hardwall]

[Aft, 14 Vanes, ATEB 2x2 1.0%, Hardwall]

[Aft, 14 Vanes, ATEB 2x2 0.55%, Softwall]

[Aft, 14 Vanes, ATEB 2x2 0.7%, Softwall]

[Aft, 14 Vanes, ATEB 2x2 0.8%, Softwall]

[Aft, 14 Vanes, ATEB 2x2 0.9%, Softwall]

Blade Passing Frequency

Page 127: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

118

Table B.6: Sound Power at Each Interaction Frequency, Configurations using Aft Duct and ATEB 2x2

(Continued).

Configuration 0.25 0.5 0.75 1 1.25 1.5 1.75 22.25 2.5 2.75 3 3.25 3.5 3.75 44.25 4.5 4.75 5 5.25 5.5 5.75 66.25 6.5 6.75 7 7.25 7.5 7.75 8 Total

78.7 74.1 85.2 93.7 76.5 90.3 92.4 98.692.5 73.9 97.4 101.6 92.2 84.2 98.3 92.394.8 83.1 90.9 90.8 82.2 76.5 89.6 89.787.3 78.2 85.4 78.9 88.1 74.2 82.4 78.1 107.479.4 72.7 84.6 93.7 76.7 88.3 91.8 96.990.7 74.8 96.5 100.7 90.2 85.1 96.5 91.691.4 85.8 90.1 88.1 81.3 78.3 88.7 90.085.3 79.2 83.4 80.8 86.6 74.2 81.4 78.4 106.279.9 73.0 84.9 94.9 77.8 92.2 93.2 94.291.1 74.9 95.5 99.8 89.8 84.4 95.1 91.988.7 85.7 87.9 88.2 80.0 79.0 85.4 89.383.4 78.9 80.4 84.1 84.6 74.9 79.5 79.6 105.579.5 72.8 84.3 96.6 77.0 91.4 95.6 93.393.1 73.2 95.7 99.3 91.4 84.6 95.8 93.689.3 86.2 87.7 90.9 81.1 77.0 82.8 89.384.5 79.5 81.0 86.8 84.5 73.2 77.8 80.7 106.077.7 71.4 83.2 97.9 78.9 92.1 99.2 92.497.6 75.5 98.7 100.9 92.8 82.7 97.7 96.593.5 86.4 88.9 93.3 82.8 79.1 83.0 91.487.9 79.9 83.6 89.4 85.0 73.0 77.8 84.1 108.279.5 75.2 86.9 87.6 72.3 87.9 90.2 92.379.9 67.6 79.3 93.7 85.5 77.2 94.0 90.085.6 73.4 86.3 87.5 76.2 67.6 80.5 85.187.7 73.8 77.5 75.7 87.0 69.5 77.6 75.5 101.579.9 75.5 86.7 86.3 72.1 85.9 89.0 89.179.4 67.9 78.5 92.8 83.4 77.2 92.0 86.282.8 75.9 84.4 86.9 74.0 66.1 77.9 83.885.9 70.6 77.4 74.6 85.9 69.0 76.7 71.5 99.981.4 75.8 87.6 87.9 72.4 89.4 90.9 87.480.0 67.5 77.1 91.5 83.2 76.1 90.6 86.281.4 76.2 81.8 86.9 72.2 65.8 75.9 84.184.8 67.9 73.8 73.9 84.9 69.9 75.3 72.5 99.780.7 74.6 87.3 90.0 73.1 88.4 93.5 86.183.1 67.7 75.6 90.7 85.9 75.8 90.7 86.084.5 77.2 79.9 87.1 71.7 67.1 72.9 84.284.2 68.2 72.2 75.0 83.9 70.7 74.2 78.1 100.180.2 74.0 86.5 91.2 74.7 88.6 96.8 86.186.8 66.6 78.5 89.9 87.6 73.5 91.9 84.288.1 76.7 79.1 88.4 75.0 65.5 76.7 86.385.0 69.4 72.0 77.2 83.7 70.0 75.3 80.3 101.6

[Aft, 28 Vanes, ATEB 2x2 0.9%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 1.0%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 1.0%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.55%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.7%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.55%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.7%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.8%, Hardwall]

[Aft, 28 Vanes, ATEB 2x2 0.9%, Hardwall]

Blade Passing Frequency

Page 128: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

119

Appendix C: Second Test Entry Far-Field Results

This appendix lists sound powers for the second test entry. Configurations discussed in

the main body of the paper correspond to Tables C.1 and C.2.

Additional configurations are described in Tables C.3 through C.5. These configurations

were not required for the discussion of the ATEB concept, but are listed for completeness. One

set of configurations uses a blade-to-vane spacing of 1 chord instead of the 1/2 chord spacing

used in all of the other configurations. One set applies blowing air only to the suction side of the

blades. Four sets apply blowing to only part of the blade span. The blades for this test entry use

13 discrete jets on each side of the blade, and these jets can be opened or closed to control the

radial application of air. The pair of jets nearest the hub are called jets #1 and the pair of jets

nearest the tip are called jets #13. The configurations labeled "Tip Blowing" use only jets 10, 11,

12, and 13; this is done for both TEB and ATEB 1x1. The configurations labeled "Alternating

Jets" use only jets 2, 4, 6, 8, 10, and 12. The configurations labeled "Alternating Spans" use only

jets 1, 2, 3, 10, 11, and 12.

Page 129: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

120

Table C.1: Sound Power at Each Interaction Frequency, Configurations using No TEB and Full TEB.

Table C.2: Sound Power at Each Interaction Frequency, Configurations using ATEB 1x1.

Configuration 1 2 3 4 5 6 7 8 Total[Inlet Duct, No TEB] 106.6 104.0 100.6 95.6 91.5 81.7 76.4 75.4 109.4[Inlet Duct, Full TEB 0%] 106.5 105.2 102.0 96.0 90.1 83.3 79.8 77.7 110.0[Inlet Duct, Full TEB 0.31%] 106.3 104.9 100.7 95.0 91.2 81.9 79.0 73.3 109.5[Inlet Duct, Full TEB 0.39%] 105.2 103.6 99.9 93.5 89.4 79.7 77.8 72.7 108.4[Inlet Duct, Full TEB 0.45%] 104.6 102.1 98.6 91.0 87.9 77.3 78.6 72.6 107.3[Inlet Duct, Full TEB 0.52%] 103.1 99.7 95.6 89.5 86.8 78.7 77.1 71.5 105.5[Inlet Duct, Full TEB 0.57%] 102.9 97.3 89.1 90.0 87.4 79.4 76.3 70.2 104.4[Inlet Duct, Full TEB 0.65%] 102.7 97.8 89.1 90.4 87.5 80.1 75.6 70.3 104.4[Inlet Duct, Full TEB 0.72%] 103.3 99.9 94.5 92.2 88.1 81.2 76.2 71.9 105.6[Inlet Duct, Full TEB 0.74%] 104.0 101.9 95.6 92.0 88.6 81.4 75.5 72.1 106.7[Inlet Duct, Full TEB 0.76%] 104.7 103.9 98.5 93.3 89.2 81.1 77.7 74.0 108.1[Inlet Duct, Full TEB 0.79%] 106.1 105.5 100.4 94.9 89.9 82.5 78.6 73.1 109.6[Inlet Duct, Full TEB 0.83%] 106.9 106.8 101.2 94.6 90.3 81.3 77.4 72.4 110.6[Aft Duct, No TEB] 106.6 105.4 112.9 102.8 98.5 90.8 88.6 77.0 114.8[Aft Duct, Full TEB 0%] 106.7 106.2 113.6 102.6 96.8 92.0 88.8 83.6 115.3[Aft Duct, Full TEB 0.31%] 104.5 105.5 112.4 101.4 96.5 91.9 87.1 76.8 114.1[Aft Duct, Full TEB 0.39%] 103.8 104.3 111.2 99.5 96.4 90.4 85.2 74.7 112.9[Aft Duct, Full TEB 0.45%] 102.8 102.2 109.8 96.2 96.0 89.6 85.8 76.4 111.5[Aft Duct, Full TEB 0.52%] 103.8 97.9 107.5 92.7 93.3 88.3 85.7 74.9 109.6[Aft Duct, Full TEB 0.57%] 104.9 91.7 104.2 93.3 92.3 89.2 86.4 73.4 108.0[Aft Duct, Full TEB 0.65%] 106.0 94.7 100.9 94.5 91.9 88.8 86.2 72.5 107.8[Aft Duct, Full TEB 0.72%] 107.0 99.4 102.7 95.4 93.9 89.5 87.2 74.5 109.3[Aft Duct, Full TEB 0.74%] 107.7 103.1 106.1 96.1 93.5 89.8 87.8 74.2 111.0[Aft Duct, Full TEB 0.76%] 108.5 104.7 108.3 97.3 94.2 90.2 88.0 78.1 112.5[Aft Duct, Full TEB 0.79%] 109.3 106.3 110.4 98.1 94.2 91.6 88.2 77.7 113.9[Aft Duct, Full TEB 0.83%] 109.8 107.8 111.9 99.5 93.9 91.0 87.5 77.8 115.1

Blade Passing Frequency

Configuration 0.5 1 1.5 2 2.5 3 3.5 44.5 5 5.5 6 6.5 7 7.5 8 Total62.1 107.1 69.1 104.7 73.6 101.0 69.3 97.168.3 89.0 67.9 83.1 63.1 78.2 61.7 76.6 110.068.0 106.7 84.8 104.0 79.0 100.3 79.9 95.774.9 89.2 74.6 82.1 69.7 78.5 64.2 73.9 109.472.5 106.0 89.7 103.5 84.4 99.9 83.2 94.779.2 88.3 76.7 80.3 72.0 77.3 66.9 75.3 108.973.9 105.0 92.4 102.4 88.4 98.5 86.1 93.881.8 88.0 79.3 80.8 73.6 78.0 67.9 74.3 107.975.5 104.4 94.1 101.2 89.9 96.6 87.8 93.183.1 87.5 80.4 80.9 74.1 76.2 68.0 71.5 107.275.0 103.0 95.6 99.6 91.3 94.6 90.1 93.584.5 87.9 81.3 80.3 73.9 76.2 67.6 75.1 106.277.3 103.4 94.9 100.7 90.8 95.5 88.8 93.183.7 88.1 80.8 80.6 73.6 77.5 68.1 73.1 106.677.1 102.3 96.1 99.6 91.6 93.6 89.9 93.484.1 88.1 81.6 81.0 73.2 75.2 67.5 74.3 105.870.3 105.5 81.6 105.7 77.0 113.6 80.5 102.775.7 97.6 73.4 92.3 73.1 88.1 66.1 77.3 115.277.6 104.0 90.3 104.8 84.9 112.5 81.5 101.485.9 96.9 79.9 91.5 79.2 87.0 72.2 76.8 114.180.2 104.0 93.8 104.2 90.0 112.0 84.8 100.088.3 96.9 80.9 90.7 82.2 86.8 74.4 74.9 113.680.8 104.1 95.5 102.7 93.3 111.2 88.0 98.489.3 95.2 82.4 90.2 82.5 86.3 74.8 75.1 112.982.2 104.0 97.1 101.3 95.2 110.1 89.6 98.090.5 95.0 83.6 90.3 83.5 86.2 75.5 76.4 112.183.0 104.6 100.5 98.1 97.2 108.4 91.2 98.292.7 95.5 84.8 91.1 82.3 87.1 74.9 75.2 111.483.8 104.4 98.7 99.5 96.0 109.1 91.0 98.291.5 95.3 83.9 90.4 82.9 87.4 75.4 78.0 111.684.5 104.7 101.9 98.5 97.7 107.9 92.2 98.193.3 95.1 84.7 90.8 82.2 87.8 74.9 75.9 111.3

[Aft Duct, ATEB 1x1 0.41%]

[Aft Duct, ATEB 1x1 0.43%]

[Aft Duct, ATEB 1x1 0.32%]

[Aft Duct, ATEB 1x1 0.33%]

[Aft Duct, ATEB 1x1 0.35%]

[Aft Duct, ATEB 1x1 0.37%]

[Inlet Duct, ATEB 1x1 0.41%]

[Inlet Duct, ATEB 1x1 0.43%]

[Aft Duct, ATEB 1x1 0%]

[Aft Duct, ATEB 1x1 0.28%]

[Inlet Duct, ATEB 1x1 0.32%]

[Inlet Duct, ATEB 1x1 0.33%]

[Inlet Duct, ATEB 1x1 0.35%]

[Inlet Duct, ATEB 1x1 0.37%]

Blade Passing Frequency

[Inlet Duct, ATEB 1x1 0%]

[Inlet Duct, ATEB 1x1 0.28%]

Page 130: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

121

Table C.3: Sound Power at Each Interaction Frequency, Additional Configurations using Inlet Duct, Full

TEB.

Configuration 1 2 3 4 5 6 7 8 Total[Inlet Duct, Full TEB 0%, Vanes at 1 Chord] 110.3 107.0 100.5 91.0 87.8 80.3 76.4 71.6 112.3[Inlet Duct, Full TEB 0.44%, Vanes at 1 Chord] 106.9 104.5 98.3 87.1 86.4 79.8 77.6 69.8 109.3[Inlet Duct, Full TEB 0.58%, Vanes at 1 Chord] 102.4 101.2 95.5 86.5 84.2 79.3 76.9 71.7 105.4[Inlet Duct, Full TEB 0.66%, Vanes at 1 Chord] 93.8 94.8 89.3 90.3 86.2 79.0 77.7 72.2 99.0[Inlet Duct, Full TEB 0.67%, Vanes at 1 Chord] 96.0 97.4 92.8 89.0 85.7 79.8 76.0 71.8 101.0[Inlet Duct, Full TEB 0.74%, Vanes at 1 Chord] 93.6 94.0 88.7 91.0 86.9 79.6 76.9 71.7 98.7[Inlet Duct, Full TEB 0.78%, Vanes at 1 Chord] 97.8 96.9 91.3 90.5 85.6 79.2 75.1 70.9 101.4[Inlet Duct, Full TEB 0%, Suction Side Blowing Only] 106.5 105.1 100.9 96.1 90.1 83.1 78.0 74.3 109.8[Inlet Duct, Full TEB 0.31%, Suction Side Blowing Only] 106.6 104.9 100.8 96.0 90.9 81.6 79.2 73.1 109.7[Inlet Duct, Full TEB 0.31%, Suction Side Blowing Only] 106.2 104.3 99.3 95.0 90.5 81.8 78.1 72.0 109.1[Inlet Duct, Full TEB 0.32%, Suction Side Blowing Only] 105.4 103.6 99.4 93.5 89.3 80.2 77.2 73.2 108.4[Inlet Duct, Full TEB 0.38%, Suction Side Blowing Only] 104.8 103.0 98.5 91.8 87.0 78.0 76.1 71.0 107.7[Inlet Duct, Full TEB 0.41%, Suction Side Blowing Only] 103.9 101.9 97.0 88.3 84.9 78.6 74.1 71.6 106.6[Inlet Duct, Full TEB 0%, Tip Blowing] 106.8 104.5 101.2 95.9 91.1 81.6 76.2 73.3 109.8[Inlet Duct, Full TEB 0.24%, Tip Blowing] 106.6 102.8 100.5 95.4 90.8 79.5 76.0 76.5 109.1[Inlet Duct, Full TEB 0.32%, Tip Blowing] 105.7 96.9 94.9 94.4 91.5 79.0 75.5 76.1 106.9[Inlet Duct, Full TEB 0.33%, Tip Blowing] 106.1 101.0 98.8 95.2 91.4 80.0 75.6 75.8 108.2[Inlet Duct, Full TEB 0.41%, Tip Blowing] 105.2 95.9 93.5 94.6 92.0 79.9 75.6 75.2 106.4[Inlet Duct, Full TEB 0.42%, Tip Blowing] 104.9 98.2 93.4 95.8 92.1 82.1 76.7 76.0 106.5[Inlet Duct, Full TEB 0.42%, Tip Blowing] 105.0 97.6 92.1 94.7 92.4 80.0 75.4 76.4 106.4[Inlet Duct, Full TEB 0%, Alternating Jets] 106.1 104.5 100.7 95.6 90.4 81.2 78.5 76.4 109.3[Inlet Duct, Full TEB 0.29%, Alternating Jets] 105.2 103.6 99.8 94.9 88.9 80.4 75.9 75.8 108.4[Inlet Duct, Full TEB 0.35%, Alternating Jets] 103.8 102.7 98.7 92.6 89.1 79.7 77.5 76.5 107.2[Inlet Duct, Full TEB 0.39%, Alternating Jets] 102.2 99.7 93.1 93.9 89.5 80.2 77.6 72.0 105.0[Inlet Duct, Full TEB 0.39%, Alternating Jets] 102.2 100.5 94.2 93.3 88.9 79.6 76.2 75.7 105.3[Inlet Duct, Full TEB 0.44%, Alternating Jets] 101.0 99.3 91.4 93.2 89.5 79.7 77.7 76.7 104.1[Inlet Duct, Full TEB 0.44%, Alternating Jets] 100.4 99.1 90.7 93.1 89.3 80.4 76.1 74.1 103.7[Inlet Duct, Full TEB 0.45%, Alternating Jets] 100.0 99.7 92.4 93.4 89.9 80.0 75.7 75.7 103.9[Inlet Duct, Full TEB 0%, Alternating Spans] 106.9 105.6 102.5 95.9 91.4 82.7 76.8 74.7 110.4[Inlet Duct, Full TEB 0.33%, Alternating Spans] 103.8 98.9 96.0 93.3 88.1 81.6 75.9 72.9 105.9[Inlet Duct, Full TEB 0.36%, Alternating Spans] 103.2 97.9 95.3 93.7 88.1 82.8 75.0 74.3 105.3[Inlet Duct, Full TEB 0.42%, Alternating Spans] 102.5 97.0 95.8 94.1 89.2 81.8 75.0 74.3 104.8[Inlet Duct, Full TEB 0.42%, Alternating Spans] 101.6 97.0 95.6 94.3 88.5 80.8 72.6 76.1 104.2

Blade Passing Frequency

Page 131: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

122

Table C.4: Sound Power at Each Interaction Frequency, Additional Configurations using Aft Duct, Full TEB.

Table C.5: Sound Power at Each Interaction Frequency, Configurations using ATEB 1x1.

Configuration 1 2 3 4 5 6 7 8 Total[Aft Duct, Full TEB 0%, Vanes at 1 Chord] 99.3 109.6 109.4 92.7 87.9 83.1 76.7 73.7 112.8[Aft Duct, Full TEB 0.44%, Vanes at 1 Chord] 99.9 107.8 106.9 90.7 85.4 80.2 78.0 75.7 110.8[Aft Duct, Full TEB 0.58%, Vanes at 1 Chord] 99.0 104.4 104.1 87.7 83.6 80.1 76.7 73.7 107.9[Aft Duct, Full TEB 0.66%, Vanes at 1 Chord] 100.6 98.4 101.0 90.3 87.0 82.6 78.5 72.2 105.2[Aft Duct, Full TEB 0.67%, Vanes at 1 Chord] 99.7 100.1 101.4 89.5 85.2 80.0 76.9 71.8 105.4[Aft Duct, Full TEB 0.74%, Vanes at 1 Chord] 99.8 100.2 102.1 89.9 86.6 80.1 76.8 73.3 105.8[Aft Duct, Full TEB 0.78%, Vanes at 1 Chord] 100.6 103.6 104.4 92.7 86.9 82.6 77.7 71.9 108.1[Aft Duct, Full TEB 0%, Suction Side Blowing Only] 106.4 105.7 113.1 101.9 95.9 91.1 86.9 76.6 114.9[Aft Duct, Full TEB 0.31%, Suction Side Blowing Only] 105.1 105.0 112.4 101.4 97.2 91.7 87.6 76.8 114.1[Aft Duct, Full TEB 0.31%, Suction Side Blowing Only] 104.1 104.3 111.9 100.5 96.2 90.3 86.1 75.8 113.5[Aft Duct, Full TEB 0.32%, Suction Side Blowing Only] 104.0 103.8 111.3 99.1 95.5 88.5 84.4 75.8 112.9[Aft Duct, Full TEB 0.38%, Suction Side Blowing Only] 103.7 102.4 110.5 97.2 94.0 87.2 83.6 75.9 112.1[Aft Duct, Full TEB 0.41%, Suction Side Blowing Only] 103.8 101.1 109.5 93.9 94.4 86.0 81.9 74.8 111.2[Aft Duct, Full TEB 0%, Tip Blowing] 106.3 105.6 113.3 102.9 98.0 90.8 87.7 81.1 115.1[Aft Duct, Full TEB 0.24%, Tip Blowing] 105.9 104.6 111.8 101.9 97.6 90.4 87.4 78.5 113.9[Aft Duct, Full TEB 0.32%, Tip Blowing] 104.2 99.7 106.6 100.9 96.8 89.1 86.2 77.6 110.0[Aft Duct, Full TEB 0.33%, Tip Blowing] 104.9 102.6 109.8 101.1 96.7 90.0 86.8 78.5 112.1[Aft Duct, Full TEB 0.41%, Tip Blowing] 103.9 97.3 102.6 100.8 97.1 89.7 86.0 78.1 108.2[Aft Duct, Full TEB 0.42%, Tip Blowing] 103.3 96.5 99.9 100.4 97.2 90.3 85.5 77.7 107.3[Aft Duct, Full TEB 0.42%, Tip Blowing] 103.5 96.7 101.3 100.5 97.8 90.5 86.8 80.1 107.7[Aft Duct, Full TEB 0%, Alternating Jets] 106.3 105.1 112.6 102.7 96.7 90.7 88.5 80.1 114.5[Aft Duct, Full TEB 0.29%, Alternating Jets] 105.9 104.4 111.5 101.7 96.6 89.8 86.3 79.6 113.6[Aft Duct, Full TEB 0.35%, Alternating Jets] 105.2 102.0 110.1 99.2 94.0 88.3 87.2 78.2 112.1[Aft Duct, Full TEB 0.39%, Alternating Jets] 105.0 96.8 107.1 97.9 94.5 89.4 87.9 76.1 109.9[Aft Duct, Full TEB 0.39%, Alternating Jets] 105.2 98.3 107.8 97.8 95.0 89.0 87.1 78.2 110.5[Aft Duct, Full TEB 0.44%, Alternating Jets] 105.5 96.0 105.8 98.1 95.0 89.5 88.3 77.9 109.5[Aft Duct, Full TEB 0.44%, Alternating Jets] 105.6 96.2 105.6 97.6 95.1 90.0 88.1 76.9 109.4[Aft Duct, Full TEB 0.45%, Alternating Jets] 105.9 98.0 105.5 97.6 95.5 89.9 87.5 75.5 109.6[Aft Duct, Full TEB 0%, Alternating Spans] 105.6 105.9 113.4 102.1 96.2 90.6 87.7 78.6 115.0[Aft Duct, Full TEB 0.33%, Alternating Spans] 104.7 100.8 108.3 98.4 94.6 90.3 86.0 76.4 110.8[Aft Duct, Full TEB 0.36%, Alternating Spans] 105.0 99.5 107.4 99.0 94.4 91.2 86.9 76.4 110.4[Aft Duct, Full TEB 0.42%, Alternating Spans] 105.3 99.4 106.2 98.9 94.2 91.0 86.5 78.1 109.8[Aft Duct, Full TEB 0.42%, Alternating Spans] 105.8 99.7 105.7 98.6 94.7 90.8 85.8 77.3 109.8

Blade Passing Frequency

Configuration 0.5 1 1.5 2 2.5 3 3.5 44.5 5 5.5 6 6.5 7 7.5 8 Total66.9 106.4 71.3 104.2 71.4 100.7 70.8 94.867.1 91.3 62.6 79.8 63.4 78.8 61.6 75.2 109.371.7 105.9 77.5 102.5 80.0 99.1 80.8 95.576.5 91.4 68.1 80.4 65.2 79.2 62.7 75.5 108.571.3 105.8 77.8 101.7 81.1 98.3 82.2 94.9

76.705 91.256 67.523 80.667 65.06 79.122 64.192 74.419 108.176.2 106.3 80.2 105.3 75.6 112.9 80.0 103.077.1 97.2 68.9 89.9 72.4 88.7 67.1 77.3 114.877.1 105.5 90.5 103.5 88.1 111.3 82.7 102.783.9 97.0 76.7 90.3 76.4 88.9 69.8 80.1 113.478.3 105.2 93.7 102.7 89.6 110.8 83.4 102.484.7 97.2 76.0 90.6 75.8 88.5 70.6 80.6 113.0

[Aft Duct, ATEB 1x1 0%, Tip Blowing]

[Aft Duct, ATEB 1x1 0.21%, Tip Blowing]

[Aft Duct, ATEB 1x1 0.27%, Tip Blowing]

Blade Passing Frequency

[Inlet Duct, ATEB 1x1 0%, Tip Blowing]

[Inlet Duct, ATEB 1x1 0.21%, Tip Blowing]

[Inlet Duct, ATEB 1x1 0.27%, Tip Blowing]

Page 132: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

123

Appendix D: Initial Numerical Predictions

This appendix presents the results of running the V072 and Eversman codes to predict

ATEB performance in the absence of any experimental data. This is done to show the initial

conclusions used to justify experimental testing. These predictions model the liner used on the

ANCF. Work was performed to examine the results of optimized liners, but presenting this

would be redundant to the more rigorous treatment of Chapter 5.

Predictions using V072-Generated Wake Profiles

This first set of predictions was performed using wake profiles generated internally by

the V072 program. Any fan blade without TEB was assumed to produce the wake calculated by

V072. Any blade with TEB was assumed to produce no wake at all (this means that conventional

TEB on every blade could not be modeled using this technique). Velocity profiles for the ATEB

layouts were formed by combining wake profiles and profiles representing only freestream

velocities. This is explained in Figure D.1, which shows normalized relative velocities. Part (a)

of the figure shows the internally calculated wake spanning 22.5 tangential degrees (one blade

width). Part (b) shows the ATEB 1x1 profile spanning 45 degrees (two blade widths); there is

one wake profile covering 22.5 degrees and one "freestream" profile covering the other 22.5

degrees. Part (c) shows the ATEB 2x2 profile covering 90 degrees (four blade widths); two wake

profiles and two freestream profiles are placed side by side.

Page 133: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

124

Figure D.1: V072 Wake Profiles (at Blade Hub).

When (A)TEB is used in combination with acoustic liners, there are two sources of noise

reduction; the source-level reduction of wake-filling and also the reduction due to the liner. The

wake-filling reduction is defined as the difference in power between a hardwall configuration

with no blowing and a hardwall configuration with blowing. The liner reduction is defined as the

change in power when a liner is added to any configuration. Using this convention the results are

shown in Figure D.2. The green "liner only" bars represent liner reductions when ATEB is not

used. When ATEB is used some noise reduction is achieved by wake-filling, represented by the

blue bars. Liner performance changes when ATEB is used, with performance being increased in

seven of the eight configurations tested. The liner modeled was the liner physically present on

the ANCF; it is not optimized for this application. Optimized liner results are given in Chapter 5

of the main body of the thesis.

Page 134: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

125

Figure D.2: Wake-Filling and Liner Reductions for (a) Inlet Duct with 14 Vanes, (b) Aft Duct with 14 Vanes,

(c) Inlet Duct with 28 Vanes, (d) Aft Duct with 28 Vanes.

Predictions using CFD-Generated Wake Profiles

Another set of predictions was run using CFD-generated wakes rather than V072-

generated wakes. The benefit of doing this was that partially filled wakes could be used to

represent blades with TEB. This means that full TEB as well as ATEB configurations could be

run. The wake profiles were provided by Techsburg, Inc and are shown in Figure D.3. Part (a)

shows a wake from a blade with no TEB and part (b) shows the wake from a blade with TEB. It

is clear how TEB partially fills the wake deficit. ATEB profiles were formed by placing these

two profiles side by side.

Page 135: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

126

Figure D.3: CFD-Generated Wake Profiles for (a) No Blowing and (b) TEB.

The same format of presenting the results is used in Figure D.4, showing reductions from

wake-filling and from liner attenuation. Liner performance is lowest with no TEB (liner alone).

Liner performance increases when ATEB 1x1 or ATEB 2x2 is used. In these predictions, liner

performance is best with full TEB. This appears contrary to the ATEB concept, but happens here

only because the modeled liner has not been optimized for use with any given configuration. The

Page 136: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

127

liner optimization study of Chapter 5 shows that liner performance is in fact best when ATEB is

used.

Figure D.4: Wake-Filling and Liner Reductions for (a) Inlet Duct with 14 Vanes, (b) Aft Duct with 14 Vanes,

(c) Inlet Duct with 28 Vanes, (d) Aft Duct with 28 Vanes.

Page 137: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

128

Appendix E: Validation of Eversman Code Accuracy

The one liner used in the ANCF experiments was used to verify the predictions of liner

performance made by the Eversman code. To do this, experimentally measured hardwall in-duct

modal pressures were used as inputs to the Eversman Code. The code was first run with no

acoustic liner present to give a theoretical hardwall far-field power. The code was then supplied

with the impedance of the liner physically installed on the ANCF and run again to give a

theoretical softwall far-field power. The difference between these two predictions is the

theoretical liner attenuation. This is compared to the experimentally measured liner attenuation.

This comparison was made for 6 configurations, those of [Inlet Duct, 14 Vanes, No TEB 0%],

[Inlet Duct, 14 Vanes, ATEB 1x1 0.9%], [Inlet Duct, 14 Vanes, ATEB 2x2 0.9%], [Inlet Duct,

28 Vanes, No TEB 0%], [Inlet Duct, 28 Vanes, ATEB 1x1 0.9%], and [Inlet Duct, 28 Vanes,

ATEB 2x2 0.9%] (No softwall full TEB experimental data is available.) The predicted

attenuations were an average of 0.7 dB greater than the measured attenuations. Predicted

attenuations were either equal to or greater than measured attenuations, with the [Inlet Duct, 14

Vanes, No TEB 0%] configuration having the greatest theoretical-to-measured difference of 1.2

dB. The [Inlet Duct, 28 Vanes, ATEB 2x2 0.9%]configuration had the smallest difference of 0.0

dB. Figure E.1 shows predicted and measured liner attenuations for these 6 cases.

0

1

2

3

4

5

6

[14 V, NoTEB]

[14 V, ATEB1x1, 0.9%]

[14 V, ATEB2x2, 0.9%]

[28 V, NoTEB]

[28 V, ATEB1x1, 0.9%]

[28 V, ATEB2x2, 0.9%]

Lin

er R

edu

ctio

n (

dB

)

Experimental Farfield Theoretical Farfield

Figure E.1: Measured and Predicted Liner Reductions

Page 138: Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental Validation · 2020. 9. 25. · Advanced Trailing Edge Blowing Concepts for Fan Noise Control: Experimental

129

Vita

Christopher Halasz was born on June 20, 1981 in the suburbs of New Jersey. Upon

completion of high school he entered the College of Engineering at Virginia Tech in 1999. He

then entered the department of Mechanical Engineering in 2000, and as a senior began

performing undergraduate research in the field of acoustics. This led to the opportunity to pursue

a graduate degree in the same area, and immediately after graduating with a B.S. degree he

began his graduate studies as a research assistant in the Vibration and Acoustics Laboratory.