advocate energy checklist

Upload: crcodreanu382

Post on 02-Jun-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Advocate Energy Checklist

    1/9

    ENERGY MANAGEMENT

    OPERATIONAL

    CHECKLIST

    YORK CHAN, CHFM

    Advocate Health Care

    Oak Brook, IL

  • 8/10/2019 Advocate Energy Checklist

    2/9

    CHILLER PLANT AND AIR CONDITIONING

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1Cycle chill water on return temperature and resettemperature by wet bulb.

    2

    Utilize chiller load management program to stage

    chiller operations based on optimal efficiency

    3

    Brush condenser tubing and check water flowthrough bundles. Monitor temperaturegains/drops through bundle.

    4

    Convert primary chilled water loop to variablepumping based on differntial pressure utilizingvariable frequency drives and two way valvesinstead of three way valves

    5

    Adjust controls to stage compressors on amultiple stage system. Should automatic controlsnot exist, purchase and install. This will allow

    compressor #2 to cut in when compressor #1 canno longer satisfy space conditioning load

    6Clean condenser on air cooled systemsCondensers are maintained on a scheduledbasis.

    7

    Chiller evaporating and condensing temperaturesare not optimized. Decrease chiller condensingtemperature following manufacturersrecommendations

    8If system is forced air, using DX coils and aircooled condenser, install economizer cycle toobtain free cooling

    9 Clean Scale build-up in condenser on watercooled systems

    10 Clean evaporator coil, fins and tubes

    11Repair joint or piping leaks in chilled watersystem

    12

    Raise chilled water supply temperature. (NOTE:This is especially important if system wasdesigned for a 75F space temperature and thespace setting has been raised to 78F for energyconservation purposes.)

    COOLING TOWERS

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1Reset water temperature set point based on wetbulb temperature

    2Clean and flush tower(s) before seasonal start upand whenever needed during cooling season

    3Perform daily chemical testing of water in coolingtowers

    4Minimize water blow down by controlling solids tothe highest cycle of concentration

  • 8/10/2019 Advocate Energy Checklist

    3/9

    AIR HANDLERS

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1Convert to variable air volume system if thereheat coils are not necessary to supply heatduring the heating season

    2Reset discharge air temperatures based onreturn air temperatures

    3Minimize the usage of reheats and hot decksytems

    4

    Reset thermostats in common areas for seasonalchanges - e.g.: 75 degrees for Summer and 71degrees for Winter

    5Install time clocks to cycle air handler(s) andexhaust fan(s) off during non-occupied periods

    6

    Utilize magnahelic gauges, manometers ordifferential pressure sensors to monitor pressuredrops across air filters

    7

    Ensure that coils are maintained and cleaned toreduce fan horsepower to overcome resistance

    caused by plugged coils

    8

    Monitor and balance flow through cooling andheating coils for proper temperature gains ordrops -T

    9Ensure that dampers and damper operators arefunctioning properly

    10 Adjust damper linkage

    11 Readjust position indicators to accurately indicatedamper positions

    12 Adjust fan belt(s) tension to reduce deflection andslippage

    13 Make sure that air intake volume is not excessivewhile maintaining minimum requirements

    14Reduce outdoor air quantity to the minimumallowed by codes by adjusting outdoor airdampers during hours of occupancy

    15 Install time clocks or on-demand sensors to cyclekitchen exhast hoods

    16 Install time clocks on laboratory exhaust/fumehoods when not in use

    BOILERS/HEATING

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1

    Reduce steam pressure for summer operationand reset to higher pressure for winter operation.Example: summer 72 psi and winter 90 psi.

    2

    Account for all condensate return water. It takesless energy and chemical usage making steamwith 180 degree condensate instead of 40 degreecity water make up

    3 Pipe high pressure flash tank vent(s) to reclaimsteam into supply side

  • 8/10/2019 Advocate Energy Checklist

    4/9

    BOILERS/HEATING (continued)

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    4

    Monitor and maintain chemical treatment forboilers. This is crucial for proper boiler operationsand heat exchange.

    5Maintain the deaerator water supply to 215degrees for boiler feedwater

    6Install burner management system utilizing stacktemperature analysis to adjust fuel/air settings

    7 Test boiler combustion efficiency on a scheduledbasis

    8 Perform flue gas analysis on a regular basis toensure proper air to fuel ratio

    9 Purchase and install automatic staging controls, ifapplicable

    10 Adjust controls so that boiler #2 will not fire untilboiler #1 can no longer satisfy the demand

    11 Ensure that proper amount of air for combustion

    is available in furnace room

    12 Stack temperature appears excessively high(greater than 400F plus room temperature

    13 Examine and clean air intake filters

    14

    Check the temperature of the pipe on thedownstream side of steam traps. If it isexcessively hot, the trap probably is passingsteam. This can be caused by dirt in the trap, avalve off the stem, excessive steam pressure, orworn trap parts (especially valves and seats). Ifthe pipe is moderately hot (as hot as a hot water

    pipe), it probably is passing condensate, which itshould do. If its cold, the trap is not working atall, and should be replaced or repaired. Initiate asteam trap maintenance program

    15 If thermostatic trap is malfunctioning, clean orreplace bellows element

    16 Clean or replace thermostatic control valves onradiators

    17 Check air vent valve. If not operating properly,replace

    18 Water pockets may be obstructing steam flow.Correct by re-pitching or rerouting pipes

    19 Inspect pipes for broken or missing insulation.Repair or replace as needed

    20Install additional pipe insulation in accordancewith design specifications and energyconservation codes

    21

    Remove scale deposits, accumulation ofsediment and boiler compounds on water sidesurfaces. Examine and treat rear portion of boiler(the area most susceptible to scale formation)

    22 Remove soot from tubes

  • 8/10/2019 Advocate Energy Checklist

    5/9

  • 8/10/2019 Advocate Energy Checklist

    6/9

    LIGHTING (continued)

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    6

    Retrofit with more efficient lighting whereverpossible - High Pressure Sodium and MercuryVapor to Compact Flourescent or LED

    7 Replace incandescent "EXIT" signs with LEDsigns

    8Retrofit incandescent "EXIT" signs with LEDlamps

    9Establish a regular inspection and cleaningschedule for lamps and luminaires (fixtures). Dustbuildup reduces effectiveness

    10Replace lens shielding that has turned yellow orhazy with new acrylic lenses which do notdiscolor

    11 Replace outdated or damaged luminaires withmodern typed that are easy to clean

    12 Establish a group re-lamping schedule tominimize single lamp replacements.

    13Clean ceiling and wall surfaces for goodreflectance

    14 Clean windows and skylights

    15Disconnect ballasts, which still use significantamount of energy even though tubes have beenremoved

    16

    Consider not replacing burned out bulbs orlamps, and disconnecting ballasts in areas wheredelamping is possible. For example, in four-lampfixtures allow two lamps to remain, disconnecting

    appropriate ballasts.

    17 Replace burned out lamps with lower wattagelamps.

    HVAC CONTROLS

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1 Control devices and sensors are inspected andcalibrated on a regular basis

    2Overrides are not allowed on Building AutomationSystem except on a temporary basis

    3

    Change the location of thermostats from areas

    subject to extreme temperature fluctuations, suchas next to window, or over a heating or coolingunit

    4Utilize building automation system to control allspaces in accordance with usage

    5 Reset thermostats to correct settings

    6 Install or replace locking covers on thermostats toprevent tampering

    7 Install pre-set solid-state electronic thermostats ifexisting controls are electric

  • 8/10/2019 Advocate Energy Checklist

    7/9

    HVAC CONTROLS (continued)

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    8 Relocate thermostats in return air ducts wherethey will be inaccessible to occupants

    9Blow out moisture, oil and dirt form pneumaticlines (for pneumatic systems); clean contacts ifelectrical control system.

    10 Recalibrate controllers

    11 Ensure that control valves and dampers aremodulated properly

    12 Adjusted thermostats to 68F in heating seasonand to 78F during cooling season

    13 For electric control system, install pre-set solid-state thermostats which do not require calibration

    14

    Routinely check all time clocks and other controlequipment for proper operation, correct time andday and for night and proper programming of on-off set points. Protect from unauthorizedadjustment

    15

    For unoccupied area, Reduce thermostat settingsby a minimum of 10F at nights, weekends andholidays during heating season, but maintainventilation.

    16 Reduce winter thermostat settings to 55F inunoccupied areas

    17 Where possible, turn off heating systems ifnothing in space can freeze

    18 Use spot heaters/coolers in large spaces with lowoccupancy

    19 Increase summer thermostat setting, inunoccupied areas, if possible

    20Heating/cooling equipment is started beforeoccupants arrive and/or is operating during lasthour of occupancy

    21 Properly adjust and balance air/water systemsand controls

    BUILDING ENVELOPE

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1Realign or re-hang windows or doors that do notclose properly. In extreme cases, considerpermanent sealing of windows

    2 Ensure that automatic door closing mechanismswork properly

    3 Replace or repair faulty gaskets in garage or onother overhead doors

    4 Install self-closing doors on openings tounconditioned spaces

    5 Assure that automatic door closers functionproperly

    6 Install vestibule doors at major entrances

  • 8/10/2019 Advocate Energy Checklist

    8/9

    BUILDING ENVELOPE (continued)

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    7 Replace worn and/or broken weather-strippingand caulking

    8 Replace broken or cracked windows to minimizeair leakage.

    9

    Where practical, cover all windows and through

    the wall cooling units when not in use. Speciallydesigned covers can be obtained at relatively lowcost

    10In areas with constant strong winds, install windscreens to protect exterior doors from direct blastof prevailing winds

    11 Install double or triple paned windows

    12 Add reflective or heat absorbing film to minimizesolar gain in summer and heat loss in winter

    13 Install adjustable outdoor shading devices

    14 Attach storm glazing to moveable sash ofoperable windows

    15 Ceiling/roof insulation is inadequate or has beenwater damaged

    16

    Add new insulation to meet recommendedstandard. (check the cost effectiveness of thismeasure particularly if your facility is over threestories.)

    17

    Use blinds and curtains to help insulate thebuilding. Instruct personnel to close interiorshading devices to reduce night heat loss inwinter and to reduce solar heat gain during thesummer.

    18

    Repair or replace damaged or missing shading

    devices19 Install outdoor shading devices where applicable

    VENTILATION

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    1

    Check ductwork for any obstructions such asloose hanging insulation (in lined ducts), looseturning vanes and accessories, and closedvolume and fire dampers. Adjust, repair orreplace as necessary.

    2

    Inspect all room air outlets and inlets (diffusers,

    registers and grilles). They should be kept cleanand free of all dirt and obstructions. Clean andremove obstructions as necessary.

    3 Clean or replace dirty or ineffective filters on aregular basis

    4Large spaces having low occupancy aremaintained at comfort conditions. Reduce overallventilation in space.

    5 Repair any malfunctioning ventilation equipment

  • 8/10/2019 Advocate Energy Checklist

    9/9

    VENTILATION (continued)

    ENERGY CONSERVATION MEASURES LOCATION YES NO PART COMMENTS

    6 Replace old style dampers with new high qualityopposed-blade models with minimal leakage.

    7Close outdoor air dampers when building isunoccupied. Be sure dampers have proper sealsand adjust to ensure complete closure

    8 Whenever possible, use outside air for coolingrather than using refrigeration

    9 Install an economizer cycle with enthalpy controlto optimize use of outside air for cooling

    10 Discontinue use of unnecessary exhaust fans

    11 Re-wire restrooms' exhaust fans to operate onlywhen lights are on

    12 Establish schedules so that exhaust fans run onlywhen needed

    13

    Group smoking and other areas with similarexhaust requirements so that they may be served

    by one exhaust system. Reduce ventilation inremaining non-contaminated areas

    14Install time clocks or other controls to shutoffexhaust system when not needed (whenpermitted by code)

    15Install a rheostat in series with exhaust fan tomodulate fan speed so that no more than thenecessary amount of air will be exhausted

    16Install chemical or electronic odor or particulateremover to reduce the need for using outside airfor ventilation

    17Install controlled or gravity dampers on allexhaust ducts to close ducts when fan is notoperating

    18Repair damaged or missing pipe and ductinsulation

    19 Repair leaks in ductwork and piping

    20 Clean air inlet and outlet diffusers and grills

    21Inspect fire/smoke dampers, turning vanes,sound attenuators. Clean and/or repair asnecessary.