ae 9000 users manual with printer interface.pdf

32
AE9000 User Manual 1 AE-9000 DIGITAL MULTIFUNCTION METER Automatic Electric Ltd. Document Number 236-103000-02 February, 2012 Revision: AEL/ENG/004 Automatic Electric Ltd. Rectifier house,570, Naigum Cross road, Wadala, Mumbai – 400031, Maharashtra, India. Phone: 091-22 -24131849 / 24151794 / 24162261. Fax:091 – 22-24112582 Mail:[email protected] Web: www.aelindia.com

Upload: bhushan-pawar

Post on 14-Apr-2015

164 views

Category:

Documents


8 download

DESCRIPTION

as

TRANSCRIPT

Page 1: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

1

AE-9000 DIGITAL MULTIFUNCTION METER

Automatic Electric Ltd.

Document Number 236-103000-02 February, 2012

Revision: AEL/ENG/004

Automatic Electric Ltd. Rectifier house,570, Naigum Cross road, Wadala, Mumbai – 400031, Maharashtra, India. Phone: 091-22 -24131849 / 24151794 / 24162261. Fax:091 – 22-24112582 Mail:[email protected] Web: www.aelindia.com

Page 2: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

2

This document contains information that is the property of Automatic Electric Ltd. This document may not be copied, reproduced, reduced to any electronic medium or machine-readable form, or otherwise duplicated, and the information herein may not be used, disseminated or otherwise disclosed, except with the prior written permission of Automatic Electric Ltd. Automatic Electric Ltd reserves the right to revise the documentation and to make changes in content from time to time without obligation on the part of Automatic Electric Ltd to provide notification of such revision or change.

Office: - Work:- Automatic Electric Ltd. Automatic Electric Ltd. Rectifier house,570, Naigum Cross road, 96,Lonavala Industrial Estate, Wadala, Mumbai – 400031, Maharashtra, India. Nangargaon, Tel: 091-22 -24131849 / 24151794 / 24162261. Lonavala-410401, Maharashtra, India. Fax: 091 – 22-24112582 Tel: +91-2114-311331. Mail: [email protected] Fax: +91-2114-311331. Web: www.aelindia.com Mail: [email protected]

Page 3: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

3

Table of Contents 1. Introduction............................................................................................................... 4 2. Keypad Operation..................................................................................................... 4

2.1. Mode Key............................................................................................................ 4 2.2. Navigation Keys.................................................................................................. 4 2.3. Enter key ............................................................................................................. 5

3. Display........................................................................................................................ 5 3.1. Run Mode........................................................................................................... 5 3.2. Configure Mode ................................................................................................ 9 3.3. Display Previous Energies . ............................................................................. 12 3.4. Select Pages for Auto Scroll Display......................................................... …... 14 3.5. Testing Mode .................................................................................................... 14

4. Reference Standards……………………………………………………………….. 15 5 . Assembly, Service and maintenance …………………………………………….. 15 5.1 Assembly………………………………………………………………………… 15 5.2 Service…………………………………………………………………………. 16 5.3 Maintenance…………………………………………………………………… 17 6. Packing, Transport and Storage………………………………………………….. 17 6.1 Packing………………………………………………………………………… 17 6.2 Transport……………………………………………………………………… 17 6.3 Storage……………………………………………………………………….. 17 7. Service and Warranty……………………………………………………………... 17 7.1 Service………………………………………………………………………… 17 7.2 Warranty……………………………………………………………………….. 18 8. Specifications ………………………………………………………………………. 19 9. MODBUS Communications: ................................................................................... 20

9.1. Writing Configuration Parameters (except CTR/PTR ratio): ........................... 20 9.2. Reading Configuration Parameters: .................................................................. 20 9.3. Writing configuration parameter for CTR/PTR ratio: ...................................... 21 9.4. Reading Parameters Online: ............................................................................. 24 9.5. Reading Logged Data: ...................................................................................... 26 9.6. Reading Interruption Data: ............................................................................... 27 9.7. Power on interruption ....................................................................................... 28

10. Installation Instruction…………………………………………………………… 28 10.1 Mechanical Installation ……………………………………………………... 28 10.2 Electrical Installation………………………………………………………... 29 10.3 Wiring Diagram …………………………………………………………….. 29 11. Ordering Information ……………………………………………………………. 30

Page 4: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

4

1. Introduction The AE-9000 (multifunction meter-MFM) will compute, store and display and print various parameters, in single phase or three phase 3-wire/4 wire systems. Stored parameters/ data can be accessible to user through RS485 interface. The AE-9000 (multifunction meter-MFM) along with AE-prin will print the On-Off time for the previous day, Total On Time and Total Active energy for the previous day as well as Total On time and Total Active energy of previous month. This is useful function for the DG monitoring.

This document provides detailed steps for the user in order to set-up and operates the system. The user can also edit the configuration during run time and view the current configuration details on 7 segment LED display panel using a 5 key keypad, which are described in this document. The user may also configure and view parameters remotely via MODBUS communication.

2. Keypad Operation

The keypad for AE-9000 consists of total 5 keys. 1. Mode Key (M) 2. Up Navigation Key (▲) 3. Down Navigation Key (▼) 4. Right Navigation Key (►) 5. Enter Key (E)

2.1 Mode Key

Pressing the Mode Key, enables menu for selecting mode of operation from the following: 1. SET 1 i.e. Run Mode 2. SET 2 i.e. Configure Mode 3. SET 3 i.e. Display Previous Energies 4. SET 4 i.e. Select Auto Scroll Pages 5. SET 5 i.e. Testing Mode

Note: Pressing the Mode Key in any of the above mentioned modes display the mode selection menu again.

2.2 Navigation Keys (▲▼►)

The Up Navigation and Down Navigation keys are used to scroll through display pages in the Run Mode, and increment and decrement the value at current cursor position in

Page 5: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

5

Configuration Mode respectively. The Right Navigation key is used for scrolling to the immediate right cursor position from the current cursor position in Configuration Mode and to start auto scrolling in run mode.

2.3. Enter key(E)

The Enter Key is used to select a particular menu option in the Mode of Operation display Page. In Configuration Mode, the key is used to select a menu option as well as to confirm a particular value to be set.

3. Display

The AE-9000 display has different behavior in all the operating modes described as follows:

3.1. SET1 - Run Mode In Run Mode, the MFM displays various parameters in separate pages as follows:

i. Page1: Avg. Voltage, Avg. Current, Avg. Power Factor.

LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8.

LED’s: V, I, Pf.

ii. Page2: Line to Neutral Voltages of all three phases.

LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8.

LED’s: V, R, Y, B

iii. Page3: Line to line Voltages of all three phases. LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8.

LED’s: V, RY, YB, BR

iv. Page4: Current for all three phases.

LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8.

Page 6: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

6

LED Row 3 : 8.8.8.8.

LED’s: I, R, Y, B

v. Page5: Avg. Freq., Neutral Current, THD % LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8. LED’s:

F, NI, THD

vi. Page6: Pf. For all three phases. LED Row 1 : -1.8 8 8 LED Row 2 : -1.8 8 8 LED Row 3 : -1.8 8 8

LED’s: Pf., R, Y, B

vii. Page7: Total Power Active, Apparent, Reactive.

LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8. (M/k)

LED’s: TOT, W, VA, VAR

viii. Page8: Total Active Energy (Import+Export).

LED Row 1 : 8.8.8.8.(M/k) LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: Wh, TOT

xi. Page9: Total Apparent Energy (Import+Export). LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: VAh, TOT

x. Page10: Total Reactive Energy (Import+Export). LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: VArh, TOT

Page 7: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

7

xi. Page11: Total Run Hours (Import+Export). LED Row 1 : run.h LED Row 2 : 8.8.8.8. LED Row 3 : LED’s: TOT

xii. Page12: Phase Angle for all three phases. LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8.

LED’s: φ, R, Y, B

xiii. Page13: Phasor Angle for all three phases.

LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8.

LED’s: φ, RY, YB, BR

xiv. Page14: Active Power of all three phases.

LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8. (M/k)

LED’s: W, R, Y, B

xv. Page15: Apparent Power of all three phases. LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8. (M/k)

LED’s: VA, R, Y, B

xvi. Page16: Reactive Power of all three phases. LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8. (M/k)

LED’s: VAR, R, Y, B

Page 8: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

8

xvii. Page17: Active Energy (Import). LED Row 1 : 8.8.8.8.(M/k) LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: Wh, Imp

xviii. Page18: Apparent Energy (Import). LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. LED Row 3 : LED’s:

VAh, Imp

xix. Page19: Reactive Energy (Import). LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8.

LED Row 3 : LED’s: VArh, Imp

xx. Page20: Run Hours (Import). LED Row 1 : run.h LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: Imp

xxi. Page21: Active Energy (Export).

LED Row 1 : 8.8.8.8.(M/k) LED Row 2 : 8.8.8.8. LED Row 3 : LED’s:

Wh, Exp

xxii. Page23: Apparent Energy (Export). LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: VAh, Exp

Page 9: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

9

xxiii. Page22: Reactive Energy (Export). LED Row 1 : 8.8.8.8. (M/k) LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: VArh, Exp

xxiv. Page24: Run Hours (Export). LED Row 1 : run.h LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: Exp

xxv. Page25: Maximum Demand

LED Row 1 : 8.8.8.8. LED Row 2 : 8.8.8.8. LED Row 3 :

LED’s: W, VA

xxvi. Page26: On Hours

LED Row 1 : On.h LED Row 2 : 8.8.8.8. LED Row 3 :

The pages can be manually cycled through, by pressing the Navigation Up and Navigation Down keys in Manual Scroll Mode. The Pages can also be displayed in auto scroll mode with a scroll rate of 5 sec. per page by default. The Pages to be displayed in Auto Scroll Mode will be configurable by the user through Key pad. In manual scroll mode, all pages will be displayed. To switch from manual scroll mode to auto scroll mode, press the “Right Navigation”.

3.2. SET 2 - Configuration Mode

In the configuration mode, following parameters can be configured to user selected values. Press MODE (M) key to enter into the MODE Menu. To select Configuration mode Scroll down through the menu using Navigation Up and Navigation Down keys and go to the SET2 then press Enter key(E) to enter into the Configuration Mode. User must enter the Password for further configuration then select desired parameter and press enter to configure that parameter. Scroll through

Page 10: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

10

the digits using the Navigation Right key, change the values using Navigation Up and Navigation Down keys to increment and decrement the value respectively, and press Enter Key to confirm the value for the selected parameter to select any configuration parameter use UP & Down key. Once a parameter is set, then press MODE (M) key two times to exit from Configuration Mode.

i. P h a s e , Three phase.

LED Row 1 : PhAS LED Row 2 : 3 Ph. LED Row 3 :

ii. St a r connection, Delta connection

LED Row 1 : con LED Row 2 : StAr. LED Row 3 :

Note:- This Page is not present in single phase operation

iii. Primary CT ratio . LED Row 1 : CtPr LED Row 2 : 8.8.8.8.

LED Row 3 : 8.8.8.8

iv. Secondary CT ratio. LED Row 1 : CtSE LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8

v. Primary PT ratio .

LED Row 1 : PtPr LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8

vi. Secondary PT ratio.

LED Row 1 : PtSE LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8

vii. Sc r o l l time. (Min-3 sec to Max-10 sec in 1 sec steps)

LED Row 1 : Scr.t. LED Row 2 : 8.8. LED Row 3 :

viii. Set integration time period.(Min.-5 minutes to Max-30 minutes in 1 minute steps)

LED Row 1 : Int.P. LED Row 2 : 8.8. LED Row 3 :

Page 11: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

11

ix. Se t data logging time period.(Min-1 minute to Max-120 minutes in 1 minute step)

LED Row 1 : LOG.P. LED Row 2 : 8.8.8. LED Row 3 :

x. RS485 network ID

LED Row 1 : n.I.d. LED Row 2 : 8.8 (Hex Value) LED Row 3 :

xi. R e mot e T e r mi n a l U n i t e

LED Row 1 : rtu LED Row 2 : on LED Row 3 :oFF

xii. Re s e t Energies

LED Row 1 : rES.E. LED Row 2 : y LED Row 3 : n

xiii. Se t user password.

LED Row 1 : PSd. LED Row 2 : 8.8.8.8. LED Row 3 : 8.8.8.8.

xiv. Set Date. LED Row 1 : dAtE. LED Row 2 : 8 8.8 8. LED Row 3 : 8 8 8 8.

xv. S e t Time. LED Row 1 : tIM. LED Row 2 : 8 8.8 8. LED Row 3 :

xvi. Voltage/ Current THD.

LED Row 1 : thd LED Row 2 : LED Row 3 : C

xvii. UART baud rate

LED Row 1: b.r. LED Row 2 : 48.96.

LED Row 3 : 19.38. xviii. P r i n t D a t a

Page 12: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

12

LED Row 1: P r n t LED Row 2 : r E P t

LED Row 3 :

3.3. SET 3 - Display Previous Energies

In this mode, user can view the Active/Reactive/Apparent Energies, before the energies w e r e reset. User can scroll through the pages using the Up Navigation and Down Navigation keys. The pages displayed in this mode are as follows:

i. Page1: Previous Active Energy (Import).

LED Row 1: Pr.En. LED Row 2: 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: Wh, Imp

ii. Page2: Previous Apparent Energy (Import). LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: VAh, Imp

iii. Page3: Previous Reactive Energy (Import). LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: VArh, Imp, Lead/Lag

iv. Pa ge 4 : Previous Run Hours (Import). LED Row 1 : Pr.En. LED Row 2 : run.h LED Row 3 : 8.8.8.8.

LED’s: Imp

v. Pa ge 5 : Previous Active Energy(Export).

LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k)

Page 13: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

13

LED Row 3 : 8.8.8.8.

LED’s: Wh, Exp

vi. Pa ge 6 : Previous Apparent Energy(Export). LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: VAh, Exp

vii. Pa ge 7 : Previous Reactive Energy (Export). LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: VArh, Exp

viii. Page8 : Previous Run Hours (Export). LED Row 1 : Pr.En. LED Row 2 : run.h LED Row 3 : 8.8.8.8. LED’s:

Exp

ix. Pa ge 9 : Previous Total Active Energy (Import + Export). LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: Wh, TOT

x. Pa ge 10 : Previous Total Reactive Energy (Import+Export).

LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k) LED Row 3 : 8.8.8.8.

LED’s: VArh, TOT

xi. Pa ge 11 : Previous Total Apparent Energy (Import+Export).

LED Row 1 : Pr.En. LED Row 2 : 8.8.8.8. (M/k)

Page 14: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

14

LED Row 3 : 8.8.8.8.

LED’s: VAh, TOT

xii. Pa ge 12 : Previous Total Run Hours (Import+Export).

LED Row 1 : Pr.En. LED Row 2 : run.h LED Row 3 : 8.8.8.8.

LED’s: TOT

3.4. SET 4 - Select Pages for Auto Scroll Display

In this option, all parameter pages available for display will be shown. The page number will be shown on LED row1, y/n option on LED row2 and LED row 3 respectively. User can set any page out of 26 pages for display in SCROLL MODE.

LED Row 1 : <pg. no.> LED Row 2: on LED Row 3: off

3.5. SET 5 - Testing Mode Testing mode contains more user selectable options:

i. LED Test ii. M em or y Test.

User can scroll to any one option using Navigation Up and Navigation Down keys, and select the test using Enter key.

i. LED Test

In LED Test, all the display LEDs will light up for 2 seconds, and then will go off for 1 second. After this the system will get back to Testing Mode menu page.

ii. M e m o r y Test

In memory testing, the data logging memory will be tested, and depending on the result, “Pass” or “Fail” will be displayed on the LEDs for 2 seconds, and the system will go back to Testing Mode menu.

Page 15: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

15

The Display will be as follows

LED Row 1 : Mry LED Row 2 : PASS LED Row 3 :

OR

LED Row 1 : Mry LED Row 2 : FAIL LED Row 3 :1/2/3

FAIL 1: BANK 1 fail FAIL 2: BANK 2 fail FAIL 3: BOTH bank fail

4. Reference standards

This meter is manufactured according to the following valid standards:

IS 14697:2004

AC Static Watt-Hour Meters, class 1 & 2 – Specification (up to Amendments 4)

IEC 61000-4:2008 Electromagnetic compatibility (EMC) .Testing and measurement techniques .

IS 1248 Direct acting analoge static watt hour meter.

5. Assembly, service and maintenance

5.1 Assembly

The device is intended for mounting on the Panel and is of the protection class IP 54 for it front display.

Page 16: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

16

It is located to the vertical panel in appropriate height, in case of necessity it can be mounted in any other position, but access to the frontal panel must be assured. The device can be located in groups with other meters, but under the device there must be left sufficient space for the leads connection. In a case, that the meter is intended to be used for centralized data connection through RS 485 Bus, there must be assured also display reading (LED) as well as access for the probe to the optical serial interface.

The panel cut out of 92 X 92 mm (+0.1mm). is to be required for fixing of meter.

The panel cut out of 142 X142 mm (+0.1mm). is to be required for fixing of Printer (AE-prin)

The device and Printer are intended for fixing by using two nos. of side clamps provided with meter. After fixing the meter to connect in accordance with its connection diagram given in the back side terminals of the meter (event. in accordance with annexed documentation). Connection of the device to the network can be performed only by persons with corresponding qualification.

It is necessary to care about correct connection of the circuits for RS 485 Bus, especially to maintain the polarity (marked with A & B on backside terminals of meter). Also the connection to Auxiliary circuit of meter.

For Connection to AE- Prin use the RJ-45 wire provided . Please do not connect this RJ- 45 wire to any PC, Laptop or telephone Jack or any other device other than to interconnect the RJ45 jacks provided on the Backside of AE 9000 and AE- Prin .

In order to comply with correct meter installation principles, it is important to follow the procedure, as described below:

To locate device into appropriate height suitable for register ( display) reading; Fixing points and a space for connection wires must be in accordance with a dimension

drawing of the device. For mounting to use Standard accessories for fixing/ openings of the meter;

To connect meters in accordance with the connection diagram located on back side of the terminal cover;

Use minimum 1.5 sq.mm Copper wires for connection of Voltage, Current & Auxiliary circuit & use two core separate wire for RS 485 Bus connection.

It is recommended to provide series fuse (with proper insulated fuse base) of 1Amp. Rating for Auxiliary circuit connection.

To care about correct connection of Current polarity, voltage line & neutral circuits, Auxiliary circuit & RS 485 Bus connection wires;

Page 17: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

17

After mounting there is necessary to perform adjustments of meter, the following parameters need to set before checking of meter functions.

Set CT & PT Ratio as per requirement. Set Star or Delta connection. Selection of Electric circuit i.e. Single / Three phase.

5.2 Service

Digital Multi function meters of the type series AE 9000 do not require any service, except the processes of data reading and occasional parameterization (recalibration) within the range of description given in this manual and regular verification in periods, determined for a given meter type in a corresponding country of utilization.

5.3 Maintenance

Digital Multi function meters of the type series AE 9000 do not require any proper regular maintenance. It is sufficient to remove from the meters dust and to maintain cleanness of interfaces and accessibility to the display. After elapsing of period of verification it is supposed their detailed cleaning and checking verification of the measurement precision.

6. Packing, transport and storage 6.1 Packing

Every Digital Multi function meters is packed into the corrugated box. Packed meters are dispatched in special cases, or in transporting boxes.

Delivered meters are tested within the range of the routine tests and their parameters correspond to declared technical parameters in the catalogue sheet and in this manual for assembly, service and maintenance. The delivered meters have had a type approval.

6.2 Transport Digital Multi function meters are very precise measuring devices and in accordance with this they must be carefully handled during manipulation and transport. Excessive shocks may influence their functionality and precision in unfavorable way. When sending the meters by transport it must be marked by the symbol “glass” handles with care.

6.3 Storage Digital Multi function meters to store at the temperature with ambient temperature from -25 °C to +70 °C in a dry and dust free ambient without aggressive gases and vapors. Average relative humidity value should not to overpass RH 75 %.

Page 18: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

18

7. Service and Warranty 7.1 Service

For this brand of the product it is provided service by his manufacturer, the firm AUTOMATIC ELECTRIC Ltd. situated At Plot No. 96, M.I.D.C. Nangargaon, Lonavala, Pune-410401;tel.No.0091-2114-310994/310996,faxNo.0091-2114-273482, email:[email protected]. Firm Automatic Electric Ltd. will provide this service in a particular country through its exclusive commercial partners and service organizations, This contact data will be consecutively fulfilled into the commercial documents.

7.2 Warranty By this warranty Automatic Electric Ltd. (Hence forth make ‘AEL’) assures the product is free from defects in material and workmanship, for a period of 12 months from date of delivery. AEL is responsible for the design and assures that the product has and will maintain the performance determined by technical standards for the above mentioned period. The features of the product are described in manual along with detail mounting instructions.

AEL’s only obligation under this warranty is to repair or replace product subject to these warranty terms conditions. AEL is not liable for any loss or damage relating to products this warranty or otherwise, including economic or intangible loss of profit/revenue. The liability under this warranty will in no case exceed the price paid for product.

The warranty does not cover:

1. Installation or use of product in a manner inconsistent with technical standards.

2. Misuse including treatment resulting in physical or aesthetic damage or changes in product or damage to LED.

3. Repair or attempted repair by persons other than the one nominated by AEL.

4. Accidents, fire, liquids, chemicals, flooding, vibrations , excessive heat, electrostatic discharges Including lighting, other external forces or impacts.

Page 19: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

19

8. Specifications

Type 1 / 3-Phase-3-wire/ 4wire (Programmable through front panel). Input voltage V AC

110V or 415 V ( L-L )

Voltage Overload 1.5 time for 10 sec Input Current A AC

1A or 5A

Current Overload 50A max for 3 sec

Auxiliary supply AC / DC : 85 V - 300 V

Burden

For Voltage / Current - 0.2 VA max per Volt/Amp input,

Auxiliary - 3VA max.

Frequency 45 Hz - 55Hz

Resolution RMS 4 digit, Integral 8 digit

Response Time <300ms

Accuracy Class 1.0 (optional: 0.5).

RS485 communication Two wire half duplex

Baud rates -2400, 4800, 9600, 19200.

Isolation 2k VAC isolation for 1min. Between communication and other circuit.

Demand Interval Programmable from 1 to 30 Minutes.

Environmental Operating Temp. -10 to +70 °C. storage temp.-25 to +70°C, Humidity 0%-95% non condensing.

Mechanical Size Bezel : 96 x 96 mm Depth : 83mm behind Bezel

Protection IP54 for front Display. Conform to IS13779 /IEC 62052-11 & 62053-21.

Casing ABS Black H II 21

Keypad 5 Functional keys

LED Indication 31 individual discrete LED’s for parameter information

Page 20: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

20

9. MODBUS Communications: Parameter display and Configuration of MFM can also be done from a remote location via MODBUS communication. Following sub-sections describe the MODBUS function codes used and, addresses for each parameter for display and configuration.

The display parameters can only be read from the unit using function code 0x03, while the configuration can be read using function code 0x03 and modified using function code 0x06.

Frame: <address><function code><data address><number of bytes>/<data><CRC>

9.1. Writing Configuration Parameters (except CTR/PTR ratio):

Function Code 0x06 (Write Holding Registers)

Request Function code 1 Byte 0x06Register Address 2 Bytes 0x0000 to 0xFFFF Register Value 2 Bytes 0x0000 to 0xFFFF

Response Function code 1 Byte 0x06Register Address 2 Bytes 0x0000 to 0xFFFF Register Value 2 Bytes 0x0000 to 0xFFFF

Error Error code 1 Byte 0x86 Exception code 1 Byte 01 or 02 or 03 or 04

For configuration parameters exception code 03 indicate that the data send is out of the boundary limit.

9.2. Reading Configuration Parameters:

Function Code 0x03(Read Holding Registers)

Request Function code 1 Byte 0x03Starting Address 2 Bytes 0x0000 to 0xFFFF Quantity of Registers 2 Bytes 1 to 32

Response Function code 1 Byte 0x03Byte count 1 Byte 2 x N*

Page 21: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

21

Register value *N = Quantity of Registers

N* x 2 Bytes

Error Error code 1 Byte 0x83Exception code 1 Byte 01 or 02 or 03 or 04

9.3. Writing configuration parameter for CTR/PTR ratio:

Function Code 0x10 (Write Multiple Registers)

Request format Function code 1 Byte 0x10Starting Address 2 Bytes 0x00F4 & 0x00FC Quantity of Register 2 Bytes 0x0004Number of Byte 1 Bytes 0x08Data Byte

Response

Function code 1 Byte 0x10Starting Address 2 Bytes 0x00F4 & 0x00FC Quantity of Register 2 Bytes 0x0004

Error Error code 1 Byte 0x90 Exception code 1 Byte 02 or 03

For CTR/PTR ratio “write multiple registers’ code is used. Since PTR/CTR primary & secondary value are of 2 word long , while write holding register can send only one byte of data at a time so because of this write multiple register code is used to send both 2 word together. Here in code we have sent both primary & secondary value of CTR/PTR together. This is done so that the ratio can be computed immediately and error can be flagged if ratio is invalid. If primary and secondary are sent independently, ratio computation may not be correct with new value of one parameter and old value of another. The ratio of CTR/PTR is calculated from the primary & secondary value, & depending upon that if the ratio is within the maximum limit than the primary & secondary values are stored in memory otherwise no change in the output takes place. Example:

Consider that if we want to set PTR ratio as 1000 for that we have consider PTR primary value as 1000 & PTR secondary value as 1. So the data that will be sent through modbus is given below 01 10 00 FC 00 04 08 03 E8 00 00 00 01 00 00:

Page 22: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

22

Here 01 is the slave address, 10 is the function code, 00 FC is the PTR primary address. 00 04 is the quantity of register, 08 is the no. of byte, 03 e8 00 00 is the value for PTR primary i.e. is 1000 & 00 01 00 00 is the value for PTR secondary i.e. is 1. Exception code logic:

If incorrect function code : Exception code = 01 If registers requested not in range 0 – 32 : Exception code = 03 If requested addresses invalid : Exception code = 02 If Slave internal error : Exception code = 04

Modbus Map for Configuration Parameters

Sr. No.

Parametr ParameterAddress

No of words

Multiplyigfactor

1 Phase F0 1 1 2 Topology (Star/Delta) F2 1 1 3 CT Ratio Primary F4 2 1 4 CT Ratio Secondary F8 2 1 5 PT Ratio Primary FC 2 1 6 PT Ratio Secondary 100 2 1 7 Scroll 104 1 1 8 MD Integration 106 1 1 9 Data Logging Time 108 1 1 10 Set user password 10C 1 1

11

Pages to be displayed inauto scroll mode along with display order

110-142 28

1

12 Parameters to be logged 148 – 1B6 56 1 13 Current date and Time 1B8 – 1C0 5 1 14 Page Register 1C2 1 1 15 Command for reset 1C4 1 1 16 Speed & memory register 1D6 1 1 17 Reset calibration 1D 1 1 18 Reset Phase Calibration 1D

D1 1

Table below will give values that can be sending from application software for system configuration:

.

In the table given below the parameter value starting with 0x is the hex e.g. 0x3 is the hex value of 3 & all other value is in decimal format. In modbus all the decimal value has to be converted into hex before sending in into the system.

Page 23: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

23

Sr. No Parameter Value 1 Single Phase 0x012 Three Phase 0x033 Star Topology 0x014 Delta 0x005 CT Primary Max = 5000 Min=1 6 CT Secondary Max = 5 Min=1

CTR ratio = CT Primary/CT Secondary

Max = 1000 Min = 1

7 PT Primary Max =220KV Min=1 8 PT Secondary Max = 110 Min=1

PTR ratio = PT Primary/PT Secondary

Max = 2000 Min = 1

9 Scroll Time Max = 10 Min=310 MD Integration Max = 5 Min=3011 Data Logging Time Max=120 Min=112 Password Max = 9999 Min = 0 13 Pages to be displayed

in auto scroll mode along with display order

For Set send 0x01 and for reset 0x00 for per page

14 Parameter to be logged For set send 0x01 and for reset send 0x00

15 Current Date and Time Data will be sendfollowing format <Hour><Min><Date>< Month><Year>

16 Hour Max =23 Min=017 Minute Max=59 Min=018 Date Max =31 Min=119 Month Max= 12 Min= 120 Year Min =200921 Page Register Max = 4 Min= 022 Speed & memory register Memory max = 4 min =

2 (Read only) Max Speed can be 4800 = 1 9600= 2 & 38400 = 3 (Read only)

23 Reset Phase calibration 0x0000

The limits checks are provided by first comparing the address of the incoming message with the assigned address for the various parameters in order to know that message belongs to particular parameter. Now the value in the message is compared with the boundary limits of that particular parameter & if the value is out of the boundary range then exception value [03 = illegal data value] is

Page 24: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

24

returned otherwise that value is updated Before Reading Configuration Parameters, Master has to write the value 0x04 to the Page register.

9.4. Reading Parameters Online:

Function Code 0x03(Read Holding Registers)

Request Function code 1 Byte 0x03Starting Address 2 Bytes 0x0000 to 0xFFFF Quantity of Registers 2 Bytes 1 to 32

Response Function code 1 Byte 0x03Byte count 1 Byte 2 x N*Register value N* x 2 Bytes

*N = Quantity of Registers

Error

Error code 1 Byte 0x83Exception code 1 Byte 01 or 02 or 03 or 04

Sr. No.

Parameter Parameter Address

No of words

Multiplyingfactor

1 Voltage line to line R-phase 00 2 12 Voltage line to line Y-phase 02 2 13 Voltage line to line B-phase 04 2 14 Voltage line to line average 06 2 15 Voltage line to neutral R-phase 08 2 16 Voltage line to neutral Y-phase 0A 2 17 Voltage line to neutral B-phase 0C 2 18 Voltage line to neutral average 0E 2 19 Current for R- phase 10 2 110 Current for Y-phase 12 2 111 Current for B-phase 14 2 112 Current average 16 2 113 Neutral Current 18 2 114 Power factor R-phase 1A 1 100015 Power factor Y-Phase 1B 1 100016 Power factor B-phase 1C 1 100017 Power factor average 1D 1 100018 Frequency 1E 1 10019 Phase angle R-phase 1F 1 10020 Phase angle Y-phase 20 1 10021 Phase angle B-phase 21 1 100

Page 25: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

25

22 Phase angle between R-phase

and Y-phase 22

1

100

23 Phase angle between Y-phaseand B-phase 23

1

100

24 Phase angle between B-phase

and R-phase 24

1

100

25 Active power R-phase 25 2 126 Active power Y- phase 27 2 127 Active power B-phase 29 2 128 Active power total 2B 2 129 Reactive power R-phase 2D 2 130 Reactive power Y-phase 2F 2 131 Reactive power B-phase 31 2 132 Reactive power total 33 2 133 Apparent power R-phase 35 2 134 Apparent power Y-phase 37 2 135 Apparent power B-phase 39 2 136 Apparent power total 3B 2 137 Import :Active energy(Wh) 3D 2 138 Import: Apparent energy VAh. 3F 2 1

39 Import: Inductive Reactive

Energy VARh. 41

2

1

40 Export :Active energy(Wh) 43 2 141 Export: Apparent energy VAh. 45 2 142 Export: Inductive Reactive 47 2 1

Energy VARh. 43 Total :Active energy(Wh) 49 2 144 Total: Apparent energy VAh. 4B 2 1

45 Total: Inductive Reactive energy VARh. 4D

2

1

46 Import : Run hours 4F 1 147 Export : Run hours 50 1 148 Total : Run hours 51 1 149 Total Interruptions 52 1 150 Current THD 53 2 151 Voltage THD 55 2 152 Maximum Demand Real Power 57 2 153 Maximum Demand for Apparent Power 59 2 1

Page 26: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

26

9.5. Reading Logged Data:

Function Code 0x03(Read Holding Registers)

Request

Function code 1 Byte 0x03Starting Address 2 Bytes 0x0000 to 0xFFFF Quantity of Registers 2 Bytes 1 to 32

Response Function code 1 Byte 0x03Byte count 1 Byte 2 x N*Register value *N = Quantity of Registers

N* x 2 Bytes

Error Error code 1 Byte 0x83Exception code 1 Byte 01 or 02 or 03 or 04

Since Logged data will be larger than 125 bytes, master would send multiple read requests, in order to read complete logging data.

It is unknown to the master before hand as to how many data bytes are logged in memory; hence the master would be required to send the read requests until it receives an exception saying invalid address, which would indicate that all logged data has been read.

In case of error in communication at any point during logged data transfer, master may initiate the read from the beginning or from the address where the communication had failed.

Since protocol allows only 64 K of memory addressing, the total available memory is divided into 4 pages, numbered 0 – 3. Hence master has to update the page register in order to read form specific page.

It is not possible to read from addresses 0x00 to 0x399 when page register 0 is selected (Reserved for configuration data can be read by selecting Page number 4 as mentioned above). Master will get an exception Invalid Address in case an attempt to read this space is made for page register 0.

Only 64 bytes of data can be read per message as opposed to 125 defined by the protocol, in order to maintain proper page boundaries. Once data from one page is read, Master must ensure incrementing the value of page register in order to read

Page 27: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

27

further data. Table below give information about page number and valid address range.

Page Number Start Add End Add0 0x0400 0xFFFF1 0x0000 0xFFFF2 0x0008 0xFFFF3 0x0000 0xFFFF4 0x0000 0x0399

The protocol for log data is given below

<0xABAB (16 bit)> <Number of data byte (16 bit)><Actual Data byte (number of data byte)><CRC (16 bit)>

In this 0xABAB is header which indicate start of data log frame, next two bytes are give number of data bytes log in log period. After that actual parameter are log. At end of each frame of data logging 16 bit CRC for error check.

9.6. Reading Interruption Data:

Function Code 0x03(Read Holding Registers)

Request Function code 1 Byte 0x03Starting Address 2 Bytes 0x0000 to 0xFFFF Quantity of Registers 2 Bytes 1 to 32

Response Function code 1 Byte 0x03

Byte count 1 Byte 2 x N* Register value N* x 2 Bytes

*N = Quantity of Registers

Error

Error code 1 Byte 0x83 Exception code 1 Byte 01 or 02 or 03 or 04

Page 28: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

28

9.7. Power on interruption:

Interruption data can be read from address 0x200 to 0x399 after selecting page number for the protocol interruption data is given below

Sr.No. Level Current Value (A)

1 Phase Offset 0 0.2 2 Phase Offset 1 2.5 3 Phase Offset 2 5

(16 bit)> <Number of data byte (16 bit)>< Power On Interruption Hr Min Date Month Year (12bytes)><CRC (16 bit)>

In this 0xABAB is header which indicate start of data log frame, next two bytes are give number of data bytes log in log period. After that actual parameter are log. At end of each frame of data logging 16 bit CRC for error check. To indicate a power on interruption 0x00D2 is send.

10. Printer Function

The AE-9000 (multifunction meter-MFM) along with AE-prin will print the On-Off time for the previous day, Total On Time and Total Active energy for the previous day as well as Total On time and Total Active energy of previous month. This is useful function for the DG monitoring. At the Midnight of Every day the AE-9000 along with AE-prin will print the daily report for the day. And at the midnight of Last day of the Month the AE-9000 along with AE-prin will print the monthly report for the month ended. For the user’s convenience the any time print facility is provided within the SETTING- 2. On pressing E key it will print both the reports for the previous day as well as previous month.

Page 29: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

29

11. Installation Instruction 11.1 Mechanical Installation:

The AE-9000 is panel-mounted and has reliable, rear-mounted terminal strips rated at 415v.The 92 x 92 mm cut-out and 96 x 96 mm bezel dimensions .Depth required behind the Bezel is 83 mm, plus space for wiring. Two side clamps are provided for mounting.

Fig.1: Dimensions of AE-9000

Fig.2: Dimensions of AE-prin

Page 30: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

30

11.2 Electrical Installation:

1. To power up internal circuitry AE-9000 and AE- Prin requires AC/DC Auxiliary supply. Auxiliary supply, AC / DC: 85V-300V.

2. Make proper connections of input voltages (R, Y, B, N) and currents (I1, I2, I3, IN). With reference to wiring diagram.

3. For input connection total 16 terminals are provided on rear side of AE-9000.In that 8 terminal at one side, 6 terminals at one side and 2 terminals at bottom.

4. For Connection to AE- Prin use the RJ-45 wire provided . 5. Caution : Please do not connect this RJ- 45 wire to any PC, Laptop or telephone Jack

or any other device other than to interconnect the RJ45 jacks provided on the Backside of AE 9000 and AE- Prin .

11.3 Wiring Diagram

Fig.2 : Wiring Diagram

Page 31: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

31

12. Ordering Information:

For detail ordering information of AE-9000 refer table given below.

Product code AE-9000 & AE- Prin Input Current 5A /1A

RS-485 communication

Yes / No

Auxiliary supply AC / DC: 85V -300V :

Accuracy Class 1 / 0.5.

Input System 1phase,3ph3w,3ph4w,

Page 32: AE 9000 USERS MANUAL with Printer interface.pdf

AE‐9000 User Manual

32