AGENDA NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 Second Draft Meeting Monday, June 24, 2013 DoubleTree by Hilton Hotel San Diego Downtown 1646 Front Street San Diego, California 1. Call to Order. Call meeting to order by Chair Warren Bonisch, at 8:00 a.m. on Monday, June 24, 2013. 2. Self-introduction of Committee Members and Guests. For a current committee roster, pg. 2. 3. Approval of Previous Meeting Minutes. Approve the August 13-14, 2012 meeting minutes, pg. 6. 4. Chair’s report – W. Bonisch. 5. Review new NFPA codes and standards development process – G. Harrington. See pg. 17 for slide presentation. 6. Definitions Task Group. See pg. 34. 7. Hazardous Materials Task Group. See pg. 35. 8. NFPA 101 Second Draft (formerly ROC) Preparation. Public Comments to be distributed prior to meeting date. 9. NFPA 5000 Second Draft (formerly ROC) Preparation. Public Comments to be distributed prior to meeting date. 10. Other Business. 11. Adjournment. Page 1 of 35

Upload: others

Post on 03-Jul-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

AGENDA NFPA Technical Committee on Residential Occupancies

NFPA 101 and NFPA 5000 Second Draft Meeting Monday, June 24, 2013

DoubleTree by Hilton Hotel San Diego Downtown 1646 Front Street

San Diego, California

1. Call to Order. Call meeting to order by Chair Warren Bonisch, at 8:00 a.m. on Monday, June 24, 2013.

2. Self-introduction of Committee Members and Guests. For a current committee roster, pg. 2.

3. Approval of Previous Meeting Minutes. Approve the August 13-14, 2012 meeting minutes, pg. 6.

4. Chair’s report – W. Bonisch.

5. Review new NFPA codes and standards development process – G. Harrington. See

pg. 17 for slide presentation.

6. Definitions Task Group. See pg. 34.

7. Hazardous Materials Task Group. See pg. 35.

8. NFPA 101 Second Draft (formerly ROC) Preparation. Public Comments to be distributed prior to meeting date.

9. NFPA 5000 Second Draft (formerly ROC) Preparation. Public Comments to be

distributed prior to meeting date. 10. Other Business.

11. Adjournment.

Page 1 of 35

Page 2: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

Address List No PhoneResidential Occupancies SAF-RES

Safety to Life

Gregory E. Harrington04/10/2013

SAF-RES

Warren D. Bonisch

ChairAon Fire Protection Engineering Corporation1701 North Collins Blvd., Suite 235Richardson, TX 75080-3553Alternate: David P. Wilmot

I 11/14/1997SAF-RES

Gregory E. Harrington

Secretary (Staff-Nonvoting)National Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

SAF-RES

H. Wayne Boyd

PrincipalUS Safety & Engineering Corporation2365 El Camino AvenueSacramento, CA 95821-5647

M 7/17/1998SAF-RES

Patrick Boyer

PrincipalState Farm Insurance Company1501 Rhodes LaneBloomington, IL 61704

I 08/09/2012

SAF-RES

Harry L. Bradley

PrincipalMaryland State Fire Marshals Office5 West Riding DriveBel-Air, MD 21014International Fire Marshals Association

E 1/1/1982SAF-RES

Phillip A. Brown

PrincipalAmerican Fire Sprinkler Association, Inc.12750 Merit Drive, Suite 350Dallas, TX 75251Alternate: Michael F. Meehan

IM 10/6/2000

SAF-RES

Bradford T. Cronin

PrincipalNewport Fire Department21 West Marlborough StreetNewport, RI 02840Rhode Island Association of Fire Marshals

E 03/05/2012SAF-RES

Daniel P. Finnegan

PrincipalSiemens Industry, Inc.Building Technology DivisionFire Safety Unit8 Fernwood RoadFlorham Park, NJ 07932Automatic Fire Alarm Association, Inc.

M 8/5/2009

SAF-RES

Sam W. Francis

PrincipalAmerican Wood Council1 Dutton Farm LaneWest Grove, PA 19390American Forest & Paper AssociationAlternate: Dennis L. Pitts

M 4/1/1996SAF-RES

Ralph D. Gerdes

PrincipalRalph Gerdes Consultants, LLC5510 South East Street, Suite EIndianapolis, IN 46227Alternate: David Cook

SE 1/1/1987

SAF-RES

Stanley C. Harbuck

PrincipalSchool of Building InspectionPO Box 1643Salt Lake City, UT 84110American Public Health AssociationAlternate: Jake Pauls

C 10/4/2001SAF-RES

Kenneth E. Isman

PrincipalNational Fire Sprinkler Association, Inc.40 Jon Barrett RoadPatterson, NY 12563Alternate: Bruce Lecair

M 1/1/1987

1Page 2 of 35

Page 3: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

Address List No PhoneResidential Occupancies SAF-RES

Safety to Life

Gregory E. Harrington04/10/2013

SAF-RES

Marshall A. Klein

PrincipalMarshall A. Klein & Associates, Inc.6815 Autumn View DriveEldersburg, MD 21784-6304Alternate: David M. Hammerman

SE 1/1/1981SAF-RES

Richard T. Long, Jr.

PrincipalExponent, Inc.17000 Science Drive, Suite 200Bowie, MD 20715Upholstered Furniture Action Council

M 10/18/2011

SAF-RES

Alfred J. Longhitano

PrincipalAlfred J. Longhitano, P.E., LLC26 Salem RoadChappaqua, NY 10514

SE 10/20/2010SAF-RES

Eric N. Mayl

PrincipalCore Engineers Consulting Group, LLC5171 MacArthur Blvd., Suite 200Washington, DC 20016

SE 3/21/2006

SAF-RES

Ronald G. Nickson

PrincipalNational Multi Housing Council1850 M Street NW, Suite 540Washington, DC 20036

U 4/1/1995SAF-RES

Steven Orlowski

PrincipalNational Association of Home Builders1201 15th Street, NWWashington, DC 20005-2800

U 7/26/2007

SAF-RES

Henry Paszczuk

PrincipalConnecticut Department of Public Safety102 Jeffrey LaneBerlin, CT 06037Alternate: Joseph Kingston

E 4/15/2004SAF-RES

Peter Puhlick

PrincipalUniversity of ConnecticutFacilities OperationsUnit 3038 Co-Generation/Central Utilities PlantStorrs, CT 06269-3038

U 1/1/1988

SAF-RES

Richard Jay Roberts

PrincipalHoneywell Life Safety3825 Ohio AvenueSt. Charles, IL 60174National Electrical Manufacturers AssociationAlternate: David Newhouse

M 7/23/2008SAF-RES

Andrew M. Schneider

PrincipalKoffel Associates, Inc.8815 Centre Park Drive, Suite 200Columbia, MD 21045-2107Alternate: Diana E. Hugue

SE 08/09/2012

SAF-RES

John A. Sharry

PrincipalBeakmann PropertiesSharry & Associates, Inc.1958 Winward PointDiscovery Bay, CA 94505

U 7/16/2003SAF-RES

Joseph H. Versteeg

PrincipalVersteeg Associates86 University DriveTorrington, CT 06790

SE 7/14/2004

SAF-RES

Andrew F. Weisfield

PrincipalMichael Baker Corporation100 Airside DriveMoon Township, PA 15108Alternate: Kevin Spangler

SE 10/20/2010SAF-RES

Bartholomew T. Wright

PrincipalMaitland Fire Rescue Department1776 Independence LaneMaitland, FL 32751Alternate: Donald P. Damron

E 03/05/2012

2Page 3 of 35

Page 4: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

Address List No PhoneResidential Occupancies SAF-RES

Safety to Life

Gregory E. Harrington04/10/2013

SAF-RES

Jeffrey D. Zwirn

PrincipalIDS Research & Development, Inc.405 Cedar LaneTeaneck, NJ 07666

SE 3/1/2011SAF-RES

Waymon Jackson

Voting AlternateUniversity of Texas at Austin1 University Station, Stop C2600PO Box 7729Austin, TX 78713Voting Alt. to UT-Austin Rep.

U 10/18/2011

SAF-RES

David Cook

AlternateRalph Gerdes Consultants, LLC5510 South East Street, Suite EIndianapolis, IN 46227Principal: Ralph D. Gerdes

SE 10/1/1995SAF-RES

Donald P. Damron

AlternateSarasota County Fire Department6750 Bee Ridge RoadSarasota, FL 34241Principal: Bartholomew T. Wright

E 08/09/2012

SAF-RES

David M. Hammerman

AlternateMarshall A. Klein and Associates, Inc.3950 Chaffey RoadRandallstown, MD 21133Principal: Marshall A. Klein

SE 4/5/2001SAF-RES

Diana E. Hugue

AlternateKoffel Associates, Inc.8815 Centre Park Drive, Suite 200Columbia, MD 21045-2107Principal: Andrew M. Schneider

SE 3/1/2011

SAF-RES

Joseph Kingston

AlternateConnecticut Office of State Fire Marshal1111 Country Club RoadMiddletown, CT 06451Principal: Henry Paszczuk

E 10/29/2012SAF-RES

Bruce Lecair

AlternateNational Fire Sprinkler Association, Inc.25417 Hyacinth StreetCorona, CA 92883Principal: Kenneth E. Isman

M 08/09/2012

SAF-RES

Michael F. Meehan

AlternateVSC Fire & Security1417 Miller Store Road, Suite CVirginia Beach, VA 23455American Fire Sprinkler AssociationPrincipal: Phillip A. Brown

IM 4/15/2004SAF-RES

David Newhouse

AlternateGentex Corporation10985 Chicago DriveZeeland, MI 49464National Electrical Manufacturers AssociationPrincipal: Richard Jay Roberts

M 10/29/2012

SAF-RES

Jake Pauls

AlternateJake Pauls Consulting Services in Building Use & Safety12507 Winexburg Manor Drive, Suite 201Silver Spring, MD 20906American Public Health AssociationPrincipal: Stanley C. Harbuck

C 7/12/2001SAF-RES

Dennis L. Pitts

AlternateAmerican Wood Council1721 West Plano Parkway, #224Plano, TX 75075American Forest & Paper AssociationPrincipal: Sam W. Francis

M 5/15/2000

3Page 4 of 35

Page 5: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

Address List No PhoneResidential Occupancies SAF-RES

Safety to Life

Gregory E. Harrington04/10/2013

SAF-RES

Kevin Spangler

AlternateMichael Baker Jr. Corporation100 Airside DriveMoon Township, PA 15108Principal: Andrew F. Weisfield

SE 10/29/2012SAF-RES

David P. Wilmot

AlternateAon Fire Protection Engineering6305 Ivy Lane, Suite 220Greenbelt, MD 20770Principal: Warren D. Bonisch

I 10/29/2012

SAF-RES

Gregory E. Harrington

Staff LiaisonNational Fire Protection Association1 Batterymarch ParkQuincy, MA 02169-7471

4Page 5 of 35

Page 6: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

BLD/SAF-RES 8-2012 FIRST DRAFT Meeting Minutes / Page 1

NFPA Technical Committee on Residential Occupancies NFPA 101 and NFPA 5000 FIRST DRAFT MEETING MINUTES

Monday-Tuesday, August 13-14, 2012

St. Louis Union Station Marriott

St. Louis, Missouri

1. Call to Order. The meeting was called to order by Chair Warren Bonisch at 8:00 AM

(CDT), August 13, 2012.

2. Introduction of Committee Members and Guests. TECHNICAL COMMITTEE MEMBERS PRESENT

NAME COMPANY Warren D. Bonisch, Chair Aon Fire Protection Engineering Corporation

Gregory E. Harrington, Nonvoting

Secretary

National Fire Protection Association

Harry L. Bradley, Principal Maryland State Fire Marshals Office

Rep: International Fire Marshals Association

Phillip A. Brown, Principal American Fire Sprinkler Association, Inc.

Bradford T. Cronin, Principal Newport Fire Department

Rep: Rhode Island Association of Fire

Marshals

Daniel P. Finnegan, Principal Siemens Industry, Inc.

Rep: Automatic Fire Alarm Association, Inc.

Sam W. Francis, Principal American Wood Council

Rep: American Forest & Paper Association

Ralph D. Gerdes, Principal Ralph Gerdes Consultants, LLC

Stanley C. Harbuck, Principal School of Building Inspection

Rep: American Public Health Association

Diana E. Hugue

Alt. to James K. Lathrop

Koffel Associates, Inc.

Kenneth E. Isman, Principal National Fire Sprinkler Association, Inc.

Marshall A. Klein, Principal Marshall A. Klein & Associates, Inc.

Alfred J. Longhitano, Principal Alfred J. Longhitano, P.E., LLC

Ronald G. Nickson, Principal National Multi Housing Council

Steven Orlowski, Principal National Association of Home Builders

Henry Paszczuk, Principal Connecticut Dept. of Public Safety

Jake Pauls

Alt. to Stanley C. Harbuck

Jake Pauls Consulting Services in Building Use

& Safety

Rep: American Public Health Association

Page 6 of 35

Page 7: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

BLD/SAF-RES 8-2012 FIRST DRAFT Meeting Minutes / Page 2

Richard Jay Roberts, Principal Honeywell Life Safety

Rep: National Electrical Manufacturers Assn.

Robert C. Schultz, Jr., Principal University of Texas at Austin

John A. Sharry, Principal Beakmann Properties

Jeffrey L. Shearman, Principal Zurich Services Corporation

Rep: NFPA Lodging Industry Section

GUESTS

NAME COMPANY Dave Newhouse Gentex/NEMA

Robert Solomon NFPA

Thom Zaremba Roetzel Andress

TECHNICAL COMMITTEE MEMBERS NOT PRESENT

NAME COMPANY H. Wayne Boyd, Principal US Safety & Engineering Corporation

Richard T. Long, Jr., Principal Exponent, Inc.

Rep: Upholstered Furniture Action Council

Eric N. Mayl, Principal Core Engineers Consulting Group, LLC

Peter Puhlick, Principal University of Connecticut

Joseph H. Versteeg, Principal Versteeg Associates

Andrew F. Weisfield, Principal Michael Baker Jr. Corporation

Bartholemew T. Wright, Principal Maitland Fire Rescue Department

Jeffrey D. Zwirn, Principal IDS Research & Development Inc.

3. Approval of Prior Meeting Minutes. The October 19, 2010 meeting minutes were

approved as written and distributed.

4. Review Re-Engineered NFPA Codes and Standards Development Process. Staff

reviewed the new codes and standards process, which is in effect for the 2015 editions of

NFPA 101 and NFPA 5000. See pg. 10 of the meeting agenda for the PowerPoint slides.

Full details on the new process are available online at www.nfpa.org. Committee

members are required to review and become familiar with the new regulations. Any

questions should be directed to NFPA staff.

5. Correlating Committee: Accessibility Scoping. Item deferred to discussion on related

public inputs. See the NFPA 5000 First Draft Report.

6. Correlating Committee: Dormitory Requirements. Item deferred to discussion on

related public inputs. See the NFPA 101 First Draft Report.

7. CO Detection Task Group Report. S. Orlowski reviewed the options presented in the

task group report addressing fireplaces (see pg. 4). Following discussion, the committee

created several first revisions based on the task group recommendations – see the NFPA

Page 7 of 35

Page 8: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

BLD/SAF-RES 8-2012 FIRST DRAFT Meeting Minutes / Page 3

101 and NFPA 5000 First Draft Reports. The task group members included: J. Versteeg,

Chair; D. Finnegan; R. Nickson; and S. Orlowski.

8. NFPA 101 New Construction/NFPA 5000 Requirements Correlation. The committee

reviewed staff-prepared draft first revisions based on a comparison of NFPA 101 and

NFPA 5000 requirements to eliminate discrepancies between the codes, as directed by

the Building Code and Life Safety Code Correlating Committees. Numerous first

revisions were created – see the NFPA 101 and NFPA 5000 First Draft Reports.

9. Review of NFPA 101 and NFPA 5000 Core Chapter First Revisions. Staff led a

discussion on core chapter first revisions affecting occupancy chapter provisions.

Following discussions on each of the items, numerous first revisions were created. See

the NFPA 101 and NFPA 5000 First Draft Reports.

10. NFPA 101 Public Input. The committee reviewed and discussed the public inputs

submitted on NFPA 101 and created numerous first revisions. See the NFPA 101 First

Draft Report.

11. NFPA 5000 Public Input. The committee reviewed and discussed the public inputs

submitted on NFPA 5000 and created numerous first revisions. See the NFPA 5000 First

Draft Report.

12. Other Business. R. Solomon led a discussion on several recent apartment building fires

in which the buildings were protected by NFPA 13R automatic sprinkler systems,

resulting in no loss of life, but significant property damage (total losses in some cases). In

some cases, it was documented that fire propagation in unprotected attics contributed to

the property loss. Although these events can be characterized as sprinkler “successes”

because of the lack of life loss, public perception is a serious concern. After much

discussion, it was agreed that the issue is a valid concern and should be addressed by the

codes. A motion passed to create committee inputs (CIs) on NFPA 101 (8.6.11.6) and

NFPA 5000 (8.14.1.5) addressing attics in buildings with residential sprinkler systems –

see the NFPA 101 and NFPA 5000 First Draft Reports. The item will flagged for review

by the Correlating Committees for further review by the TC on Fire Protection Features

during the second draft (comment) stage.

13. Future Meetings. The next meeting is tentatively scheduled for June 24, 2013 (location

to be determined). Meeting notices will be distributed when the details are finalized.

14. Adjournment. The meeting adjourned at 11:00 AM (CDT), August 14, 2012.

Page 8 of 35

Page 9: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA 101 & 5000 Technical Committee on Residential Occupancies

_______________________________________

Task Group on Fireplaces & Carbon Monoxide Detection

August 10, 2012 To: Warren Bonisch, Chair

Residential Occupancies Technical Committee Gregory Harrington, P.E. Principal Fire Protection Engineer NFPA

From: Joe Versteeg, Task Group Chair JHV

Subject: Report of Findings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - Shortly after issuance of the 2012 editions of NFPA 101 and NFPA 5000, the Technical Committee on Residential Occupancies was asked to evaluate a Request for Formal Interpretation that asked the TC to determine if a fireplace constitutes a fuel-burning appliance. Although a majority of the TC members voted in the affirmative, the ballot did not receive the required ¾ majority agreement. The Task Group’s objective is evaluate whether or not fireplaces constitute a hazard with respect to carbon monoxide in residential occupancies; and develop proposed text for review by the Residential Technical Committee, if appropriate. Task Group Members:

Daniel P. Finnegan, Automatic Fire Alarm Association (AFAA) Ronald Nickson, National Multi Housing Council (NMHC) Steven Orlowski, National Association of Home Builders (NAHB) Richard Roberts, National Electrical Manufacturers Association (NEMA) Joseph Versteeg, Versteeg Associates

Documents Reviewed:

1. Non-Fire Carbon Monoxide Deaths Associated with the Use of Consumer Products – 2006 Annual Estimates prepared by the U. S. Consumer Product Safety Commission, September 2009.

- Table 2 on page 10 lists the deaths attributed to fireplaces.

2. Development of a Technical Basis for Carbon Monoxide Detector Siting prepared for the Fire Protection Research Foundation by Hughes Associates, Inc., October 8, 2007.

Page 9 of 35

Page 10: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 2 & Carbon Monoxide Detection August 10, 2012

- Page 3 reports that fireplaces contributed to CO poisonings in Colorado. - Page 7 reports that fireplaces are an efficient producer of CO and therefore pose a

potential threat of CO poisoning.

3. Definitions of fuel-burning appliance and fireplace from NFPA 720 and NFPA 211. (Refer Pages 7 & 8 of this report.

Findings:

Based on a review of the data and the three (3) possible options, two task group members (Nickerson & Orlowski) opted for Option 1 and two members (Richards & Finnegan) opted for Option 3. Options: 1. No Action. With consideration of the available data re carbon monoxide occurrences

with fireplaces, no changes to the 2012 NFPA 101 & 5000 wording are necessary. 2. Generate an Annex note to each section within the residential occupancies of NFPA 101

& 5000 that basically states that although fireplaces have not been included as a trigger for the installation of carbon monoxide detectors/alarms within the body of the Code, consideration should be given to the installation of such detectors/alarms when other than masonry or factory-built fireplaces are in use, i.e. free-standing stoves or fireplace inserts that burn wood, wood pellets, coal, natural gas or propane as a fuel source. Refer Attachment A for proposed revisions to implement Option 2 on Page 3 of this report.

3. Amend each section within the residential occupancies of NFPA 101 & 5000 addressing

carbon monoxide detector/alarms to include fuel-burning fireplaces as a trigger for the installation of such detectors/alarms; and

Generate an Annex note to each section within the residential occupancies of NFPA 101 & 5000 that basically states that masonry, factory-built, or decorative electrical fireplaces do not warrant the devices.

Refer Attachment B for proposed revisions to implement Option 3 on Pages 4 through 6 of this report.

Page 10 of 35

Page 11: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 3 & Carbon Monoxide Detection August 10, 2012

Attachment “A” 

Draft Committee Input to Implement Option 2 NFPA 101

Submitter: SAF-RES Task Group on Carbon Monoxide Alarms Committee Input: CI-xxxx Recommendation: New committee input as follows: 24.3.4.2.1(2)* Existing text remains unchanged. New Annex not to read. A.24.3.4.2.1(2) It is not the intent of this section to require carbon monoxide detectors or alarms when masonry, factory-built, or decorative electrical fireplaces are present. The use of free-standing stoves or fireplace inserts that burn wood, wood pellets, coal, natural gas or propane as a fuel source in conjunction with masonry or factory-built fireplaces are considered fuel-burning appliances and require carbon monoxide detections/alarms. 26.3.4.6.1(2)* Existing text remains unchanged. New Annex not to read. A.26.3.4.6.1(2) See A.24.3.4.2.1(2). 28.3.5.2* Existing text remains unchanged. New Annex not to read. A.28.3 4.6.1(2) See A.24.3.4.2.1(2). 28.3.4.6.5(1)* Existing text remains unchanged. New Annex not to read. A.28.3 4.6.5(1) See A.24.3.4.2.1(2). 30.3.4.6.1(2)* Existing text remains unchanged. New Annex not to read. A.30.3.4.6.1(2) See A.24.3.4.2.1(2).

30.3.4.6.5(1)* Existing text remains unchanged. New Annex not to read. A.30.3 4.6.5(1) See A.24.3.4.2.1(2).

Committee Statement:   Although fireplaces have not been included as a trigger for the installation of carbon monoxide detectors/alarms within the body of the Code, consideration should be given to the installation of such detectors/alarms when other than masonry or factory-built fireplaces are in use, i.e. free-standing stoves or fireplace inserts that burn wood, wood pellets, coal, natural gas or propane as a fuel source

Do the same for NFPA 5000 Page 11 of 35

Page 12: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 4 & Carbon Monoxide Detection August 10, 2012

Attachment “B” 

Draft Committee Input to Implement Option 3

Submitter: BDL-RES Task Group on Carbon Monoxide Alarms Committee Input: CI-xxxx Recommendation: Revise existing text as follows: 24.3.4.2 Carbon Monoxide and Carbon Monoxide Detection Systems. 24.3.4.2.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with Section 9.8 and 24.3.4.2* shall be provided in new one- and two-family dwellings where either of the following conditions exists: (1) Dwelling units with communicating attached garages, unless otherwise exempted by 24.3.4.2.3 (2)* Dwelling units containing fuel-burning appliances or fireplaces. 24.3.4.2.2* Where required by 24.3.4.2.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations: (1) Outside of each separate dwelling unit sleeping area in the immediate vicinity of the sleeping rooms (2) On every occupiable level of a dwelling unit, including basements, and excluding attics and crawl spaces 24.3.4.2.3 Carbon monoxide alarms and carbon monoxide detectors as specified in 24.3.4.2.1(1) shall not be required in the following locations: (1) In garages (2) Within dwelling units with communicating attached garages that are open parking structures as defined by the building code (3) Within dwelling units with communicating attached garages that are mechanically ventilated in accordance with the mechanical code

New Annex not to read. A.24.3.4.2.1(2) It is not the intent of this section to require carbon monoxide detectors or alarms when masonry, factory-built, or decorative electrical fireplaces are present. The use of free-standing stoves or fireplace inserts that burn wood, wood pellets, coal, natural gas or propane as a fuel source in conjunction with masonry or factory-built fireplaces are considered fuel-burning appliances and require carbon monoxide detections/alarms.

Chapter 26 Lodging or Rooming Houses

26.3.4.6 Carbon Monoxide Alarms and Carbon Monoxide Detection Systems. 26.3.4.6.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with Section 9.8 and 26.3.4.6 shall be provided in new lodging or rooming houses where either of the following conditions exists: (1) Lodging or rooming houses with communicating attached garages, unless otherwise exempted by 26.3.4.6.3 (2)* Lodging or rooming houses containing fuel-burning appliances or fireplaces.

Page 12 of 35

Page 13: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 5 & Carbon Monoxide Detection August 10, 2012

26.3.4.6.2* Where required by 26.3.4.6.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations: (1) Outside of each separate sleeping area in the immediate vicinity of the sleeping rooms (2) On every occupiable level, including basements, and excluding attics and crawl spaces 26.3.4.6.3 Carbon monoxide alarms and carbon monoxide detectors as specified in 26.3.4.6.1(1) shall not be required in the following locations: (1) In garages (2) Within lodging or rooming houses with communicating attached garages that are open parking structures as defined by the building code (3) Within lodging or rooming houses with communicating attached garages that are mechanically ventilated in accordance with the mechanical code

New Annex not to read. A.26.3.4.6(2) See A.24.3.4.2.1(2).

Chapter 28 New Hotels and Dormitories

28.3.4.6 Carbon Monoxide Alarms and Carbon Monoxide Detection Systems. 28.3.4.6.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with Section 9.8 and 28.3.4.6 shall be provided in new hotels and dormitories where either of the following conditions exists: (1) Guest rooms or guest suites with communicating attached garages, unless otherwise exempted by 28.3.4.6.3 (2)*Guest rooms or guest suites containing a permanently installed fuel-burning appliance or fireplaces. 28.3.4.6.2 Where required by 28.3.4.6.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations: (1) Outside of each separate guest room or guest suite sleeping area in the immediate vicinity of the sleeping rooms (2) On every occupiable level of a guest room and guest suite 28.3.4.6.3 Carbon monoxide alarms and carbon monoxide detectors as specified in 28.3.4.6.1(1) shall not be required in the following locations: (1) In garages (2) Within guest rooms or guest suites with communicating attached garages that are open parking structures as defined by the building code (3) Within guest rooms or guest suites with communicating attached garages that are mechanically ventilated in accordance with the mechanical code 28.3.4.6.4 Carbon monoxide alarms or carbon monoxide detectors shall be provided in areas other than guest rooms and guest suites in accordance with Section 9.8, as modified by 28.3.4.6.5. 28.3.4.6.5 Carbon monoxide alarms or carbon monoxide detectors shall be installed in accordance with the manufacturer’s published instructions in the locations specified as follows: (1)* On the ceilings of rooms containing permanently installed fuel-burning appliances or fireplaces. (2) Centrally located within occupiable spaces served by the first supply air register from a permanently installed, fuel-burning HVAC system (3) Centrally located within occupiable spaces adjacent to a communicating attached garage

Page 13 of 35

Page 14: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 6 & Carbon Monoxide Detection August 10, 2012

New Annex not to read. A.28.3.4.6.1(2) See A.24.3.4.2.1(2). New Annex not to read. A.28.3.4.6.5(1) See A.24.3.4.2.1(2).

Chapter 30 New Apartment Buildings

30.3.4.6 Carbon Monoxide Alarms and Carbon Monoxide Detection Systems. 30.3.4.6.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with Section 9.8 and 30.3.4.6 shall be provided in new apartment buildings where either of the following conditions exists: (1) Dwelling units with communicating attached garages, unless otherwise exempted by 30.3.4.6.3 (2)* Dwelling units containing a permanently installed fuel-burning appliance or fireplaces.

30.3.4.6.2 Where required by 30.3.4.6.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations: (1) Outside of each separate dwelling unit sleeping area in the immediate vicinity of the sleeping rooms (2) On every occupiable level of a dwelling unit

30.3.4.6.3 Carbon monoxide alarms and carbon monoxide detectors as specified in 30.3.4.6.1(1) shall not be required in the following locations: (1) In garages (2) Within dwelling units with communicating attached garages that are open parking structures as defined by the building code (3) Within dwelling units with communicating attached garages that are mechanically ventilated in accordance with the mechanical code 30.3.4.6.4 Carbon monoxide alarms or carbon monoxide detectors shall be provided in areas other than dwelling units in accordance with Section 9.8, as modified by 30.3.4.7.5. 30.3.4.6.5 Carbon monoxide alarms or carbon monoxide detectors shall be installed in accordance with the manufacturer’s published instructions in the locations specified as follows: (1)* On the ceilings of rooms containing permanently installed fuel-burning appliances or fireplaces. (2) Centrally located within occupiable spaces served by the first supply air register from a permanently installed, fuel-burning HVAC system (3) Centrally located within occupiable spaces adjacent to a communicating attached garage

New Annex not to read. A.30.3.4.6.1(2) See A.24.3.4.2.1(2).

New Annex not to read. A.30.3.4.6.5(1) See A.24.3.4.2.1(2).

Do the same for NFPA 5000

Page 14 of 35

Page 15: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 7 & Carbon Monoxide Detection August 10, 2012 Definitions Reviewed:

The following have been extracted from NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, 2012 Edition

Fuel-burning appliance. A device that burns solid, liquid, or gaseous fuel or a combination thereof. Fireplace. A hearth, fire chamber or similarly prepared area and a chimney. [211-2010] Note. The annex note to the definition of fuel-burning appliance states that such appliances include, but are not limited to, devices used for cooking, heating, lighting, or decorative purposes; and examples include wood stoves, portable space heaters, ranges, furnaces, water heaters, clothes dryers, gas refrigerators, and gas lamps.

The following have been extracted from NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel–Burning Appliances, 2010 Edition

Appliance. Any device that utilizes a fuel to produce light, heat, power, refrigeration, or air conditioning.

Fuel-Burning Appliance.

Pellet Fuel–Burning Appliance. A closed combustion pellet vent or chimney- connected solid pellet fuel–burning appliance incorporating a fuel–feed control mechanism. Solid Fuel–Burning Appliance. A chimney-connected device that burns solid fuel designed for purposes of heating, cooking, or both. Residential-Type Heating Appliance. Fuel-burning appliances, not including high-pressure steam boilers, that are mainly used in residences but that might be used in other buildings, and that do not produce continuous flue gas temperatures exceeding 1000°F (538°C). Heat-Producing Appliance. An appliance that produces heat by utilizing electric energy or by burning fuel.

Fireplace. A hearth, fire chamber, or similarly prepared area and a chimney. Factory-Built Fireplace. A fireplace composed of listed, factory-built components assembled in accordance with the terms of the listing. Masonry Fireplace. A hearth and fire chamber of solid masonry units, such as bricks, stones, listed masonry units, or reinforced concrete, provided with a suitable chimney. Fireplace Accessories. Accessories intended for field installation into or attachment to existing masonry fireplaces. These include such items as heat exchangers, door assemblies,

Page 15 of 35

Page 16: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

NFPA Residential Task Group on Fireplaces Page 8 & Carbon Monoxide Detection August 10, 2012

tubular grates, and blowers. Fireplace Insert. A factory-built, field-installed product consisting of a firebox assembly designed to be installed within or partially within the fire chamber of a fireplace that uses the fireplace flue to vent the products of combustion. Fireplace Stove. A freestanding, chimney-connected, solid fuel–burning appliance that is designed to be operated with the fire chamber either open or closed. Combination Room Heater/Fireplace Stove. A chimney-connected, solid fuel–burning room heater that is designed to be operated with the fire chamber either open or closed.

Page 16 of 35

Page 17: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

1

NFPA Second Draft MeetingNFPA Second Draft Meeting

NFPA 101/5000

June 24, 2013

NFPA 101/5000RESIDENTIAL OCCUPANCIES

COMMITTEE

June 24, 2013

San Diego, CA

1

NFPA Second Draft MeetingNFPA Second Draft Meeting

At this and all NFPA committee meetings we are concerned with yourmeetings we are concerned with your safety

If the fire alarm sounds, please proceed to an exit

2

Page 17 of 35

Page 18: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

2

NFPA Second Draft MeetingNFPA Second Draft Meeting

Members, please verify/update your contact informationcontact information

Use of tape recorders or other means capable of reproducing verbatim transcriptions of this meeting is not permitted

3

NFPA Second Draft MeetingNFPA Second Draft Meeting

GuestsAll guests are asked to sign in andAll guests are asked to sign in and

identify their affiliations

Participation is limited to TC members or those individuals who have previously requested time to address the committee

Other participation is granted at theOther participation is granted at the discretion of the Chair

Guest seating is located around the room

4

Page 18 of 35

Page 19: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

3

NFPA Second Draft MeetingNFPA Second Draft Meeting

Members categorized in ANY interest category who have been retained tocategory who have been retained to represent the interests of ANOTHER interest category must declare those interests to the committee and refrain from voting, both in the meeting and on the ballot itemthe ballot item

5

NFPA Second Draft MeetingNFPA Second Draft Meeting

General ProceduresGeneral ProceduresFollow Robert’s Rules of Order

Discussion requires a motion

6

Page 19 of 35

Page 20: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

4

NFPA Second Draft MeetingNFPA Second Draft Meeting

Motions for Ending Debate - Move Previous Question or “Call thePrevious Question or Call the Question”Not in order when another has the floor

Requires a second

This motion is not debatable and does not automatically stop debateautomatically stop debate

A 2/3 affirmative vote immediately closes debate and returns to the original motion on the floor

Less then 2/3 allows debate to continue

7

NFPA Second Draft MeetingNFPA Second Draft Meeting

Committee member actions:

M b dd th h i Member addresses the chair Receives recognition from the chair Introduces the motion Another member seconds the

motionmotion

8

Page 20 of 35

Page 21: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

5

NFPA Second Draft MeetingNFPA Second Draft Meeting

Committee chair actions:

States the motionCalls for discussionEnsures all issues have been heardTakes the voteA th lt f th tAnnounces the result of the vote

9

NFPA Second Draft MeetingNFPA Second Draft Meeting

Technical Committee on Residential OccupanciespConsumer, 1 Member: 4%Enforcer, 4 Members: 15%Insurance, 2 Members: 7%Installer/Maintainer, 1 Member: 4%Manufacturer, 6 Members: 22%S i l E t 8 M b 30%Special Expert, 8 Members: 30%User, 5 Members: 19%Research & Testing, 0 Members: 0%Labor, 0 Members: 0%

10

Page 21 of 35

Page 22: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

6

NFPA Second Draft MeetingNFPA Second Draft Meeting

Timeline

C t St (S d D ft) Comment Stage (Second Draft):Public Comment Closing Date: 05/03/2013Second Draft Meeting: TodayPosting of Second Draft for TC Balloting: 08/23/2013Posting of Second Draft for NITMAM: 01/03/2014

Tech Session Preparation:NITMAM Closing Date: 02/07/2014NITMAM /CAM P ti D t 04/04/2014NITMAM /CAM Posting Date: 04/04/2014NFPA Annual Meeting: 06/09-12/2014 (Las Vegas)

Standards Council Issuance: Issuance of Documents with CAM: 08/14/2014 edition date

11

NFPA Second Draft MeetingNFPA Second Draft MeetingNew Process New Process –– What’s New?What’s New?

Changes in Terms:New Term Old Term

Comment Stage ROC Stage

Public Comment Public Comment

Second Draft Meeting ROC Meeting

Second RevisionCommittee Comment or Accepted

Public Comment

Committee Comment (a Comment reported as RejectedCommittee Comment(a Second Revision that failed

ballot)

(a Comment reported as Rejected due to failed ballot)

Second Draft Report ROC

Second Draft ROC Draft

12

Page 22 of 35

Page 23: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

7

NFPA Second Draft MeetingNFPA Second Draft Meeting

T h i l C itt A ti• Technical Committee Actions:

Resolving Public Comments Committee Action and Committee Statement

Creating Second Revisions

13

14

Page 23 of 35

Page 24: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

8

NFPA Second Draft MeetingNFPA Second Draft Meeting

• Resolving Public Comments (See Regs §4 4 8 1)(See Regs §4.4.8.1)Committee develops a Committee Action Accept

Reject but see…

Reject

Reject but Holdeject but o d

15

NFPA Second Draft MeetingNFPA Second Draft Meeting

• Committee StatementsCommittee must clearly indicate reasons for not

i h d i d/ iaccepting the recommendation and/or point to a relevant Second RevisionAll Public Comments Actions must have a

Committee StatementMust include a valid technical reasonNo vague references to “intent”E l i h th b itt ’ b t ti ti iExplain how the submitter’s substantiation is

inadequateNeither Public Comment Actions nor Committee

Statements get balloted

16

Page 24 of 35

Page 25: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

9

NFPA Second Draft MeetingNFPA Second Draft Meeting

• Create a Second Revision (SR)Committee wants to make a change (toCommittee wants to make a change (to

add, delete or modify) the First Draft

Committee develops a Committee Statement (CS) substantiating the change

Each SR gets balloted

17

NFPA Second Draft MeetingNFPA Second Draft Meeting

No “new material” after the Public Input Stage since it hasn’t had the benefit of gpublic review

What constitutes new material is decided by the Technical Committee or Correlating Committee

Adding “new material” at the Comment gStage could successfully be challenged through appeal to the Standards Council

18

Page 25 of 35

Page 26: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

10

NFPA Second Draft MeetingNFPA Second Draft Meeting

Formal voting V ti d i ti i d tVoting during meeting is used to

establish a sense of agreement (simple majority)Secured by letter ballot (2/3

agreement)g )Only the results of the formal ballot

determine the official position of the committee on the Second Draft

19

NFPA Second Draft MeetingNFPA Second Draft Meeting

Ballots are on the Second Revisions (SR) ONLYPublic Comment Actions and Committee

Statements not ballotedStatements not ballotedReference materials are available - Second Draft, Public Comments, First Draft Report

Ballot form allows you to vote: Affirmative on all SRAffirmative on all SR with exceptions specifically

notednoted Ballot form provides a column for affirmative

with commentNote: This box needs to be checked only if there

is an accompanying comment Reject or abstain requires a reason 20

Page 26 of 35

Page 27: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

11

NFPA Second Draft MeetingNFPA Second Draft Meeting

Initial ballot

Circulation of negatives and comments

Members may change votes during circulation

Second Revision that fails letter ballot is designated as a Committee Comment (indesignated as a Committee Comment (in the 2nd Draft Report), marked as “Reject” and deleted from the Second Draft.

21

NFPA Second Draft MeetingNFPA Second Draft Meeting

If a Second Revision fails ballot and the subject text was a result of a First Draft h S l t B ll t i d t dchange, a Supplementary Ballot is conducted

Ballot asks TC if it still favors the First Revision change reported in the First Draft

If Yes, same change appears as Second Revision and is shown in the Second Draft

If No, the change appears as a Committee Comment (rejected) and the text reverts toComment (rejected) and the text reverts to previous edition

See Regs §4.4.10.2.1

22

Page 27 of 35

Page 28: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

12

Electronic Balloting Electronic Balloting • Ballots will be an online format• Alternates are strongly encouraged g y g

to return ballots

• Ballot session will time out after 90• Ballot session will time out after 90 minutes

• Use “submit” to save your work

23

Electronic Balloting Electronic Balloting

Click link on the ballot email received

Sign in with NFPA org Committee Login and Sign in with NFPA.org Committee Login and Password

24

Page 28 of 35

Page 29: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

13

Electronic Balloting Electronic Balloting

Select either Affirmative on All or Affirmative with Exception(s)Affirmative with Exception(s)

25

Electronic Balloting Electronic Balloting

Use “See FR/SR - #” link to review all First/Second Revisions

Choosing AFFIRMATIVE ON ALL

Revisions Use “Edit election” to change individual votes or to

modify vote after submitting ballot

26

Page 29 of 35

Page 30: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

14

Electronic Balloting Electronic Balloting

Make selection: Affirmative with Comment, Negative, or AbstainN l ti d d f lt t ffi ti

Choosing AFFIRMATIVE WITH EXCEPTION(S)

No selection made-defaults to affirmative Must include comment on each vote

27

Electronic Balloting Electronic Balloting

To complete ballot click Participant Consent and SubmitConsent and Submit

Return and edit any votes before ballot due date

28

Page 30 of 35

Page 31: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

15

TC Struggles Code Fund Research ProjectTC Struggles with an Issue

• TC needs data on a new technology or emerging issue

• Two opposing views on an issue with no real data

Code Fund Lends a Hand

• TC rep and/or staff liaison submits a Code Fund Request

• Requests are reviewed by a Panel and chosen based

Research Project Carried Out

• Funding for project is provided by the Code Fund and/or industry sponsors

• Project is completed and data is

• Data presented is not trusted by committee

on need / feasibility

available to TC

www.nfpa.org/codefund29

LegalLegal

Antitrust: the single most important provision- Federal law prohibits contracts, p p ,combinations, or conspiracies which unreasonably restrain trade or commerce Section 1 of the Sherman Act

Patent: Disclosures of essential patent claims should be made by the patent holder but others may also notify NFPAholder, but others may also notify NFPA if they believe that a proposed or existing NFPA standard includes an essential patent claim

30

Page 31 of 35

Page 32: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

16

LegalLegal

Activities Disapproved by the CourtsPacking meetingsPacking meetings

Hiding commercial interest throwing the committees out of balance

No final decision-making authority to unbalanced Task Groups; include all interested partiesinterested parties

Hiding scientific or technical information from committees

31

Doc Info PagesDoc Info Pages

Document Information Next Edition

S

Technical Committee

C• Document scope• Current/Previous

Edition information• Issued TIAs, FIs and

Errata• Archived revision

information• Standard Council

Decisions• Articles and Reports

• Submit Public Input/Comments via Electronic Submission System.

• Meetings and Ballots• ROP/ROC or First

Draft Report and Second Draft Report

• NITMAM and Standard Council Decisions

• Committee name, responsibility and scope

• Staff liaison• Committee list

• Private committee contact information

• Current committee documents in PDF format• Articles and Reports

• Read only document • Private TC info• Ballot circulations,

informational ballots and other committee info

format• Committees seeking

members and committee online application

32

Page 32 of 35

Page 33: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

4/10/2013

17

NFPA Second Draft MeetingNFPA Second Draft Meeting

Any questions?

33

Page 33 of 35

Page 34: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

1

Harrington, Greg

From: Cote, RonSent: Wednesday, November 21, 2012 2:33 PMTo: Bigda, Kristin; Harrington, Greg; Fraser, Allan; Vecchiarelli, TracyCc: Solomon, RobertSubject: SAF Agenda Item for Second Draft Meetings

Follow Up Flag: Follow upFlag Status: Flagged

Please add the subject of Definitions to each SAF/BLD technical committee Second Draft meeting agenda for which you serve as staff liaison. Each Technical Committee chair is asked to identify a member to serve on the definitions task group. The Minutes item from the SAF-AAC Correlating Committee’s November 6, 2012 meeting follows:

Definitions. The committee agreed to have each defined term assigned to a specific technical committee so that committee would have responsibility for the maintenance and revision of such term. A task group is to be formed after the Second Draft meetings of the current revision cycle. The task group will report to the Correlating Committee (CC) its recommendations for the definitions assignments in time for the CC to review the recommendations at its first meeting of the 2018 revision cycle. Each Technical Committee chair is asked to identify a member to serve on the task group.

Allan and Tracy, the BLD-AAC Correlating Committee asked that same be done by the NFPA 5000 TCs. Ron Coté, P.E. Principal Life Safety Engineer NFPA - Quincy, MA USA  

 

Page 34 of 35

Page 35: AGENDA NFPA Technical Committee on Residential Occupancies ... · Newport Fire Department 21 West Marlborough Street Newport, RI 02840 Rhode Island Association of Fire Marshals E

1

Harrington, Greg

From: Cote, RonSent: Wednesday, November 21, 2012 2:43 PMTo: Bigda, Kristin; Harrington, Greg; Fraser, Allan; Vecchiarelli, TracyCc: Solomon, RobertSubject: Hazardous Materials - Agenda Item

Follow Up Flag: Follow upFlag Status: Flagged

Please add the subject of Hazardous Areas to each SAF/BLD technical committee Second Draft meeting agenda for which you serve as staff liaison. Each Technical Committee is asked to decide whether it wants to participate in a task group on the subject of hazardous materials. The Minutes item from the SAF-AAC Correlating Committee’s November 6, 2012 meeting follows:

Hazardous Materials. Jeff Tubbs raised the issue of whether NFPA 101 should address hazardous materials (as done in NFPA 5000 Chapter 34). The committee noted that health hazards are not within the scope of NFPA 101. Conflicts exist among the NFPA codes. It was agreed to:

o Add the subject of hazardous materials to the agenda for all NFPA 101 technical committee Second Draft meetings

o Gather comments from each technical committee including whether it wants to participate in a task group on the subject of hazardous materials

o Report results to the Correlating Committee at its Second Draft review meeting o Ask the Standards Council, after the Correlating Committee’s Second Draft meeting, to

establish a task group from the membership of the NFPA 1, 30, 101, 400 and 5000 committees to address conflicts and overlapping requirements related to hazardous materials

Allan and Tracy, the BLD-AAC Correlating Committee asked that same be done by the NFPA 5000 TCs. Ron Coté, P.E. Principal Life Safety Engineer NFPA - Quincy, MA USA  

 

Page 35 of 35