This research study aimed at creating a data base that will assist in the effective rational
use of energy and high-quality base in this kind of buildings (hospitals). This study focused on
the new methods and improvements that will ensure our consumption of energy, thus reducingthe economic cost.
The following table and figures summarizes the effect of each improvement on thermal
load if it has been added separately to the building.
Table (5-1):- effect of total improvements on thermal loads.
ImprovementHeating load saving
(kW)
Cooling load
saving(kW)U 33 22
SC 0 17.4
Lights 0 28.6
Total 33 68
Figure (5-1):- percentage of saving in heating load .
saving10%
Total heatingload
90%
Percentage saving in heating load
-
8/8/2019 air conditioning (ch5)
3/4
116
Figure (5-2):- Percentage saves in cooling load from different improvement s .
Adding to these improvements the use of solar system to produce the domestic hot water
and incineration of solid waste by which we are getting rid of the steam boiler and so removing
these wastes from the environment.
If all improvements has been added for the base case, fixed cost of the improved case was
higher than the base case, on the other hand the total annual operating cost was lower for the
improved case and the pay back period for the improved case was about 5 years and 7 months
which is logical since the life of this project is assumed to be 20 years.
Also it has been detailed the energy saving and money saving by adding each
improvement alone and the pay back period for each. All these improvement have a pay back
period less than 1 year
From previous chapters we can notice that there was big chance to improve health carebuilding has a introduced different types of improvements that are recommended to be added to
our base case with cost analysis for each .In this section we will discuss the case in which we
have added total improvements with detailed economical analysis.
U7% Sc
6%
Lights10%
Total heatingload77%
Percentage saving in cooling load
-
8/8/2019 air conditioning (ch5)
4/4
117
In winter (heating mode) as shown in the previous table that load saving in heating load
is equal to 33 kW . Total heating load with domestic hot water has been reduced from 283 kW to
250 kW
In summer (cooling Mode) as shown in the previous table that load saving in cooling
load is equal to 68 kW . Total cooling load has been changed from 293.4kW to 225.4kW.
Finally, we recommend those who are planning for new projects for applying some or all
our improvements that has been done on this building which we consider as energy efficient
building. And for those who are interested in our project subject to test more improvements to bedone on this type of buildings; such as system used for heating and cooling and searching for the
most economical system between chiller and air handling units or VRV system or absorption
etc. In the field of medical waste incineration it is highly recommended to make more specified
studies on the exhaust gases that produced from incinerating and it effect on environments and
do all possible ways to reduce its hazardous effects.