Range 8 TR to 147 TR(26 kW to 516 kW)

R-134a

ACUV-D Series Air Cooled Condesing Units

Sharjah Economic Excellence Award winnerwww.skm.aefacebook.com/skmuae youtube.com/marketingskm

SKM Air Cooled Condensing UnitsACUV Series - R134a

2

ACU V - 5 1 008 D Y

Nomenclature

ContentsLegend ............................................ 2Nomenclature ................................. 2Introduction ..................................... 2 General Features ............................ 3Component Features ...................... 3Control Panel .................................. 5Unit Controller ................................. 5Optional Features ........................... 6Engineering Specifications ............. 8Capacity Ratings ............................ 12Compressor Starting ...................... 16Capacity Control Steps .................. 17

Selection Procedure ..................... 17Field Connections ......................... 18Typical Wiring Diagram ................. 19Electrical Data .............................. 20Dimensional Data ......................... 24Loading Points .............................. 27Location & Space Requirements .. 29Unit Installation ............................. 29Typical Refrigerant Piping ............. 31Recommended Line Sizes ............ 32Guide Specification ....................... 34

IntroductionSKM ACUV series Air cooled condensing unit are designed for the use on systems with indoor units connected to remote condensing units located outside either on ground or on roof level.

SKM ACUV units are manufactured to meet the requirements of the gulf severe climatic conditions.

SKM ACUV Air Cooled Condensing unit are ideal for warehouses, large halls, schools, mosques, or wherever the requirement calls for a heavy duty unit with a semi-hermetic compressor.

SKM ACUV series Air Cooled Condensing units are used for commercial and industrial applications where high efficient condensing units are needed to match an indoor central station AHUs or coils to get maximum performance advantages of split sytem with reasonable initial cost.

SKM ACUV series provide efficient operation, wide range of design flexibility coupled with packaged concept requiring least on-site work.

The ACUV Air Cooled Condensing unit are available in 30 different models from 8 TR to 126 TR (26 kW to 443 kW) in 50 Hz and 9 TR to 147 TR (32 kW to 516 kW) in 60Hz at nominal conditions in one, two, three or four refrigeration circuits.

SKM ACUV Air Cooled Condensing unit are rated in accordance with AHRI-365.

SKM provides qualified service and stock of replacement parts in all major cities of the G.C.C. countries, Egypt, Jordan, and Pakistan. See back cover for details or call SKM.

SKM Air Conditioning Equipment,

You name it.....We cool it

Legend

The following abbreviations are used throughout this manual:

BPF .......... By-pass Factorcfm .......... cubic feet per minuteEER .......... Energy Efficiency RatioHz .......... Hertzinwg .......... inches of water gaugekW .......... kilowattskg .......... kilogramlbs .......... pounds weight (British units)L/S .......... liters per second

MBh .......... BTUH x 1000Ph .......... PhasePa .......... PascalsPD .......... Pressure DropPI .......... Power InputRPM .......... Rotations per MinuteTR .......... Tons of Refrigeration = 12 MBhV .......... Volt

SKM reserves the right to change, in part or in whole the specifications of its Air Conditioning Equipment at any time in order to add the latest technology. Therefore, the enclosed information may change without any prior notice.

Air cooledCondensing Unit

V-Shape CondenserConstruction

Power Supply 5 : 50HzFrequency 6 : 60Hz

No. of Refrigerant Circuits

Nominal Capacity (TR)

Power Supply CodeY: 380V-415V/3Ph/50HzP: 440V/3Ph/50HzR: 380V/3Ph/60HzE: 460V/3Ph/60HzT: 220V/3Ph/60Hz

Semi hermetic Reciprocating Compressor(R-134a)

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

3

All coils are tested against leakage by air pressure of 450 psig (3100 kPa) under water. All standard coils are 2,3 or 4 rows/ 14 FPI, 3/8” (9.5 mm) O.D. tubes. An integral subcooling circuit is provided to increase the cooling capacity, without additional operating cost.

For different application requirements, other optional condenser fin materials are available:

• Copper fins

• Electrotinned Copper fins

• Copper finned coils with electro-tinned after manufacturing

• Precoated Aluminum fins The pre-coated is hydrophobic polyurethane resin. This

option provides substantial corrosion protection beyond standard coil construction.

• Aeris Guard Coil coating The Aeris Guard Coil is a self etching high performance

modified epoxy finish that is specifically designed to coat and protect Aluminum and Copper surfaces. In addition, the coating is ideal for the protection of ferrous and non ferrous materials.

SKM ACUV series, all models, are restricted to a 14 FPI (1.8 mm) fin spacing condenser coil. Gulf dust storms and the general level of available maintenance in Gulf countries ensures this condenser coil design shall provide long life and maintenance-free operation with the least possibility of operational blockage on the condenser. Ample condenser surface and sensible air flow across the condenser ensures a low temperature differential between condensing temperature and the high Gulf ambients making the ACUV condensing unit perform efficiently and durably.

Condenser Fans

Condenser fans a re propeller type, aluminium alloy blades, directly driven by electric motors. Motors are Totally Enclosed Air Over (TEAO) six pole with class ‘F’ insulation and minimum IP55 protection. The TEAO and class ‘F’ insulation features ensure long life and are unique for SKM.

General FeaturesThe ACUV series is a modern, diversified and environment friendly series of air cooled condensing unit which uses R-134a as a refrigerant.

The complete ACUV condensing unit provides an extremely rugged, heavy duty, long-life and energy efficient that will provide higher efficiency over a long and extended life. What makes ACUV series the pride of SKM products is the use of:

• Semi Hermetic Reciprocating, heavy duty, energy efficient compressors

• Totally enclosed, Class F insulated, IP55 protected condenser fan motor

• Heavy duty condenser optimised in design for long-life maintenance free operation

• Cabinet construction specifically designed for Gulf climates

• IP 54 Electrical panel

• Factory installed, advanced and user friendly microprocessor based control system

• Interface capability with major BMS protocols (option)

The SKM ACUV series air cooled condensing units are durable, dependable, strong, reliable, versatile, quiet and energy efficient. Wherever a heavy duty condensing unit is required, the ACUV series should be an automatic choice.

Component Features

Compressor

Compressors used in ACUV-D series are fully accessible, semi-hermetic, reciprocating type. They are equipped with an oil sight glass, suction and discharge service valves and crankcase heater. All compressors are refrigerant gas cooled and equipped with an oil pressure lubrication system. The oil pump working in either direction is protected by an oil screen and a valve provided for the fitting of an oil pressure gauge.

For protection, all compressors are equipped with preset internal relief valve between suction and discharge sides.

The compressors are provided with vibration isolator springs underneath and therefore, external to ACUV-D series, AVM’s may be necessary only for critical applications.

The compressor motors have inherent thermal protection. This is in addition to other standard safety and protection controls. Compressors conform to DIN standards.

Condensers

Condenser coils are manufactured of seamless copper tubes mechanically bonded to aluminum fins to ensure optimum heat transfer.

Condenser Coil

Condenser Fan

SKM Air Cooled Condensing UnitsACUV Series - R134a

4

The motors are factory wired, using wires specially selected for high ambients operation, to unit control panel where the motor contactors are located to control the operation of these motors.The condenser fans are individually statically and dynamically balanced at the factory. Complete fan assembly is provided with suitable acrylic coated fan guard.

Casing/Structure

Designed for ease of handling and low cost to install. The ACUV Air cooled condensing Units are factory assembled and mounted on a rigid base. The casing used in ACUV condensing units is made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM A653 which is phosphatized then baked after an electrostatic powder coat of approximately 60 microns.

This finish and coating passed a 1000 hours in 5 % salt spray testing at 95°F (35°C) and 95% relative humidity as per ASTM B117.

The entire assembly comes complete with lifting holes on the base frame for rigging and installation. Access panels are provided for easy service and maintainance

Options available include hot dipped galvanized base frame and structural members aluminium/stainless steel panels on request, as an option.

Refrigerant Charge

ACUV Air Cooled Condensing units are shipped with nitrogen holding charge only. Actual charging with refrigerant R-134a should be done at site.

Piping connections

ACUV Air Cooled Condensing units piping connections come, as standard, terminated with sealed and soldered copper pipe ends.

Normal installation would require the cutting off (using roller-type tube cutters) of the ends prior to connections being resoldered and connected to the field supplied refrigerant pipework.

Refrigerant Pipe work

SKM ACUV series Condensing units are provided with all internal piping, using ACR grade copper tubing, between compressor and condenser.

Loose supplied liquid line refrigerant controls are available as an option for field installation (Please specify CRSP). When this option is ordered, the unit will be supplied with a correctly sized thermostatic expansion valve, liquid line solenoid valve, liquid line sight glass/moisture indicator and filter drier having flared or soldered ends isolatable with one shut-off valve.

Shut-off valve for the other side of the filter drier can be supplied, if option CXFV is specified.

Whether or not, these options are include, installation of solenoid valve in the liquid line near the evaporator is mandatory for proper operation of the unit since the unit will switch off only after a pump down cycle. Solenoid valve is to interlocked with controller as per terminals in the wiring diagram.

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

5

Control Panel

The unit mounted control panel enclosure is fabricated out of heavy gauge sheet steel in phosphatized powder coated baked finish. The enclosure conforms to IP54 as per guidelines in IEC 529. A hinged access door and key-fastener is provided for easy access and security. The panel is factory wired in accordance with NEC 430 & 440, labelled, tagged and features 220V / 240V controls.

• Compressors are with DOL or part winding starting, depending on model

• Individual compressor & condenser fan motor contactors

• Motor protector circuit breaker for condenser fan motors

• Control circuit breaker

• Unit on/off Switch

• Microprocessor control boards

• Control Relays

• Power and control terminal blocks

Microprocessor Controller

All ACUV series condensing units are equipped with a full function microprocessor based controller as a standard feature. The controller is factory programmed for the control of AHU fan motor, compressors and condenser fans. The controller comes with a built in keypad and display for simple but meaningful man machine interface. This controller provides complete operational control for the unit and has built-in auto diagnostic capability that can signal normal operation or alarm conditions as well as shutting down the unit or system if necessary.

The controller comes with a loose supplied sleek and elegant design room unit for installing in the conditioned space. Communication between unit controller and room unit is through two wire interface. The communication cable should be 2 core, twisted pair, unscreened with stranded conductors. Maximum distance between room unit and controller can be 700 meters. The room unit has a built in sensor for measuring the room temperature. It transmits room temperature, set point, unit operating mode, operating schedule etc. to the unit controller. Control of the compressors is based on room temperature and the set point, as standard. If unit control needs to be based on duct temperature, please specify during time of order.

Microprocessor Controller

The Main Features of the controller are as follows:

• Built in LCD display with back light

• Roll & push knob and 3 function buttons

• Battery backed up built in real time clock

• Multiple authorization level to provide tight security for the control system

• Capacity control based on room temperature or return air temperature

• Alarm history

• A sleek & elegant design room unit.

Display Information

SKM ACUV series condensing units offer LCD display which allows the operator to access different parameters of the unit. Operator can view and change the unit parameters. The display information includes:

• Status• Outputs• Inputs• Alarms• Set points• Password

System Control Philosophy

Unit maybe enabled or disabled through the on/off switch in the unit control panel. Control is based on room temperature sensed by room unit. Compressors will be staged based on the set point and actual room temperature. On an increase in room temperature, cooling stages will be added and on a decrease in room temperature, cooling stages will be removed from the system.

System Protection

The intelligent microprocessor based controller monitors all the safeties related to the unit and makes the necessary protections, by shutting down the entire unit or the effected circuit. The protection includes:

• Low suction pressure• High discharge pressure• Low oil pressure• High compressor motor temperature• Compressor short cycling

BMS Connectivity (Optional)

Volt free contacts for run status, common fault status, auto mode status and provision for remote on/off shall be provided as option if required.

In addition, the ACUV microprocessor can support the major BMS protocols such as BACnet, Modbus & LON. Extra hardware may be required depending on the protocol.

Room Unit

SKM Air Cooled Condensing UnitsACUV Series - R134a

6

Optional Features

Alternative Condenser MaterialMade of copper tubes and alternative fin material and/or protective coating.

• For pre-coated Aluminum fins, specify(FAP)

• For Aluminum fins with Aeris Post Coat Protection, specify (FAA)

• For Copper fins, specify (FC)

• For Copper fins with Aeris Post Coat Protection, specify(FCA)

• For electrotinned Copper fins only, specify (CFT)

• For Copper finned coils electrotinned post manufacturing, specify (FCT)

Condenser Coil Guard (CGP)Galvanized wire mesh frame with painted finish for condensers. Recommended on ground level installations where coil needs to be protected against vandalism.

Galvanized Frame And Base (GFB) Steel frame and base which are hot dip galvanized after manufacturing process. This is recommended for highly corrosive environments.

Pressure Gauges (SDG)Suction and discharge pressure indication of each refrigerant circuit. Gauges are mounted outside the Control Panel.

Marine Paint (MP)To provide increased corrosion resistance coastal environments and offshore locations.

Capacity Control Steps (CRS)To provide additional capacity steps on the units. See Table 6 (Page 17) for optional steps available.

Hot Gas Bypass System (GBP)with solenoid valve to enable operation of a large sized unit at very low loads, during low load demand due to application requirements or where unit is selected to work on 100% fresh air applications.

IP-55 Control Panel (ICP)Control Panel for special applications to meet IP55 requirements.

Low Ambient Operation Kit (LAO)For unit operation down to lower than normal gulf ambient. Please specify during the time of order.

Main Isolator (Without Door Interlock) (ISO)For the main Power Isolation. (Consult SKM)

Control Transformer (CXT)This option is necessary and available for ACUV models rated for 440V/3PH/50Hz or 460V/3PH/60Hz or power supplies without neutral. When ordering for these voltages, this option must be ordered.

Voltage Monitoring Module (VMM)To prevent ACUV unit operation in the event of Phase loss, Phase reversal, and Under / Over voltage on the incoming line voltage.

Voltage Monitoring Module as per DEWA (DVM)Under voltage relay as per DEWA regulations. This option is available for Dubai, UAE only.

Circuit Breaker for Compressor (CBC)For those electrical specification calls for additional over load and short circuit protection.

External Overload Protection (EOP)For those electrical specification requires additional overload protection for the compressors.

Part Winding Start (PWS)Where specifically required by local codes, compressors may be with Part Winding Start to reduce the high inrush current at starting. (Not available for D10 & D15 Compressor at 380/3/60 Hz & 220/3/60 Hz). Some of the compressors are with part winding start as standard. Refer to page 16 for more details.

Unload Start Kit (USK)This option is required when the compressor needs a high starting torque such as when the load is high.

Star – Delta Starter (SDS)To reduce the starting current of compressors using reduced voltage starting method. Compressors will be started in Star & after few seconds it will be changed over to Delta.

Soft Starter (SSS)To reduce the starting current of compressors using reduced voltage starting method. Compressors will be started using electronic solid state soft starters that will ramp up the speed of the compressors to rated speed within few seconds thus reducing the mechanical & electrical stresses .

Suction Pressure read out Capability (SPC) Additional transducer in suction line to display suction pressure in microprocessor.

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

7

BMS Interface Volt free Contacts (VFC)Volt free contacts for run status, common fault status, auto mode status and provision for remote on/off shall be provided as option if required. For additional requirements, please contact SKM.

BMS Interface thru protocol (BMSP)For interfacing the units with major BMS protocols such as BACNet, Modbus or LON. Extra hardware may be required depending on the protocol.

Options for Field Installations

Anti-vibration mounts (CAVM)Recommended for roof mounted units or other locations in the vicinity of occupied spaces, where noise/vibration may be objectionable.

Hi-Lo Gauges (CSDG)Without piping or isolating pet cocks.

Liquid Line Controls (CRSP)Comprises of correctly sized thermostatic expansion valve,suitable solenoid valve,filter drier,sight glass and one number shut-off per circuit

Extra Shut Off Valve (CXFV)To fully isolate filter drier, an additional shut-off valve can be incorporated in the liquid line. Must be ordered, if required, with CRSP option.

Duct Temperature Sensor (DTS)In order to control the unit based on return / supply air duct temperature.

Contact SKM for all such applications or requirements.

SKM Air Cooled Condensing UnitsACUV Series - R134a

8

ENGINEERING SPECIFICATIONS - 50 HZ

Table 1

Notes:

1. Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365. 2. Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST. 3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil. 4. Condensing units are shipped with nitrogen holding charge only.

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

Cooling Capacity (1)

Cooling Capacity (2)

Cooling Capacity (1)

92404361

Condenser Motor

Air Flow Rate

Totally enclosed, air over Class F insulation, 6-pole, IP-551.5/2

18180181808438

1.5/214.11

1004

0.37/2

4210

723/28920

0.75/2

6249

273100

9/98.4

561

18.52

1526

92614

1237

52030-D316000264000

957434

52022-D

31.5

9847629010085023

51028-D

455

26160

Propeller direct drive 960 RPM

77374

2.9

18180

Semi-Hermetic Reciprocating 1450 RPM

26160823/3823/3

4.2 / 4.2

228300

Condenser Motor

Face AreaCondenser Coil

Compressor

Condenser FanAir Flow Rate

1.5/2

66911

2

Number of Refrigerant Circuits

Unit Operating Weight

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

22.1/11

8580

271237912

40.0

17217

1

1140872 8951980

994 98521921923

27.1/5.0

1.5/3

2

14.7/14.731.53

898

26.7/6.714.3

1

15.7/1114.3

741

31.53

99648

D-04025D-03015384000340000

699

829/3

52034-D

811

53.3

4.2 / 4.2 4.2 / 4.2

53.3

2

98242332700

823/4

293900112544

135756114654

64.0

3/3283/328

335200

1.5/3

26160

114302

12346Totally enclosed, air over Class F insulation, 6-pole, IP-55

12346 12346

3.7

80041

1.5/4

3.4

723/2

2

535000

1634

52045-D455000390000336000

19.4Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

2 1 110.9

210.9 / 0.9 0.9 / 0.9

9.48

1

0.37/2

Model17200016000052015-D51008-D

8800051010-D

4.2/4.22

52028-D

692

4.3 6.41 1

51014-D

Condenser Coil Face Area

0.9

1.8 1.8

Compressor

3.4

823/2

24.4

628/2

24.42.3

2/3282/826

2.3

823/2

2.93.924.424.91

2.731.5

2.3

51022-D

78546

51021-D

231200201000

26800068581

234000

22304 29220

1

114000

7610025791

Semi-Hermetic Reciprocating 1450 RPM

9970040709

33411

677615891014850013890050410

43523

52017-D226000

168100 19540049267

46893

2/5.12/57.0 0.75/212.1/8.8 11/11

52019-D

57268

6623719400056858

Propeller direct drive 960 RPM

8580 8580

0.9 / 0.91.1

13240132406249

2.931.5

26160

20.4/20.4 24.4/24.4

3648012346

723/2132406249

17880

11.6

3204013167

1.5/3 1.5/3

221.11/1.116.7/2.11

24.7/16.8

2790015121

13002514 2595 2867

1177

9.25/9.25

5/5

1541 17882

3.7 5.95.03.7 3.7 5.0

156800

720

391200

2 2

463200133353

1588

1.94.2 7.2

25.58

111

24.26

1

1.14.2 3.4 / 3.4 3.4 / 3.4 3.4 / 3.4

1.1 / 1.10.21.1 / 1.10.2

25.5/4.0

97509

7.2 / 7.26.74.3 / 2.46.74.3 / 2.41.1 / 1.1 1.9 / 1.9

2 2

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)

Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

823/2

86137

1.1 / 0.9

40.0

1.5/3 1.5/3

10/5

1

823/3

11.1 / 0.9

40.040.0

Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

Condenser Fan

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)Number of Refrigerant Circuits

Unit Operating Weight

Model

Cooling Capacity (2)

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

9

ENGINEERING SPECIFICATIONS - 50 HZ

Table 1 ends

Notes:

1. Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365. 2. Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST. 3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil. 4. Condensing units are shipped with nitrogen holding charge only.

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)

6.7

4

936600

1.5/4

19312

30.4/24.5

Number of Refrigerant Circuits13.8/11.1

22

33.2/33.2 27.1/27.1/27.112.3/12.3/12.317.3/14.3

38.1/31.5

27.2 / 7.2 / 7.2

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)

2 / 1.9

2 / 2 / 2

854200

Condenser FanAir Flow Rate

Condenser Motor

Compressor

54114-D

5965

7.6 / 7.2 7.6 / 7.6 7.6 / 7.6 7.6 / 7.6 7.2 / 4.2 / 4.2

9.1

34971586

2 / 2 2 / 2

1138900317995

4092019312

119000053086-D

25910

72.0

3734079120829/8

823/4

2

59340

28.5/28.5/28.5

54095-D

386870348769

6/9286/92879120

Model

Unit Operating Weight

829/8

7.6 / 7.6 / 7.6 / 7.6

1085000

2705

1320000

37280

4/5.14/5.1

40920

250352896000262603

990000

3334

17594

1035000

Face Area9.1

2 / 2 / 1.9 / 1.9 2 / 2 / 2 / 27.6 / 7.6 / 7.2 / 7.2Oil Charge(Polyol Ester) per Crkt

(1/2/3/4)

1436

Number of Refrigerant Circuits

28005

3166

290152

53080-D

3

16.2/16.2/16..2

Condenser FanAir Flow Rate

3

Condenser Motor

303341

97.5 97.5Condenser Coil

59340

7.6 / 7.6 / 7.6 7.6 / 7.6 / 7.6

35.9/35.9/35.916.3/16.3/16.3

274502

3630

35.9/35.9/35.916.3/16.3/16.3

37.6 / 7.6 / 7.6

43

9.1

Unit Operating Weight 6688 66923033 3035

66943036

7.6 / 7.6 / 7.6 / 7.67.6 / 7.6 / 7.6 / 7.63

2 / 2 / 2

0.0315.79

2 / 2 / 2

4

1415000

3337923010841027300

130.0130.0

58792666

53084-D

1.5/6

54106-D

26/26

23497

68512151

11.9/11.9

42880

1.5/4

25910

829/4

3

2023754900

33

1.9 / 1.1 / 1.1 1.9 / 1.9 / 1.9

3

54900

15.1/15.1

6/3284/928

37.6 / 7.2 / 7.22 / 1.9 / 1.9

6.7

Model

Condenser Coil

Compressor

Face Area

53064-D735000

6.7

193435181389150381

2 2

97.572.0 72.072.0 97.5

216647

97.5

823/6

563900

829/4

6.7

2

165270660000618900

2 / 2

186342

595000190504174385 235932

513100224209209555

635800

765000

203986

3

215416

52049-D 52053-D650000

52060-D52058-D715000

53070-D855000805000

53068-D

823/6

250586739200696000

9.19.1

12.9/12.9/12.912.9/12.9/12.928.5/28.5/25.8

25910

1.5/6

27836137

1.5/6

54900

414713 4425561221900

12.1

4 4

2 / 2 / 2 / 2

358118

2 / 2 / 2 / 2

130.0

54120-D1510000

1301500

16.6/16.6/16.6/16.6

1.5/836.6/36.6/36.6/36.6 36.6/36.6/36.6/36.6

1.5/8

381448

12.1

29.3/29.3/29.3/29.3 36.6/36.6/36.6/36.68/5.16/5.16/5.1 1.5/6

35.8/35.8/35.8

829/6

1.5/8

416.6/16.6/16.6/16.6

39198633 86413915

4

3912

16.6/16.6/16.6/16.613.3/13.3/13.3/13.34

8004

5934039342

79120

86263

Propeller direct drive 960 RPM

Totally enclosed, air over Class F insulation, 6-pole, IP-55

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

Semi-Hermetic Reciprocating Discus 1450 RPM

3734083360

043735008250082

829/8

Totally enclosed, air over Class F insulation, 6-pole, IP-55

Cooling Capacity (2)

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

Propeller direct drive 960 RPM

Semi-Hermetic Reciprocating Discus 1450 RPM

12.1 12.1

829/8

9.1

Cooling Capacity (1)

Cooling Capacity (2)

Cooling Capacity (1)

Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

SKM Air Cooled Condensing UnitsACUV Series - R134a

10

ENGINEERING SPECIFICATIONS - 60 HZ

Table 2

Notes:

1. Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365. 2. Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST. 3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil. 4. Condensing units are shipped with nitrogen holding charge only.

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

Cooling Capacity (2)

Cooling Capacity (1)

Cooling Capacity (2)

265500

6.5

1014

62026-D

962436

61032-D

114302

460

308000

628/2

4.3

Condenser Motor

1

112005286

9.48Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)Number of Refrigerant Circuits

628/2108205106

1

14.33

Condenser Coil

Condenser FanAir Flow Rate

Face Area 19.4

Unit Operating Weight

Condenser Coil

Compressor

Model

Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

Face Area

Cooling Capacity (1)

78664685053024325996

24.419.4 31.5

3.4 / 3.4

2

1252568

15660

696

8.5

62034-D

21535 1552

1.1/2

7.1/5.015.7/11

723/2 723/215660

14.25/4.25

2

39000090270

Condenser Fan

Condenser Motor2.2/2

Air Flow Rate 2212010439

Unit Operating Weight

21748 2009884 911

14.523.2/11.9

2.2/3

1008 1008

12223 2223

4.5/5.015.41

3186031860 31860

2.2/331.931.9

15036

2.2/3

6305163051

7.3/7.3

31860

100059

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)

1Number of Refrigerant Circuits

40.040.0 40.0

7.6

913

2 22013

16/16

77814

3.740.0

1.1 / 0.94.2 / 3.4

38700

390400

2.2/3Totally enclosed, air over Class F insulation, 6-pole, IP-55

1503633990

823/2

98740

5.0 5.0

368000

93083

62032-D395000

61036-D

2.0

336900107855

112954

5.9

823/3

3.7 7.37.3Propeller direct drive 1150 RPM

2.9

823/3823/3823/3

4.2 / 4.2

9.4/9.4 8.8/1.2147.815.5/4.0

7.6

445000

4.2 / 3.4

317600

704

723/2

2.924.4 29.3 31.524.4

62018-D

Semi-Hermetic Reciprocating 1750 RPM

79719

61011-D

39273

61016-D

58617

47392

134000

161700

7391

1.1/20.55/2 0.55/2

62020-D22600066237

195300006271007611

200000

5.05/5.0511.1/11.1

18600054513

1.1/2

57239

2.3

3.4 / 3.4

7391

Model

Compressor Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

61009-D1020002989488700

10.9 / 0.9 0.9 / 0.9

2.9Propeller direct drive 1150 RPM

2.7

1.14.2

0.93.4

2.3

61026-D

233900 268400

00001300026290856

27200061024-D

66735 68552

76788227700

62022-D

12

823/2

10270 10439

823/2 823/2

10439

25.80 26.02

21760 22120 22120

2.2/2 2/2.22/2.2Totally enclosed, air over Class F insulation, 6-pole, IP-55

7391

2 2 212.2/7.6 9.9/9.9 11.1/11.1

620000

157649

153869

64.0

829/3 823/4

21.1 / 1.14.2 / 4.2 7.2 / 7.2

2.2/324.4/24.426.9/16.8 21.8/21.8

2.2/42.2/3

62040-D 62046-D 62052-D

2

8231618 16521815734 749

11.71

11.8

1157 1197 13212551 2639 2913

1

537900

44400

1.9 / 1.9

2095416041 18264

1.1 / 1.1

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

823/3

1.1 / 1.1

15660

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

53.3 53.3

Semi-Hermetic Reciprocating 1750 RPM

181712131887

2.0

31.5

1.1 / 0.9

4.2 3.4 / 3.43.4

1.81.8

2

2.3

450000 525000

453900

1 1 20.9 1.1 0.9 / 0.9

4.2 / 4.2

11.97.2

2 1 2 2 1 2

133030114420341400 385400115768 130422

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

11

ENGINEERING SPECIFICATIONS - 60 HZ

Table 2 ends

Notes:

1. Cooling capacity at 95°F (35°C) ambient temperature according to AHRI-365. 2. Cooling capacity at Gulf conditions : 115°F (46.1°C) condenser entering air temperature & 45°F (7.2°C) SST. 3. Operating charge is approximate for condensing unit only and does not include refrigerant lines and evaporator coil. 4. Condensing units are shipped with nitrogen holding charge only.

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

ACUVBTUH

WBTUH

W-epyT-ytitnauQ

US GalLiter

-epyTft²m²-epyT-ytitnauQ / edoC

cfml/s-epyTWkytitnauQ / eziS

lbskg-

lbskg

Propeller direct drive 1150 RPM

Totally enclosed, air over Class F insulation, 6-pole, IP-55

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

Cooling Capacity (1)

Cooling Capacity (2)

Propeller direct drive 1150 RPM

Totally enclosed, air over Class F insulation, 6-pole, IP-55

Semi-Hermetic Reciprocating 1750 RPM

Air cooled 2, 3 or 4 rows 14 FPI (1.8 mm) fin spacing Cu tubes Al fins

Cooling Capacity (1)

Cooling Capacity (2)

Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

Oil Charge(Polyol Ester) per Crkt (1/2/3/4)

829/8 829/8

348828

12.9/12.9/12.93

49560

9.172.0

100880829/8

36.6/36.6/36.6/36.62.2/8 2.2/82.2/8

36.6/36.6/36.6/36.6

39608727 8731

4 4 416.6/16.6/16.6/16.6 16.6/16.6/16.6/16.6

3956

97.5

2.2/8

829/8

30688722

72000

3958

130.0130.0130.097.512.112.112.1

130.012.1

16.6/16.6/16.6/16.616.3/16.3/16.3 13.3/13.3/13.3/13.335.9/35.9/35.9 35.9/35.9/35.9 29.3/29.3/29.3/29.3 36.6/36.6/36.6/36.6

16.3/16.3/16.3

515826

7.6 / 7.6 / 7.2 / 7.2 7.6 / 7.6 / 7.6 / 7.6

404455

3883351420000

442819416178

4Semi-Hermetic Reciprocating 1750 RPM

2 / 2 / 2 / 2

1510900483587

2 / 2 / 2 / 2 2 / 2 / 2 / 2

47.6 / 7.6 / 7.6 / 7.6

47.6 / 7.6 / 7.6 / 7.6

97.5

1760000

281627386038

64132-D

6210

64140-D

66840

808500

3

3

97.5

12.9/12.9/12.9

31545

28.5/28.5/28.52.2/6

3

28.5/28.5/28.5

97.5

63078-D

236958 251407

63082-D995000935000

274033 291618857800

823/6

216794

6.7 6.7 6.7

7.6 / 7.62 / 1.9 2 / 2

7.2 / 7.2 / 7.2

13.8/11.2 12.2/12.2 17.3/14.3

2.2/4

Condenser FanAir Flow Rate

Condenser Motor2.2/4

829/4

24428

15.45/15.45

823/666840

823/6

31545

823/4

3154551760

829/4

38.1/31.5

Face Area

Compressor

Condenser Coil9.1

2 27.2 / 4.2 / 4.2

72.0

3

75500062058-D690000

653300191471174766

596300

Model

5959

62067-D835000

62071-D

72.0

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)Number of Refrigerant Circuits

62062-D

2.2/4

72.0

202227

2

720400

2339045400

211137

221278 244725

7.6 / 7.6

260844

2 / 2

767400

2

224912

Condenser Motor2.2/6 2.2/6 2.2/6

890000

2702

64124-D

34/34

49560

1608

64113-D

3546

12.9/12.9/12.9

23390

63074-D860000252052739700

3 3

829/6

370750

2 / 2 / 2

3

35.9/35.9/35.9

1.91.9

36763 6765

829/6

3398072000

33980

16083382 3546

2

Refrigerant (R - 134a) Operating Charge per Circuit(1/2/3/4) (3)

3066

Number of Refrigerant Circuits

829/6

1210000

2

8103

16.3/16.3/16.34

3675Unit Operating Weight

30676761

32151458

1041600

7.6 / 7.6 / 7.6

9938003370461150000

97.5

3

63098-D

30.4/24.6 26.9/26.9

354631

2

291266 305275

63094-D1265000

1088100318904

4

1650000

9.1 / 9.1 / 2 / 2 2 / 2 / 2

3

Unit Operating Weight

Air Flow Rate

Face Area

Condenser Fan

Compressor

Condenser Coil

Model 63100-D

1534

1190200

9.1

2 / 2 / 2

1380000

7.6 / 7.6 / 7.6

1325000

1535000

3

96000720007035401674 4530745307

9600033980

96000

28.5/28.5/28.5

449883

7.6 / 7.6 / 7.6

7.6 / 7.62 / 1.9 / 1.91.9 / 1.9 / 1.92 / 2 1.9 / 1.1 / 1.1

7.6 / 7.2 / 7.2

2

2.2/62.2/4

21426

2.2/6

7.6 / 7.2

829/4

1.97.6

66840

SKM Air Cooled Condensing UnitsACUV Series - R134a

12

Table 3

PI * PI * PI * PI *°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW35 1.7 71.4 20.9 5.5 66.3 19.4 5.8 61.1 17.9 6.2 55.9 16.4 6.540 4.4 79.7 23.4 5.7 74.1 21.7 6.1 68.3 20 6.4 62.6 18.3 6.845 7.2 88.6 26 5.9 82.4 24.2 6.3 76.1 22.3 6.7 69.8 20.5 7.250 10 97.9 28.7 6 91.2 26.7 6.5 84.3 24.7 7 77.5 22.7 7.535 1.7 93.8 27.5 7.6 87.4 25.6 8 80.9 23.7 8.5 74.4 21.8 8.940 4.4 104.2 30.5 7.9 97.2 28.5 8.4 90 26.4 8.9 82.9 24.3 9.445 7.2 115.1 33.7 8.1 107.5 31.5 8.7 99.7 29.2 9.3 92 27 9.950 10 126.5 37.1 8.4 118.3 34.7 9.1 110 32.3 9.7 101.9 29.9 10.435 1.7 131.4 38.5 10.9 121.9 35.7 11.6 112.4 32.9 12.2 102.8 30.1 12.840 4.4 145.9 42.8 11.3 135.6 39.7 12.1 125.2 36.7 12.8 114.9 33.7 13.645 7.2 161.4 47.3 11.8 150.2 44 12.7 138.9 40.7 13.5 127.7 37.4 14.350 10 177.7 52.1 12.2 165.6 48.5 13.2 153.5 45 14.1 141.4 41.4 15.135 1.7 190.7 55.9 16.5 176.8 51.8 17.3 162.8 47.7 18.1 148.9 43.6 18.940 4.4 211.7 62 17.3 196.5 57.6 18.2 181.3 53.1 19.1 166.1 48.7 2045 7.2 234 68.6 18 217.5 63.8 19.1 201 58.9 20 184.5 54.1 21.150 10 257.9 75.6 18.7 239.9 70.3 19.9 222 65.1 21 204.2 59.8 22.235 1.7 221 64.8 20.5 205.5 60.2 21.5 190.1 55.7 22.5 174.6 51.2 23.640 4.4 243.9 71.5 21.7 226.9 66.5 22.8 210 61.6 23.9 193 56.6 25.145 7.2 268.2 78.6 22.9 249.7 73.2 24.1 231.2 67.8 25.4 212.4 62.3 26.750 10 293.9 86.1 24.1 273.7 80.2 25.5 253.5 74.3 26.9 232.9 68.3 28.435 1.7 273.3 80.1 23.7 254 74.4 25.1 234.6 68.8 26.5 215.3 63.1 27.840 4.4 303.7 89 24.7 282.6 82.8 26.3 261.5 76.6 27.8 240.4 70.5 29.445 7.2 336 98.5 25.8 313.1 91.8 27.5 290.1 85 29.1 267.2 78.3 30.950 10 370.2 108.5 26.8 345.3 101.2 28.6 320.4 93.9 30.5 295.6 86.6 32.435 1.7 316.4 92.7 28.9 293.7 86.1 30.5 271 79.4 32.1 248.3 72.8 33.840 4.4 350 102.6 30.4 325.4 95.4 32.2 300.8 88.2 34 276.1 80.9 35.845 7.2 385.9 113.1 31.9 359.3 105.3 33.9 332.7 97.5 35.8 305.7 89.6 37.950 10 424.3 124.4 33.4 395.5 115.9 35.6 366.6 107.4 37.8 337.5 98.9 4035 1.7 140.1 41.1 11.1 130 38.1 11.8 119.7 35.1 12.4 109.4 32.1 13.140 4.4 156.2 45.8 11.6 145.1 42.5 12.4 133.7 39.2 13.1 122.4 35.9 13.845 7.2 173.3 50.8 12 161 47.2 12.9 148.5 43.5 13.7 136.2 39.9 14.650 10 191.2 56 12.4 177.8 52.1 13.4 164.3 48.2 14.3 151.1 44.3 15.335 1.7 159.5 46.8 13.5 148.1 43.4 14.2 136.7 40.1 15 125.3 36.7 15.740 4.4 177.1 51.9 14.1 164.6 48.2 14.9 151.9 44.5 15.8 139.5 40.9 16.745 7.2 195.5 57.3 14.6 181.8 53.3 15.6 168.1 49.3 16.6 154.7 45.4 17.650 10 214.7 62.9 15.2 200.1 58.6 16.3 185.4 54.3 17.4 171.1 50.1 18.635 1.7 184.7 54.1 15.4 172 50.4 16.3 159.1 46.6 17.1 146.2 42.8 1840 4.4 204.8 60 16 190.9 56 17 176.7 51.8 18 162.6 47.7 1945 7.2 226.1 66.3 16.6 210.9 61.8 17.8 195.4 57.3 18.9 180.3 52.9 20.150 10 248.1 72.7 17.3 231.9 68 18.5 215.5 63.2 19.8 199.4 58.5 21.135 1.7 217.4 63.7 19.1 201.7 59.1 20.1 186 54.5 21.2 170.4 49.9 22.240 4.4 240.7 70.6 19.9 223.7 65.6 21.2 206.5 60.5 22.3 189.6 55.6 23.645 7.2 265.4 77.8 20.8 246.9 72.4 22.2 228.3 66.9 23.5 210.2 61.6 2550 10 291.2 85.3 21.7 271.3 79.5 23.2 251.5 73.7 24.8 231.9 68 26.435 1.7 259.1 75.9 22.1 240.3 70.4 23.4 221.3 64.9 24.6 202.4 59.3 25.940 4.4 287.4 84.2 23 267 78.2 24.5 246.4 72.2 25.9 225.9 66.2 27.445 7.2 317.5 93.1 24 295.3 86.6 25.7 273.1 80 27.3 250.9 73.6 2950 10 349.2 102.4 25 325.3 95.3 26.8 301.3 88.3 28.7 277.4 81.3 30.635 1.7 279.4 81.9 24.5 259.2 76 25.7 239 70 26.9 218.8 64.1 28.140 4.4 309.7 90.8 25.6 287.7 84.3 27 265.5 77.8 28.3 243.6 71.4 29.845 7.2 341.8 100.2 26.7 317.9 93.2 28.3 293.9 86.1 29.8 270.2 79.2 31.450 10 375.7 110.1 27.8 349.9 102.6 29.5 324.1 95 31.3 298.6 87.5 33.135 1.7 318.4 93.3 27.7 295.2 86.5 29.2 271.8 79.7 30.5 248.5 72.8 31.940 4.4 353.2 103.5 29 327.9 96.1 30.6 302.5 88.7 32.2 277.2 81.2 33.845 7.2 390.2 114.4 30.2 362.7 106.3 32.1 335.2 98.2 33.8 307.8 90.2 35.750 10 429.4 125.9 31.4 399.6 117.1 33.5 369.8 108.4 35.5 340.2 99.7 37.735 1.7 373.2 109.4 33.6 345.7 101.3 35.1 318.1 93.2 36.6 290.6 85.2 38.240 4.4 413.4 121.2 35.2 383.5 112.4 37 353.5 103.6 38.7 323.7 94.9 40.545 7.2 456.3 133.7 36.8 423.8 124.2 38.8 391.2 114.7 40.7 359 105.2 42.850 10 501.8 147.1 38.4 466.5 136.7 40.6 431.3 126.4 42.8 396.5 116.2 45.2

51028-D

51030-D

52015-D

52017-D

SST

51021-D

51022-D

Condenser Entering Air Temperature

Total Capacity

51008-D

51010-D

51014-D

ModelACUV-D

95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)Total Capacity Total Capacity Total Capacity

52019-D

52028-D

52030-D

52034-D

52040-D

52022-D

Note:

* Power Input mentioned in these pages should not be used for Cable/Fuse selection. MCA & MFA Values given in the electrical data (Pages 20 to 24) should be referred for the same.

Computer Print outs for matched ratings with SKM Air Handling Units are available.

CAPACITY RATINGS - 50 HZ

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

13

Table 3 ends

PI * PI * PI * PI *°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW35 1.7 442.6 129.7 40.9 411.6 120.6 43 380.7 111.6 45 349.7 102.5 47.140 4.4 488.5 143.2 43.3 454.6 133.2 45.6 420.7 123.3 47.8 386.6 113.3 50.245 7.2 537.2 157.5 45.8 500.2 146.6 48.2 463.2 135.8 50.7 425.6 124.7 53.450 10 588.8 172.6 48.2 548.5 160.8 50.9 508 148.9 53.7 466.7 136.8 56.635 1.7 488 143 44.6 453.5 132.9 47 418.9 122.8 49.4 384.4 112.7 51.840 4.4 540.1 158.3 47 502.3 147.2 49.6 464.6 136.2 52.2 426.8 125.1 5545 7.2 595.3 174.5 49.4 554.2 162.4 52.2 513.1 150.4 55.1 471.8 138.3 58.250 10 653.5 191.5 51.7 608.9 178.5 54.9 564.2 165.4 58 519.2 152.2 61.535 1.7 534.1 156.5 48.3 496 145.4 51 457.7 134.2 53.7 419.7 123 56.540 4.4 592.5 173.7 50.6 550.9 161.5 53.6 509.2 149.2 56.6 467.8 137.1 59.745 7.2 654.3 191.8 52.9 609.1 178.5 56.2 563.9 165.3 59.5 519 152.1 6350 10 719.3 210.8 55.2 670.4 196.5 58.7 621.6 182.2 62.4 572.9 167.9 66.435 1.7 586.8 172 52.8 544.9 159.7 55.8 502.9 147.4 58.8 461 135.1 61.840 4.4 650.3 190.6 55.4 604.7 177.2 58.7 559.1 163.9 62 513.5 150.5 65.445 7.2 717.8 210.4 58 668.4 195.9 61.6 618.9 181.4 65.3 569.4 166.9 69.150 10 789.6 231.4 60.6 736 215.7 64.5 682.5 200 68.5 628.9 184.3 72.835 1.7 628.7 184.3 58.1 583.4 171 61.4 538.2 157.7 64.5 492.9 144.5 67.840 4.4 695.1 203.7 61.2 646.1 189.4 64.7 597.1 175 68.3 547.8 160.6 7245 7.2 766.1 224.5 64.2 713.1 209 68.1 660 193.4 72.1 606.3 177.7 76.250 10 841.8 246.7 67.3 784.4 229.9 71.6 726.9 213.1 76 669 196.1 80.535 1.7 604.5 177.2 53.4 561 164.4 56.1 517.5 151.7 58.6 474.1 139 61.240 4.4 669.6 196.3 56.1 622.2 182.4 59.1 574.7 168.5 61.9 527.3 154.5 64.945 7.2 739.1 216.6 58.8 687.5 201.5 62.1 635.8 186.3 65.3 584.1 171.2 68.650 10 813.1 238.3 61.4 756.9 221.8 65 700.6 205.4 68.6 644.5 188.9 72.535 1.7 664.9 194.9 61.3 618.3 181.2 64.5 572 167.7 67.5 525.4 154 70.640 4.4 733.9 215.1 64.9 682.9 200.2 68.3 632.2 185.3 71.7 580.9 170.3 75.245 7.2 807.2 236.6 68.6 751.6 220.3 72.3 696 204 76 639.6 187.5 79.950 10 884.9 259.4 72.2 824.3 241.6 76.3 763.5 223.8 80.4 701.5 205.6 84.835 1.7 705.2 206.7 65.4 655.3 192.1 68.8 605.5 177.5 72.2 555.6 162.9 75.640 4.4 779.4 228.4 69 724.9 212.5 72.7 670.5 196.5 76.4 615.8 180.5 80.445 7.2 858 251.5 72.7 798.7 234.1 76.7 739.3 216.7 80.8 679.4 199.1 85.350 10 941 275.8 76.3 876.5 256.9 80.8 811.8 237.9 85.3 746.4 218.8 90.335 1.7 807.6 236.7 72 750.1 219.9 76.1 692.5 203 80.2 635.1 186.1 84.340 4.4 896.4 262.7 75.3 833.7 244.4 79.9 770.8 225.9 84.4 708.4 207.6 89.145 7.2 990.6 290.3 78.7 922.4 270.3 83.6 854.2 250.4 88.6 786.4 230.5 93.950 10 1089.7 319.4 82 1016 297.8 87.4 942.2 276.2 92.8 868.8 254.6 98.735 1.7 850.1 249.2 77.2 789.2 231.3 81.6 728.3 213.5 85.9 667.6 195.7 90.340 4.4 942 276.1 81 875.8 256.7 85.8 809.5 237.3 90.6 743.4 217.9 95.645 7.2 1039.6 304.7 84.8 967.8 283.7 90.1 896 262.6 95.4 824.2 241.6 10150 10 1142.9 335 88.6 1065.2 312.2 94.3 987.5 289.4 100.2 909.8 266.7 106.435 1.7 891.6 261.3 82.6 827.5 242.5 87.2 763.3 223.7 91.7 699.2 204.9 96.440 4.4 986.5 289.1 86.8 916.9 268.7 91.9 847.2 248.3 96.9 777.5 227.9 102.245 7.2 1087.4 318.7 91.1 1012.1 296.6 96.6 936.6 274.5 102.2 860.8 252.3 108.150 10 1194.6 350.1 95.4 1113.1 326.2 101.5 1031.4 302.3 107.7 949.5 278.3 114.235 1.7 976.9 286.3 89.2 907.8 266.1 94 838.7 245.8 98.7 769.5 225.5 103.640 4.4 1081.2 316.9 93.9 1005.7 294.8 99.2 930.2 272.6 104.4 854.6 250.5 109.945 7.2 1191.8 349.3 98.6 1109.6 325.2 104.4 1027.3 301.1 110.1 944.8 276.9 116.350 10 1308.5 383.5 103.4 1219.2 357.4 109.6 1129.8 331.2 116 1039.8 304.8 12335 1.7 1076.7 315.6 96 1000.2 293.1 101.5 923.3 270.6 106.9 846.7 248.2 112.540 4.4 1195.2 350.3 100.4 1111.6 325.8 106.5 1027.8 301.2 112.5 944.5 276.8 118.845 7.2 1320.8 387.1 104.9 1229.8 360.5 111.5 1138.9 333.8 118.1 1048.6 307.3 125.250 10 1453 425.9 109.3 1354.6 397 116.5 1256.3 368.2 123.8 1158.3 339.5 131.735 1.7 1161.3 340.4 106.5 1077.9 315.9 112.5 994.5 291.5 118.4 911.3 267.1 124.540 4.4 1285.8 376.9 111.9 1195.3 350.3 118.4 1104.7 323.8 125 1014.1 297.2 131.945 7.2 1418.2 415.7 117.3 1320.1 386.9 124.5 1221.9 358.2 131.7 1123.6 329.3 139.450 10 1558.6 456.8 122.7 1452.4 425.7 130.5 1346.2 394.6 138.5 1239.8 363.4 147.135 1.7 1243 364.3 117.3 1153.1 338 123.7 1063.2 311.6 130 973.4 285.3 136.640 4.4 1373.2 402.5 123.6 1276 374 130.6 1178.7 345.5 137.7 1080.6 316.7 145.145 7.2 1512.1 443.2 129.9 1407 412.4 137.7 1301.5 381.5 145.6 1194.7 350.2 153.850 10 1660 486.5 136.4 1546.2 453.2 144.9 1432 419.7 153.6 1317.1 386 162.7

52053-D

52058-D

52045-D

52049-D

Total CapacityModel

ACUV-DSST

Condenser Entering Air Temperature 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)

Total Capacity Total Capacity Total Capacity

52060-D

53064-D

53068-D

54120-D

53080-D

53084-D

53086-D

54095-D

54106-D

54114-D

53070-D

Note:

* Power Input mentioned in these pages should not be used for Cable/Fuse selection. MCA & MFA Values given in the electrical data (Pages 20 to 24) should be referred for the same.

Computer Print outs for matched ratings with SKM Air Handling Units are available.

CAPACITY RATINGS - 50 HZ

SKM Air Cooled Condensing UnitsACUV Series - R134a

14

Table 4

PI * PI * PI * PI *°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW35 1.7 83.4 24.5 6.6 77.5 22.7 7.1 71.4 20.9 7.4 65.3 19.1 7.840 4.4 92.9 27.2 6.9 86.4 25.3 7.3 79.7 23.4 7.8 73.1 21.4 8.245 7.2 103.1 30.2 7.1 95.9 28.1 7.6 88.7 26 8.1 81.5 23.9 8.750 10 114.1 33.4 7.3 106.2 31.1 7.9 98.2 28.8 8.5 90.3 26.5 9.135 1.7 110 32.2 9.1 102.5 30 9.7 94.8 27.8 10.2 87.1 25.5 10.840 4.4 121.9 35.7 9.5 113.8 33.3 10.1 105.4 30.9 10.7 97.1 28.5 11.445 7.2 134.7 39.5 9.9 125.7 36.9 10.6 116.7 34.2 11.3 107.7 31.6 1250 10 148 43.4 10.2 138.3 40.5 11 128.5 37.7 11.8 118.9 34.8 12.635 1.7 153.3 44.9 13.2 142.2 41.7 14 131.1 38.4 14.7 120 35.2 15.540 4.4 169.9 49.8 13.8 157.9 46.3 14.7 145.9 42.8 15.6 133.9 39.2 16.445 7.2 187.7 55 14.4 174.7 51.2 15.4 161.7 47.4 16.4 148.7 43.6 17.450 10 206.6 60.6 14.9 192.5 56.4 16.1 178.4 52.3 17.2 164.3 48.2 18.335 1.7 222.7 65.3 20 206.4 60.5 21 190 55.7 21.8 173.6 50.9 22.840 4.4 246.8 72.3 20.9 229 67.1 22 211.2 61.9 23 193.5 56.7 24.145 7.2 272.5 79.9 21.8 253.2 74.2 23 233.9 68.6 24.3 214.7 62.9 25.550 10 299.9 87.9 22.8 279 81.8 24.1 258 75.6 25.5 237.1 69.5 26.935 1.7 257.6 75.5 24.8 239.3 70.1 26 221.1 64.8 27.2 202.8 59.5 28.440 4.4 283.9 83.2 26.3 264 77.4 27.6 244.1 71.5 29 224 65.7 30.445 7.2 311.8 91.4 27.8 290.1 85 29.3 268.4 78.7 30.8 246.4 72.2 32.450 10 341.1 100 29.4 317.6 93.1 31 294 86.2 32.7 270.1 79.2 34.535 1.7 318.7 93.4 28.7 296 86.8 30.3 273.2 80.1 32 250.5 73.4 33.640 4.4 353.9 103.7 30 329 96.4 31.8 304 89.1 33.6 279.2 81.8 35.545 7.2 391.2 114.7 31.3 364.1 106.7 33.3 336.9 98.8 35.3 310 90.9 37.450 10 430.6 126.2 32.6 401.4 117.6 34.9 372.2 109.1 37.1 343.3 100.6 39.535 1.7 367.8 107.8 35.1 341.2 100 37 314.5 92.2 38.9 287.9 84.4 40.940 4.4 407.4 119.4 36.9 378 110.8 39.1 348.8 102.2 41.2 320 93.8 43.545 7.2 448.7 131.5 38.8 416.9 122.2 41.2 385.4 112.9 43.5 354.6 103.9 4650 10 491.7 144.1 40.8 458.2 134.3 43.4 424.6 124.5 46 390.8 114.5 48.735 1.7 163.4 47.9 13.5 151.5 44.4 14.3 139.4 40.9 15.1 127.4 37.3 15.840 4.4 181.5 53.2 14.1 168.6 49.4 15 155.5 45.6 15.8 142.5 41.8 16.745 7.2 201 58.9 14.6 186.9 54.8 15.6 172.6 50.6 16.6 158.5 46.5 17.750 10 222 65.1 15.2 206.4 60.5 16.3 190.7 55.9 17.4 175.3 51.4 18.635 1.7 185.8 54.5 16.3 172.5 50.5 17.2 159 46.6 18.1 145.7 42.7 1940 4.4 205.7 60.3 17.1 191.2 56 18.1 176.6 51.8 19.1 162.3 47.6 20.245 7.2 226.8 66.5 17.8 211 61.9 19 195.3 57.2 20.2 179.9 52.7 21.450 10 249.1 73 18.6 231.9 68 19.9 214.8 62.9 21.2 198.1 58.1 22.735 1.7 215.8 63.2 18.6 200.8 58.9 19.7 185.5 54.4 20.7 170.4 49.9 21.840 4.4 238.9 70 19.4 222.6 65.2 20.6 206 60.4 21.8 189.8 55.6 23.145 7.2 263.4 77.2 20.2 245.6 72 21.6 227.7 66.8 23 210.3 61.6 24.450 10 289 84.7 21.1 269.7 79.1 22.6 250.5 73.4 24.1 231.7 67.9 25.735 1.7 253.4 74.3 23.1 235.1 68.9 24.4 216.7 63.5 25.6 198.5 58.2 26.940 4.4 280.1 82.1 24.2 260.3 76.3 25.7 240.4 70.5 27.1 220.8 64.7 28.645 7.2 308.4 90.4 25.3 287 84.1 27 265.5 77.8 28.6 244.4 71.6 30.450 10 338.2 99.1 26.5 315 92.3 28.3 291.9 85.6 30.2 269.1 78.9 32.235 1.7 302 88.5 26.8 280.1 82.1 28.3 258.1 75.6 29.8 236.1 69.2 31.340 4.4 334.5 98 28 310.7 91.1 29.8 286.9 84.1 31.5 263.1 77.1 33.245 7.2 369 108.2 29.3 343.3 100.6 31.3 317.6 93.1 33.2 291.8 85.5 35.350 10 405.8 118.9 30.5 377.9 110.8 32.7 350 102.6 34.9 322.1 94.4 37.335 1.7 325.7 95.5 29.6 302 88.5 31.1 278.2 81.5 32.5 254.6 74.6 33.940 4.4 360.4 105.6 31 334.7 98.1 32.6 308.9 90.5 34.3 283.4 83.1 3645 7.2 397.3 116.4 32.4 369.4 108.3 34.3 341.4 100.1 36.2 313.9 92 38.150 10 436.2 127.9 33.9 406 119 36 375.8 110.1 38.1 345.9 101.4 40.335 1.7 371.9 109 33.5 344.7 101 35.2 317.4 93 36.8 290.1 85 38.540 4.4 411.9 120.7 35.1 382.3 112.1 37 352.7 103.4 38.9 323.2 94.7 40.945 7.2 454.5 133.2 36.6 422.5 123.8 38.8 390.4 114.4 41 358.4 105 43.350 10 499.8 146.5 38.2 465.1 136.3 40.7 430.3 126.1 43.1 395.5 115.9 45.835 1.7 434.5 127.4 40.7 402.3 117.9 42.5 370.1 108.5 44.2 338 99.1 46.140 4.4 480.7 140.9 42.6 445.7 130.6 44.7 410.7 120.4 46.8 375.9 110.2 4945 7.2 529.7 155.3 44.6 491.8 144.1 47 453.9 133 49.4 416.2 122 51.950 10 581.7 170.5 46.7 540.6 158.5 49.4 499.5 146.4 52.1 458.5 134.4 55

62022-D

62032-D

62034-D

62040-D

62046-D

62026-D

Condenser Entering Air Temperature

Total Capacity

61009-D

61011-D

61016-D

ModelACUV-D

95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)Total Capacity Total Capacity Total Capacity

61032-D

61036-D

62018-D

62020-D

SST

61024-D

61026-D

Note:

* Power Input mentioned in these pages should not be used for Cable/Fuse selection. MCA & MFA Values given in the electrical data (Pages 20 to 24) should be referred for the same.

Computer Print outs for matched ratings with SKM Air Handling Units are available.

CAPACITY RATINGS - 60 HZ

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

15

Table 4 ends

PI * PI * PI * PI *°F °C MBh kW kW MBh kW kW MBh kW kW MBh kW kW35 1.7 516 151.2 49.6 479.5 140.5 52 443.1 129.9 54.3 406.4 119.1 56.840 4.4 568.8 166.7 52.5 529 155 55.2 489.1 143.4 57.8 448.9 131.6 60.745 7.2 624.7 183.1 55.5 581.3 170.4 58.5 537.9 157.7 61.5 494 144.8 64.750 10 683.6 200.4 58.7 636.6 186.6 61.9 589.4 172.7 65.3 541.4 158.7 6935 1.7 569.4 166.9 54 528.7 155 56.8 488 143 59.6 447.4 131.1 62.540 4.4 629.5 184.5 56.9 585 171.5 60 540.5 158.4 63.1 496.1 145.4 66.445 7.2 693.1 203.1 59.8 644.7 189 63.3 596.3 174.8 66.8 548 160.6 70.550 10 760.1 222.8 62.9 707.9 207.5 66.7 655.7 192.2 70.6 603.3 176.8 74.935 1.7 621.6 182.2 58.6 576.8 169.1 61.8 531.9 155.9 65 487.4 142.9 68.340 4.4 688.8 201.9 61.4 639.7 187.5 64.9 590.7 173.1 68.5 542 158.9 72.345 7.2 759.8 222.7 64.3 706.5 207.1 68.2 653.3 191.5 72.2 600.7 176.1 76.550 10 834.7 244.6 67.3 777.3 227.8 71.7 720.2 211.1 76.1 663.8 194.6 80.935 1.7 685.1 200.8 63.9 635.8 186.4 67.5 586.5 171.9 71 537.3 157.5 74.740 4.4 759.6 222.6 67 705.4 206.8 71 651.2 190.9 74.9 597.7 175.2 79.145 7.2 837.9 245.6 70.3 779.1 228.3 74.6 720.4 211.2 79 662.7 194.2 83.650 10 919.8 269.6 73.6 857.2 251.2 78.4 794.6 232.9 83.3 732.1 214.6 88.435 1.7 733.1 214.9 70.4 679.9 199.3 74.2 626.7 183.7 78.1 573.6 168.1 82.140 4.4 811.7 237.9 74.1 753.1 220.7 78.3 694.7 203.6 82.6 637.5 186.8 87.145 7.2 893.8 262 77.9 830.4 243.4 82.6 767.4 224.9 87.3 706.1 207 92.350 10 979.3 287 81.9 912.5 267.4 87 845.4 247.8 92.3 777.9 228 97.835 1.7 705.6 206.8 64.6 654.6 191.9 67.7 603.5 176.9 70.7 552.5 161.9 73.740 4.4 780.7 228.8 67.8 725.1 212.5 71.3 669.5 196.2 74.8 613.9 179.9 78.445 7.2 860.7 252.3 71.1 800.2 234.5 75.1 739.7 216.8 79 679.3 199.1 83.150 10 945.4 277.1 74.6 879.8 257.9 78.9 814.2 238.6 83.3 748.4 219.3 8835 1.7 775.3 227.2 74.3 720.5 211.2 77.9 665.8 195.1 81.4 610.8 179 85.140 4.4 854.9 250.6 78.6 795 233 82.6 735.1 215.5 86.7 674.8 197.8 90.945 7.2 938.9 275.2 83.1 873.8 256.1 87.6 808.5 237 92.1 742.6 217.7 9750 10 1027.5 301.2 87.9 957 280.5 92.7 886.1 259.7 97.8 814.1 238.6 103.335 1.7 821.6 240.8 79.2 763 223.6 83.2 704.3 206.4 87.1 645.6 189.2 91.340 4.4 907.1 265.9 83.6 842.9 247.1 88 778.8 228.3 92.5 714.5 209.4 97.245 7.2 997.3 292.3 88.2 927.6 271.9 93.1 857.8 251.4 98.1 787.8 230.9 103.550 10 1092.3 320.2 92.9 1017 298.1 98.3 941.6 276 103.9 865.6 253.7 11035 1.7 943.1 276.4 87 875.5 256.6 91.9 807.7 236.7 96.7 740.3 217 101.740 4.4 1046 306.6 91.2 971.9 284.9 96.5 897.7 263.1 101.9 824.1 241.5 107.645 7.2 1154.8 338.5 95.3 1074.3 314.9 101.2 993.8 291.3 107.2 914 267.9 113.650 10 1269.8 372.2 99.5 1183.1 346.8 106.2 1096.6 321.4 112.9 1011 296.3 12035 1.7 991.7 290.7 93.5 920.2 269.7 98.6 848.6 248.7 103.7 777.3 227.8 109.140 4.4 1098.9 322.1 98.1 1020.4 299.1 103.8 941.9 276.1 109.5 864.4 253.4 115.645 7.2 1211.8 355.2 102.9 1126.5 330.2 109.1 1041.6 305.3 115.5 958 280.8 122.350 10 1330.2 389.9 107.7 1239.2 363.2 114.7 1148.3 336.6 121.8 1057.9 310.1 129.335 1.7 1039.2 304.6 100 963.8 282.5 105.4 888.4 260.4 110.8 813.3 238.4 116.540 4.4 1150.5 337.2 105.2 1067.6 312.9 111.2 984.9 288.7 117.3 903.7 264.9 123.745 7.2 1267 371.4 110.5 1177.2 345 117.2 1088.1 318.9 123.9 1000.8 293.3 131.150 10 1388.9 407.1 116.1 1293.7 379.2 123.4 1198.5 351.3 130.9 1103.1 323.3 138.835 1.7 1136.9 333.2 108.2 1055.6 309.4 113.8 974.4 285.6 119.3 893.2 261.8 125.140 4.4 1256.8 368.4 113.9 1167.9 342.3 120.2 1079 316.3 126.4 990.2 290.2 13345 7.2 1383.5 405.5 119.9 1286.9 377.2 126.7 1190.2 348.9 133.7 1093.7 320.6 141.350 10 1517.1 444.7 126 1412.8 414.1 133.6 1308.5 383.5 141.5 1204 352.9 149.935 1.7 1257.5 368.6 116 1167.3 342.1 122.6 1076.9 315.6 129 987 289.3 135.740 4.4 1394.6 408.8 121.6 1295.8 379.8 128.7 1196.9 350.8 135.8 1098.8 322 143.445 7.2 1539.8 451.3 127.1 1432.4 419.8 135 1325 388.4 143 1218.7 357.2 151.550 10 1693.1 496.2 132.7 1577.4 462.3 141.6 1462.1 428.5 150.5 1348 395.1 16035 1.7 1354.1 396.9 129 1256.2 368.2 136 1158.2 339.5 143 1060.5 310.8 150.440 4.4 1499.8 439.6 135.5 1392.2 408.1 143.3 1284.8 376.6 151.2 1178.9 345.5 159.545 7.2 1652.8 484.4 142.3 1536.1 450.2 150.8 1420 416.2 159.6 1306 382.8 168.950 10 1813 531.4 149.2 1688.8 495 158.7 1564.8 458.6 168.5 1440.9 422.3 178.735 1.7 1447.3 424.2 142.1 1341.8 393.3 149.7 1236.3 362.4 157.4 1130.9 331.5 165.440 4.4 1600.9 469.2 149.8 1484.6 435.1 158.2 1369 401.3 166.8 1256 368.1 175.845 7.2 1760.9 516.1 157.8 1635.2 479.3 167.1 1510.9 442.9 176.6 1390.2 407.5 186.650 10 1928 565.1 166.1 1795.6 526.3 176.3 1662.6 487.3 186.8 1528.5 448 197.8

62062-D

62067-D

62052-D

62058-D

Total CapacityModel

ACUV-DSST

Condenser Entering Air Temperature 95°F (35°C) 105°F (40.6°C) 115°F (46.1°C) 125°F (51.7°C)

Total Capacity Total Capacity Total Capacity

62071-D

63074-D

63078-D

64140-D

63094-D

63098-D

63100-D

64113-D

64124-D

64132-D

63082-D

Note:

* Power Input mentioned in these pages should not be used for Cable/Fuse selection. MCA & MFA Values given in the electrical data (Pages 20 to 24) should be referred for the same.

Computer Print outs for matched ratings with SKM Air Handling Units are available.

CAPACITY RATINGS - 60 HZ

SKM Air Cooled Condensing UnitsACUV Series - R134a

16

Compressor Starting

The ACUV Units standard mode of compressor starting is given as per Table No. 5.

Maximum Instantaneous Current Flow (ICF) as shown in Electrical Specifications, Pages 20 to 24, must be used in determining the need for part winding start for models with DOL as standard.

If part winding start is required, please specify option PWS at enquiry/order, available only for the models shown with PWS as option in Table 5.

STANDARD OPTION STANDARD OPTION STANDARD OPTIONACUV-51008-D ACUV-61009-DACUV-51010-D ACUV-61011-DACUV-51014-D ACUV-61016-D PWS PWSACUV-52015-D ACUV-62018-DACUV-52017-D ACUV-62020-DACUV-52019-D ACUV-62022-DACUV-51021-D ACUV-61024-D ACUV-51022-D ACUV-61026-D

-

ACUV-52022-D ACUV-62026-D DOL PWSACUV-51028-D ACUV-61032-D PWS - PWS - PWS -ACUV-52028-D ACUV-62032-DACUV-52030-D ACUV-62034-DACUV-51030-D ACUV-61036-D PWS - PWS - PWS -ACUV-52034-D ACUV-62040-D DOL PWSACUV-52040-D ACUV-62046-DACUV-52045-D ACUV-62052-DACUV-52049-D ACUV-62058-DACUV-52053-D ACUV-62062-DACUV-52058-D ACUV-62067-DACUV-52060-D ACUV-62071-DACUV-53064-D ACUV-63074-DACUV-53068-D ACUV-63078-DACUV-53070-D ACUV-63082-DACUV-53080-D ACUV-63094-DACUV-53084-D ACUV-63098-DACUV-53086-D ACUV-63100-DACUV-54095-D ACUV-64113-D DOL PWS DOL PWSACUV-54106-D ACUV-64124-DACUV-54114-D ACUV-64132-DACUV-54120-D ACUV-64140-D

-

PWS - PWS -

PWSPWS -

DOL PWS

PWSDOL

PWS -

DOL PWS

DOL PWS

PWS

-PWS

DOL PWS-

DOL PWS DOL PWS

DOL PWS DOL

PWS

-

-

380-415/3/50,440/3/50,460/3/60 380/3/60 220/3/60MODEL

-

-

DOL

PWS

Table 5

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

17

Standard Numberof Steps Optional Number

of Steps

51008-D 61009-D 100 - 0 1 100 - 67 - 0 251010-D 61011-D 100 - 0 1 100 - 67 - 0 251014-D 61016-D 100 - 0 1 100 - 50 - 0 252015-D 62018-D 100 - 50 - 0 2 100 - 84 - 50 - 34 - 0 452017-D 62020-D 100 - 57 - 0 2 100 - 86 - 57 - 38 - 0 452019-D 62022-D 100 - 50 - 0 2 100 - 84 - 50 - 34 - 0 451021-D 61024-D 100 - 0 1 100 - 67 - 0 251022-D 61026-D 100 - 0 1 100 - 67 - 0 252022-D 62026-D 100 - 62 - 0 2 100 - 86 - 58 - 29 - 0 451028-D 61032-D 100 - 0 1 100 - 75 - 0 252028-D 62032-D 100 - 50 - 0 2 100 - 75 - 50 - 25 - 0 452030-D 62034-D 100 - 68 - 0 2 100 - 89 - 67 - 45 - 0 451030-D 61036-D 100 - 0 1 100 - 75 - 0 252034-D 62040-D 100 - 58 - 0 2 100 - 80 - 60 - 40 - 0 452040-D 62046-D 100 - 50 - 0 2 100 - 84 - 50 - 34 - 0 452045-D 62052-D 100 - 50 - 0 2 100 - 84 - 50 - 34 - 0 452049-D 62058-D 100 - 55 - 0 2 100 - 85 - 55 - 41 - 0 452053-D 62062-D 100 - 50 - 0 2 100 - 88 - 50 - 38 - 0 452058-D 62067-D 100 - 54 - 0 2 100 - 89 - 54 - 41 - 0 452060-D 62071-D 100 - 50 - 0 2 100 - 88 - 50 - 38 - 0 453064-D 63074-D 100 - 69 - 37 - 0 3 100 - 89 - 68 - 58 - 37 - 25 - 0 653068-D 63078-D 100 - 67 - 33 - 0 3 100 - 89 - 67 - 55 - 33 - 22 - 0 653070-D 63082-D 100 - 69 - 38 - 0 3 100 - 90 - 69 - 59 - 38 - 29 - 0 653080-D 63094-D 100 - 66 - 33 - 0 3 100 - 91 - 66 - 58 - 33 - 25 - 0 653084-D 63098-D 100 - 68 - 37 - 0 3 100 - 91 - 68 - 60 - 37 - 28 - 0 653086-D 63100-D 100 - 70 - 35 - 0 3 100 - 93 - 70 - 61 - 35 - 26 - 0 654095-D 64113-D 100 - 78 - 56 - 28 - 0 4 100 - 92 - 78 - 69 - 54 - 49 - 28 - 21 - 0 854106-D 64124-D 100 - 75 - 50 - 25 - 0 4 100 - 94 - 75 - 69 - 50 - 44 - 25 - 19 - 0 854114-D 64132-D 100 - 77 - 54 - 27 - 0 4 100 - 94 - 77 - 71 - 54 - 47 - 27 - 20 - 0 854120-D 64140-D 100 - 75 - 50 - 25 - 0 4 100 - 94 - 75 - 69 - 50 - 44 - 25 - 19 - 0 8

ACUV

Capacity Control Steps

The Standard Capacity Control Steps are shown below.

Table 6

Selection Procedure Example

The following information should be determined:

1. Required total capacity = 430 MBh (126 kW)2. Saturated suction temperature = 50°F (10°C) 3. Condenser entering air temperature = 115°F (46°C)4. Power Supply (V/Ph/Hz) = 380/3/50

Enter capacity ratings from Table 3 at 115°F (46°C) condenser entering air temperature and select model ACUV 52040-D having a cooling capacity of 431.3 MBh (126.4 kW) at 50°F (10°C) saturated suction temperature, compressor motor power input is 42.3 kW. For further details refer to physical data and specifications sheets.

Capacity ratings are based on sea level operation. Above sea level, apply the following corrections method.

Actual capacity (at level) = Sea level capacity x altitude correction factor (from Table 7).

Altitude Correction FactorsThe unit ratings are based on sea level. Above sea level apply the following correction factors:

feet meter0 0 1 1

2000 610 0.99 1.014000 1219 0.98 1.026000 1829 0.97 1.038000 2438 0.96 1.04

10000 3048 0.95 1.05

Altitude Capacity Multiplier

PowerMultiplier

Table 7

SKM Air Cooled Condensing UnitsACUV Series - R134a

18

Field ConnectionsACUV series self-contained heavy duty air cooled condensing units are designed for minimum field interaction.

Power hook-ups for AHU starter and fan interlock and control wiring of room unit as per Electrical hook-up diagram is all that is required to electrically connect any model of ACUV series.

Every ACUV series condensing unit requires, at most, field installed fused disconnect switches or circuit breakers, and room unit.

Refer below for a schematic representation of required field electrical hook-ups for a standard ACUV series condensing unit.

All field wiring must be done in accordance with applicable local and national codes.

For maximum recommended fuse sizes and minimum circuit amps for cable sizing, see Page 20~24 of this bulletin.

The ACUV series is then ready to provide cooling, on demand.

Field Wiring Requirement Schematic

CIRCUIT BREAKEROR FUSED

3 WIRE SYSTEM440V/3PH/50Hz

4 WIRE SYSTEM380-415V/3PH/50Hz380V/3PH/60HzL1

L2L3N

E

GROUND

L1 L2 L3 N

ACUV-D SERIES

3 PHASE,

DISCONNECT SWITCH

3 PHASE,

CONTROL PANEL

(NOT BY SKM)

220V/3PH/60Hz

L2L1

L N**

FAN INTERLOCK FROM AHUDOL/STAR DELTA

AIR HANDLING UNIT

WVU

E

~3M

(CONTACTOR, OVERLOADRELAY & ON/OFF CONTROL etc.)

CUSTOMER SUPPLIEDAND INSTALLEDFIELD ACCESSORY

380V/3PH/60Hz380-415V/3PH/50Hz

AHU STARTER BOX

4 WIRE SYSTEM

DISCONNECT SWITCH

CIRCUIT BREAKER

(NOT BY SKM)

3 PHASE,

L2L1 L3 N

OR FUSED

FIELD WIRING

FIELD WIRINGLOW VOLTAGE

LINE VOLTAGE

REFER ACTUAL WIRING DIAGRAMFURNISHED WITH THE UNIT FOREXACT IDENTIFICATION OF WIRE NUMBERS.

EFM STARTER INTERLOCK TO AHU

460V/3PH/60Hz

ACUV-D SERIES UNITS RATED FOR 440V/3PH/50Hz, 460V/3PH/60Hz, OR POWER SUPPLIES WITH OUT NEUTRALREQUIRE SEPARATE SOURCE OF CONTROL POWER SUPPLY THRU FIELD SUPPLIED & INSTALLED 15A/220V FUSEDCONTROL DISCONNECT SWITCH OR ORDER WITH FACTORY BUILT IN OPTION ' CXT '.

**

-CE+

+CE-

ROOM UNIT(LOOSESUPPLY)

2 CORE UNSCREENED TWISTED PAIR CABLE (BY OTHERS)

(BY OTHERS)

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

19

Typical Wiring Diagram

T9Q12

MIC

ROPR

OCE

SSO

RCO

NTR

OLL

ER

24~G0

E24V

220~240V

TFR

T8_

CR3

C6C5

C4C3

C2C1

CFM2Q64Q54Q53

Q33

T10

Q11Q14

Q21Q24

Q22

Q44Q43Q34

T11

COMP.-1

COMP.-2

CFM1

T-IP

D01

Q84

Q73Q74

T12C

DNDL1

D02T13

DL2

CFM3

CFM4

EFM

HPS-2

HPS-1

ESC

INFO

T-HI

CCH1

CCH2

OK

C1C2

RS48

5

B3

MCB

2

B1T1

B2M

M

L2 L3L1 N

NL1

MCB

1CM

1

C1

5V=

DISC.PRESSURE-2

DISC.PRESSURE-1

X3

M

T2X1

5V=24V=

X2

T3

MX4

MX5

X6

IG

IG

LPS-1

LPS-2

M

M

24V=X7

T4X8

D1

24~ DG

T5DU1

D2

T6DU2

_

A+

CS

RUN/STOP

MPC

B3 C5

POW

ERSU

PPLY

MPC

B1

CM2

C2

CFM1

C3

CFM

2

C4

MPC

B2

I>I>

I>I>

I>I>

CFM

4CF

M3

C6

I>I>

I>I>

MPC

B4

I>I>

2COREUNSCREENEDTWISTEDPAIRCABLE

(BYOTHERS)CE+

REFT7

B-

CE-

PB

+-

ROOM

UNIT

(LOO

SESU

PPLY

)

CR4

CR5

**

OPS-1

OPS-2

OFH-1 P

R

MM

MP2

CR4

CR5

1L

N1411

2

12

MP1

2L

1 12N

1411

CR6

CR7

OPS2

L

OPS1

M

L

M

MP-1

MP-2

CR7

CR6

OFH-2

P

R

CR3

INTE

RLOC

KEF

MST

ARTE

R

MAT

CHIN

GAH

UFO

RVO

LTFR

EECO

NTAC

TTO

(BYOTHERS)FANINTERLOCKFROMAHU

CR8

LSV-

1

CR1

LSV-

2

CR2

LSV-1 CR1

LSV-2

CR2

CR8 FANINTERLOCK

Typi

calw

iring

diag

ram

give

nhe

reis

foru

nits

with

380~

415/

3/50

or

MOT

ORPR

OTEC

TOR

CIRC

UTBR

EAKE

R

NOTE

:-

380/

3/60

,4w

irepo

wer

supp

lies.

CXT

optio

nis

am

ust.

pow

ersu

pplie

sar

eav

ailab

leon

requ

est.

CONT

ACTO

R

COM

PRES

SOR

MOT

ORLO

WPR

ESSU

RESW

ITCH

HIGH

PRES

SURE

SWIT

CH

COND

ENSE

RFA

NM

OTOR

CRAN

KCA

SEHE

ATER

MIN

IATU

RECI

RCUI

TBR

EAKE

R

CONT

ROL

SWIT

CH

For4

40/3

/50

or46

0/3/

60or

pow

ersu

pplie

sw

ithou

tneu

tral,

Wiri

ngdi

agra

ms

for4

40/3

/50,

220/

3/60

or46

0/3/

60

DISC

ONNE

CTM

EANS

ASRE

QUIR

EDBY

LOCA

L&

NATI

ONAL

ELEC

TRIC

CODE

.PR

OVID

EOV

ERCU

RREN

T,EA

RTH

FAUL

TPR

OTEC

TION

,SHO

RTCI

RCUI

TAN

D

CFM

** LPS

HPS

CMCS CCH

MCB

CTFR***

LE

GE

ND

EFM CR

TRAN

SFOR

MER

MP

OL LSV

MPC

B

EVAP

ORAT

ORFA

NM

OTOR

CONT

ROL

RELA

Y

FIEL

DW

IRIN

G

MOT

ORPR

OTEC

TOR

OVER

LOAD

RELA

YLI

QUID

LINE

SOLE

NOID

VALV

E

PPR

ESSU

REAC

TIVA

TED

SWIT

CHOF

HOI

LFA

ILUR

EHE

ATER

OPS

OIL

PRES

SURE

SWIT

CH

SKM Air Cooled Condensing UnitsACUV Series - R134a

20

ELECTRICAL DATA

Table 8

POWER SUPPLY : 380-415V /3Ph / 50Hz

Voltage imbalance between phases to be < 2%

LEGEND:

MFA Maximum Fuse Ampere (For Fuse sizing) as per NEC Article 440-22 & 430-52

MCA Minimum Circuit Ampere (For Wire sizing), as per NEC Article 440-33

RLA Rated Load Ampere at Worst Condition.

ICF Instantaneous Current Flow

DOL Direct On Line Start

PWS Part Winding Start

LRA Locked Rotor Ampere (DOL)

FLA Full Load Ampere

DOL PWS QTY RLA LRA QTY FLA LRA51008 50 25 129 99 1 18 121 2 1.1 3.951010 63 32 137 105 1 24 129 2 1.1 3.951014 100 49 210 161 1 35 199 2 2.4 8.952015 63 45 157 127 1 + 1 18 + 18 121 + 121 2 2.4 8.952017 80 53 158 126 1 + 1 24 + 18 129 + 121 2 2.4 8.952019 100 62 174 142 1 + 1 24 + 24 129 + 129 2 3.9 17.251021 125 72 338 262 1 51 304 2 3.9 17.251022 160 85 338 262 1 62 304 2 3.9 17.252022 125 76 244 194 1 + 1 35 + 24 199 + 129 2 3.9 17.251028 200 109 - 441 1 78 458 3 3.9 17.252028 125 90 259 209 1 + 1 35 + 35 199 + 199 3 3.9 17.252030 160 99 353 277 1 + 1 51 + 24 304 + 129 3 3.9 17.251030 250 122 - 456 1 88 476 3 3.9 17.252034 200 110 364 288 1 + 1 51 + 35 304 + 199 3 3.9 17.252040 200 126 380 304 1 + 1 51 + 51 304 + 304 3 3.9 17.252045 250 155 395 319 1 + 1 62 + 62 304 + 304 4 3.9 17.252049 315 175 549 434 1 + 1 78 + 62 458 + 304 4 3.9 17.252053 315 191 - 496 1 + 1 78 + 78 458 + 458 4 3.9 17.252058 315 204 - 512 1 + 1 88 + 78 476 + 458 4 3.9 17.252060 315 214 - 522 1 + 1 88 + 88 476 + 476 4 3.9 17.253064 315 203 456 380 1 + 2 62 + 51 304 + 304 6 3.9 17.253068 315 225 478 402 3 62 304 6 3.9 17.253070 400 245 632 518 1 + 2 78 + 62 458 + 304 6 3.9 17.253080 400 277 - 595 3 78 458 6 3.9 17.253084 400 289 - 611 1 + 2 88 + 78 476 + 458 6 3.9 17.253086 400 299 - 621 2 + 1 88 + 78 476 + 458 6 3.9 17.254095 500 331 718 649 2 + 2 78 + 62 458 + 304 8 3.9 17.254106 500 363 - 681 4 78 458 8 3.9 17.254114 500 385 - 706 2 + 2 88 + 78 476 + 458 8 3.9 17.254120 500 405 - 726 4 88 476 8 3.9 17.2

DOL PWS QTY RLA LRA QTY FLA LRA51008 50 26 129 99 1 19 121 2 1.1 3.951010 63 33 137 105 1 25 129 2 1.1 3.951014 100 52 211 161 1 37 199 2 2.8 9.252015 80 48 158 128 1 + 1 19 + 19 121 + 121 2 2.8 9.252017 100 56 160 128 1 + 1 25 + 19 129 + 121 2 2.8 9.252019 100 65 176 144 1 + 1 25 + 25 129 + 129 2 4.3 17.651021 160 75 339 263 1 53 304 2 4.3 17.651022 160 89 339 263 1 64 304 2 4.3 17.652022 125 80 246 196 1 + 1 37 + 25 199 + 129 2 4.3 17.651028 200 115 - 442 1 82 458 3 4.3 17.652028 160 96 262 212 1 + 1 37 + 37 199 + 199 3 4.3 17.652030 160 104 355 279 1 + 1 53 + 25 304 + 129 3 4.3 17.651030 250 128 - 457 1 92 476 3 4.3 17.652034 200 116 367 291 1 + 1 53 + 37 304 + 199 3 4.3 17.652040 200 132 383 307 1 + 1 53 + 53 304 + 304 3 4.3 17.652045 250 161 399 323 1 + 1 64 + 64 304 + 304 4 4.3 17.652049 315 184 553 438 1 + 1 82 + 64 458 + 304 4 4.3 17.652053 315 202 - 502 1 + 1 82 + 82 458 + 458 4 4.3 17.652058 315 214 - 517 1 + 1 92 + 82 476 + 458 4 4.3 17.652060 400 224 - 527 1 + 1 92 + 92 476 + 476 4 4.3 17.653064 315 212 462 386 1 + 2 64 + 53 304 + 304 6 4.3 17.653068 315 234 484 408 3 64 304 6 4.3 17.653070 400 256 638 524 1 + 2 82 + 64 458 + 304 6 4.3 17.653080 400 292 - 606 3 82 458 6 4.3 17.653084 400 305 - 621 1 + 2 92 + 82 476 + 458 6 4.3 17.653086 500 315 - 631 2 + 1 92 + 82 476 + 458 6 4.3 17.654095 500 347 729 660 2 + 2 82 + 64 458 + 304 8 4.3 17.654106 500 383 - 696 4 82 458 8 4.3 17.654114 500 405 - 722 2 + 2 92 + 82 476 + 458 8 4.3 17.654120 630 425 - 742 4 92 476 8 4.3 17.6

MFA MCAICF Model

ACUV-D

380~415/3/50

Unit CharacteristicrotoM naF resnednoCrosserpmoC

MFA MCAICFModel

440-3-50

Unit CharacteristicrotoM naF resnednoCrosserpmoC

ACUV-D

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

21

POWER SUPPLY : 380-415V /3Ph / 50Hz

DOL PWS QTY RLA LRA QTY FLA LRA51008 50 25 129 99 1 18 121 2 1.1 3.951010 63 32 137 105 1 24 129 2 1.1 3.951014 100 49 210 161 1 35 199 2 2.4 8.952015 63 45 157 127 1 + 1 18 + 18 121 + 121 2 2.4 8.952017 80 53 158 126 1 + 1 24 + 18 129 + 121 2 2.4 8.952019 100 62 174 142 1 + 1 24 + 24 129 + 129 2 3.9 17.251021 125 72 338 262 1 51 304 2 3.9 17.251022 160 85 338 262 1 62 304 2 3.9 17.252022 125 76 244 194 1 + 1 35 + 24 199 + 129 2 3.9 17.251028 200 109 - 441 1 78 458 3 3.9 17.252028 125 90 259 209 1 + 1 35 + 35 199 + 199 3 3.9 17.252030 160 99 353 277 1 + 1 51 + 24 304 + 129 3 3.9 17.251030 250 122 - 456 1 88 476 3 3.9 17.252034 200 110 364 288 1 + 1 51 + 35 304 + 199 3 3.9 17.252040 200 126 380 304 1 + 1 51 + 51 304 + 304 3 3.9 17.252045 250 155 395 319 1 + 1 62 + 62 304 + 304 4 3.9 17.252049 315 175 549 434 1 + 1 78 + 62 458 + 304 4 3.9 17.252053 315 191 - 496 1 + 1 78 + 78 458 + 458 4 3.9 17.252058 315 204 - 512 1 + 1 88 + 78 476 + 458 4 3.9 17.252060 315 214 - 522 1 + 1 88 + 88 476 + 476 4 3.9 17.253064 315 203 456 380 1 + 2 62 + 51 304 + 304 6 3.9 17.253068 315 225 478 402 3 62 304 6 3.9 17.253070 400 245 632 518 1 + 2 78 + 62 458 + 304 6 3.9 17.253080 400 277 - 595 3 78 458 6 3.9 17.253084 400 289 - 611 1 + 2 88 + 78 476 + 458 6 3.9 17.253086 400 299 - 621 2 + 1 88 + 78 476 + 458 6 3.9 17.254095 500 331 718 649 2 + 2 78 + 62 458 + 304 8 3.9 17.254106 500 363 - 681 4 78 458 8 3.9 17.254114 500 385 - 706 2 + 2 88 + 78 476 + 458 8 3.9 17.254120 500 405 - 726 4 88 476 8 3.9 17.2

DOL PWS QTY RLA LRA QTY FLA LRA51008 50 26 129 99 1 19 121 2 1.1 3.951010 63 33 137 105 1 25 129 2 1.1 3.951014 100 52 211 161 1 37 199 2 2.8 9.252015 80 48 158 128 1 + 1 19 + 19 121 + 121 2 2.8 9.252017 100 56 160 128 1 + 1 25 + 19 129 + 121 2 2.8 9.252019 100 65 176 144 1 + 1 25 + 25 129 + 129 2 4.3 17.651021 160 75 339 263 1 53 304 2 4.3 17.651022 160 89 339 263 1 64 304 2 4.3 17.652022 125 80 246 196 1 + 1 37 + 25 199 + 129 2 4.3 17.651028 200 115 - 442 1 82 458 3 4.3 17.652028 160 96 262 212 1 + 1 37 + 37 199 + 199 3 4.3 17.652030 160 104 355 279 1 + 1 53 + 25 304 + 129 3 4.3 17.651030 250 128 - 457 1 92 476 3 4.3 17.652034 200 116 367 291 1 + 1 53 + 37 304 + 199 3 4.3 17.652040 200 132 383 307 1 + 1 53 + 53 304 + 304 3 4.3 17.652045 250 161 399 323 1 + 1 64 + 64 304 + 304 4 4.3 17.652049 315 184 553 438 1 + 1 82 + 64 458 + 304 4 4.3 17.652053 315 202 - 502 1 + 1 82 + 82 458 + 458 4 4.3 17.652058 315 214 - 517 1 + 1 92 + 82 476 + 458 4 4.3 17.652060 400 224 - 527 1 + 1 92 + 92 476 + 476 4 4.3 17.653064 315 212 462 386 1 + 2 64 + 53 304 + 304 6 4.3 17.653068 315 234 484 408 3 64 304 6 4.3 17.653070 400 256 638 524 1 + 2 82 + 64 458 + 304 6 4.3 17.653080 400 292 - 606 3 82 458 6 4.3 17.653084 400 305 - 621 1 + 2 92 + 82 476 + 458 6 4.3 17.653086 500 315 - 631 2 + 1 92 + 82 476 + 458 6 4.3 17.654095 500 347 729 660 2 + 2 82 + 64 458 + 304 8 4.3 17.654106 500 383 - 696 4 82 458 8 4.3 17.654114 500 405 - 722 2 + 2 92 + 82 476 + 458 8 4.3 17.654120 630 425 - 742 4 92 476 8 4.3 17.6

MFA MCAICF Model

ACUV-D

380~415/3/50

Unit CharacteristicrotoM naF resnednoCrosserpmoC

MFA MCAICFModel

440-3-50

Unit CharacteristicrotoM naF resnednoCrosserpmoC

ACUV-D

ELECTRICAL DATA

Table 9

POWER SUPPLY : 440V /3Ph/50Hz

Voltage imbalance between phases to be < 2%

LEGEND:

MFA Maximum Fuse Ampere (For Fuse sizing) as per NEC Article 440-22 & 430-52

MCA Minimum Circuit Ampere (For Wire sizing), as per NEC Article 440-33

RLA Rated Load Ampere at Worst Condition.

ICF Instantaneous Current Flow

DOL Direct On Line Start

PWS Part Winding Start

LRA Locked Rotor Ampere (DOL)

FLA Full Load Ampere

SKM Air Cooled Condensing UnitsACUV Series - R134a

22

DOL PWS QTY RLA LRA QTY FLA LRA61009 50 28 167 1 20 158 2 1.5 4.561011 80 38 161 1 28 152 2 1.5 4.561016 100 56 247 190 1 40 228 2 3.1 9.662018 80 51 191 1 + 1 20 + 20 158 + 158 2 3.1 9.662020 100 61 185 1 + 1 28 + 20 152 + 158 2 3.1 9.662022 125 74 203 1 + 1 28 + 28 152 + 152 2 5.3 17.561024 160 83 367 284 1 58 332 2 5.3 17.561026 200 99 367 284 1 71 332 2 5.3 17.562026 160 89 279 222 1 + 1 40 + 28 228 + 152 2 5.3 17.561032 250 127 - 482 1 89 505 3 5.3 17.562032 160 106 296 239 1 + 1 40 + 40 228 + 228 3 5.3 17.562034 200 116 388 305 1 + 1 58 + 28 332 + 152 3 5.3 17.561036 250 142 - 545 1 101 579 3 5.3 17.562040 200 128 400 317 1 + 1 58 + 40 332 + 228 3 5.3 17.562046 250 146 418 335 1 + 1 58 + 58 332 + 332 3 5.3 17.562052 315 181 436 353 1 + 1 71 + 71 332 + 332 4 5.3 17.562058 315 203 609 483 1 + 1 89 + 71 505 + 332 4 5.3 17.562062 315 221 - 552 1 + 1 89 + 89 505 + 505 4 5.3 17.562067 400 236 - 615 1 + 1 101 + 89 579 + 505 4 5.3 17.562071 400 248 - 627 1 + 1 101 + 101 579 + 579 4 5.3 17.563074 315 237 504 421 1 + 2 71 + 58 332 + 332 6 5.3 17.563078 400 263 530 447 3 71 332 6 5.3 17.563082 400 285 703 577 1 + 2 89 + 71 505 + 332 6 5.3 17.563094 500 321 - 663 3 89 505 6 5.3 17.563098 500 336 - 726 1 + 2 101 + 89 579 + 505 6 5.3 17.563100 500 348 - 738 2 + 1 101 + 89 579 + 505 6 5.3 17.564113 500 385 803 727 2 + 2 89 + 71 505 + 332 8 5.3 17.564124 630 421 - 763 4 89 505 8 5.3 17.564132 630 448 - 838 2 + 2 101 + 89 579 + 505 8 5.3 17.564140 630 472 - 862 4 101 579 8 5.3 17.5

DOL PWS QTY RLA LRA QTY FLA LRA61009 40 23 123 95 1 16 113 2 1.3 5.261011 63 30 133 103 1 22 123 2 1.3 5.261016 80 46 224 174 1 32 200 2 3.1 11.862018 63 42 144 116 1 + 1 16 + 16 113 + 113 2 3.1 11.862020 80 50 154 123 1 + 1 22 + 16 123 + 113 2 3.1 11.862022 100 60 171 140 1 + 1 22 + 22 123 + 123 2 5 21.061024 125 68 334 261 1 46 292 2 5 21.061026 160 80 334 261 1 56 292 2 5 21.062026 125 72 248 198 1 + 1 32 + 22 200 + 123 2 5 21.061032 200 104 - 452 1 71 458 3 5 21.062032 125 87 263 213 1 + 1 32 + 32 200 + 200 3 5 21.062034 160 95 345 272 1 + 1 46 + 22 292 + 123 3 5 21.061036 200 115 - 469 1 80 478 3 5 21.062040 160 105 355 282 1 + 1 46 + 32 292 + 200 3 5 21.062046 200 119 369 296 1 + 1 46 + 46 292 + 292 3 5 21.062052 250 146 384 311 1 + 1 56 + 56 292 + 292 4 5 21.062058 250 165 550 436 1 + 1 71 + 56 458 + 292 4 5 21.062062 315 180 - 496 1 + 1 71 + 71 458 + 458 4 5 21.062067 315 191 - 513 1 + 1 80 + 71 478 + 458 4 5 21.062071 315 200 - 522 1 + 1 80 + 80 478 + 478 4 5 21.063074 250 192 446 373 1 + 2 56 + 46 292 + 292 6 5 21.063078 315 212 466 393 3 56 292 6 5 21.063082 315 231 632 518 1 + 2 71 + 56 458 + 292 6 5 21.063094 400 261 - 593 3 71 458 6 5 21.063098 400 272 - 610 1 + 2 80 + 71 478 + 458 6 5 21.063100 400 281 - 619 2 + 1 80 + 71 478 + 458 6 5 21.064113 400 312 713 644 2 + 2 71 + 56 458 + 292 8 5 21.064124 500 342 - 674 4 71 458 8 5 21.064132 500 362 - 700 2 + 2 80 + 71 478 + 458 8 5 21.064140 500 380 - 718 4 80 478 8 5 21.0

DOL PWS QTY RLA LRA QTY FLA LRA61009 80 45 289 1 32 274 2 2.5 7.561011 125 60 278 1 44 263 2 2.5 7.561016 200 96 452 348 1 68 419 2 5.4 16.762018 125 83 328 1 + 1 32 + 32 274 + 274 2 5.4 16.762020 160 98 317 1 + 1 44 + 32 263 + 274 2 5.4 16.762022 200 117 346 1 + 1 44 + 44 263 + 263 2 9 29.761024 250 144 - 518 1 101 611 2 9 29.761026 315 172 - 712 1 123 870 2 9 29.762026 250 147 502 397 1 + 1 68 + 44 419 + 263 2 9 29.761032 400 222 - 905 1 156 960 3 9 29.762032 250 180 535 430 1 + 1 68 + 68 419 + 419 3 9 29.762034 315 197 703 550 1 + 1 101 + 44 611 + 263 3 9 29.761036 500 243 - 941 1 173 1002 3 9 29.762040 400 221 727 574 1 + 1 101 + 68 611 + 419 3 9 29.762046 400 254 - 607 1 + 1 101 + 101 611 + 611 3 9 29.762052 500 313 - 832 1 + 1 123 + 123 870 + 870 4 9 29.762058 630 354 - 900 1 + 1 156 + 123 960 + 870 4 9 29.762062 630 387 - 1029 1 + 1 156 + 156 960 + 960 4 9 29.762067 630 408 - 1064 1 + 1 173 + 156 1002 + 960 4 9 29.762071 630 425 - 1081 1 + 1 173 + 173 1002 + 1002 4 9 29.763074 630 410 - 950 1 + 2 123 + 101 870 + 611 6 9 29.763078 630 454 - 994 3 123 870 6 9 29.763082 800 495 - 1061 1 + 2 156 + 123 960 + 870 6 9 29.763094 800 561 - 1223 3 156 960 6 9 29.763098 800 582 - 1259 1 + 2 173 + 156 1002 + 960 6 9 29.763100 800 599 - 1276 2 + 1 173 + 156 1002 + 960 6 9 29.764113 1000 669 - 1331 2 + 2 156 + 123 960 + 870 8 9 29.764124 1000 735 - 1397 4 156 960 8 9 29.764132 1000 773 - 1450 2 + 2 173 + 156 1002 + 960 8 9 29.764140 1000 807 - 1484 4 173 1002 8 9 29.7

MFA MCAICFModel

380-3-60

Unit CharacteristicrotoM naF resnednoCrosserpmoC

MFA MCAICFModel

460-3-60Unit Characteristic

rotoM naF resnednoCrosserpmoC

MFA MCAICFModel

220-3-60

Unit CharacteristicrotoM naF resnednoCrosserpmoC

ACUV-D

ACUV-D

--

---

--

---

ELECTRICAL DATA

Table 10

POWER SUPPLY : 380V /3Ph / 60Hz

Voltage imbalance between phases to be < 2%

LEGEND:

MFA Maximum Fuse Ampere (For Fuse sizing) as per NEC Article 440-22 & 430-52

MCA Minimum Circuit Ampere (For Wire sizing), as per NEC Article 440-33

RLA Rated Load Ampere at Worst Condition.

ICF Instantaneous Current Flow

DOL Direct On Line Start

PWS Part Winding Start

LRA Locked Rotor Ampere (DOL)

FLA Full Load Ampere

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

23

DOL PWS QTY RLA LRA QTY FLA LRA61009 50 28 167 1 20 158 2 1.5 4.561011 80 38 161 1 28 152 2 1.5 4.561016 100 56 247 190 1 40 228 2 3.1 9.662018 80 51 191 1 + 1 20 + 20 158 + 158 2 3.1 9.662020 100 61 185 1 + 1 28 + 20 152 + 158 2 3.1 9.662022 125 74 203 1 + 1 28 + 28 152 + 152 2 5.3 17.561024 160 83 367 284 1 58 332 2 5.3 17.561026 200 99 367 284 1 71 332 2 5.3 17.562026 160 89 279 222 1 + 1 40 + 28 228 + 152 2 5.3 17.561032 250 127 - 482 1 89 505 3 5.3 17.562032 160 106 296 239 1 + 1 40 + 40 228 + 228 3 5.3 17.562034 200 116 388 305 1 + 1 58 + 28 332 + 152 3 5.3 17.561036 250 142 - 545 1 101 579 3 5.3 17.562040 200 128 400 317 1 + 1 58 + 40 332 + 228 3 5.3 17.562046 250 146 418 335 1 + 1 58 + 58 332 + 332 3 5.3 17.562052 315 181 436 353 1 + 1 71 + 71 332 + 332 4 5.3 17.562058 315 203 609 483 1 + 1 89 + 71 505 + 332 4 5.3 17.562062 315 221 - 552 1 + 1 89 + 89 505 + 505 4 5.3 17.562067 400 236 - 615 1 + 1 101 + 89 579 + 505 4 5.3 17.562071 400 248 - 627 1 + 1 101 + 101 579 + 579 4 5.3 17.563074 315 237 504 421 1 + 2 71 + 58 332 + 332 6 5.3 17.563078 400 263 530 447 3 71 332 6 5.3 17.563082 400 285 703 577 1 + 2 89 + 71 505 + 332 6 5.3 17.563094 500 321 - 663 3 89 505 6 5.3 17.563098 500 336 - 726 1 + 2 101 + 89 579 + 505 6 5.3 17.563100 500 348 - 738 2 + 1 101 + 89 579 + 505 6 5.3 17.564113 500 385 803 727 2 + 2 89 + 71 505 + 332 8 5.3 17.564124 630 421 - 763 4 89 505 8 5.3 17.564132 630 448 - 838 2 + 2 101 + 89 579 + 505 8 5.3 17.564140 630 472 - 862 4 101 579 8 5.3 17.5

DOL PWS QTY RLA LRA QTY FLA LRA61009 40 23 123 95 1 16 113 2 1.3 5.261011 63 30 133 103 1 22 123 2 1.3 5.261016 80 46 224 174 1 32 200 2 3.1 11.862018 63 42 144 116 1 + 1 16 + 16 113 + 113 2 3.1 11.862020 80 50 154 123 1 + 1 22 + 16 123 + 113 2 3.1 11.862022 100 60 171 140 1 + 1 22 + 22 123 + 123 2 5 21.061024 125 68 334 261 1 46 292 2 5 21.061026 160 80 334 261 1 56 292 2 5 21.062026 125 72 248 198 1 + 1 32 + 22 200 + 123 2 5 21.061032 200 104 - 452 1 71 458 3 5 21.062032 125 87 263 213 1 + 1 32 + 32 200 + 200 3 5 21.062034 160 95 345 272 1 + 1 46 + 22 292 + 123 3 5 21.061036 200 115 - 469 1 80 478 3 5 21.062040 160 105 355 282 1 + 1 46 + 32 292 + 200 3 5 21.062046 200 119 369 296 1 + 1 46 + 46 292 + 292 3 5 21.062052 250 146 384 311 1 + 1 56 + 56 292 + 292 4 5 21.062058 250 165 550 436 1 + 1 71 + 56 458 + 292 4 5 21.062062 315 180 - 496 1 + 1 71 + 71 458 + 458 4 5 21.062067 315 191 - 513 1 + 1 80 + 71 478 + 458 4 5 21.062071 315 200 - 522 1 + 1 80 + 80 478 + 478 4 5 21.063074 250 192 446 373 1 + 2 56 + 46 292 + 292 6 5 21.063078 315 212 466 393 3 56 292 6 5 21.063082 315 231 632 518 1 + 2 71 + 56 458 + 292 6 5 21.063094 400 261 - 593 3 71 458 6 5 21.063098 400 272 - 610 1 + 2 80 + 71 478 + 458 6 5 21.063100 400 281 - 619 2 + 1 80 + 71 478 + 458 6 5 21.064113 400 312 713 644 2 + 2 71 + 56 458 + 292 8 5 21.064124 500 342 - 674 4 71 458 8 5 21.064132 500 362 - 700 2 + 2 80 + 71 478 + 458 8 5 21.064140 500 380 - 718 4 80 478 8 5 21.0

DOL PWS QTY RLA LRA QTY FLA LRA61009 80 45 289 1 32 274 2 2.5 7.561011 125 60 278 1 44 263 2 2.5 7.561016 200 96 452 348 1 68 419 2 5.4 16.762018 125 83 328 1 + 1 32 + 32 274 + 274 2 5.4 16.762020 160 98 317 1 + 1 44 + 32 263 + 274 2 5.4 16.762022 200 117 346 1 + 1 44 + 44 263 + 263 2 9 29.761024 250 144 - 518 1 101 611 2 9 29.761026 315 172 - 712 1 123 870 2 9 29.762026 250 147 502 397 1 + 1 68 + 44 419 + 263 2 9 29.761032 400 222 - 905 1 156 960 3 9 29.762032 250 180 535 430 1 + 1 68 + 68 419 + 419 3 9 29.762034 315 197 703 550 1 + 1 101 + 44 611 + 263 3 9 29.761036 500 243 - 941 1 173 1002 3 9 29.762040 400 221 727 574 1 + 1 101 + 68 611 + 419 3 9 29.762046 400 254 - 607 1 + 1 101 + 101 611 + 611 3 9 29.762052 500 313 - 832 1 + 1 123 + 123 870 + 870 4 9 29.762058 630 354 - 900 1 + 1 156 + 123 960 + 870 4 9 29.762062 630 387 - 1029 1 + 1 156 + 156 960 + 960 4 9 29.762067 630 408 - 1064 1 + 1 173 + 156 1002 + 960 4 9 29.762071 630 425 - 1081 1 + 1 173 + 173 1002 + 1002 4 9 29.763074 630 410 - 950 1 + 2 123 + 101 870 + 611 6 9 29.763078 630 454 - 994 3 123 870 6 9 29.763082 800 495 - 1061 1 + 2 156 + 123 960 + 870 6 9 29.763094 800 561 - 1223 3 156 960 6 9 29.763098 800 582 - 1259 1 + 2 173 + 156 1002 + 960 6 9 29.763100 800 599 - 1276 2 + 1 173 + 156 1002 + 960 6 9 29.764113 1000 669 - 1331 2 + 2 156 + 123 960 + 870 8 9 29.764124 1000 735 - 1397 4 156 960 8 9 29.764132 1000 773 - 1450 2 + 2 173 + 156 1002 + 960 8 9 29.764140 1000 807 - 1484 4 173 1002 8 9 29.7

MFA MCAICFModel

380-3-60

Unit CharacteristicrotoM naF resnednoCrosserpmoC

MFA MCAICFModel

460-3-60Unit Characteristic

rotoM naF resnednoCrosserpmoC

MFA MCAICFModel

220-3-60

Unit CharacteristicrotoM naF resnednoCrosserpmoC

ACUV-D

ACUV-D

--

---

--

---

POWER SUPPLY : 380V /3Ph / 60HzELECTRICAL DATA

Table 11

POWER SUPPLY : 460V /3Ph/ 60Hz

Voltage imbalance between phases to be < 2%

LEGEND:

MFA Maximum Fuse Ampere (For Fuse sizing) as per NEC Article 440-22 & 430-52

MCA Minimum Circuit Ampere (For Wire sizing), as per NEC Article 440-33

RLA Rated Load Ampere at Worst Condition.

ICF Instantaneous Current Flow

DOL Direct On Line Start

PWS Part Winding Start

LRA Locked Rotor Ampere (DOL)

FLA Full Load Ampere

SKM Air Cooled Condensing UnitsACUV Series - R134a

24

Table 12

Dimensional Data

Note: See Pages 20-23 for Legend.

ACUV Models- 51008D to 51010D & 61009D to 61011D

ALL DIMENSIONS ARE IN INCHES [mm]LINE SIZES ARE BASED ON 100ft EQUIVALENT LENGTH

LINE SIZES ARE BASED ON 100ft EQUIVALENT LENGTH

20.67[525]

[457]

[457]

[457]

22.72[577]

20.67[525]

[525]20.67

ALL DIMENSIONS ARE IN INCHES

DIM.12" INSTEAD OF 10" & 4" FOR ONE COMPRESSOR MODELMODEL WITH ONE COMPRESSOR*

4

3.94

H

[100

]

* [1515]61024D [1473] [2134]

L

*61026D

62026D

52022D

*51022D

[2134]84

[1473]58

[1515]59.65

84[2134]

58[1473]

59.65[1515]

51.655652017D 76

*51021D

62022D

52019D

62020D

59.65[1515]

56[1422]

84[2134]

8458 59.65

[1930][1422] [1312]

52015D

62018D

*61016D

51014D*

[1880]74

[1422]56

[1312]51.65

74[1880][1422]

56[1312]51.65

[101]

[254]10

LIQUID #1

[mm]

[178

]7

2

A

CABLE ENTRY HOLES

(WITH RUBBER GROMMET)Ø1 & 1 1/2

[101]*

[254]10

[25]

4* ACCESS

[38]

*

[178

]4*

7

B

[20]

LIQUID #2RIGGING HOLESØ0.79 4 Nos.

1 1/8[29]2 5/8[67]

[22]

[22]

SUCTION #1

1

[67]2 5/8

[457]18

2 1/8[54]

2 1/8[54]

-[67]2 5/8

[29]1 1/8

[22]

[22]

7/8

7/8

7/8

7/8

1 1/8[29]-

W

A2 A4

[22]

[22]

[22]

[16]

[16]

5/8[22]7/8[41]1 5/81818

18[457]

18

-[54]2 1/8

2 1/8[54]

[457]

1 5/8[41]

2 1/8[54]

[22]

[22]

7/8

7/8

-

7/8

[22]

[22]7/8

7/8

7/8

7/8

1 5/8[41][457]

18 18[41]1 5/8

-2 1/8[54]

2 1/8[54]

5/85/8[16]

[22]7/8

[22]

[22]

7/8

7/8-

[254]

A1

10[254]

A3

10

SUCTION #2

DIMENSIONS

ACUV Models - 51008D-51010D & 61009D-61011D

ACUV Models - 51014D to 52022D & 61016D to 62026D

MODELACUV- L W H LIQ.#2

CONNECTION SIZES, Ø

LIQ.#1A B SUC.#1 SUC.#2

LIQUIDØ

A1A3

A2 A4

SUCTIONØ

ACCESS

LEGEND

COMPRESSORCONTROL PANELCONDENSER COILCONDENSER FAN

2

43

1

61011D

51010D

[22]

[22]

2 1/8

1 5/8

7/8[54]

7/8[41]

MODELACUV-

51008D

61009D [22]

[16]

SUC.Ø LIQ.Ø

1 5/8

1 5/8 5/8[41]

7/8[41]

CONNECTIONS

RIGGING HOLESØ0.79 4 Nos.[20]

7[1

78]

18 [457

]

45[1143]

68[1727]

8[203]

10[254]

10[254]

[54]

[41]1 5/8

2 1/8

-

[41]

[54]

[41]

[41]

[41]

[41]

1 5/8

-

2 1/8

1 5/8

1 5/8

1 5/8

1 5/8

-

CIRCUIT-1 CIRCUIT-2

CABLE ENTRY HOLES[38]

GROMMET)(WITH RUBBERØ1 & 1 1/2[25]

[22]7/8

ON BOTH SIDES

CABLE ENTRY

DETACHABLEPLATE FOR

VENTILATION

3

51.6

[131

2]

3.9

[100

]

PLATE FORCABLE ENTRY

ON BOTH SIDES

DETACHABLE

VENTILATION

3

DOL PWS QTY RLA LRA QTY FLA LRA61009 50 28 167 1 20 158 2 1.5 4.561011 80 38 161 1 28 152 2 1.5 4.561016 100 56 247 190 1 40 228 2 3.1 9.662018 80 51 191 1 + 1 20 + 20 158 + 158 2 3.1 9.662020 100 61 185 1 + 1 28 + 20 152 + 158 2 3.1 9.662022 125 74 203 1 + 1 28 + 28 152 + 152 2 5.3 17.561024 160 83 367 284 1 58 332 2 5.3 17.561026 200 99 367 284 1 71 332 2 5.3 17.562026 160 89 279 222 1 + 1 40 + 28 228 + 152 2 5.3 17.561032 250 127 - 482 1 89 505 3 5.3 17.562032 160 106 296 239 1 + 1 40 + 40 228 + 228 3 5.3 17.562034 200 116 388 305 1 + 1 58 + 28 332 + 152 3 5.3 17.561036 250 142 - 545 1 101 579 3 5.3 17.562040 200 128 400 317 1 + 1 58 + 40 332 + 228 3 5.3 17.562046 250 146 418 335 1 + 1 58 + 58 332 + 332 3 5.3 17.562052 315 181 436 353 1 + 1 71 + 71 332 + 332 4 5.3 17.562058 315 203 609 483 1 + 1 89 + 71 505 + 332 4 5.3 17.562062 315 221 - 552 1 + 1 89 + 89 505 + 505 4 5.3 17.562067 400 236 - 615 1 + 1 101 + 89 579 + 505 4 5.3 17.562071 400 248 - 627 1 + 1 101 + 101 579 + 579 4 5.3 17.563074 315 237 504 421 1 + 2 71 + 58 332 + 332 6 5.3 17.563078 400 263 530 447 3 71 332 6 5.3 17.563082 400 285 703 577 1 + 2 89 + 71 505 + 332 6 5.3 17.563094 500 321 - 663 3 89 505 6 5.3 17.563098 500 336 - 726 1 + 2 101 + 89 579 + 505 6 5.3 17.563100 500 348 - 738 2 + 1 101 + 89 579 + 505 6 5.3 17.564113 500 385 803 727 2 + 2 89 + 71 505 + 332 8 5.3 17.564124 630 421 - 763 4 89 505 8 5.3 17.564132 630 448 - 838 2 + 2 101 + 89 579 + 505 8 5.3 17.564140 630 472 - 862 4 101 579 8 5.3 17.5

DOL PWS QTY RLA LRA QTY FLA LRA61009 40 23 123 95 1 16 113 2 1.3 5.261011 63 30 133 103 1 22 123 2 1.3 5.261016 80 46 224 174 1 32 200 2 3.1 11.862018 63 42 144 116 1 + 1 16 + 16 113 + 113 2 3.1 11.862020 80 50 154 123 1 + 1 22 + 16 123 + 113 2 3.1 11.862022 100 60 171 140 1 + 1 22 + 22 123 + 123 2 5 21.061024 125 68 334 261 1 46 292 2 5 21.061026 160 80 334 261 1 56 292 2 5 21.062026 125 72 248 198 1 + 1 32 + 22 200 + 123 2 5 21.061032 200 104 - 452 1 71 458 3 5 21.062032 125 87 263 213 1 + 1 32 + 32 200 + 200 3 5 21.062034 160 95 345 272 1 + 1 46 + 22 292 + 123 3 5 21.061036 200 115 - 469 1 80 478 3 5 21.062040 160 105 355 282 1 + 1 46 + 32 292 + 200 3 5 21.062046 200 119 369 296 1 + 1 46 + 46 292 + 292 3 5 21.062052 250 146 384 311 1 + 1 56 + 56 292 + 292 4 5 21.062058 250 165 550 436 1 + 1 71 + 56 458 + 292 4 5 21.062062 315 180 - 496 1 + 1 71 + 71 458 + 458 4 5 21.062067 315 191 - 513 1 + 1 80 + 71 478 + 458 4 5 21.062071 315 200 - 522 1 + 1 80 + 80 478 + 478 4 5 21.063074 250 192 446 373 1 + 2 56 + 46 292 + 292 6 5 21.063078 315 212 466 393 3 56 292 6 5 21.063082 315 231 632 518 1 + 2 71 + 56 458 + 292 6 5 21.063094 400 261 - 593 3 71 458 6 5 21.063098 400 272 - 610 1 + 2 80 + 71 478 + 458 6 5 21.063100 400 281 - 619 2 + 1 80 + 71 478 + 458 6 5 21.064113 400 312 713 644 2 + 2 71 + 56 458 + 292 8 5 21.064124 500 342 - 674 4 71 458 8 5 21.064132 500 362 - 700 2 + 2 80 + 71 478 + 458 8 5 21.064140 500 380 - 718 4 80 478 8 5 21.0

DOL PWS QTY RLA LRA QTY FLA LRA61009 80 45 289 1 32 274 2 2.5 7.561011 125 60 278 1 44 263 2 2.5 7.561016 200 96 452 348 1 68 419 2 5.4 16.762018 125 83 328 1 + 1 32 + 32 274 + 274 2 5.4 16.762020 160 98 317 1 + 1 44 + 32 263 + 274 2 5.4 16.762022 200 117 346 1 + 1 44 + 44 263 + 263 2 9 29.761024 250 144 - 518 1 101 611 2 9 29.761026 315 172 - 712 1 123 870 2 9 29.762026 250 147 502 397 1 + 1 68 + 44 419 + 263 2 9 29.761032 400 222 - 905 1 156 960 3 9 29.762032 250 180 535 430 1 + 1 68 + 68 419 + 419 3 9 29.762034 315 197 703 550 1 + 1 101 + 44 611 + 263 3 9 29.761036 500 243 - 941 1 173 1002 3 9 29.762040 400 221 727 574 1 + 1 101 + 68 611 + 419 3 9 29.762046 400 254 - 607 1 + 1 101 + 101 611 + 611 3 9 29.762052 500 313 - 832 1 + 1 123 + 123 870 + 870 4 9 29.762058 630 354 - 900 1 + 1 156 + 123 960 + 870 4 9 29.762062 630 387 - 1029 1 + 1 156 + 156 960 + 960 4 9 29.762067 630 408 - 1064 1 + 1 173 + 156 1002 + 960 4 9 29.762071 630 425 - 1081 1 + 1 173 + 173 1002 + 1002 4 9 29.763074 630 410 - 950 1 + 2 123 + 101 870 + 611 6 9 29.763078 630 454 - 994 3 123 870 6 9 29.763082 800 495 - 1061 1 + 2 156 + 123 960 + 870 6 9 29.763094 800 561 - 1223 3 156 960 6 9 29.763098 800 582 - 1259 1 + 2 173 + 156 1002 + 960 6 9 29.763100 800 599 - 1276 2 + 1 173 + 156 1002 + 960 6 9 29.764113 1000 669 - 1331 2 + 2 156 + 123 960 + 870 8 9 29.764124 1000 735 - 1397 4 156 960 8 9 29.764132 1000 773 - 1450 2 + 2 173 + 156 1002 + 960 8 9 29.764140 1000 807 - 1484 4 173 1002 8 9 29.7

MFA MCAICFModel

380-3-60

Unit CharacteristicrotoM naF resnednoCrosserpmoC

MFA MCAICFModel

460-3-60Unit Characteristic

rotoM naF resnednoCrosserpmoC

MFA MCAICFModel

220-3-60

Unit CharacteristicrotoM naF resnednoCrosserpmoC

ACUV-D

ACUV-D

--

---

--

---

ELECTRICAL DATAPOWER SUPPLY : 220V /3Ph/ 60Hz

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

25

[20]Ø.79 4 Nos.RIGGING HOLES

4

2

[254]10

[2134]

A2

84

1

A4

A1 A3

10[254]

[254]

(WITH RUBBER GROMMET)4[102]

8[2

03]

LIQUID #1

A

CABLE ENTRY HOLESØ1 & 2

10

ACCESS

[25]

[254]10

[51]

[102]4 [2

03]

8

B

LIQUID #2

ALL DIMENSIONS ARE IN INCHES

SUCTION #1

[2235]88

[mm]

CONDENSER FANCONDENSER COILCONTROL PANELCOMPRESSOR

234

1LEGEND

SUCTION #2

ACUV Models - 51028D to 52040D & 61032D to 62046D

ACUV Models - 52045D to 52060D & 62052D to 62071D

H

4

A

A2

76[1930]

2

1

A4

10[254]

A1 A3

[102]

[254]

ACCESS

(WITH RUBBER GROMMET)

CABLE ENTRY HOLES

10[254]

4[102]

[51][25]Ø1 & 2MODEL WITH ONE COMPRESSOR

ALL DIMENSIONS ARE IN INCHES

LIQUID#1

SUCTION#1

*

[2235]88

[mm]

10

4

B

LIQUID #2

SUCTION #2

CONDENSER COILCONTROL PANEL

CONDENSER FANLEGEND

34

12

COMPRESSOR

LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

52053D

52060D62071D

52058D62067D

62062D

77.63[1972]

25.79[655]

ACUV-

62052D

62058D52049D

52045D

MODELBAH

[602]

[655]25.79

23.7

DIMENSIONS

85.63[2175]

[2175]85.63

[2175]85.63

[2175]85.63

[602]23.7

[602]23.7

[655]25.79

[655]25.79

[655]25.79

[655]25.79 25.79

[655]

DIM.12" INSTEAD OF 10" & 4" FOR ONE COMPRESSOR MODEL.

*

* *

*

*51028D

62046D

62034D

61036D

62040D52034D

51030D

52040D

**

52028D62032D

52030D

61032D*

1947

[525]20.67

76.65

[1947]76.65

[525]20.67

24.8[630][1540]

60.63 - -

DIMENSIONSMODELACUV-

CONNECTION SIZES, Ø

SUC.#2AH B LIQ.#1SUC.#1 LIQ.#2

60.63[1540]

60.63[1540]

60.63[1540]

[525]20.67

[457]18

[630]24.8 -

[525]20.67

[525]20.67 20.67

[525]

-

[254]10

LIQ.#1

CONNECTION SIZE,Ø

1 1/82 5/8

2 5/8[67]

[67]1 1/8[29]

[29]

2 5/8

2 5/8[67]

[67]

SUC.#11 1/8

1 1/8[29]

[29]

1 1/8

1 1/8[29]

[29]

1 1/8

1 1/8[29]

[29]

LIQ.#2

[67]2 5/8

[29]1 1/8

[29]1 1/8

20.67[525]

[67]2 5/8 1 1/8[29][67]2 5/8 [29]1 1/8[54]2 1/8 [22] [22]7/87/8[54]2 1/8 7/8[22] [22]7/8[54]2 1/8 [22]7/8 7/8[22]

1 1/8[29] 7/8[22][67]2 5/8

[67]2 5/82 5/8[67]

1 1/8[29][29]1 1/8

[54]2 1/8 7/8[22] 7/8[22][67]2 5/8 1 1/8[29] [22]7/8[54]2 1/8 [22]7/8 [22]7/8[67]2 5/8 1 1/8[29] [29]1 1/8

CIRCUIT-1 CIRCUIT-2

1 5/8[41]

2 1/8[54]2 5/8[67]

-

2 1/8

2 1/8[54]

[54]

2 1/8[54]

2 1/82 1/8

[54]

[54]

-

CIRCUIT-1 CIRCUIT-2

[67]

[67]

[67]2 5/8

2 5/8

[67]2 5/8

2 5/8[67]

2 5/8

SUC.#2

PLATE FORDETACHABLE

CABLE ENTRY

VENTILATIONON BOTH SIDES

3

4.92

[125

]

H

ON BOTH SIDES

CABLE ENTRYPLATE FOR

DETACHABLE

VENTILATIONFILTERED

3

3.9

[100

]

7[1

78]

7[1

78]

Dimensional Data ACUV Models- 51014D to 52022D & 61016D to 62026D

ALL DIMENSIONS ARE IN INCHES [mm]LINE SIZES ARE BASED ON 100ft EQUIVALENT LENGTH

LINE SIZES ARE BASED ON 100ft EQUIVALENT LENGTH

20.67[525]

[457]

[457]

[457]

22.72[577]

20.67[525]

[525]20.67

ALL DIMENSIONS ARE IN INCHES

DIM.12" INSTEAD OF 10" & 4" FOR ONE COMPRESSOR MODELMODEL WITH ONE COMPRESSOR*

4

3.94

H

[100

]* [1515]61024D [1473] [2134]

L

*61026D

62026D

52022D

*51022D

[2134]84

[1473]58

[1515]59.65

84[2134]

58[1473]

59.65[1515]

51.655652017D 76

*51021D

62022D

52019D

62020D

59.65[1515]

56[1422]

84[2134]

8458 59.65

[1930][1422] [1312]

52015D

62018D

*61016D

51014D*

[1880]74

[1422]56

[1312]51.65

74[1880][1422]

56[1312]51.65

[101]

[254]10

LIQUID #1

[mm]

[178

]7

2

A

CABLE ENTRY HOLES

(WITH RUBBER GROMMET)Ø1 & 1 1/2

[101]*

[254]10

[25]

4* ACCESS

[38]

*

[178

]4*

7

B

[20]

LIQUID #2RIGGING HOLESØ0.79 4 Nos.

1 1/8[29]2 5/8[67]

[22]

[22]

SUCTION #1

1

[67]2 5/8

[457]18

2 1/8[54]

2 1/8[54]

-[67]2 5/8

[29]1 1/8

[22]

[22]

7/8

7/8

7/8

7/8

1 1/8[29]-

W

A2 A4

[22]

[22]

[22]

[16]

[16]

5/8[22]7/8[41]1 5/81818

18[457]

18

-[54]2 1/8

2 1/8[54]

[457]

1 5/8[41]

2 1/8[54]

[22]

[22]

7/8

7/8

-

7/8

[22]

[22]7/8

7/8

7/8

7/8

1 5/8[41][457]

18 18[41]1 5/8

-2 1/8[54]

2 1/8[54]

5/85/8[16]

[22]7/8

[22]

[22]

7/8

7/8-

[254]

A1

10[254]

A3

10

SUCTION #2

DIMENSIONS

ACUV Models - 51008D-51010D & 61009D-61011D

ACUV Models - 51014D to 52022D & 61016D to 62026D

MODELACUV- L W H LIQ.#2

CONNECTION SIZES, Ø

LIQ.#1A B SUC.#1 SUC.#2

LIQUIDØ

A1A3

A2 A4

SUCTIONØ

ACCESS

LEGEND

COMPRESSORCONTROL PANELCONDENSER COILCONDENSER FAN

2

43

1

61011D

51010D

[22]

[22]

2 1/8

1 5/8

7/8[54]

7/8[41]

MODELACUV-

51008D

61009D [22]

[16]

SUC.Ø LIQ.Ø

1 5/8

1 5/8 5/8[41]

7/8[41]

CONNECTIONS

RIGGING HOLESØ0.79 4 Nos.[20]

7[1

78]

18 [457

]

45[1143]

68[1727]

8[203]

10[254]

10[254]

[54]

[41]1 5/8

2 1/8

-

[41]

[54]

[41]

[41]

[41]

[41]

1 5/8

-

2 1/8

1 5/8

1 5/8

1 5/8

1 5/8

-

CIRCUIT-1 CIRCUIT-2

CABLE ENTRY HOLES[38]

GROMMET)(WITH RUBBERØ1 & 1 1/2[25]

[22]7/8

ON BOTH SIDES

CABLE ENTRY

DETACHABLEPLATE FOR

VENTILATION

3

51.6

[131

2]

3.9

[100

]

PLATE FORCABLE ENTRY

ON BOTH SIDES

DETACHABLE

VENTILATION

3

ACUV Models- 51028D to 52040D & 61032D to 62046D

SKM Air Cooled Condensing UnitsACUV Series - R134a

26

[20]Ø.79 4 Nos.RIGGING HOLES

4

2

[254]10

[2134]

A2

84

1

A4

A1 A3

10[254]

[254]

(WITH RUBBER GROMMET)4[102]

8[2

03]

LIQUID #1

A

CABLE ENTRY HOLESØ1 & 2

10

ACCESS

[25]

[254]10

[51]

[102]4 [2

03]

8

B

LIQUID #2

ALL DIMENSIONS ARE IN INCHES

SUCTION #1

[2235]88

[mm]

CONDENSER FANCONDENSER COILCONTROL PANELCOMPRESSOR

234

1LEGEND

SUCTION #2

ACUV Models - 51028D to 52040D & 61032D to 62046D

ACUV Models - 52045D to 52060D & 62052D to 62071D

H

4

A

A2

76[1930]

2

1

A4

10[254]

A1 A3

[102]

[254]

ACCESS

(WITH RUBBER GROMMET)

CABLE ENTRY HOLES

10[254]

4[102]

[51][25]Ø1 & 2MODEL WITH ONE COMPRESSOR

ALL DIMENSIONS ARE IN INCHES

LIQUID#1

SUCTION#1

*

[2235]88

[mm]

10

4

B

LIQUID #2

SUCTION #2

CONDENSER COILCONTROL PANEL

CONDENSER FANLEGEND

34

12

COMPRESSOR

LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

52053D

52060D62071D

52058D62067D

62062D

77.63[1972]

25.79[655]

ACUV-

62052D

62058D52049D

52045D

MODELBAH

[602]

[655]25.79

23.7

DIMENSIONS

85.63[2175]

[2175]85.63

[2175]85.63

[2175]85.63

[602]23.7

[602]23.7

[655]25.79

[655]25.79

[655]25.79

[655]25.79 25.79

[655]

DIM.12" INSTEAD OF 10" & 4" FOR ONE COMPRESSOR MODEL.

*

* *

*

*51028D

62046D

62034D

61036D

62040D52034D

51030D

52040D

**

52028D62032D

52030D

61032D*

1947

[525]20.67

76.65

[1947]76.65

[525]20.67

24.8[630][1540]

60.63 - -

DIMENSIONSMODELACUV-

CONNECTION SIZES, Ø

SUC.#2AH B LIQ.#1SUC.#1 LIQ.#2

60.63[1540]

60.63[1540]

60.63[1540]

[525]20.67

[457]18

[630]24.8 -

[525]20.67

[525]20.67 20.67

[525]

-

[254]10

LIQ.#1

CONNECTION SIZE,Ø

1 1/82 5/8

2 5/8[67]

[67]1 1/8[29]

[29]

2 5/8

2 5/8[67]

[67]

SUC.#11 1/8

1 1/8[29]

[29]

1 1/8

1 1/8[29]

[29]

1 1/8

1 1/8[29]

[29]

LIQ.#2

[67]2 5/8

[29]1 1/8

[29]1 1/8

20.67[525]

[67]2 5/8 1 1/8[29][67]2 5/8 [29]1 1/8[54]2 1/8 [22] [22]7/87/8[54]2 1/8 7/8[22] [22]7/8[54]2 1/8 [22]7/8 7/8[22]

1 1/8[29] 7/8[22][67]2 5/8

[67]2 5/82 5/8[67]

1 1/8[29][29]1 1/8

[54]2 1/8 7/8[22] 7/8[22][67]2 5/8 1 1/8[29] [22]7/8[54]2 1/8 [22]7/8 [22]7/8[67]2 5/8 1 1/8[29] [29]1 1/8

CIRCUIT-1 CIRCUIT-2

1 5/8[41]

2 1/8[54]2 5/8[67]

-

2 1/8

2 1/8[54]

[54]

2 1/8[54]

2 1/82 1/8

[54]

[54]

-

CIRCUIT-1 CIRCUIT-2

[67]

[67]

[67]2 5/8

2 5/8

[67]2 5/8

2 5/8[67]

2 5/8

SUC.#2

PLATE FORDETACHABLE

CABLE ENTRY

VENTILATIONON BOTH SIDES

3

4.92

[125

]

H

ON BOTH SIDES

CABLE ENTRYPLATE FOR

DETACHABLE

VENTILATIONFILTERED

3

3.9

[100

]

7[1

78]

7[1

78]

ALL DIMENSIONS ARE IN INCHESLINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

ACUV Models - 54095D to 54120D & 64113D to 64140D

4

[2235]88

COMPRESSOR

LEGEND

23

1

CONTROL PANEL

CONDENSER FANCONDENSER COIL

SUCTION Ø 44 RIGGING HOLESØ7/8 x 4 Nos.2 5/8 x 4Nos.[67] [22]

1 1/8 x 4Nos.LIQUID Ø

[29]PLATE FORCABLE ENTRY

DETACHABLE

VENTILATIONON BOTH SIDES

FILTERED

[254]

[2250]

[mm] 88.6

PARTITION

A2

[4500]

2

A4177.2

A6

88.6

PARTITION1

[2250]

A8

RIGGING HOLESØ7/8 x 4 Nos.

[254]10

A1

SUCTION Øx3Nos.[22]

A5A3 A7

4

12

3

[305]

10

CONNECTION SIZES,Ø

LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

ACUV Models - 53064D to 53086D & 63074D to 63100D

88[2235]

[mm]

2 5/8 [67]63074D

[67]2 5/863098D53084D

ALL DIMENSIONS ARE IN INCHES

63100D53086D [67]2 5/8

53070D63082D53080D63094D

53068D63078D

[67]2 5/8

[67]2 5/8

2 5/8 [67]

MODEL

53064D

ACUV-

[67]2 5/8

SUC.#1

[29]1 1/8[29]1 1/8

ON BOTH SIDES

CABLE ENTRY

12[305]

VENTILATIONFILTERED

[2250][1195]2 CONDENSER COIL

LIQUID Øx3Nos.

CONTROL PANELCOMPRESSOR

34

2 1 PARTITION3

47

1 1/8 [29]1 1/8 [29]

LEGEND

CONDENSER FAN1

1 1/8 [29] 1 1/8 [29] A2

1 1/8 [29]

1 1/8 [29]

[29]1 1/8

1 1/8 [29]

1 1/8 [29]

1 1/8 [29]

88.6[3445]135.6

A4 A6

DETACHABLEPLATE FOR

A1

10[254]

7/8 [22]

LIQ.#2

[22]7/8

LIQ.#3A3

10

A5[254]

CIRCUIT-CCIRCUIT-BCIRCUIT-A

4.92

[125

]

105.

92[2

690]

95.2

9[2

420]

29.5

[750

]

106.

92[2

715]

95.2

9[2

420]

29.5

[750

]

5.92

[150

]

CIRCUIT-D

CIRCUIT-ACIRCUIT-BCIRCUIT-C

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

LIQ.#1

2 5/8 [67]

2 5/8 [67]

2 5/8

2 5/8 [67]

[67]

2 5/8

2 5/8 [67]

[67]

SUC.#2

2 1/8 [54]

2 5/8 [67]

[67]2 5/8

[67]

[67]

[67]

[67]

2 5/8

2 5/8

2 5/8

2 5/8

SUC.#3

[54]2 1/8

CIRCUIT-1 CIRCUIT-2 CIRCUIT-3

20[508]

Dimensional Data ACUV Models- 52045D to 52060D & 62052D to 62071D

ACUV Models- 53064D to 53086D & 63074 to 63100D

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

27

LOADING POINTS - 50HzA1 A2 A3 A4

Ib. 221 208 283 245 957Kg. 100 94 128 111 434Ib. 229 217 297 261 1004Kg. 104 99 135 118 455Ib. 312 298 330 298 1237Kg. 142 135 150 135 561Ib. 379 375 397 375 1526Kg. 172 170 180 170 692Ib. 384 379 399 379 1541Kg. 174 172 181 172 699Ib. 448 432 476 432 1788Kg. 203 196 216 196 811Ib. 423 269 626 269 1588Kg. 192 122 284 122 720Ib. 412 390 441 390 1634Kg. 187 177 200 177 741Ib. 496 485 492 450 1923Kg. 225 220 223 204 872Ib. 472 440 529 531 1973Kg. 214 200 240 241 895Ib. 534 503 578 578 2192Kg. 242 228 262 262 994Ib. 516 512 549 595 2172Kg. 234 232 249 270 985Ib. 474 442 531 533 1980Kg. 215 200 241 242 898Ib. 609 584 650 670 2514Kg. 276 265 295 304 1140Ib. 631 593 686 686 2595Kg. 286 269 311 311 1177Ib. 609 564 847 847 2867Kg. 276 256 384 384 1300Ib. 664 626 913 964 3166Kg. 301 284 414 437 1436Ib. 690 637 1003 1003 3334Kg. 313 289 455 455 1512Ib. 734 681 1041 1041 3497Kg. 333 309 472 472 1586Ib. 734 679 1041 1041 3495Kg. 333 308 472 472 1585

51028-D

TOTALWEIGHTUNIT

52030-D

52028-D

ACUV-

51008-D

51010-D

51014-D

52017-D

52019-D

51021-D

51022-D

52060-D

51030-D

52034-D

52049-D

52053-D

52058-D

52040-D

52045-D

52022-D

LOADING POINTS

52015-D

LOADING POINTS - 60HzA1 A2 A3 A4

Ib. 222 209 284 246 962Kg. 101 95 129 112 436Ib. 232 219 301 263 1014Kg. 105 99 137 119 460Ib. 315 302 333 302 1252Kg. 143 137 151 137 568Ib. 381 377 399 377 1535Kg. 173 171 181 171 696Ib. 388 381 404 379 1552Kg. 176 173 183 172 704Ib. 454 439 483 439 1815Kg. 206 199 219 199 823Ib. 410 386 437 386 1618Kg. 186 175 198 175 734Ib. 417 395 445 395 1652Kg. 189 179 202 179 749Ib. 503 492 498 456 1949Kg. 228 223 226 207 884Ib. 483 451 536 538 2008Kg. 219 204 243 244 911Ib. 542 512 584 584 2223Kg. 246 232 265 265 1008Ib. 529 525 558 604 2216Kg. 240 238 253 274 1005Ib. 484 452 537 540 2013Kg. 220 205 244 245 913Ib. 620 595 657 679 2551Kg. 281 270 298 308 1157Ib. 644 606 695 695 2639Kg. 292 275 315 315 1197Ib. 622 576 858 858 2913Kg. 282 261 389 389 1321Ib. 677 639 924 975 3215Kg. 307 290 419 442 1458Ib. 703 650 1014 1014 3382Kg. 319 295 460 460 1534Ib. 747 695 1052 1052 3546Kg. 339 315 477 477 1608Ib. 747 695 1052 1052 3546Kg. 339 315 477 477 1608

62022-D

TOTALWEIGHT

61009-D

61011-D

62032-D

62034-D

ACUV- UNIT

61026-D

61024-D

61016-D

62018-D

62020-D

62062-D

62067-D

62071-D

62026-D

61032-D

62058-D

LOADING POINTS

62046-D

62052-D

61036-D

62040-D

ALL DIMENSIONS ARE IN INCHESLINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

ACUV Models - 54095D to 54120D & 64113D to 64140D

4

[2235]88

COMPRESSOR

LEGEND

23

1

CONTROL PANEL

CONDENSER FANCONDENSER COIL

SUCTION Ø 44 RIGGING HOLESØ7/8 x 4 Nos.2 5/8 x 4Nos.[67] [22]

1 1/8 x 4Nos.LIQUID Ø

[29]PLATE FORCABLE ENTRY

DETACHABLE

VENTILATIONON BOTH SIDES

FILTERED

[254]

[2250]

[mm] 88.6

PARTITION

A2

[4500]

2

A4177.2

A6

88.6

PARTITION1

[2250]

A8

RIGGING HOLESØ7/8 x 4 Nos.

[254]10

A1

SUCTION Øx3Nos.[22]

A5A3 A7

4

12

3

[305]

10

CONNECTION SIZES,Ø

LINE SIZES ARE BASED ON 100f EQUIVALENT LENGTH

ACUV Models - 53064D to 53086D & 63074D to 63100D

88[2235]

[mm]

2 5/8 [67]63074D

[67]2 5/863098D53084D

ALL DIMENSIONS ARE IN INCHES

63100D53086D [67]2 5/8

53070D63082D53080D63094D

53068D63078D

[67]2 5/8

[67]2 5/8

2 5/8 [67]

MODEL

53064D

ACUV-

[67]2 5/8

SUC.#1

[29]1 1/8[29]1 1/8

ON BOTH SIDES

CABLE ENTRY

12[305]

VENTILATIONFILTERED

[2250][1195]2 CONDENSER COIL

LIQUID Øx3Nos.

CONTROL PANELCOMPRESSOR

34

2 1 PARTITION3

47

1 1/8 [29]1 1/8 [29]

LEGEND

CONDENSER FAN1

1 1/8 [29] 1 1/8 [29] A2

1 1/8 [29]

1 1/8 [29]

[29]1 1/8

1 1/8 [29]

1 1/8 [29]

1 1/8 [29]

88.6[3445]135.6

A4 A6

DETACHABLEPLATE FOR

A1

10[254]

7/8 [22]

LIQ.#2

[22]7/8

LIQ.#3A3

10

A5[254]

CIRCUIT-CCIRCUIT-BCIRCUIT-A

4.92

[125

]

105.

92[2

690]

95.2

9[2

420]

29.5

[750

]

106.

92[2

715]

95.2

9[2

420]

29.5

[750

]

5.92

[150

]

CIRCUIT-D

CIRCUIT-ACIRCUIT-BCIRCUIT-C

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

1 1/8[29]

LIQ.#1

2 5/8 [67]

2 5/8 [67]

2 5/8

2 5/8 [67]

[67]

2 5/8

2 5/8 [67]

[67]

SUC.#2

2 1/8 [54]

2 5/8 [67]

[67]2 5/8

[67]

[67]

[67]

[67]

2 5/8

2 5/8

2 5/8

2 5/8

SUC.#3

[54]2 1/8

CIRCUIT-1 CIRCUIT-2 CIRCUIT-3

20[508]

Table 13

Dimensional Data ACUV Models- 54095D to 54120D & 64113 to 64140D

Table 14

SKM Air Cooled Condensing UnitsACUV Series - R134a

28

A1 A2 A3 A4 A5 A6 A7 A8Ib. 739 972 1148 983 892 1145 - - 5878Kg. 335 441 520 446 404 519 - - 2666Ib. 749 995 1179 1000 894 1148 - - 5965Kg. 340 451 535 454 406 521 - - 2705Ib. 782 1093 1189 1031 894 1148 - - 6136Kg. 355 496 539 467 406 521 - - 2783Ib. 816 1128 1361 1135 963 1284 - - 6687Kg. 370 511 617 515 437 582 - - 3033Ib. 817 1129 1361 1136 963 1284 - - 6691Kg. 371 512 617 515 437 582 - - 3035Ib. 817 1128 1363 1136 964 1286 - - 6695Kg. 371 512 618 515 437 583 - - 3036Ib. 1132 855 841 1033 1132 855 982 1174 8004Kg. 514 388 381 469 514 388 445 532 3630Ib. 1175 912 911 1174 1175 912 1052 1315 8625Kg. 533 414 413 532 533 414 477 596 3912Ib. 1176 913 912 1174 1176 913 1053 1315 8633Kg. 534 414 414 532 534 414 477 596 3915Ib. 1177 914 913 1176 1177 914 1054 1317 8640Kg. 534 414 414 533 534 414 478 597 3919

53080-D

53084-D

TOTALWEIGHTUNIT

53068-D

53070-D

53064-D

ACUV-LOADING POINTS

53086-D

54095-D

54106-D

54114-D

54120-D

A1 A2 A3 A4 A5 A6 A7 A8Ib. 753 985 1161 996 905 1158 - - 5959Kg. 341 447 527 452 410 525 - - 2702Ib. 761 1007 1191 1013 907 1160 - - 6038Kg. 345 457 540 459 411 526 - - 2738Ib. 794 1105 1201 1043 907 1160 - - 6210Kg. 360 501 545 473 411 526 - - 2816Ib. 829 1140 1373 1147 975 1296 - - 6761Kg. 376 517 623 520 442 588 - - 3066Ib. 829 1140 1373 1148 976 1298 - - 6763Kg. 376 517 623 520 443 589 - - 3067Ib. 829 1140 1375 1148 976 1298 - - 6765Kg. 376 517 624 521 443 589 - - 3068Ib. 1145 867 854 1046 1145 867 995 1187 8103Kg. 519 393 387 474 519 393 451 538 3675Ib. 1187 924 923 1186 1187 924 1064 1327 8722Kg. 538 419 419 538 538 419 483 602 3956Ib. 1187 924 924 1187 1187 924 1065 1328 8727Kg. 538 419 419 538 538 419 483 602 3958Ib. 1188 925 925 1187 1188 925 1065 1328 8731Kg. 539 419 419 538 539 419 483 602 3960

TOTALWEIGHT

63082-D

ACUV- UNIT

63094-D

LOADING POINTS

64140-D

63100-D

64113-D

64124-D

64132-D

63098-D

63074-D

63078-D

LOADING POINTS - 50Hz

LOADING POINTS - 60HzTable 13 ends

Table 14 ends

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

29

Location and Space RequirementsDue to the vertical air flow discharge condenser design, it is recommended that certain precautions are to be taken before installation. There should be no obstruction on the air flow.

Orient the unit so that prevailing winds blow parallel to the unit length thus minimizing the effects on condensing pressure. If it is not practical to orient the unit in this manner, a wind deflecting shield should be considered.

It is also necessary to provide adequate clearance on all sides of the unit for service access and satisfactory performance. This will prevent excessive condensing temperatures and enhance system performance and operating economy.

A flat concrete foundation or floor which can support the weight of the equipment must be provided as the unit must be level for proper operation and functioning of controls.

Under certain critical conditions it is recommended that vibration isolators of rubber-in-shear or spring type be installed under the base.

The isolators must be designed for the operating weight of the unit. For operating load points refer to Loading Points Data (page 27 & 28). Correct selection of types of isolators depends upon application and structure.

A B C51008-D 61009-D51010-D 61011-D51014-D 61016-D52015-D 62018-D52017-D 62020-D52019-D 62022-D51021-D 61024-D51022-D 61026-D52022-D 62026-D51028-D 61032-D52028-D 62032-D52030-D 62034-D51030-D 61036-D52034-D 62040-D52040-D 62046-D52045-D 62052-D52049-D 62058-D52053-D 62062-D52058-D 62067-D52060-D 62071-D53064-D 63074-D53068-D 63078-D53070-D 63082-D53080-D 63094-D53084-D 63098-D53086-D 63100-D54095-D 64113-D54106-D 64124-D54114-D 64132-D54120-D 64140-D

ACUV

40

90

48

64

72

72

56

66

78

4684

60

96

108

42

50

Single Unit Installation

Table 15

A

SPACING FOR AIRFLOW & SERVICE*

B

A*

SPACING FOR SERVICE AND ACCESSSPACING FOR AIR FLOW

B

A

A*

B

ACUV-53064D to 54120DACUV-63074D to 64140D

ACUV-51008D to 52060DACUV-61009D to 62071D

ALL DIMENSIONS ARE IN INCHES [mm]

SKM Air Cooled Condensing UnitsACUV Series - R134a

30

Multiple Units Installation

A

* A

* C

SPACING FOR AIR FLOW

B

SPACING FOR SERVICE AND ACCESS

B * A

SPACING FOR AIRFLOW & SERVICE*

A

C

B

ACUV-51008D to 52060DACUV-61009D to 62071D

ACUV-53064D to 54120DACUV-63074D to 64140D

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

31

Typical Refrigeration PipingLegend

1. Expansion Valve2. Sight Glass3. Solenoid Valve4. Filter Drier5. Shut Off Valve6. Liquid Line7. Suction Line

Single Circuit Unit Shown. For unit with multiple circuits, piping will be identical.

Refrigerant Piping

Correct design and size of refrigerant piping is necessary for proper operation. The refrigerant piping generally should be designed to accomplish the following:

a. To ensure proper refrigerant feed to the evaporator

b. To provide practical refrigerant line sizes without excessive pressure drop

c. To maintain uniform return of lubricating oil to the compressor

d. To prevent liquid refrigerant from entering the compressor and causing compressor damage due to "slugging"

Field Expansion Valve Selection

The following recommendations should be taken into consideration when selecting expansion valves in field.

1. Expansion valves should be installed as close to the evaporator as possible, mounted directly to the distributor.

2. The following possible sources of pressure drop to be considered:

a. Friction losses through refrigerant lines

b. Pressure drop across valves and controls

c. Pressure drop due to vertical lift of liquid line for R-134a 1°F (0.55°C) sub cooling must be allowed for each 5.5 ft (1.7m) vertical rise in order to avoid flash gas forming due to the weight of the column of liquid refrigerant.

SKM ACUV Series units are designed with a sub cooling circuit enough to sub cool the liquid 12°F (6.6 °C), which gives the liquid maximum 66 ft. (20m) lift without additional sub cooling. Liquid suction heat exchanger can be used for additional sub cooling in order to avoid flash gas forming.

Matching DX Coil Selection

For single circuit ACUV Series, the DX coil selection in a MAH or other air handler from SKM should be based on total capacity. For multiple circuit ACUV Series, extra care should be exercised and correspondingly split, by face area or number of rows to correspond and match the capacity split available in the multiple circuited ACUV Series selected. For optimum matching the DX coil should be ordered from SKM as well.

SKM provides correct no. of feeds and circuits and properly sized distribution to ensure the correct split on the DX coil is made available to match the particular selected ACUV Series model.

1

7

4

5

6

2

3

AHU

DOUBLE SUCTION RISERDOTTED IN CASE OF

AIRFLOW

UNITCONDENSING

1 EXPANSION VALVE

7 SUCTION LINE6 LIQUID LINE5 SHUT OFF VALVE4 FILTER DRIER3 SOLENOID VALVE2 SIGHT GLASS

7

L E G E N D

CONDENSINGUNIT

6

54

3

2

1

AHU

FLOWAIR

SKM Air Cooled Condensing UnitsACUV Series - R134a

32

Recommended Refrigerant Line Sizes - 50 Hz

SKM ACUV Series Condensing Units are designed for satisfactory operation with single suction line.

1. Suction Line sizing selection recommendation in Table 16 & 17 is based on 2ºF temperature drop.

2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure proper oil flow up and return to compressor.

3. Liquid line sizing selection recommendation in Table 16 & 17 is based on 2ºF temperature drop.

4. Recommended line sizes in Table 16 & 17 are for guidance only. For detailed proper piping, consult recognized piping references like ASHRAE Guide and Data Book for assistance.

5. Equivalent suction and liquid line lengths are shown in Table 16 & 17.

SKM is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do not incorporate necessary slopes, etc. that may be required on horizontal risers, etc.

25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft51008-D 1/2 5/8 5/8 5/8 - - - - - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - - - - - -51010-D 5/8 5/8 7/8 7/8 - - - - - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - - - - - -51014-D 5/8 7/8 7/8 7/8 - - - - - - - - - - - - 1 3/8 1 5/8 2 1/8 2 1/8 - - - - - - - - - - - -52015-D 1/2 5/8 5/8 5/8 1/2 5/8 5/8 5/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -52017-D 5/8 5/8 7/8 7/8 1/2 5/8 5/8 5/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -52019-D 5/8 5/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -51021-D 7/8 7/8 7/8 7/8 - - - - - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - - - - - -51022-D 7/8 7/8 7/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - - - - - -52022-D 5/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -51028-D 7/8 7/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - - - - - -52028-D 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 2 1/8 2 1/8 1 3/8 2 1/8 2 1/8 2 1/8 - - - - - - - -52030-D 7/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -51030-D 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - - - - - -52034-D 7/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 2 1/8 2 1/8 2 1/8 - - - - - - - -52040-D 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -52045-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -52049-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -52053-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -52058-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -52060-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -53064-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - -53068-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -53070-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -53080-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -53084-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -53086-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -54095-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/854106-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/854114-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/854120-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8

Suction Line, InchesLiquid Line, InchesCircuit 1 Circuit 3 Circuit 4Circuit 1 Circuit 2Circuit 3 Circuit 4Model

ACUV Circuit 2

Table 16

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

33

Table 17

Recommended Refrigerant Line Sizes - 60 Hz

SKM ACUV Series Condensing Units are designed for satisfactory operation with single suction line.

1. Suction Line sizing selection recommendation in Table 16 & 17 is based on 2ºF temperature drop.

2. Double suction risers, for applications with systems having large variations in capacity , are recommended to ensure proper oil flow up and return to compressor.

3. Liquid line sizing selection recommendation in Table 16 & 17 is based on 2ºF temperature drop.

4. Recommended line sizes in Table 16 & 17 are for guidance only. For detailed proper piping, consult recognized piping references like ASHRAE Guide and Data Book for assistance.

5. Equivalent suction and liquid line lengths are shown in Table 16 & 17.

SKM is not responsible for faulty or improper design or sizing of refrigerant lines. The above recommendations do not incorporate necessary slopes, etc. that may be required on horizontal risers, etc.

25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft 25ft 50ft 75ft 100ft61009-D 1/2 5/8 5/8 7/8 - - - - - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 - - - - - - - - - - - -61011-D 5/8 5/8 7/8 7/8 - - - - - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - - - - - -61016-D 5/8 7/8 7/8 7/8 - - - - - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - - - - - -62018-D 1/2 5/8 5/8 7/8 1/2 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 3/8 1 5/8 1 5/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -62020-D 5/8 5/8 7/8 7/8 1/2 5/8 5/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8 1 5/8 - - - - - - - -61022-D 5/8 5/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 3/8 1 5/8 1 5/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -61024-D 7/8 7/8 7/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - - - - - -61026-D 7/8 7/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 - - - - - - - - - - - -62026-D 5/8 7/8 7/8 7/8 5/8 5/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -61032-D 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - - - - - -62032-D 5/8 7/8 7/8 7/8 5/8 7/8 7/8 7/8 - - - - - - - - 1 5/8 2 1/8 2 1/8 2 1/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -62034-D 7/8 7/8 7/8 1 1/8 5/8 5/8 7/8 7/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 1 3/8 1 5/8 1 5/8 2 1/8 - - - - - - - -61036-D 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - - - - - -62040-D 7/8 7/8 7/8 1 1/8 5/8 7/8 7/8 7/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 1 5/8 2 1/8 2 1/8 2 1/8 - - - - - - - -62045-D 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - - - - - -62052-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -62058-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -62062-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -62067-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -62071-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - - - - - -63074-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 7/8 1 1/8 7/8 7/8 7/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 1/8 2 1/8 2 5/8 - - - -63078-D 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -63082-D 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 - - - -63094-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -63098-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -63100-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 - - - - 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 - - - -64113-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 7/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/8 2 1/8 2 1/8 2 5/8 2 5/864124-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/864132-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/864140-D 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 7/8 1 1/8 1 1/8 1 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8 2 1/8 2 5/8 2 5/8 2 5/8

Circuit 4Suction Line, Inches

Circuit 1 Circuit 2 Circuit 3Circuit 3 Circuit 4ModelACUV Circuit 1 Circuit 2

Liquid Line, Inches

SKM Air Cooled Condensing UnitsACUV Series - R134a

34

GENERAL FEATURES

Condensing units shall be composed of compressor(s), fan(s), Coil(s), refrigerant piping, electrical components & enclosing cabinet in one piece.

Unit shall be factory assembled, internally wired, piping connections terminated with sealed and soldered copper pipe ends. Unit shall be shipped with nitrogen holding charge (actual charging with refrigerant R-134a should be done at site). Unit shall be capable to operate from 50°F (10°C) to 125°F (52°C) ambient temperature and shall be rated in accordance with AHRI-365 standard.

COIL(S)

Coil shall be air cooled with integral sub-cooling circuit, constructed of seamless copper tubes 3/8" OD mechanically bonded to wavy Aluminium (Copper) fins with maximum 14 FPI (1.8mm) spacing. Coil shall be tested against leakage by pressurizing air at 450 psig (3100 kPa) in coil, under water, cleaned and dehydrated at the factory.

COMPRESSOR(S)

Compressor shall be of high energy efficiency ratio, fully accessible, semi hermetic reciprocating type equipped with crankcase heater, oil pump, refrigerant gas cooled electric motor, preset internal relief valve, inherent thermistor motor protection, suction and discharge service valves, oil sight glass and shall be mounted on spring anti vibration mounts to minimize vibration transmissions. Compressors shall conform to DIN standards.

CONDENSER FAN(S) & MOTOR(S)

The machine shall be furnished with direct driven propeller type discharging air upward condenser fans. Fans shall be constructed of corrosion resistant blades such as heavy gauge aluminum. The fan and drive shall be held in proper alignment. Fan assemblies shall be provided with heavy gauge, rust resistant steel wire fan guard. All condenser fans shall be individually, statically, and dynamically balanced for vibration free operation.

Motors shall be Totally Enclosed Air Over (TEAO), 6 poles, with class ‘F’ insulation, minimum IP-55 protection and factory wired to unit control panel.

REFRIGERANT PIPING

The refrigerant circuit piping shall be fabricated from ACR grade copper piping, with 1, 2, 3, or 4 refrigeration circuits.The piping connections shall be terminated with sealed & soldered copper pipe ends,which give much simplicity & ease to the installation.

CASING

Unit casing shall be made of zinc coated galvanized steel sheets conforming to JIS-G3302 and ASTM A653 which shall be phosphatized and then electrostatically dry powder coated of approx.60 microns to provide an extremely tough, scratch resistance, excellent anti-corrosive protection that can pass 1000 hrs in 5% salt spray testing at 95°F (35°C) and 95% relative humidity as per ASTM B117.

Unit casing shall be provided with access panels for easy service and maintenance of all units parts.

CONTROL PANEL

The unit mounted control panel enclosure shall be fabricated out of heavy gauge sheet steel in phosphatized powder coated baked finish. The enclosure shall conform to IP54 as per guidelines in IEC 529. A hinged access door and key-fastener shall be provided for easy access and security. The panel shall be factory wired in accordance with NEC 430 & 440, labeled, tagged and features 220V / 240V controls and shall include the following as minimum.

• All compressors shall be with DOL/part winding starting• Individual compressor and condenser fan motor contactors• Motor protector circuit breaker for condenser fan motors• Control circuit breaker• Unit on/off switch• Microprocessor control boards• Control Relays• Power and control terminal blocks

GUIDE SPECIFICATIONS

SKM Air Cooled Condensing UnitsACUV Series - R134a

SKM Air Cooled Condensing UnitsACUV Series - R134a

35

MICROPROCESSOR CONTROLLER

Condensing units shall be equipped with a full function microprocessor based controller as a standard feature. The controller shall be factory programmed for the control of AHU fan motor, compressors and condenser fans. The controller shall come with a built in keypad and display for simple but meaningful man machine interface. This controller shall provide complete operational control for the unit and shall have built-in auto diagnostic capability that can signal normal operation or alarm conditions as well as shutting down the unit or system if necessary.

The controller shall come with a loose supplied sleek and elegant design room unit for installing in the conditioned space. Communication between unit controller and room unit shall be through two wire interface. The communication cable shall be 2 core, twisted pair, unscreened with stranded conductors. Maximum distance between room unit and controller shall be 700 meters. The room unit shall have a built in sensor for measuring the room temperature. It shall transmit room temperature, set point, unit operating mode, operating schedule etc. to the unit controller. Control of the compressors shall be based on room temperature and the set point, as standard. Control based on duct temperature shall be available if required.

The Main Features of the controller shall be as follows:

• Built in LCD display with back light• Built in keypad• Battery backed up built in real time clock• Multiple authorization level to provide tight security for the control system• Capacity control based on room temperature or return air temperature• Alarm history• A sleek & elegant design room unit.

DISPLAY INFORMATION

Condensing units shall offer an LCD display which will allow the operator to access different parameters of the unit. Operator shall be able to view and change the unit parameters. The display information shall include:

• Status• Outputs• Inputs• Alarms• Set points• Password The intelligent microprocessor based controller shall monitor all the safeties related to the unit and makes the necessary protections, by shutting down the entire unit or the effected circuit. The protections shall include:

• Low suction pressure• High discharge pressure• Low oil pressure• High compressor motor temperature• Compressor short cycling

Volt free contacts for run status, common fault status, auto mode status and provision for remote on/off shall be available as option.

In addition, the unit microprocessor shall be able to support the major BMS protocols such as BACnet, Modbus & LON as option.

GUIDE SPECIFICATIONS

You name it.....We cool itYou name it.....We cool it48

SKM Air Cooled Packaged ChillersAPCN-S Series - R134a

visit us at www.skm.ae

UAEAbu Dhabi P.O Box: 27788Abu Dhabi, United Arab EmiratesTel: +971 2 6445223Fax: +971 2 6445145Email: [email protected] Ain Al Ain, United Arab EmiratesTel: +971 3 7619921Fax: +971 3 7619941Email: [email protected] P.O Box: 98822Dubai, United Arab EmiratesTel: +971 4 2940900Fax: +971 4 2940029Email: [email protected]

KuwaitP.O Box: 1215-PC 15463Dasman, KuwaitTel: +965 2 2492200Fax: +965 2 2494400Email: [email protected]

Saudi [email protected]

Al KhobarFawaz Ref. & Air Conditioning Co.P.O Box: 1189Al Khobar, Saudi ArabiaTel: +966 3 8598666Fax: +966 3 8598520Email: [email protected]

JeddahFawaz Ref. & Air Conditioning Co.P.O Box: 13218Jeddah, Saudi ArabiaTel: +966 2 6691848Fax: +966 2 6608316Email: [email protected]

RiyadhFawaz Ref. & Air Conditioning Co.P.O Box: 85123Riyadh, Saudi ArabiaTel: +966 1 4794499Fax: +966 1 4785354Email: [email protected]

JordanIdeal A/C Systems Co. L.L.CAl Gardenz Street, Building 111,Al Bakri ComplexP.O Box 5502 Amman, Jordan 11953Tel: +962 6 5538640Fax: +962 6 5538641Email: [email protected]

Spare Parts DivisionSharjah, United Arab Emirates Tel: +971 6 5347347Fax: +971 6 5349292 Email: [email protected]

P.O Box: 6004Sharjah, United Arab EmiratesTel: +971 6 5347347Fax: +971 6 5349292 Email: [email protected]

Service CentreSharjah, United Arab Emirates Tel: +971 6 5347347Fax: +971 6 5349292 Email: [email protected]

Saudi Arabia AL Messila HVAC Equipment Factory (Part of SKM A/C factory in Saudi Arabia)Saudi Arabia, Eastern provenanceAD Dammam2nd industrial city Abqiq main road Hail StreetTel: +966 3 8123332 / 4 / 5Fax: +966 3 8123337 / +966 3 8123092

Egypt9 Mosadak Street,3rd floor, Dokki, Giza, EgyptTel: +20 2 37619617 / +20 2 37621974Fax: +20 2 37621973Email: [email protected]

AlgeriaAissat Idir ( EX-ENMA) CityBldg1, Flat 2, Dar El Beida Algiers,AlgeriaTel: +213 21 508197Fax: +213 21 508197Email: [email protected]

QatarMannai Trading Co. WLLP.O Box: 76Doha, QatarTel: +974 4 4558787 / +974 4 4558788Fax: +974 4 4558781Email: [email protected] [email protected]

IraqAl Rawbitt Al Iraqia Co. Erbil – Bagdad – BasraTel: +964 7507441111 +964 7711117776 +965 99608916Email: [email protected]

IranHivasanat 4th Floor, Building. No. 74,5th Golestan Ave.Abazar Blvd Ayatollah Kashani Exp.,TehranTel: +98 21 44951422 / 23Fax: +98 21 44952135Email: [email protected]

Kuwait (for Unitary Products Only)British Link Kuwait (BLK)P.O Box: 53054 Al NuzhaTel: +965 1820099Fax: +965 22465005Email: [email protected]

HEAD OFFICE

REGIONAL OFFICES

DISTRIBUTORS

095/2013 Supersedes # 095/2012