Products that perform...By people who care AFHX Series (High Ambient) Air Cooled Screw Flooded Chillers R 22 50Hz Cooling Capacity: 97 to 637 Tons (341 to 2240 kW)

Upload: buidieu

Post on 16-Apr-2018

255 views

Category:

Documents


8 download

TRANSCRIPT

Page 1: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

Products that perform...By people who care

AFHX Series (High Ambient)Air Cooled Screw Flooded Chillers

R134a R22R407c 50Hz60Hz

Cooling Capacity: 97 to 637 Tons (341 to 2240 kW)

R2260Hz R407c

50Hz

97 to 637 Tons

(341 to 2240 kW)

AFHX Series (High Ambient)Air Cooled Rotary Screw Flooded Chillers

R22

Page 2: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 2 -

TABLE OF CONTENT DESCRIPTION PAGE NO Nomenclature .............................................................................................................................................. 2 Advantages of Flooded Chiller..................................................................................................................... 3 Unit Features ............................................................................................................................................... 5 Operating Benefits ....................................................................................................................................... 8 Typical Sequence of Operation ................................................................................................................... 9 Application Data .......................................................................................................................................... 10

Physical Specifications ............................................................................................................................... 11 Performance Data ....................................................................................................................................... 15 Dimensional Data ....................................................................................................................................... 17 Floor Loading Diagram ............................................................................................................................... 21

Dimensional Clearance ............................................................................................................................... 24

Condenser Fan ........................................................................................................................................... 25 Sound Pressure Level At 10 M – Free Field ............................................................................................... 26

Pressure Drop ............................................................................................................................................. 26

Electrical Data ............................................................................................................................................. 27

Typical Wiring Schematic ........................................................................................................................... 28

NOMENCLATURE

A F HX 110 T - 5 S R - HR

Air Cooled Chiller

Flooded Evaporator

Nominal Tons Single Compressor= 100, 125, 145,

170, 190, 245, 265

Two Compressors= 100T, 115T, 135T, 155T, 175T, 195T, 230, 255, 305, 330, 355, 390, 450, 515, 550

Three Compressors= 585, 640

HR = Heat Recovery LN = Low Noise

5 = 50Hz 6 = 60Hz

H = High Ambient S = Standard C = Compact Q = Special

Horizontal Screw Compressor

T = Optional Two Compressors Blank = Standard

Blank = R22 R = R134a

Page 3: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 3 -

ADVANTAGES OF FLOODED CHILLER In a flooded evaporator the refrigerant surrounds the tubes in the shell and the water to be cooled flows through the tubes. The level of liquid refrigerant in the shell is maintained by the combined action of an electronic level controller and a mod-motor actuated ball valve which modulates the subcooled liquid refrigerant into the evaporator. This ensures that all the evaporator tubes are completely immersed in the liquid refrigerant for better heat transfer efficiency. For a Direct Expansion (DX) evaporator the refrigerant is expanded into the tubes while the chilled water is circulated through the shell. Thermostatic expansion valve is used to throttle the refrigerant in maintaining constant superheat of suction gas to the compressor. The following are the advantages of using flooded chiller:

1. Higher Capacity and Higher EER Achievable with the Same Compressor The flooded evaporator with all the copper tubes immersed in the “boiling” liquid refrigerant enables a small approach temperature between the “boiling” liquid refrigerant temperature in the shell and the outlet chilled water temperature in the evaporator tubes to be achieved. This approach temperature or temperature difference between the evaporating temperature of the boiling liquid refrigerant and the chilled water outlet temperature, for a flooded evaporator, is typically less than 3°F. On the contrary, for a DX or Direct Expansion Evaporator, the typical approach temperature is between 8°F to 10°F. This simply means that the same compressor in a flooded evaporator system will operate at a higher saturated evaporating temperature when compared to the same compressor in a DX-Evaporator system, when outlet chilled water temperatures in both cases are set at the same temperature. Figure 1 shows the typical screw compressor capacity performance curve at a particular condensing temperature over saturated evaporating temperature of between 30°F to 50°F, and the typical power

input curve over the same conditions. It can be noted that the same compressor when operating with a flooded evaporator will generate approximately 8% more cooling capacity while kw input increases negligibly by about 1.8%. Therefore, the same compressor when coupled to a flooded evaporator will typically achieved higher cooling capacity performance with correspondingly higher Energy Efficiency Ratio (EER) i.e. (Btu/watt) or lower kw/Ton.

FIGURE 1

A DX evaporator uses TXV throttling to maintain about 10 to 15°F suction superheat to prevent liquid flood back to the compressor. In a flooded evaporator, the refrigerant boils off in the shell and gas can be sucked out from the top of evaporator back to compressor. The suction superheat is usually about 2 to 3°F. Reduction in suction superheat will further increase the capacity performance of the compressor.

Page 4: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 4 -

ADVANTAGES OF FLOODED CHILLER

DX evaporators are typically designed with higher tube velocities to ensure proper oil return to compressor both at full load and at reduced load. This will contribute to higher refrigerant pressure drop through the evaporator. On the contrary, there is very little shell side pressure losses for a flooded evaporator. Therefore, lower suction pressure drop in the flooded design will impose less capacity penalty on the compressor and this will further enable the compressor in a flooded evaporator to generate more capacity than one with a DX Evaporator.

2. Better Part Load Performance

The Dunham-Bush Air Cooled Flooded Chiller with its sophisticated advanced controller and patented oil management system has all evaporator tubes completely immersed in the “boiling” liquid refrigerant to achieve superior heat transfer efficiency while ensuring adequate oil return to the compressor(s). This ensures superior full-load efficiency and even better part-load efficiency as the full heat transfer surface areas of the evaporator tubes are utilized even at part-load conditions. On the contrary, in the Direct Expansion Evaporator, because of the need to maintain adequate refrigerant gas velocities in the evaporator tubes for proper oil return, it is typical for certain bundle of evaporator tubes to be “blocked” or “baffled off” at part-load conditions. Thus not utilizing the full heat transfer surface areas of the evaporator tubes and therefore have a lower efficiency when compared with a flooded evaporator chiller at part-load conditions.

3. Excellent Capacity Modulation in

Response to Building Loads Dunham-Bush utilizes its state-of-the-art advanced controller in combination with the electronic level controller and mod-motor actuated ball valve to ensure instantaneous and precise feeding of liquid refrigerant to the flooded evaporator

in response to changes in building demand; and maintains precise (±1/2°F) preset outlet chilled water temperatures even at very low load conditions; whereas most of Dunham-Bush’s competitors, in screw chillers, still utilizes the conventional “centrifugal chiller” method of using orifice plates to modulate refrigerant feed to the evaporator; and as such their machines do not function efficiently at low-load conditions and can encounter oil return problem!

4. Cleanable Evaporator

For a single pass evaporator, the end plates at both ends of the water boxes (2 pass only at return end) can be removed easily without dismantling the chilled water piping connections, for inspection and for mechanical tubes cleaning with brushes or auto-brush. This will enable low tube fouling factor in the evaporator to be ensured, thus maintaining system efficiency.

5. Lower Water Side Pressure Drop

In a DX evaporator, the water flows transversely over the outside of the tubes. The water flow is guided with vertical baffles. This will have a higher-pressure drop as compared with the water flow in the tubes of a flooded evaporator. In other words, the equivalent flooded chiller will require smaller water pump to operate at lower power consumption.

6. Commonly Used In Large Tonnage

Chillers Where Efficiency Is Critical As a general rule, DX-evaporator are typically used in small and medium tonnage chillers where efficiency is not important and the low initial cost is the main consideration! However, with increasing energy cost and the drive to reduce global warming, flooded evaporator chillers will increasingly become more popular not only in the large tonnage but also in the small and medium tonnage chillers. Dunham-Bush, again, leads the industry in this respect!

Page 5: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 5 -

UNIT FEATURES ADVANCE CONTROLLER Vision2020i a flexible and advance programmable electronic controller designed specifically for the applications and precise control of Dunham-Bush Rotary Screw compressor chillers.

The controller board is provided with a set of terminals that connected to various devices such as temperature sensors, pressure and current transducers, solenoid valves, compressors and fans contactors, control relays and etc. Three sizes of controller boards are provided to handle different number of input and output requirements: DB3-S small board, DB3-M medium board and DB3-L large board.

The unit algorithm program and operating parameters are stored in FLASH-MEMORY that does not require a back-up battery. The program can be loaded through PC or programming key.

Vision2020i controller is equipped with a user friendly terminal with a semi-graphic display and dedicated keys that provides easy access to the unit operating conditions, control set points and alarm history.

Each unit’s controller can be configured and connected to the local DBLAN network that allows multiple units sequencing control without additional hardware. The DBLAN is local area network made up of several chillers’ controller. Display and User Terminal Vision2020i controller is design to work with a user friendly back-lit 132 by 64 pixels DBG1 Semi-Graphic Display panel connected with

controller through telephone cable. The terminal allows carrying out all program operations. The user terminal allows displaying the unit working conditions, compressor run times, alarm history and modifying the parameters. The display also has an automatically self-test of the controller on system start-up. Multiple messages will be displayed by automatically scrolling from each message to the next. All of these messages are spelled out in English language on the display terminal.

There are 15 dedicated buttons enable user to access information, base on the security level of the password. For more detail operation of the DBG1 Display Terminal, please refer to the Unit Operation Manual. Easily accessible measurements include: Leaving chilled water temperature

Entering chilled water temperature Compressor discharge temperature Leaving chiller water temperature derivative Evaporator Pressure Condenser Pressure Compressor amp draw of each compressor Compressor elapsed run time of each

compressor Compressor starts status Oil level sensor status Water temperature reset value Water flow switch status External start/stop command status

Optional ambient temperature is available. With this option the operator can quickly and accurately read all significant water temperatures and eliminate the need for often-inaccurate thermometers. Voltage is also offered as an optional feature. Capacity Control Leaving chilled water temperature control is accomplished by entering the water temperature setpoint and placing the controller in automatic control. The unit will monitor all control functions and move the slide valve to the required operating position. The compressor ramp (loading) cycle is programmable and may be set for specific building requirements. Remote adjustment of the leaving chilled water setpoint is accomplished through either direct connection of other Dunham-Bush control packages to the

Page 6: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 6 -

UNIT FEATURES controller through either the RS485 long distance differential communications port, via terminal or modem connected to the RS232 communication port, or from an external Building Automation System supplying a simple 4 to 20mA signal. Remote reset of compressor current limit may be accomplished in a similar fashion.

System Control The unit may be started or stopped manually, or through the use of an external signal from a Building Automation System. In addition, the controller may be programmed with seven-day operating cycle or other Dunham-Bush control packages may start and stop the system through inter-connecting wiring.

System Protection The following system protection controls will automatically act to insure system reliability:

Low suction pressure High discharge pressure Freeze protection Low differential pressure Low oil level Compressor run error Power loss Chilled water flow loss Sensor error Compressor over current Compressor Anti-recycle

The controller can retains up to 99 alarm conditions complete with time of failure together data stamping on critical sensor readings in an alarm history. This tool will aid service technicians in troubleshooting tasks enabling downtime and nuisance trip-outs to be minimized.

Remote Monitoring Vision 2020i controller can be completed with an optional RS485 communications card and NETVISOR software for remote monitoring and controlled from a PC terminal and optional phone modem.

With various optional add-on cards the Vision2020i controller can also be interfaced directly to the Building Management System (BMS) with the standard communication protocols using MODBUS, LONWORKS, BACNET MSTP as well as over IP.

This sophisticated feature makes servicing easier and more convenient to the system. The controller as standard is additionally equipped with history files which may be used to take logs which may be retrieved via the phone modem or internet connection periodically. Now owners of multiple buildings have a simple and inexpensive method of investigating potential problems quickly and in a highly cost effective manner.

Refrigerating Cycle The refrigerant management system, is very similar to centrifugal water chillers and is shown in the refrigerant cycle diagram below.

Liquid refrigerant enters the flooded evaporator uniformly where it absorbs heat from water flowing through the evaporator tubes. The vaporized refrigerant is then drawn into the suction port of the compressor where the compression begins.

This partially compressed gas is then joined by additional gas from the flash economizer as the rotors rotate past the vapor injection port at an intermediate pressure. Compressed gaseous refrigerant is then discharged into the integral oil separator where oil, which is contained in the refrigerant vapor, is removed and returned to the oil sump.

Fully compressed and superheated refrigerant is then discharged into the condenser, where air is being drawn through the condenser tube by the propeller fan cools and condenses the refrigerant. Liquid refrigerant then passes through the first expansion device and into the flash economizer where flash gas and liquid refrigerant are separated.

The gaseous refrigerant is then drawn out of the flash economizer and into the vapor injection port of the compressor. The remaining

Page 7: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 7 -

UNIT FEATURES liquid refrigerant then passes through a second expansion device which reduces refrigerant pressure to evaporator levels where it is then distributed evenly into the evaporator.

By removing the flash gas from the flash economizer at an intermediate pressure, the enthalpy of the refrigerant flowing into the evaporator is reduced. This increases the refrigeration effect and improves the efficiency of the refrigeration cycle.

Refrigerant flow into and out of the flash economizer is controlled by modulating valves which eliminate the energy wasting hot gas bypass effect inherent with fixed orifices. Part-Load Performance Through the use of flash economizer modulating flow control and multiple compressors, Dunham-Bush air cooled chillers have best part-load performance characteristics

in the industry when measured in accordance with ARI Standard 550/590-2003.

In most cases, actual building system loads are significantly less than full load design conditions, therefore chillers operate at part load most of the time.

Dunham-Bush air cooled chillers combine the efficient operation of multiple compressors with an economizer cycle and advanced controller to yield the best total energy efficiency and significant operating saving under any load.

When specifying air conditioning equipment, it is important to consider the system load characteristics for the building application. In a typical city, the air conditioning load will vary according to changes in the ambient temperature. Weather data compiled over many years will predict the number of hours that equipment will operate at various load percentages.

Page 8: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 8 -

OPERATING BENEFITS EFFICIENCY AND RELIABILITY

ENERGY EFFICIENCY

Designed to provide the greatest amount of cooling for the least kilowatt input over the entire operating range of your building.

Delivers outstanding efficiency and total energy savings through the utilization of economizer cycle and advanced controller staging producing greater capacity with fewer compressors.

Maximized performance through computer-matched components and multiple compressors on a single refrigerant circuit.

High efficiency oil recovery system guarantees removal of oil carried over in the refrigerant and maintains the heat exchangers at their maximum efficiency at both full and part load.

INSTALLATION EASE

Dramatic payback in reduced maintenance and overhaul costs both in down time and in labor expenditures.

Ease of troubleshooting through controller retention of monitored functions.

Factory run tested.

SAFETY CODE

ASME Boiler and Pressure Vessel Code, Section VIII Division 1 "Unfired Pressure Vessels".

JKKP Code.

ASME Standard B31.5 Refrigeration Piping.

ASHRAE Standard 15 Safety Code for Mechanical Refrigeration.

IEEE.

REFRIGERANT COMPATIBILITY

Designed to operate with environmentally safe and economically smart HCFC-22 with proven efficiency and reliability.

Consult Factory for use of other HFC refrigerants.

CONTROL FLEXIBILITY

Controller-based with DDC (direct digital control) features precise push button control over every aspect of operation with built-in standard features that allow extra energy savings on start-up and throughout the life of your equipment.

Insured uniform compressor loading and optimal energy efficiency through controller to controls which utilize pressure transducers to measure evaporator and condenser pressure.

Lower energy costs resulting from automatic load monitoring and increased accuracy and efficiency in compressor staging.

Monitor your chiller's key functions from a remote location with a simple, low cost, phone modem option.

Proactive control by controller that anticipates problems and takes corrective action before they occur. Controls will unload compressor(s) if head or suction pressure approach limits. This will enable unit to stay on the line while warning operator of potential problems.

Page 9: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 9 -

TYPICAL SEQUENCE OF OPERATION The Dunham-Bush air cooled water chiller depends mainly on its on-board controller for control. Operation described is for a two-compressor units and is very similar for single, four-compressor units.

For initial start-up, the following conditions must be met:

Power supply to unit energized. Unit circuit breakers in the "on" position. Control power switch on for at least 15 minutes. Compressor switches on. Reset pressed on controller keypad. Chilled water pump running and chilled water flow switch made. Leaving chilled water temperature at least 2°F above setpoint. All safety conditions satisfied.

After all above conditions are met, the controller will call for the lead compressor to start. The compressor 15-minute anti-recycle timer is initiated at compressor start.

The controller monitors compressor amps, volts, leaving water temperature and suction and discharge pressures. The compressor and cooling capacity is controlled by pulsed signals to load and unload solenoid valves on the compressor. When the compressor starts, it is fully unloaded, yielding about 25% of its full load capacity. As the computer gives it load signals, capacity gradually increases. The rate of compressor loading is governed by ramp control which is adjustable in the computer.

The computer responds to leaving chilled water temperature and its rate of change which is proportional and derivative control. If leaving chilled water temperature is within the deadband (+/-0.8°F from setpoint), no load or unload commands are given. If chilled water temperature is above deadband, the computer will continue loading the compressor until a satisfactory rate of decline is observed. If leaving chilled water temperature is below the deadband, the compressor is commanded to unload. Thus the compressor capacity is continuously modulated to match applied load

and hold leaving chilled water temperature at setpoint.

If the applied load is greater than one compressor can handle, it will load fully and then the controller will call for a second compressor. After one minute, the second compressor will start in the same manner as the first. Then both compressors will be commanded to adjust load to 50%. They are gradually loaded up together until the applied load is satisfied. In this way the two compressors share the load equally.

If the applied load decreases to the point that both compressors are running at about 40% capacity, the computer shuts down the lag compressor and loads the remaining compressor to about 80%. If applied load decreases further, the remaining compressor unloads proportionately. If applied load decreases to less than the minimum capacity of one compressor, the leaving chilled water temperature will decline to 2°F below setpoint, at which time the lead compressor will shut down. It will restart automatically if leaving chilled water temperature rises to 2°F above setpoint and both 15 minute anti-recycle and one minute start delay timers are satisfied.

During start-up operation, the computer monitors the difference between discharge and suction pressures to ensure that minimum of 30 psi differential is available for compressor lubrication. If the difference falls below a minimum of 30psi, the computer closes refrigerant flow control valves, starving the evaporator, causing evaporator pressure to drop, increasing differential pressure. This is especially helpful at startup, when warm chilled water and low ambient temperature would cause a low head situation. This feature is called EPCAS: Evaporator Pressure Control at Startup. It is one of several proactive control features of the controller which overcome potential problems while continuing operation. Two additional proactive features are low suction and high discharge pressure override. If operating pressures approach trip level, compressors are unloaded as necessary to continue operation.

Page 10: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 10 -

APPLICATION DATA Low Ambient Operation / Freeze Protection If unit is required to operate below 20°F (-7°C), optional head pressure control is required. Though heater tape is provided on vessel, all water piping must also be protected by heater tape. Glycol is recommended for added protection. If wind in area is over 5 mph (8 kph), a wind barrier is recommended. Desuperheaters A hot gas desuperheater can be factory supplied for field installation. Tees in refrigerant lines with shut off valves can be supplied. Consult factory for further details. Water Circuit Constant water flow required with a minimum of 3 gallons per ton (3.3 liters / kWo) increasing up to 10 gallons (11 lifers) for process, low load applications with small temperature ranges and/or vastly fluctuating load conditions.

Glycol Freeze Protection If the chiller or fluid piping may be exposed to temperatures below freezing, glycol protection is recommended. The re-commended protection is 15°F (8.3°C) below the minimum ambient temperature. Use only glycol solutions approved for heat exchanger duty. The use of automotive anti-freeze is not recommended because they have short-lived inhibitors and fouling of the vessels will occur. If the equipment is exposed to freezing temperature and not being used, the vessels and piping should be drained. If the equipment is being used for operating conditions below 42°F (5.5°C) with standard vessels or below 40°F (4.4°C) with optional 40°F (4.4°C) vessels, glycol should be used to prevent freeze damage. The freeze protection level should be 20°F (11°C) lower than the leaving brine temperature. The use of glycol causes a performance aerate as shown in table for ethylene glycol and table for propylene glycol and needs to be included in the unit selection procedure.

Ethylene Glycol

% E. G. By Weight Freeze Point C1

Capacity Factor K1

kW Rate G1

Flow Factor P1

P.D. Factor °F °C

10 26.2 -3.2 0.995 0.998 1.019 1.050 15 22.4 -5.3 0.991 0.997 1.030 1.083 20 17.8 -7.9 0.988 0.996 1.044 1.121 25 12.6 -10.8 0.984 0.995 1.060 1.170 30 6.7 -14.1 0.981 0.994 1.077 1.219 35 0.0 -17.8 0.977 0.992 1.097 1.275 40 -10.0 -23.3 0.973 0.991 1.116 1.331 45 -17.5 -27.5 0.968 0.990 1.138 1.398 50 -28.9 -33.8 0.964 0.989 1.161 1.466

Propylene Glycol

% P. G. By Weight Freeze Point C2

Capacity Factor K2

kW Rate G2

Flow Factor P2

P.D.Factor °F °C

10 26.1 -3.3 0.988 0.994 1.005 1.019 15 22.8 -5.1 0.984 0.992 1.008 1.031 20 19.1 -7.2 0.978 0.990 1.010 1.051 25 14.5 -9.7 0.970 0.988 1.015 1.081 30 8.9 -12.8 0.962 0.986 1.021 1.120

Correction Factor - Elevation Elevation above Sea Level Capacity

Correction Factor

kW Correction

Factor Feet Meters Factor

0 0 1.00 1.00 2000 600 0.99 1.01 4000 1200 0.98 1.02 6000 1800 0.97 1.03

Correction Factor - FF Fouling Factor Capacity

Correction Factor

kW Correction

Factor hr-ft. - °F/BTU m² °C kw

0.00010 0.018 1.000 1.000 0.00025 0.044 0.990 0.995 0.00050 0.088 0.970 0.990

Page 11: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 11 -

PHYSICAL SPECIFICATIONS

MODEL AFHX 100-5H 100T-5H 115T-5H 125-5H 135T-5H 145-5H

COMPRESSOR

MODEL (QTY) HX 1512 x 1 HX 1309 x 2 HX 1311 x 2 HX 1709 x 1 HX 1311 x 1 HX 1509 x 1

HX 1711 x 1

RPM 2950 2950 2950 2950 2950 2950

NOMINAL CAPACITY TR 97.33 100.99 114.7 122.13 133.55 146.74

MIN. % UNIT CAPACITY REDUCTION 25% 12.5% 12.5% 25% 12.5% 25%

EVAPORATOR

MODEL (QTY) B1(1) B1(1) C1(1) C1(1) C1(1) D1(1)

WATER CONNECTOR INCH[MM] 5[127] 5[127] 5[127] 5[127] 5[127] 6[152]

NOM. WATER FLOW / P D GPM / FT IN WG

233.9/12.37 242.4/13.20 275.6/5.75 293.4/12.00 320.90/14.11 352.6/10.24

MIN/ MAX WATER FLOW GPM 74/372 74/372 96/479 96/479 96/479 125/626

MIN/ MAX WATER PD FT IN WG 1.57/28.56 1.57/28.56 1.61/29.16 1.61/29.16 1.61/29.16 1.59/28.86

CONDENSER

COIL ROWS DEEP/ TOTAL FA (SQ.FT) 4/121.9 4/121.9 3/162.6 4/162.6 3/188.2 3/188.2

NO. OF FAN 6 6 8 8 8 8

FAN DIA. (QTY) MM 800(6) 800(6) 800(8) 800(8) 900(8) 900(8)

MOTOR KWI (QTY) 1.5(6) 1.5(6) 1.5(8) 1.5(8) 3.0(8) 3.0(8)

FLA, AMP (QTY) 3.2(6) 3.2(6) 3.2(8) 3.2(8) 4.9(8) 4.9(8)

TOTAL CFM 67032 67032 95676 91560 128016 126000

MIN. OPERATING AMBIENT °F 45 45 45 45 45 45

ELECTRICAL

NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50

UNIT RLA A 173 194 214 222 256 267

UNIT MAX. INRUSH A 247 218 266 270 309 360

GENERAL

UNIT LENGTH INCH[MM] 150[3810] 150[3810] 192[4877] 192[4877] 192[4877] 192[4877]

UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235]

UNIT HEIGHT INCH[MM] 86 ½[2197] 86 ½[2197] 87 ½[2223] 87 ½[2223] 95 ½[2426] 95 ½[2426]

SHIPPING WEIGHT LBS[KG] 8968[4067] 9306[4221] 10815[4906] 10728[4866] 12136[5505] 12148[5511]

OPERATING WEIGHT LBS[KG] 9101[4128] 9440[4282] 10988[4984] 10901[4945] 12308[5583] 12372[5612]

OPERATING CHARGE R-22 LBS[KG] 214[97] 223[101] 254[115] 269[122] 295[134] 324[147]

Page 12: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 12 -

PHYSICAL SPECIFICATIONS

MODEL AFHX 155T-5H 170-5H 175T-5H 190-5H 195T-5H 230-5H

COMPRESSOR

MODEL (QTY) HX 1509 x 2 HX 1811 x 1

HX 1509 x 1 HX 1512 x 1

HX 1813 x 1 HX 1512 x 2 HX 1512 x 1 HX 1709 x 1

RPM 2950 2950 2950 2950 2950 2950

NOMINAL CAPACITY TR 151.2 170.84 172.38 188.06 195.09 227.75

MIN. % UNIT CAPACITY REDUCTION 12.5% 25% 12.5% 25% 12.5% 12.5%

EVAPORATOR

MODEL (QTY) D1(1) D2(1) D2(1) J1(1) J1(1) C1(2)

WATER CONNECTOR INCH[MM] 6[152] 6[152] 6[152] 6[152] 6[152] 6[152]

NOM. WATER FLOW / P D GPM / FT IN WG

363.3/10.80 410.50/11.00 414.2/11.18 451.9/15.37 486.45/9.64 547.2/11.95

MIN/ MAX WATER FLOW GPM 125/626 141/704 141/704 140.9/703.8 140.9/703.8 192.6/959.5

MIN/ MAX WATER PD FT IN WG 1.59/28.86 1.6/29.21 1.6/29.21 1.90/34.15 1.90/34.15 1.78/33.42

CONDENSER

COIL ROWS DEEP/ TOTAL FA (SQ.FT) 3/188.2 4/188.2 4/188.2 3/235.3 4/235.3 3/141.2, 4/141.2

NO. OF FAN 8 8 8 10 10 12

FAN DIA. MM 900(8) 900(8) 900(8) 900(10) 900(10) 900(12)

MOTOR KWI (QTY) 3.0(8) 3.0(8) 3.0(8) 3.0(10) 3.0(10) 3.0(12)

FLA, AMP (QTY) 4.9(8) 4.9(8) 4.9(8) 4.9(10) 4.9(10) 4.9(12)

TOTAL CFM 126000 118440 118440 157500 151750 187047

MIN. OPERATING AMBIENT °F 45 45 45 45 45 45

ELECTRICAL

NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50

UNIT RLA A 293 301 322 336 352 414

UNIT MAX. INRUSH A 334 406 395 542 429 485

GENERAL

UNIT LENGTH INCH[MM] 192[4877] 192[4877] 192[4877] 234[5944] 234[5944] 276[7010]

UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235]

UNIT HEIGHT INCH[MM] 95 ½[2426] 95 ½[2426] 95 ½[2426] 97 ½[2476] 97 ½[2476] 97 ½[2476]

SHIPPING WEIGHT LBS[KG] 12520[5679] 13169[5973] 13940[6323] 14348[6508] 15345[6960] 18505[8394]

OPERATING WEIGHT LBS[KG] 12693[5757] 13416[6085] 14187[6435] 14641[6641] 15639[7094] 18850[8550]

OPERATING CHARGE R-22 LBS[KG] 333[151] 377[171] 379[172] 434[197] 450[204] 527[239]

Page 13: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 13 -

PHYSICAL SPECIFICATIONS

MODEL AFHX 245-5H 255-5H 265-5H 305-5H 330-5H 355-5H

COMPRESSOR

MODEL (QTY) HX 1816 x 1 HX 1709 x 2 HX 1817 x 1 HX 1711 x 2 HX 1711 x 1 HX 1811 x 1

HX 1811 x 2

RPM 2950 2950 2950 2950 2950 2950

NOMINAL CAPACITY TR 245.8 252.9 265.2 304.6 330.4 356.2

MIN. % UNIT CAPACITY REDUCTION 25% 12.5% 25% 12.5% 12.5% 12.5%

EVAPORATOR

MODEL (QTY) K2(1) D1(2) L1(1) J1(2) J1(2) J1(2)

WATER CONNECTOR INCH[MM] 6[152] 8[203] 8[203] 8[203] 8[203] 8[203]

NOM. WATER FLOW / PD GPM / FT IN WG

590.6/18.05 607.65/8.3 637.2/15.70 731.9/11.22 794.25/13.00 855.8/14.89

MIN/ MAX WATER FLOW GPM 171.5/851.9 250/1252 195.5/974.4 281/1409 281/1409 281/1409

MIN/ MAX WATER PD FT IN WG. 1.96/34.97 1.67/30.91 1.89/33.70 2.01/36.79 2.01/36.79 2.01/36.79

CONDENSER

COIL ROWS DEEP/ TOTAL FA (SQ.FT) 4/282.3 4/282.3 3/329.4 4/188.2, 3/188.2 4/376.4 3/235.3, 4/188.2

NO. OF FAN 12 12 14 16 16 18

FAN DIA. MM 900(12) 900(12) 900(14) 900(16) 900(16) 900(18)

MOTOR KWI (QTY) 2.5(12) 2.5(12) 2.5(14) 2.5(16) 2.5(16) 2.5(18)

FLA, AMP (QTY) 4.9(12) 4.9(12) 4.9(14) 4.9(16) 4.9(16) 4.9(18)

TOTAL CFM 182070 179865 220500 250320 239820 275940

MIN. OPERATING AMBIENT °F 45 45 45 45 45 45

ELECTRICAL

NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50

UNT RLA A 334 458 471 541 572 615

UNIT MAX. INRUSH A 645 506 655 635 677 719

GENERAL

UNIT LENGTH INCH[MM] 276[7010] 276[7010] 318[3451] 360[9144] 360[9144] 402[10211]

UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235]

UNIT HEIGHT INCH[MM] 97 ½[2476] 97 ½[2476] 97 ½[2476] 97 ½[2476] 97 ½[2476] 97 ½[2476]

SHIPPING WEIGHT LBS[KG] 18209[8259] 19985[9065] 20780[9426] 24325[11034] 25075[11374] 26057[11819]

OPERATING WEIGHT LBS[KG] 18565[8421] 20432[9268] 21191[9612] 24913[11301] 25663[11641] 26645[12086]

OPERATING CHARGE R-22 LBS[KG] 569[258] 584[265] 613[278] 736[334] 798[362] 860[390]

Page 14: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 14 -

PHYSICAL SPECIFICATIONS

MODEL AFHX 390-5H 450-5H 515-5H 550-5H 585-5H 640-5H

COMPRESSOR

MODEL (QTY) HX 1813 x 2 HX 1813 x 1 HX 1816 x 1

HX 1816 x 2 HX 1817 x 2 HX 1813 x 3 HX 1816 x 1 HX 1813 x 2

RPM 2950 2950 2950 2950 2950 2950

NOMINAL CAPACITY TR 391.5 450.8 512.2 550.8 582.0 637.1

MIN. % UNIT CAPACITY REDUCTION 12.5% 12.5% 12.5% 12.5% 8.33% 8.33%

EVAPORATOR

MODEL (QTY) K1(2) L2(2) L2(2) L3(2) M2(1), L2(1) M1(1), M2(1)

WATER CONNECTOR INCH[MM] 8[203] 10[254] 10[254] 10[254] 12[305], 10[254] 12[305]

NOM. WATER FLOW / PD GPM / FT IN WG

940.75/15.25 1083.35/10.28 1230.6/12.96 1323.45/12.61 1398.4/13.3 1530.75/12.69

MIN/ MAX WATER FLOW GPM 308.7/1545.4 434.6/2171.2 434.6/2171.2 479/2396 496.1/2474.5 541.05/2701.15

MIN/ MAX WATER PD FT IN WG. 2.04/37.60 1.98/36.24 1.98/36.24 2.01/37.02 1.97/35.88 1.95/35.38

CONDENSER

COIL ROWS DEEP/ TOTAL FA (SQ.FT) 4/235.3, 3/235.3 4/577.5 4/641.7 4/641.7 6/385, 4/256.7 4/320.8,3/385

NO. OF FAN 20 18 20 20 20 22

FAN DIA. MM 900(20) 900(18) 860(20) 860(20) 860(20) 900(22)

MOTOR KWI (QTY) 2.5(20) 2.5(18) 3.0(10), 4.0(10) 4.0(20) 4.0(20) 2.5(22)

FLA, AMP (QTY) 4.9(20) 4.9(18) 5.5(10), 7.1(10) 7.1(20) 7.1(20) 4.9(22)

TOTAL CFM 309225 294882 355845 366870 345996 346164

MIN. OPERATING AMBIENT °F 45 45 45 45 45 45

ELECTRICAL

NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50

UNIT RLA A 677 755 875 955 1024 1109

UNIT MAX. INRUSH A 883 968 1090 1140 1223 1302

GENERAL

UNIT LENGTH INCH[MM] 465[11811] 402[10211] 444[11278] 444[11278] 444[11278] 471[11963]

UNIT WIDTH INCH[MM] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235] 88[2235]

UNIT HEIGHT INCH[MM] 97 ½[2476] 120[3048] 120[3048] 120[3048] 120[3048] 120[3048]

SHIPPING WEIGHT LBS[KG] 31952[14493] 32197[14604] 35354[16037] 36958[16764] 39118[17744] 43605[19779]

OPERATING WEIGHT LBS[KG] 32608[14791] 33100[15014] 36258[16446] 37943[17211] 40167[18220] 44722[20286]

OPERATING CHARGE R-22 LBS[KG] 946429] 1089[494] 1237[561] 1329[603] 1404[637] 1616[733]

Page 15: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 15 -

PERFORMANCE DATA

LWT °F

MODEL AFHX

AMBIENT TEMPERATURE, °F 85.0 95.0 105.0 115.0 125.0

TR kWO kWI TR kWO kWI TR kWO kWI TR kWO kWI TR kWO kWI

40.0

100-5H 92.5 325.4 83.9 90.9 319.9 94.7 89.7 315.5 109.0 88.9 312.6 125.7 72.0 253.2 105.6 100T-5H 96.6 339.7 93.6 95.0 334.0 105.9 93.7 329.4 122.0 92.8 326.4 140.8 74.2 261.1 118.3 115T-5H 108.9 383.0 103.2 107.1 376.5 116.7 105.6 371.4 134.2 104.6 367.9 155.0 84.7 298.0 130.2 125-5H 115.9 407.7 107.7 114.0 400.8 121.6 112.4 395.3 139.9 111.4 391.7 161.3 88.0 309.4 135.5

135T-5H 126.6 445.1 120.7 124.4 437.7 136.5 122.7 431.7 157.1 121.6 427.6 181.4 97.3 342.1 152.3 145-5H 139.3 490.0 125.7 137.0 481.7 141.6 135.1 475.2 163.0 133.8 470.7 187.9 108.4 381.3 157.8

155T-5H 144.2 507.3 138.1 141.8 498.8 156.3 139.9 492.0 179.9 138.6 487.3 207.8 112.2 394.7 174.5 170-5H 162.7 572.2 143.7 160.0 562.6 162.0 157.8 554.9 186.3 156.3 549.7 214.7 126.6 445.3 180.4

175T-5H 164.6 579.0 153.0 161.9 569.3 172.8 159.7 561.5 199.0 158.2 556.2 229.6 124.9 439.4 192.8 190-5H 178.9 629.2 157.7 175.9 618.6 177.7 173.5 610.2 204.3 171.9 604.5 235.5 139.2 489.7 197.8

195T-5H 185.0 650.7 167.9 181.9 639.7 189.3 179.4 631.0 218.1 177.8 625.2 251.4 142.2 500.1 211.1 230-5H 216.8 762.6 193.7 213.3 750.1 218.4 210.6 740.6 251.4 208.8 734.3 290.7 167.0 587.4 244.2 245-5H 234.0 823.0 204.1 230.1 809.1 230.0 226.9 798.1 264.2 224.8 790.7 304.9 182.1 640.4 256.1 255-5H 241.3 848.6 217.9 237.4 834.8 245.2 234.3 824.1 282.5 232.3 817.1 325.5 183.5 645.5 273.4 265-5H 252.4 887.5 219.5 248.1 872.6 247.5 244.7 860.7 284.2 242.5 852.7 327.7 196.4 690.7 275.3 305-5H 290.0 1020.0 253.8 285.3 1003.4 285.9 281.7 990.6 329.2 279.3 982.2 379.2 226.2 795.5 318.5 330-5H 314.3 1105.3 272.2 309.1 1087.3 306.6 305.2 1073.4 352.8 302.6 1064.3 407.9 242.1 851.4 342.7 355-5H 338.6 1191.0 290.8 333.1 1171.6 327.0 328.9 1156.7 376.1 326.1 1146.8 433.2 264.1 928.9 363.9 390-5H 372.4 1309.6 319.1 366.3 1288.3 358.8 361.6 1271.8 412.6 358.6 1261.1 475.3 286.9 1008.9 399.3 450-5H 429.5 1510.6 365.4 422.5 1486.0 411.9 417.1 1467.0 473.2 413.6 1454.5 547.4 335.0 1178.2 459.8 515-5H 487.1 1713.1 413.0 479.2 1685.3 464.4 473.0 1663.7 533.6 469.0 1649.6 615.0 370.5 1303.2 516.6 550-5H 525.3 1847.5 444.2 516.7 1817.4 499.6 510.1 1794.2 573.9 505.8 1779.0 661.3 409.7 1441.0 555.5 585-5H 556.3 1956.6 477.5 547.3 1924.7 538.2 540.2 1899.9 617.7 535.6 1883.7 711.8 433.8 1525.8 597.9 640-5H 611.4 2150.3 536.0 600.9 2113.3 604.5 592.6 2084.3 697.4 590.2 2075.8 782.5 466.3 1639.9 657.3

42.0

100-5H 95.6 336.2 84.8 94.0 330.7 95.3 92.8 326.4 110.2 92.0 323.7 127.7 74.5 262.2 107.2 100T-5H 99.8 351.1 94.5 98.2 345.3 106.5 96.9 340.8 123.2 96.1 337.9 143.4 76.9 270.3 120.4 115T-5H 112.5 395.8 104.2 110.7 389.3 117.3 109.3 384.3 135.7 108.3 380.9 157.3 87.7 308.5 132.1 125-5H 119.8 421.3 108.7 117.8 414.4 122.2 116.3 409.0 141.4 115.3 405.4 164.1 91.1 320.3 137.9

135T-5H 130.8 460.0 121.9 128.7 452.5 137.2 127.0 446.6 158.8 125.9 442.7 184.1 100.7 354.2 154.6 145-5H 144.0 506.4 126.9 141.6 498.1 142.6 139.8 491.6 164.7 138.6 487.4 190.9 112.2 394.8 160.4

155T-5H 149.1 524.2 139.5 146.6 515.6 157.1 144.7 509.0 182.0 143.5 504.6 210.9 116.2 408.7 177.2 170-5H 168.1 591.3 145.1 165.4 581.7 163.1 163.2 574.1 188.2 161.8 569.2 218.0 131.1 461.1 183.1

175T-5H 170.1 598.3 154.5 167.3 588.5 173.8 165.2 580.9 201.1 163.8 576.0 233.1 129.4 455.0 195.8 190-5H 184.9 650.2 159.2 181.9 639.6 179.0 179.5 631.3 206.4 178.0 625.9 239.4 144.1 507.0 201.1

195T-5H 191.2 672.5 169.5 188.1 661.5 190.5 185.6 652.9 220.3 184.1 647.3 255.3 147.2 517.9 214.5 230-5H 224.0 787.7 195.3 220.4 775.3 219.9 217.8 765.9 253.6 216.0 759.8 293.0 172.8 607.8 246.1 245-5H 241.8 850.5 206.0 237.9 836.6 231.5 234.8 825.7 266.9 232.8 818.6 309.3 188.5 663.1 259.8 255-5H 249.2 876.6 219.8 245.3 862.7 247.0 242.3 852.3 285.0 240.4 845.4 331.1 189.9 667.9 278.2 265-5H 260.9 917.5 221.6 256.5 902.2 249.2 253.2 890.5 287.1 251.0 882.7 332.8 203.3 715.0 279.6 305-5H 299.6 1053.7 256.5 294.9 1037.0 288.3 291.3 1024.4 332.0 289.0 1016.4 385.2 234.1 823.3 323.6 330-5H 324.6 1141.7 274.6 319.5 1123.7 309.2 315.6 1110.0 355.9 313.1 1101.3 412.6 250.5 881.1 346.6 355-5H 349.8 1230.3 293.5 344.3 1210.9 329.7 340.1 1196.1 379.3 337.4 1186.8 439.8 273.3 961.3 369.5 390-5H 384.6 1352.8 321.9 378.6 1331.4 361.9 374.0 1315.2 416.2 371.1 1305.0 483.1 296.8 1044.0 405.8 450-5H 443.7 1560.3 368.8 436.7 1535.7 414.5 431.4 1517.1 477.2 427.9 1505.1 550.9 346.6 1219.1 462.8 515-5H 503.2 1769.6 416.6 495.2 1741.7 468.1 489.2 1720.5 538.2 485.3 1707.0 624.1 383.4 1348.5 524.3 550-5H 542.6 1908.4 448.1 534.0 1878.2 503.7 527.6 1855.4 578.9 523.4 1840.8 671.3 423.9 1491.0 563.9 585-5H 574.7 2021.1 482.4 565.6 1989.2 542.2 558.7 1964.9 623.7 554.3 1949.5 723.3 449.0 1579.1 607.5 640-5H 631.6 2221.3 540.8 621.0 2184.2 608.8 613.0 2155.8 702.7 610.8 2148.3 791.3 482.5 1697.1 664.7

44.0

100-5H 98.8 347.3 85.7 97.3 342.3 96.6 96.0 337.6 110.9 95.2 335.0 128.3 77.1 271.3 107.8 100T-5H 103.1 362.7 95.5 101.0 355.2 110.2 100.2 352.6 124.0 99.4 349.7 143.5 79.5 279.8 120.6 115T-5H 116.3 408.9 105.3 114.7 403.4 118.3 113.0 397.4 136.5 112.1 394.2 158.5 90.8 319.3 133.1 125-5H 123.8 435.2 109.8 122.1 429.5 123.3 120.3 423.0 142.3 119.3 419.7 164.9 94.3 331.6 138.6

135T-5H 135.1 475.2 123.1 133.6 469.7 136.7 131.3 461.9 159.7 130.3 458.2 185.5 104.2 366.5 155.9 145-5H 148.7 523.1 128.1 146.7 516.1 143.1 144.6 508.4 165.8 143.4 504.5 192.0 116.2 408.6 161.2

155T-5H 154.0 541.6 141.0 151.2 531.8 159.5 149.7 526.4 183.0 148.4 522.1 212.6 120.2 422.9 178.6 170-5H 173.7 610.9 146.6 170.8 600.8 164.9 168.8 593.7 189.4 167.5 589.1 219.1 135.7 477.2 184.0

175T-5H 175.8 618.1 156.2 172.4 606.3 177.8 170.8 600.8 202.4 169.5 596.0 234.6 133.9 470.8 197.0 190-5H 191.0 671.7 160.9 188.1 661.4 180.4 185.6 652.9 207.8 184.2 647.8 240.6 149.2 524.7 202.1

195T-5H 197.5 694.7 171.8 195.1 686.1 190.5 192.0 675.2 221.7 190.5 669.9 256.6 152.4 535.9 215.5 230-5H 231.3 813.4 197.3 227.8 801.0 223.2 225.1 791.7 255.2 223.5 786.1 295.6 178.8 628.9 248.3 245-5H 249.8 878.6 208.1 245.8 864.5 235.5 242.8 854.0 268.8 240.9 847.2 310.9 195.1 686.2 261.2 255-5H 257.4 905.2 221.5 252.9 889.4 251.0 250.5 881.1 286.6 248.7 874.8 332.5 196.5 691.1 279.3 265-5H 269.4 947.5 223.9 265.2 932.6 253.2 261.9 920.9 289.1 259.8 913.7 334.6 210.4 740.1 281.0 305-5H 309.4 1088.0 258.6 304.6 1071.3 291.3 301.1 1059.1 333.8 299.0 1051.5 387.5 242.2 851.7 325.5 330-5H 335.2 1178.9 277.3 330.4 1162.2 310.9 326.3 1147.5 357.9 324.0 1139.4 412.8 259.2 911.6 346.8 355-5H 361.2 1270.4 295.8 356.2 1252.7 331.2 351.6 1236.6 381.5 349.1 1227.7 442.0 282.8 994.5 371.3 390-5H 397.2 1396.9 324.6 391.5 1376.9 363.8 386.6 1359.7 418.5 383.8 1350.0 485.6 307.1 1080.0 407.9 450-5H 458.1 1611.2 372.5 450.8 1585.6 419.6 445.9 1568.3 480.5 442.7 1557.1 556.0 358.6 1261.3 467.1 515-5H 519.6 1827.3 419.8 512.2 1801.3 471.1 505.7 1778.7 541.3 502.1 1766.0 627.6 396.7 1395.1 527.2 550-5H 560.3 1970.6 451.8 550.8 1937.1 511.3 545.4 1918.2 582.2 541.5 1904.5 675.1 438.6 1542.6 567.1 585-5H 593.4 2087.1 486.6 582.0 2047.0 554.6 577.6 2031.3 627.8 573.4 2016.5 726.7 464.4 1633.4 610.4 640-5H 652.3 2294.0 545.0 637.1 2240.7 630.0 633.7 2228.8 708.0 631.9 2222.5 799.3 499.2 1755.8 671.4

Notes: 1.) Ratings based on 10°F water range in evaporator and .0001 fouling factor. 2.) Interpolation between ratings is permissible but extrapolation is NOT. 3.) KWI is for compressor input. 4.) Unit is running on part load for ambient temperature of 115°F and above due to current limiter. 5.) Consult factory for 60 Hz operation.

Page 16: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 16 -

PERFORMANCE DATA

LWT °F

MODEL AFHX

AMBIENT TEMPERATURE, °F 85.0 95.0 105.0 115.0 125.0

TR kWO kWI TR kWO kWI TR kWO kWI TR kWO kWI TR kWO kWI

46.0

100-5H 102.0 358.7 86.4 100.4 353.1 97.1 99.2 349.0 111.7 98.5 346.5 129.2 79.8 280.7 108.5 100T-5H 106.5 374.6 96.3 104.8 368.7 108.1 103.6 364.5 125.1 102.9 361.9 144.6 82.3 289.5 121.4 115T-5H 120.1 422.3 106.1 118.2 415.7 119.3 116.8 410.9 137.7 116.0 407.9 159.1 93.9 330.4 133.6 125-5H 127.8 449.5 110.8 125.8 442.5 124.4 124.3 437.3 143.4 123.4 434.1 166.1 97.5 343.0 139.5

135T-5H 139.5 490.8 124.1 137.4 483.1 139.5 135.8 477.5 161.1 134.8 474.1 186.0 107.8 379.3 156.3 145-5H 153.6 540.2 129.2 151.2 531.8 145.2 149.5 525.6 167.1 148.4 521.9 193.2 120.2 422.7 162.3

155T-5H 159.0 559.3 142.2 156.6 550.6 159.7 154.7 544.2 184.4 153.6 540.3 212.9 124.4 437.7 178.9 170-5H 179.4 630.9 147.8 176.6 621.1 166.2 174.5 613.8 190.9 173.3 609.4 220.6 140.3 493.6 185.3

175T-5H 181.5 638.4 157.5 178.7 628.4 177.0 176.6 621.1 203.9 175.3 616.7 235.7 138.5 487.2 198.0 190-5H 197.2 693.7 162.2 194.2 682.9 182.4 191.9 675.0 209.4 190.5 670.1 242.0 154.3 542.8 203.3

195T-5H 204.0 717.4 172.8 200.8 706.3 194.2 198.5 698.1 223.4 197.0 693.0 258.4 157.6 554.4 217.1 230-5H 238.7 839.6 198.9 235.2 827.2 223.7 232.6 818.2 256.8 231.1 812.9 297.2 184.9 650.3 249.6 245-5H 258.0 907.3 209.9 254.0 893.3 235.9 251.0 882.9 270.9 249.2 876.4 313.3 201.8 709.9 263.2 255-5H 265.7 934.3 223.7 261.7 920.5 251.6 258.9 910.5 289.1 257.2 904.6 334.2 203.2 714.6 280.7 265-5H 278.2 978.5 225.8 273.9 963.3 253.8 270.7 952.1 291.3 268.8 945.2 336.6 217.7 765.6 282.8 305-5H 319.3 1123.1 261.1 314.6 1106.4 293.8 311.2 1094.4 336.8 309.2 1087.4 389.1 250.4 880.8 326.9 330-5H 346.0 1216.9 279.5 340.9 1198.9 314.5 337.2 1185.8 360.4 335.0 1178.1 416.8 268.0 942.5 350.1 355-5H 372.9 1311.3 298.6 367.3 1291.9 336.0 363.3 1277.9 384.8 361.0 1269.5 444.3 292.4 1028.3 373.2 390-5H 410.0 1441.9 327.6 403.9 1420.5 368.7 399.5 1405.1 422.2 396.9 1396.0 487.1 317.5 1116.8 409.1 450-5H 472.9 1663.2 375.6 465.9 1638.5 422.5 460.8 1620.7 483.7 457.8 1610.2 561.4 370.8 1304.2 471.6 515-5H 536.3 1886.2 424.0 528.4 1858.2 477.1 522.6 1838.0 546.1 519.2 1826.1 630.7 410.2 1442.6 529.8 550-5H 578.4 2034.1 456.1 569.8 2004.0 513.2 563.6 1982.2 587.3 560.0 1969.4 677.9 453.6 1595.2 569.4 585-5H 612.6 2154.5 491.0 603.5 2122.5 552.2 596.9 2099.2 632.4 593.0 2085.6 732.3 480.3 1689.3 615.1 640-5H 673.3 2368.1 549.5 662.8 2331.0 618.8 655.0 2303.5 712.1 653.5 2298.5 805.3 516.3 1815.8 676.4

48.0

100-5H 105.3 370.3 87.0 103.7 364.8 97.8 102.6 360.7 112.1 101.9 358.3 130.0 82.5 290.3 109.2 100T-5H 109.9 386.6 96.9 108.3 380.9 108.9 107.1 376.7 125.5 106.4 374.1 145.2 85.1 299.3 121.9 115T-5H 123.9 435.9 106.9 122.1 429.4 120.2 120.7 424.7 138.1 119.9 421.8 160.3 97.1 341.6 134.7 125-5H 131.9 464.0 111.5 130.0 457.1 125.4 128.5 452.0 143.9 127.7 449.0 167.1 100.9 354.7 140.4

135T-5H 144.1 506.6 125.0 141.9 499.0 140.6 140.3 493.6 161.6 139.4 490.2 187.4 111.5 392.2 157.4 145-5H 158.6 557.7 130.2 156.2 549.3 146.3 154.5 543.3 167.7 153.4 539.7 194.4 124.3 437.1 163.3

155T-5H 164.2 577.4 143.0 161.7 568.7 161.0 159.9 562.5 185.0 158.9 558.7 214.4 128.7 452.6 180.1 170-5H 185.2 651.2 148.8 182.4 641.5 167.4 180.4 634.5 191.7 179.2 630.2 222.4 145.1 510.5 186.8

175T-5H 187.4 659.0 158.5 184.6 649.1 178.3 182.5 642.0 204.6 181.3 637.7 237.2 143.2 503.8 199.3 190-5H 203.6 716.1 163.3 200.6 705.4 183.6 198.4 697.7 210.2 197.0 692.9 243.7 159.6 561.3 204.7

195T-5H 210.6 740.6 174.0 207.4 729.5 195.6 205.1 721.5 224.2 203.8 716.7 260.1 163.0 573.4 218.4 230-5H 246.3 866.4 200.5 242.8 854.1 225.4 240.3 845.3 258.2 239.0 840.5 300.3 191.2 672.4 252.3 245-5H 266.3 936.7 211.3 262.3 922.7 237.6 259.5 912.6 271.8 257.7 906.4 315.0 208.7 734.2 264.6 255-5H 274.1 964.1 225.1 270.2 950.4 253.6 267.4 940.6 290.5 265.9 935.1 335.6 210.0 738.7 281.9 265-5H 287.2 1010.1 227.4 282.9 995.0 255.6 279.8 984.1 292.5 277.9 977.5 339.2 225.1 791.8 284.9 305-5H 329.5 1158.8 262.8 324.8 1142.4 295.9 321.5 1130.6 338.4 319.6 1124.1 390.9 258.9 910.5 328.4 330-5H 357.0 1255.7 282.0 352.0 1237.8 317.1 348.3 1225.1 362.5 346.3 1218.1 421.5 277.1 974.5 354.0 355-5H 384.7 1353.1 300.5 379.3 1333.9 338.5 375.4 1320.2 386.8 373.2 1312.5 446.8 302.3 1063.1 375.3 390-5H 423.0 1487.9 329.7 417.0 1466.7 371.4 412.7 1451.6 424.3 410.3 1443.1 489.7 328.3 1154.5 411.4 450-5H 488.0 1716.2 378.4 481.0 1691.8 425.3 476.1 1674.4 485.9 473.3 1664.6 562.8 383.4 1348.4 472.7 515-5H 553.4 1946.3 426.7 545.5 1918.6 480.5 539.9 1898.9 548.7 536.8 1887.8 633.5 424.0 1491.4 532.1 550-5H 596.8 2098.9 459.0 588.3 2069.0 517.0 582.2 2047.8 590.4 578.9 2035.9 681.6 468.9 1649.1 572.5 585-5H 632.1 2223.2 494.2 623.1 2191.4 556.3 616.7 2168.8 635.4 613.0 2156.1 737.9 496.6 1746.4 619.9 640-5H 694.8 2443.7 554.1 684.4 2406.9 624.6 676.7 2380.1 715.8 675.6 2376.1 807.9 533.7 1877.1 678.6

50.0

100-5H 110.3 388.1 88.2 108.8 382.6 99.0 107.7 378.8 113.6 105.3 370.4 134.3 85.3 300.0 112.8 100T-5H 115.2 405.2 98.3 113.6 399.6 110.4 112.5 395.5 127.1 110.0 386.9 145.6 88.0 309.5 122.3 115T-5H 129.9 456.9 108.3 128.1 450.5 121.6 126.8 445.9 139.9 124.0 436.1 160.3 100.4 353.2 134.6 125-5H 138.3 486.3 113.1 136.3 479.5 126.9 134.9 474.6 145.9 132.0 464.2 167.1 104.3 366.7 140.4

135T-5H 151.0 531.0 126.8 148.9 523.6 142.3 147.3 518.2 163.7 144.1 506.9 187.8 115.3 405.5 157.8 145-5H 166.2 584.5 132.0 163.9 576.3 148.1 162.2 570.4 169.9 158.6 557.9 194.7 128.5 451.9 163.5

155T-5H 172.1 605.1 145.2 169.6 596.6 163.0 167.9 590.6 187.5 164.3 577.7 215.4 133.0 467.9 180.9 170-5H 194.1 682.6 151.1 191.3 673.0 169.4 189.4 666.1 194.2 185.2 651.5 222.6 150.1 527.7 187.0

175T-5H 196.4 690.7 160.9 193.6 681.0 180.5 191.7 674.1 207.4 187.4 659.3 238.1 148.1 520.8 200.0 190-5H 213.4 750.6 165.8 210.4 740.0 185.9 208.3 732.5 213.0 203.7 716.4 244.0 165.0 580.3 205.0

195T-5H 220.7 776.2 176.5 217.6 765.3 198.1 215.4 757.5 227.3 210.6 740.8 260.8 168.5 592.7 219.1 230-5H 256.2 901.2 202.8 252.8 889.0 227.7 250.4 880.5 260.9 246.9 868.5 300.5 197.6 694.8 252.5 245-5H 279.1 981.7 214.4 275.2 967.9 240.6 272.4 958.1 275.5 266.5 937.1 315.7 215.8 759.1 265.2 255-5H 284.9 1002.0 227.8 281.0 988.4 255.7 278.4 979.0 293.1 274.8 966.4 338.7 217.1 763.5 284.5 265-5H 301.0 1058.7 230.7 296.8 1043.8 258.8 293.8 1033.2 296.3 287.3 1010.5 339.4 232.7 818.5 285.1 305-5H 342.4 1204.4 265.7 337.8 1188.1 298.5 334.6 1176.7 341.6 330.3 1161.6 394.7 267.5 940.9 331.5 330-5H 371.3 1305.8 285.1 366.2 1288.1 320.9 362.8 1275.8 366.1 357.9 1258.8 422.1 286.3 1007.0 354.5 355-5H 399.9 1406.3 304.1 394.4 1387.2 341.4 390.7 1373.9 390.4 385.6 1356.3 450.8 312.4 1098.6 378.6 390-5H 439.7 1546.3 333.6 433.7 1525.4 374.6 429.6 1510.8 428.2 424.1 1491.4 494.5 339.3 1193.2 415.4 450-5H 507.7 1785.4 383.0 500.8 1761.2 430.0 496.0 1744.4 491.5 489.1 1720.3 565.8 396.2 1393.5 475.2 515-5H 575.1 2022.8 431.7 567.3 1995.3 484.8 561.9 1976.3 553.9 554.8 1951.1 639.4 438.3 1541.3 537.1 550-5H 620.2 2181.4 464.4 611.8 2151.8 521.5 606.0 2131.2 595.8 598.2 2103.9 687.3 484.5 1704.1 577.4 585-5H 658.7 2316.6 500.5 649.7 2285.0 562.4 643.5 2263.2 642.6 633.6 2228.3 739.8 513.2 1804.9 621.5 640-5H 716.8 2521.1 558.6 706.4 2484.3 629.7 698.9 2458.1 504.3 698.3 2455.8 808.4 551.6 1940.1 679.1

Notes: 1.) Ratings based on 10°F water range in evaporator and .0001 fouling factor. 2.) Interpolation between ratings is permissible but extrapolation is NOT. 3.) KWI is for compressor input. 4.) Unit is running on part load for ambient temperature of 115°F and above due to current limiter. 5.) Consult factory for 60 Hz operation.

Page 17: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 17 -

DIMENSIONAL DATA

AFHX 100-5H, 100T-5H

AFHX 115T-5H, 125-5H, 135T-5H, 145-5H, 155T-5H, 170-5H, 175T-5H

AFHX 190-5H, 195T-5H NOTE : ALL DIMENSIONS ARE IN INCHES(MM).

Page 18: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 18 -

DIMENSIONAL DATA

AFHX 230-5H, 245-5H, 255-5H

AFHX 265-5H

AFHX 305-5H, 330-5H NOTE : ALL DIMENSIONS ARE IN INCHES(MM).

Page 19: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 19 -

DIMENSIONAL DATA

AFHX 355-5H

AFHX 390-5H

AFHX 450-5H NOTE : ALL DIMENSIONS ARE IN INCHES(MM).

Page 20: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 20 -

DIMENSIONAL DATA

AFHX 515-5H, 550-5H

AFHX 585-5H

AFHX 640-5H NOTE : ALL DIMENSIONS ARE IN INCHES(MM).

Page 21: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 21 -

FLOOR LOADING DIAGRAM 1.) AFHX 100-5H, 110T-5H, 115T-5H, 125-5H, 135T-5H, 145-5H, 155T-5H, 170-5H,

175T-5H, 190-5H, 195T-5H, 230-5H, 245-5H, 255-5H, 265-5H a.) Point Load Location – Inches [mm]

Unit Model AFHX A Dim. B Dim. C Dim. D Dim. E Dim.

100-5H 86 [2184] 18 [457] 57 [1448] 57 [1448] 18 [457] 100T-5H 86 [2184] 18 [457] 57 [1448] 57 [1448] 18 [457] 115T-5H 86 [2184] 18 [457] 78 [1981] 78 [1981] 18 [457] 125-5H 86 [2184] 18 [457] 78 [1981] 78 [1981] 18 [457]

135T-5H 86 [2184] 18 [457] 78 [1981] 78 [1981] 18 [457] 145-5H 86 [2184] 18 [457] 78 [1981] 78 [1981] 18 [457]

155T-5H 86 [2184] 18 [457] 78 [1981] 78 [1981] 18 [457] 170-5H 86 [2184] 18 [457] 78 [1981] 78 [1981] 18 [457]

175T-5H 86 [2184]] 18 [457] 78 [1981] 78 [1981] 18 [457] 190-5H 86 [2184] 18 [457] 99 [2515] 99 [2515] 18 [457]

195T-5H 86 [2184] 18 [457] 99 [2515] 99 [2515] 18 [457] 230-5H 86 [2184] 21 [533] 117 [2972] 117 [2972] 21 [533] 245-5H 86 [2184] 21 [533] 117 [2972] 117 [2972] 21 [533] 255-5H 86 [2184] 21 [533] 117 [2972] 117 [2972] 21 [533] 265-5H 86 [2184] 21 [533] 138 [3505] 138 [3505] 21 [533 ]

b.) Point Load Data – lbs [kg] Unit Model

AFHX Pos. #1 Pos. #2 Pos. #3 Pos. #4 Pos. #5 Pos. #6 Total Operating Weight

100-5H 1375 [624] 1529 [694] 1684 [764] 1545 [701] 1504 [682] 1463 [664] 9101 [4128] 100T-5H 1673 [759] 1617 [734] 1561 [708] 1499 [680] 1529 [694] 1560 [708] 9440 [4282] 115T-5H 1922 [872] 1871 [849] 1819 [825] 1650 [748] 1792 [813] 1933 [877] 10988 [4984] 125-5H 1610 [730] 1831 [830] 2051 [931] 1748 [793] 1803 [818] 1859 [843] 10902 [4945]

135T-5H 2137 [970] 2112 [958] 2086 [946] 1851 [840] 1991 [903] 2132 [967] 12308 [5583] 145-5H 1839 [834] 2060 [934] 2281 [1035] 1970 [894] 2064 [936] 2158 [979] 12372 [5612]

155T-5H 2234 [1013] 2165 [982] 2097 [951] 1883 [854] 2065 [937] 2247 [1020] 12692 [5757] 170-5H 2000 [907] 2238 [1015] 2477 [1123] 2335 [1059] 2233 [1013] 2132 [967] 13415 [6085]

175T-5H 2667 [1210] 2428 [1101] 2190 [993] 1918 [870] 2301 [1044] 2683 [1217] 14187 [6435] 190-5H 2103 [954] 2258 [1024] 2414 [1095] 2612 [1185] 2262 [1189] 2632 [1194] 14641 [6641]

195T-5H 2761 [1252] 2768 [1255] 2774 [1259] 2275 [1032] 2445 [1109] 2626 [1187] 15639 [7094] 230-5H 3077 [1396] 3094 [1404] 3112 [1412] 3243 [1471] 3189 [1446] 3134 [1422] 18849 [8550] 245-5H 2593 [1176] 2847 [1291] 3101 [1407] 3337 [1514] 3342 [1516] 3346 [1518] 18565 [8421] 255-5H 3379 [1533] 3386 [1536] 3392 [1539] 3431 [1557] 3425 [1554] 3418 [1551] 20432 [9268] 265-5H 3004 [1363] 3238 [1469] 3472 [1575] 3718 [1686] 3825 [1735] 3933 [1784] 21191 [9612]

Page 22: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 22 -

FLOOR LOADING DIAGRAM 2.) AFHX 305-5H, 330-5H

a.) Point Load Location – Inches [mm]

Unit Model AFHX A Dim. B Dim. C Dim. D Dim. E Dim. F Dim.

305-5H 86 [2184] 28 [711] 101 [2565] 102 [2591] 101 [2565] 28 [711]

330-5H 86 [2184] 28 [711] 101 [2565] 102 [2591] 101 [2565] 28 [711]

b.) Point Load Data – lbs [kg] Unit Model

AFHX Pos. #1 Pos. #2 Pos. #3 Pos. #4 Pos. #5 Pos. #6 Pos. #7 Pos. #8 Total Operating Weight

305-5H 3108 [1410] 3102 [1407] 3096 [1405] 3090 [1402] 3120 [1415] 3126 [1418] 3132 [1421] 3138 [1424] 24914 [11301]

330-5H 3221 [1461] 3207 [1455] 3194 [1449] 3180 [1443] 3185 [1445] 3205 [1454] 3226 [1463] 3246 [1472] 25664 [11641]

Page 23: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 23 -

FLOOR LOADING DIAGRAM 3.) AFHX 355-5H, 390-5H, 450-5H, 515-5H, 550-5H, 585-5H, 640-5H

a.) Point Load Location – Inches [mm]

Unit Model AFHX A Dim. B Dim. C Dim. D Dim. E Dim. F Dim. G Dim. H Dim.

355-5H 86 [2184] 39.75 [1010] 64.5 [1638] 64.5 [1638] 64.5 [1638] 64.5 [1638] 64.5 [1638] 39.75 [1010]

390-5H 86 [2184] 40.75 [1035] 76.5 [1944] 76.5 [1944] 76.5 [1944] 76.5 [1944] 76.5 [1944] 40.75 [1035]

450-5H 86 [2184] 39.75 [1010] 64.5 [1638] 64.5 [1638] 64.5 [1638] 64.5 [1638] 64.5 [1638] 39.75 [1010]

515-5H 86 [2184] 40.75 [1035] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 40.75 [1035]

550-5H 86 [2184] 40.75 [1035] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 40.75 [1035]

585-5H 86 [2184] 40.75 [1035] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 72.5 [1842] 40.75 [1035]

640-5H 86 [2184] 43 [1092] 77 [1956] 77 [1956] 77 [1956] 77 [1956] 77 [1956] 43 [1092]

b.) Point Load Data – lbs [kg]

Unit Model AFHX

Pos. #1

Pos. #2

Pos. #3

Pos. #4

Pos. #5

Pos. #6

Pos. #7

Pos. #8

Pos. #9

Pos. #10

Pos. #11

Pos. #12

Total Operating

Weight

355-5H 2217 [1006]

2214 [1004]

2212 [1003]

2209 [1002]

2207 [1001]

2204 [1000]

2224 [1009]

2226 [1010]

2229 [1011]

2232 [1012]

2234 [1013]

2237 [1015]

26645 [12086]

390-5H 2831 [1284]

2782 [1262]

2732 [1239]

2682 [1217]

2633 [1194]

2583 [1172]

2603 [1181]

2653 [1203]

2703 [1226]

2752 [1248]

2802 [1271]

2851 [1293]

32608 [14791]

450-5H 2940 [1333]

2876 [1305]

2813 [1276]

2750 [1247]

2686 [1219]

2623 [1190

2520 [1143]

2606 [1182]

2692 [1221]

2778 [1260]

2864 [1299]

2951 [1338]

33100 [15014]

515-5H 3008 [1364]

3005 [1363]

3002 [1362]

3000 [1361]

2997 [1360]

2995 [1358]

3035 [1377]

3038 [1378]

3040 [1379]

3043 [1380]

3046 [1382]

3048 [1383]

36257 [16446]

550-5H 3157 [1432]

3151 [1429]

3144 [1426]

3138 [1424]

3132 [1421]

3126 [1418]

3167 [1437]

3173 [1439]

3179 [1442]

3186 [1445]

3192 [1448]

3198 [1451]

37943 [17211]

585-5H 3521 [1597]

3442 [1561]

3363 [1525]

3284 [1490]

3205 [1454]

3125 [1418]

3173 [1439]

3252 [1475]

3332 [1511]

3411 [1547]

3490 [1583]

3570 [1619]

40168 [18220]

640-5H 3897 [1768]

3810 [1728]

3724 [1689]

3638 [1650]

3551 [1611]

3465 [1572]

3576 [1622]

3655 [1658]

3733 [1694]

3812 [1729]

3891 [1765]

3970 [1801]

44722 [20286]

Page 24: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 24 -

DIMENSIONAL CLEARANCE SPACE REQUIREMENTS

Single Pit (See Note 2) Double Pit (See Note 2) Multi Pit Corner Wall

Notes: 1.) All dimensions are minimal, unless

otherwise noted. 2.) Pit installations are not re-

commended. Re-circulation of hot condenser air in combination with surface air turbulence cannot be predicted. Hot air re-circulation will severely affect unit efficiency (EER) and can cause high pressure or fan motor temperature trips. Dunham-Bush will not be responsible for ducting fans to a higher level to alleviate the above mentioned conditions.

Page 25: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 25 -

CONDENSER FAN Fan Position Number & Cycling Sequence

AFHX 100-5H, 100T-5H

AFHX 115T-5H, 125-5H, 135T-5H, 145-5H, 155T-5H, 170-5H, 175T-5H,

AFHX 190-5H, 195T-5H

BASE FANS 2, 4, 6, 8, 10 BASE FANS 2, 4, 6 BASE FANS 2, 4, 6, 8 STAGE 1 1, 5

STAGE 1 1, 5 STAGE 1 1, 5 STAGE 2 3, 7 STAGE 2 3 STAGE 3 3, 7 STAGE 3 9

AFHX 230-5H, 255-5H

AFHX 245-5H

SYSTEM1 SYSTEM 2 BASE FANS 2, 4, 6, 8, 10, 12 BASE FANS 8, 10, 12 2, 4, 6 STAGE 1 1, 5

STAGE 1 7, 11 1.5 STAGE 2 3, 7 STAGE 2 9 3 STAGE 3 9, 11

AFHX 265-5H

AFHX 305-5H, 330-5H

BASE FANS 2, 4, 6, 8, 10, 12, 14 SYSTEM 1 SYSTEM 2STAGE 1 1, 5, 11 BASE FANS 10, 12, 14, 16 2, 4, 6, 8 STAGE 2 3, 9 STAGE 1 9, 13 1, 5 STAGE 3 7, 13 STAGE 2 11, 15 3, 7

AFHX 355-5H

AFHX 390-5H, 515-5H, 550-5H

SYSTEM 1 SYSTEM 2 SYSTEM 1 SYSTEM 2 BASE FANS 12, 14, 16, 18, 20 2, 4, 6, 8, 10

BASE FANS 12, 14, 16, 18 2, 4, 6, 8, 10 STAGE 1 11, 15 1, 5 STAGE 1 11, 15 1, 5, 9 STAGE 2 13, 17 3, 7 STAGE 2 13, 17 3, 7 STAGE 3 19 9

AFHX 450-5H

AFHX 585-5H

SYSTEM 1 SYSTEM 2 SYSTEM 1 SYSTEM 2BASE FANS 10, 12, 14, 16, 18 2, 4, 6, 8 BASE FANS 10, 12, 14, 16, 18, 20 2, 4, 6, 8

STAGE 1 9, 13 1, 5 STAGE 1 9, 13 1, 5 STAGE 2 11, 15 3, 7 STAGE 2 15, 19 3, 7 STAGE 3 17 - STAGE 3 11, 17 -

AFHX 640-5H

SYSTEM 1 SYSTEM 2 BASE FANS 12, 14, 16, 18, 20, 22 2, 4, 6, 8, 10

STAGE 1 11, 15 1, 5 STAGE 2 17, 21 3, 9 STAGE 3 13, 19 7

Page 26: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 26 -

1

10

100

10 100 1000 10000

WATER FLOW RATE - GPM

PRE

SSU

RE D

ROP

- FT

IN W

G

AFHX 100-5HAFHX 100T-5HAFHX 115T-5H

AFHX 125-5HAFHX 135T-5H

AFHX 145-5HAFHX 155T-5H

AFHX 190-5HAFHX 195T-5H

AFHX 170-5HAFHX 175T-5H

AFHX 245-5HAFHX 230-5HAFHX 265-5HAFHX 255-5H

AFHX 305-5H AFHX 330-5H AFHX 355-5H AFHX 390-5H AFHX 450-5H AFHX 515-5H AFHX 550-5H AFHX 585-5H AFHX 640-5H

SOUND PRESSURE LEVEL AT 10M- FREE FIELD

SPL dBA BAND (Hz)

Model 63 125 250 500 1K 2K 4K 8K TOTAL NC

AFHX 100-5H 45 44 50 52 57 55 51 43 61 55

AFHX 100T-5H 46 45 51 53 58 56 51 44 62 60

AFHX 115T-5H 46 45 51 53 58 56 51 44 62 60

AFHX 125-5H 48 46 52 53 60 57 52 44 63 60

AFHX 135T-5H 47 46 51 53 58 56 52 44 62 60

AFHX 145-5H 48 47 53 54 60 58 53 44 64 60

AFHX 155T-5H 47 46 51 53 59 56 52 44 62 60

AFHX 170-5H 50 49 54 54 62 60 54 45 66 60

AFHX 175T-5H 47 46 52 53 59 57 52 44 63 60

AFHX 190-5H 51 49 55 55 63 60 55 46 66 60

AFHX 195T-5H 48 47 52 54 60 57 53 45 63 60

AFHX 230-5H 49 48 53 55 61 59 54 46 65 60

AFHX 245-5H 51 49 55 55 63 60 55 46 67 65

AFHX 255-5H 50 49 54 55 62 60 55 46 66 60

AFHX 265-5H 51 49 55 56 63 61 56 46 67 65

AFHX 305-5H 51 49 55 56 63 60 55 47 66 65

AFHX 330-5H 52 50 56 56 64 61 56 47 67 65

AFHX 355-5H 53 51 57 57 65 62 57 48 68 65

AFHX 390-5H 53 51 57 57 65 62 57 48 68 65

AFHX 450-5H 53 51 57 57 65 62 57 47 69 65

AFHX 515-5H 53 52 58 60 66 64 59 51 70 65

AFHX 550-5H 54 53 59 61 67 64 59 52 70 65

AFHX 585-5H 55 53 60 61 67 65 60 52 71 65

AFHX 640-5H 55 53 58 58 67 64 59 49 70 65

PRESSURE DROP

Page 27: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 27 -

ELECTRICAL DATA

AFHX MODEL

COMPRESSOR DATA COND. FAN MOTOR DATA UNIT ELECTRICAL DATA

MODEL QTY RLA LRA QTY HP FLA FLA MCA MFS

100-5 HX1512 1 154 815 6 1.5 3.2 173 212 350

100T-5 HX1309 2 88 420 6 1.5 3.2 195 217 300

115T-5 HX1311 2 94 485 8 1.5 3.2 214 237 300

125-5 HX1709 1 196 915 8 1.5 3.2 222 271 450

135T-5 HX1311 HX1509

1 1

93 124

485 720 8 3 4.9 256 287 400

145-5 HX1711 1 228 1285 8 3 4.9 267 324 500

155T-5 HX1509 2 127 720 8 3 4.9 293 325 450

170-5 HX1811 1 262 1390 8 3 4.9 301 367 600

175T-5 HX1509 HX1512

1 1

128 155

720 815 8 3 4.9 322 361 500

190-5 HX1813 1 287 1635 10 3 4.9 336 408 600

195T-5 HX1512 2 152 815 10 3 4.9 353 391 500

230-5 HX1512 HX1709

1 1

157 198

815 915

6 6

3 3

4.9 4.9 414 463 600

245-5 HX1813 1 375 1635 12 3 4.9 434 528 800

255-5 HX1709 HX1709

1 1

202 197

915 915

6 6

3 3

4.9 4.9 458 508 700

265-5 HX1817 1 403 2480 14 3 4.9 472 572 800

305-5 HX1711 HX1711

1 1

236 228

1285 1285

8 8

3 3

4.9 4.9 542 601 800

330-5 HX1711 HX1811

1 1

232 262

1285 1390

8 8

3 3

4.9 4.9 572 638 800

355-5 HX1811 HX1811

1 1

264 262

1390 1390

10 8

3 3

4.9 4.9 614 680 800

390-5 HX1813 HX1813

1 1

292 287

1635 1635

10 10

3 3

4.9 4.9 677 750 1000

450-5 HX1816 HX1816

1 1

294 373

2330 2330

8 10

3 3

4.9 4.9 755 848 1200

515-5 HX1816 HX1816

1 1

379 371

2330 2330

10 10

4 3

7.1 5.5 876 971 1200

550-5 HX1817 HX1817

1 1

412 401

2480 2480

10 10

4 4

7.1 7.1 955 1058 1200

585-5 HX1813 HX1813

1 2

293 294

1635 1635

8 12

4 4

7.1 7.1 1023 1097 1200

640-5 HX1816 HX1813

1 2

394 304

2330 1635

10 12

3 3

4.9 4.9 1110 1208 1600

Note: MCA - Minimum Circuit Ampacity MFS - Maximum Fuse Size RLA - Running Load Amps FLA – Full Load Amps LRA - Locked Rotor Amps

Page 28: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 28 -

TYPICAL WIRING SCHEMATIC TWO COMPRESSORS UNIT

Page 29: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 29 -

TYPICAL WIRING SCHEMATIC

Page 30: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 30 -

Ω

Ω

TYPICAL WIRING SCHEMATIC

Page 31: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

- 31 -

TYPICAL WIRING SCHEMATIC

Page 32: Air Cooled Screw Flooded Chillers Cooling Capacity: 97 …€¦ ·  · 2013-09-28The flooded evaporator with all the copper ... return to compressor both at full load and at reduced

M-S-0446E-1209Manufacturer reserves the right to change specifications without prior notice.

[email protected]

Americas

United States of AmericaDunham-Bush, Inc175 South Street, West Hartford,CT 06110, USA

Tel: 1-860-956 8500Fax: 1-860-953 3300

Africa

South AfricaDunham-Bush International(Africa) (Pty) LtdNo. 57 Sovereign DriveRoute 21 Corporate ParkIrene, PretoriaSouth Africa

Tel: 27-12-345 4202Fax: 27-12-345 4203

Europe

United KingdomDunham-Bush Limited8 Downley Road,Havant, Hampshire,England PO9 2JD

Tel : 44-23-9247 7700Fax: 44-23-9245 0396

India

Dunham Bush International (India) Pvt Ltd.Level 6, Pentagon P-2,Magarpatta CityHadapsar,Pune 411013, India Tel: 91-20-4014 7522Fax: 91-20-6628 0011

Russia & CIS

RussiaDunham-Bush ClimateEquipment LLCLot 11, Novinskiy Boulevard,Moscow,121099 Russian Federation

Tel: 7-499-255 6953Fax: 7-499-255 6953

Malaysia

Dunham-Bush Industries Sdn BhdLot 5755-6, Kidamai Industrial Park,Bukit Angkat,43000 Kajang,Selangor Darul Ehsan,Malaysia

Tel: 603-8733 9898Fax: 603-8739 5020

China

The People's Republic of ChinaDunhan-Bush Yantai Co.,LtdNo. 1 Dunham-Bush Road,Laishan District, Yantai,Shandong Province,China 264003

Tel: 86-535-658 8999Fax: 86-535-658 1999

Middle East & North Africa

United Arab EmiratesDunham-Bush LLCWarehouse #3, Plot 111Damascus Street,PO Box 30922Al Qusais, Dubai, UAE

Tel: 971-4-261 7423Fax: 971-4-261 7424

Asia

SingaporeDunham-Bush InternationalPte Ltd146B, Paya Lebar Road,No. 05-01, ACE Building,Singapore 409017

Tel: 65-6842 2012Fax: 65-6842 2013

Products that perform...By people who care