air flow meter dc 24 v modelvibration: 10 to 500 hz, 2with 1.5 mm amplitude or 98 m/s acceleration,...

16
No. CP-SS-1874E Air Flow meter DC 24 V model Features • With a microflow sensor made possible by silicon micro- machining and thin-film technologies, a wide measurement range of 50:1 and mass flow rate measurement that does not require temperature and pressure compensation have been achieved. • Standard features include 4–20 mA output and pulse out- put. Modbus communication is available as an optional function. • Display of the instantaneous flow rate and totalized flow enables easy checking in the field. • With the waterproof structure for indoor use (IP65), the device can be installed in a wet area. • cULus-marked (MCF_ _ _ _ ARND models only) Specifications General specifications Characteristics stated in these tables are under the standard conditions below, unless otherwise specified. · Operating environment: Standard (see page 3) · Measured gas: Air · Pressure: 0.3 ± 0.025 MPa · Flow rate: Converted for 0 °C and 101.325 kPa (abs) · Settings: Factory defaults · Warm-up time: 30 minutes after power-on Item MCF0080 MCF0150 MCF0151 MCF0250 MCF0400 MCF0500 Compatible gas Air/nitrogen The gas must be dry and not contain corrosive components (chlorine, sulfur, or acid). Also, it must be clean, without dust or oil mist. Full scale (FS) flow rate * 1 [L/min] 200 500 1000 3000 6000 12000 Accuracy-guaranteed flow rate range [L/min] * 2 4 to 200 10 to 500 20 to 1000 60 to 3000 120 to 6000 240 to 12000 Minimum sensitivity [L/min] 2 5 10 30 60 120 Display resolution [L/min] * 3 Instantaneous flow rate 1 1 2 5 10 10 Totalized flow 10 10 10 10 100 100 Maximum display range [L/min] -60 to +400 -150 to +1000 -300 to +2000 -900 to +6000 -1800 to +12000 -3600 to +24000 [m 3 /h] -3.6 to +24.0 -9.0 to +60.0 -18.0 to +120.0 -54.0 to +360 -108.0 to +720.0 -220.0 to +1440.0 [m 3 /min] -0.060 to +0.400 -0.150 to +1.000 -0.300 to +2.000 -0.900 to +6.000 -1.800 to +12.000 -3.600 to +24.000 [kg/h] -4.7 to +31.0 -11.6 to +77.6 -23.2 to +155.2 -70 to +465.5 -140.0 to +931.0 -279.0 to +1862.0 Indication accuracy for instantaneous flow rate ±3 % FS ± 1 digit (excluding 0 to 2 % of FS flow rate) * 6, * 7 Indication repeatability for instantaneous flow rate ±1 % FS ± 1 digit (2 to 100 % of FS flow rate) Temperature characteristics ±0.15 % FS / °C ± 1 digit or less Pressure characteristics Operating pressure 0 to 1 MPa -0.25 % FS / 0.1 MPa ± 1 digit or less (2 to 40 % of FS flow rate) -0.55 % FS / 0.1 MPa ± 1 digit or less (40 to 100 % of FS flow rate) Operating pressure -0.07 to 0 MPa ±0.25 % FS / 0.01 MPa ± 1 digit or less (2 to 40 % of FS flow rate) ±0.55 % FS / 0.01 MPa ± 1 digit or less (40 to 100 % of FS flow rate) 1

Upload: others

Post on 08-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

No. CP-SS-1874E

Air Flow meterDC 24 V model

Features•Withamicroflowsensormadepossiblebysiliconmicro-machiningandthin-filmtechnologies,awidemeasurementrangeof50:1andmassflowratemeasurementthatdoesnotrequiretemperatureandpressurecompensationhavebeenachieved.

•Standardfeaturesinclude4–20mAoutputandpulseout-put.Modbus communication is available as anoptionalfunction.

•Displayoftheinstantaneousflowrateandtotalizedflowenableseasycheckinginthefield.

•Withthewaterproofstructureforindooruse(IP65),thedevicecanbeinstalledinawetarea.

• cULus-marked(MCF____ARNDmodelsonly)

Specifications General specifications

Characteristicsstatedinthesetablesareunderthestandardconditionsbelow,unlessotherwisespecified.·Operatingenvironment:Standard(seepage3)·Measuredgas: Air·Pressure: 0.3±0.025MPa·Flowrate: Convertedfor0°Cand101.325kPa(abs)·Settings: Factorydefaults·Warm-uptime: 30minutesafterpower-on

Item MCF0080 MCF0150 MCF0151 MCF0250 MCF0400 MCF0500Compatible gas Air/nitrogen

The gas must be dry and not contain corrosive components (chlorine, sulfur, or acid).Also, it must be clean, without dust or oil mist.

Full scale (FS) flow rate *1 [L/min]

200 500 1000 3000 6000 12000

Accuracy-guaranteed flow rate range [L/min] *2

4 to 200 10 to 500 20 to 1000 60 to 3000 120 to 6000 240 to 12000

Minimum sensitivity [L/min] 2 5 10 30 60 120Display resolution[L/min] *3

Instantaneous flow rate

1 1 2 5 10 10

Totalized flow 10 10 10 10 100 100Maximum display range

[L/min] -60 to +400 -150 to +1000 -300 to +2000 -900 to +6000 -1800 to +12000 -3600 to +24000[m3/h] -3.6 to +24.0 -9.0 to +60.0 -18.0 to +120.0 -54.0 to +360 -108.0 to +720.0 -220.0 to +1440.0[m3/min] -0.060 to +0.400 -0.150 to +1.000 -0.300 to +2.000 -0.900 to +6.000 -1.800 to +12.000 -3.600 to +24.000[kg/h] -4.7 to +31.0 -11.6 to +77.6 -23.2 to +155.2 -70 to +465.5 -140.0 to +931.0 -279.0 to +1862.0

Indication accuracy for instantaneous flow rate

±3 % FS ± 1 digit (excluding 0 to 2 % of FS flow rate) *6, *7

Indication repeatability for instantaneous flow rate

±1 % FS ± 1 digit (2 to 100 % of FS flow rate)

Temperature characteristics ±0.15 % FS / °C ± 1 digit or lessPressure characteristics

Operating pressure0 to 1 MPa

-0.25 % FS / 0.1 MPa ± 1 digit or less (2 to 40 % of FS flow rate)-0.55 % FS / 0.1 MPa ± 1 digit or less (40 to 100 % of FS flow rate)

Operating pressure-0.07 to 0 MPa

±0.25 % FS / 0.01 MPa ± 1 digit or less (2 to 40 % of FS flow rate)±0.55 % FS / 0.01 MPa ± 1 digit or less (40 to 100 % of FS flow rate)

1

Page 2: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Item MCF0080 MCF0150 MCF0151 MCF0250 MCF0400 MCF0500Error in instantaneous flow rate display for mounting ori-entation #2 *4

Operating pressure0 to 1 MPa

0.5 % FS / 0.1 MPa ± 1 digit or less (5 to 100 % of FS flow rate)

Operating pressure-0.07 to 0 MPa

0.5 % FS / 0.01 MPa ± 1 digit or less (5 to 100 % of FS flow rate)

Error in instantaneous flow rate display for mounting ori-entation #3 *5

Operating pressure0 to 1 MPa

-0.5 % FS / 0.1 MPa ± 1 digit or less (5 to 100 % of FS flow rate)

Operating pressure-0.07 to 0 MPa

-0.5 % FS / 0.01 MPa ± 1 digit or less (5 to 100 % of FS flow rate)

Operating pressure -0.07 to +1.0 MPa (gauge pressure)Operating temperature -10 to +60 °C (without freezing)Operating humidity 0–90 % RH (without condensation)Storage temperature -20 to +70 °C (without freezing)Storage humidity range 0–90 % RH (without condensation)Pressure resistance 1.5 MPa (gauge pressure)Allowable leakage rate 100 mL/h (at an internal pressure of 1.5 MPa)Pipe size (RC or G depending on the model)

¼B ½B ½B 1B 1½B 2B

Rated voltage 24 V DCSupply voltage range 22.8 to 25.2 V DCCurrent consumption 120 mA max.Measurement cycle 50 ± 5 ms (factory default)Instantaneous flow rate output (4 to 20 mA output models only)

Current output: 4 to 20 mA (output range: 3.2 to 20.8 mA)Output at alarm occurrence (upper): 21.6 ±0.4 mA (factory default, selectable)Output at alarm occurrence (lower): 0.0 ±0.4 mA (fixed)Allowable load resistance: 300 Ω max.Maximum output current: 24 mA max.

Response time 1.5 s max. (time until the output reaches 95 % of the final value after a 0→100 % FS step input,with a 50 ms measurement cycle and calculation filter 8)*8

Event output *9 Open collector output: 30 V DC, 50 mA max.Selectable from the following functions:

• Instantaneous flow rate (upper limit, lower limit, or within range)• Totalized flow (count-up, countdown)• Alarm output• Totalizer pulse output (three pulse weight options are available)

RS-485 communication(models with RS-485 function only)

3-wire systemTransmission speed: 4800, 9600, 19200 bpsProtocol: Modbus

Data storage Nonvolatile semiconductor memory (EEPROM)Recorded data: function settings, parameters, total flow, etc.

Dielectric strength Leak current: 1 mA max.when 500 V AC is applied for 1 s between connector pins and the main flow path or mounting bolts.

Insulation resistance 50 mΩ min.50 MΩ or more between connector pins and the main flow path or mounting bolts, with 500 V DC megger

Measurement module mount-ing bolt tightening torque

2.6 to 3.3N·m

Protective structure IP65 (JIS C0920 and IEC 529): drip-proof and dust-proof structure premised on indoor useStandards compliance CE-marked: EN 61326-2-3:2013, EN 61326-1:2013 (To be used in industrial electromagnetic environment)

During EMC testing, the reading or output may fluctuate by the equivalent of ±10 % FS.UL-certified: UL File No. E246616 (MCF_ _ _ _ARND010000, MCF_ _ _ _ARND0100D0, MCF_ _ _ _ARND0100Y0 only)

Weight Approx. 400 g Approx. 400 g Approx. 400 g Approx. 500 g Approx. 700 g Approx. 1.1 kg

*1 "FS flow rate" means full scale flow rate.*2 If the primary pressure is lower than the pressure shown below, do not use the device with an actual flow rate of more than 40 m/s.

A measurement error may occur because of decreased flow rate in the measurement module. 0.05 MPa (gauge): MCF0080, MCF0150, MCF0151 0.15 MPa (gauge): MCF0250, MCF0400, MCF0500

Note: The accuracy-guaranteed flow rate range when the fluid temperature is 20 °C and the primary pressure is 101.325 kPa (abs) (i.e., atmospheric pressure) is shown below (converted to 0 °C and 101.325 kPa (abs)).

MCF0080: 4 to 200 L/min (normal) MCF0150: 10 to 500 L/min (normal) MCF0151: 20 to 540 L/min (normal) MCF0250: 60 to 1470 L/min (normal) MCF0400: 120 to 3300 L/min (normal) MCF0500: 240 to 5300 L/min (normal)

*3 The resolution is for the least-significant displayed digit, regardless of the position of the decimal point or the unit of flow rate.*4 Horizontal piping with the display facing right when viewing the air inlet.*5 Horizontal piping with the display facing left when viewing the air inlet.*6 The accuracy of the instantaneous flow rate indication changes to ±5 % FS ± 1 digit if the measurement module is reassembled.*7 The accuracy of the instantaneous flow rate indication changes to ±5 % FS ± 1 digit if the measurement module is replaced with

a new one. (MCF0250, MCF0400, MCF0500)*8 The response time is approx. 0.5 s with a 50 ms calculation cycle and calculation filter 1.*9 Terminal output is not available for models with RS-485 communication. Only LED lighting and status flag reading are available.

2

Page 3: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Material and Treatment

(2)

(1)

(4)(3)

Model No. MCF_ _ _ _A_ _ _ _ _ _ _ _ _ MCF_ _ _ _F_ _ _ _ _ _ _ _ _(1) Main flow path Aluminum alloy (anodized) Aluminum alloy (anodized, ultrasonically

cleaned in cleaning solution)(2) Measurement module SUS304, PBT, HNBR, urethane foam SUS304 (immersed in cleaning solution), PBT,

FKM, urethane foam(3) Packing HNBR FKM (immersed in cleaning solution)(4) Measurement module electronic

component caseModified PPO Modified PPO

Note:ThemainflowpathofGthreadconnectionmodelshasnoanodizingtreatment.

Environmental Conditions Standard conditionsAmbienttemperature: 23±3°CAmbienthumidity: 60±5%RHSupplypower: 24VDCVibration: 0m/s2Shock: 0m/s2Mountingorientation: Mountedonahorizontalpipewiththedisplayunitfacingupward

Operation conditionsAmbienttemperature: –10to+60°C(withoutfreezing)Ambienthumidity: 0to90%RH(withoutcondensation)Supplypower: 22.8to25.2VDCVibration: 0m/s2Shock: 0m/s2Mountingorientation: Horizontalorvertical

Transportation conditionsAmbienttemperature: –20to+70°CAmbienthumidity: 0to90%RHVibration: 10to500Hz,with1.5mmamplitudeor98m/s2acceleration,whicheverissmallerShock: 490m/s2Packagedroptest: Dropheight60cm(freefallon1corner,3edges,6sides)

Filter Installation(1) Ifoilmist,dust,etc.,entersthedevice,measurementerrorordevicefailuremayresult.Ifthereisapossibilityofforeign

matterenteringthedevice,besuretoinstallthefiltershownbelow.Inaddition,ifcompressedairisused,adryermustbeinstalledupstreamofthedevice.

(2) Purgeandthoroughlycleantheinsideofpipingthatisupstreamanddownstreamofthedevicetoremoveweldingfumesanddust,whichmayenterduringpipingwork.

MCFapplicablefilter:MFF25S

MFF25S

3

Page 4: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Model Selection TableBasic Model

No.

Pipe size/ flow rate

range

Material Con-nection

Gas type

Power/output/comm.

Option 1

Option 2

Option 3

Ap-pendix

Specifications

MCF Air flowmeter, model MCF0080 Diameter: 8A (¼B), flow rate range 200 L/min (normal)

0150 Diameter: 15A (½B), flow rate range 500 L/min (normal)0151 Diameter: 15A (½B), flow rate range 1000 L/min (normal)0250 Diameter: 25A (1B), flow rate range 3000 L/min (normal)0400 Diameter: 40A (1½B), flow rate range 6000 L/min (normal)0500 Diameter: 50A (2B), flow rate range 12000 L/min (normal)

A Main unit material: aluminum alloyRubber: HNBR

F Main unit material: aluminum alloy (degreased *1)Rubber: FKM

R Rc thread (JIS B 203 / ISO 7-1)G G thread (JIS B 202 / ISO 228-1)

N Air/nitrogenD01 24 V DC / 4 to 40 mA / event output D10 24 V DC / RS-485 communications

0 None0 None

0 Without optionsK Anti-sulfuration treatment *2, *3

D With inspection reportL Anti-sulfuration treatment and inspection certificate *2, *3

Y With traceability certificationX Anti-sulfuration treatment and traceability certificate *2, *3

0 Product version

*1 For degreasing, see “Material and Treatment” on page 3.*2 HumiSeal, manufactured by AR Brown Co., Ltd, is applied to the circuit board, with the exception of some parts that cannot be varnished due to

their function, such as the display unit, switches, etc.*3 K, L, and X of Option 3 are not available for MCF_ _ _ _ F models (main unit: degreased aluminum alloy; rubber: FKM).

Optional Parts (sold separately)Name Model No. Cable length Characteristics Color

Cable with dedicated connectors PA5-4ISX2SKPA5-4ISX3SKPA5-4ISX5SK

2 m3 m5 m

Oil-resistant, bend-tolerantFlame-resistant cableUL 2464Compliant with EN standards

1− Brown2− White3− Blue4− Black

PA5-4ISX2HK-EPA5-4ISX3HK-EPA5-4ISX5HK-E

2 m3 m5 m

Oil-resistantFlame-resistant cableUL2464Compliant with EN standards

Cable with relay connector(straight cable) PA5-4ISB2SK

PA5-4ISB3SKPA5-4ISB5SK

2 m3 m5 m

Oil-resistant, bend-tolerantFlame-resistant cableUL 2464Compliant with EN standards

PA5-4ISB2HK-EPA5-4ISB3HK-EPA5-4ISB5HK-E

2 m3 m5 m

Oil-resistantFlame-resistant cableUL 2464Compliant with EN standards

Product name Model No. DescriptionMounting bracket 81446721-001 For MCF0080/0150/0151/0250

Maintenance PartsName Model No. Description

Measurement module

81447192-201 For MCF _ _ _ _ A _ND01 _ _ _ _ For MCF0250/0400/050081447192-221 For MCF _ _ _ _ A _ND10 _ _ _ _81447192-401 For MCF _ _ _ _ F _ND01 _ _ _ _81447192-421 For MCF _ _ _ _ F _ND10 _ _ _ _81447192-601 For MCF _ _ _ _ A _ND01 _ _ _ _ (anti-sulfuration)81447192-621 For MCF _ _ _ _ A _ND10 _ _ _ _ (anti-sulfuration)

4

Page 5: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

External Dimensions(Unit:mm)

MCF0080

M4 (2), thread depth: 7(for screws)

Mounting bracket

ThreadRc ¼ (2) or G ¼ (2) (thread depth: 11)(depends on the model)

Cable with dedicated connectors

M12 connector

23.5

65.8

27

4824

13.5

(90)

(75)

4775

(78)

(63)

(4.5)

3415

(46.

5)(8

)

mode

enter

ALEVLL/min

MCF0150/0151

Mounting bracket

ThreadRc ½ (2) or G ½ (2) (thread depth: 15)(depends on the model)

Cable with dedicated connectors

M4 (2), thread depth: 7(for screws)

M12 connector

23.5

(4.5)

4775 (8)

(46.

5)

3415

(63)

(78)

65.8

27

4824

13.5

(90)

(75) mode

enter

ALEVLL/min

5

Page 6: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

(Unit:mm) MCF0250

ThreadRc 1 (2) or G 1 (2) (thread depth: 15)(depends on the model)

Cable with dedicated connectors

M4 (2), thread depth: 7(for screws)

Mounting bracket

M12 connector

23.5

(90)

(75)

47

79.8

27

4824

13.5

(63)

(78)

(4.5)

90(6

0.5)

(8)

23.5

48

mode

enter

ALEVLL/min

MCF0400

M5 (2), thread depth: 7(for screws)

Cable with dedicated connectors

ThreadRc 1½ (2) or G 1½ (2) (thread depth: 19.1)(depends on the model)

M12 connector

30

30

(74.

5)

62

100

93.8

60

34

17

6130.5

mode

enter

ALEVLL/min

6

Page 7: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

(Unit:mm) MCF0500

M12 connector

M4 (2), thread depth: 7(for screws)

ThreadRc 2 (2) or G 2 (2) (thread depth: 21.4)(depends on the model)

37.5

(87.

5)

7537

.5

75

106.

8

110

30.561

1734

mode

enter

ALEVLL/min

Cable with dedicated connectors

7

Page 8: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Wiring Connector

Pin No. Signal name 4 to 20 mA output modelsMCF_ _ _ _ _ _ _D01_ _ _ _

RS-485 communication modelsMCF_ _ _ _ _ _ _D10_ _ _ _

1 V+ 24 V DC 24 V DC2 I+ /DB Instantaneous flow rate output (4 to 20 mA) RS-485 communication (DB)3 COM COM COM4 EV/DA Event output RS-485 communication (DA)

Correspondence of pin No. and color of wire in cable with dedicated connectorPin No. Signal name Wire color

1 V+ Brown2 I+ /DB White3 COM Blue4 EV/DA Black

Wiring example• 4 to 20 mA output models (MCF_ _ _ _ _ _ _D01_ _ _ _)

1

2

3

4

V+

I+

COM

EV

Instantaneous flow rate output4 to 20 mA

Allowable load resistance300 Ω max.

Load

22.8–25.2 V DC

30 V DC max.

30 V DC, 50 mA max.

External connection exampleInternal circuit

• RS-485 communication models (MCF_ _ _ _ _ _ _D10_ _ _ _)Attachterminatingresistors(150Ω±5%,½Wmin.)tobothendsofthetransmissionline.Theframegroundshouldbeconnectedtooneendoftheshieldedcableonly.CMC10L001A000,madebyAzbilCorporation,canbeusedasaconverterforcommunicationwiththemasterstation.

Terminating resistor

DA

DB

SG

DA

DB

COM

FG

Shielded frame groundFG

Host station

MCF (slave station)

V+

Internal circuit

DA

DB

SG

Shielded frame groundFG

Slave station(MCF, etc.)

Terminating resistor

4

2

3

1

External connection example

22.8–25.2 V DC

8

Page 9: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Straight Pipe Length• Connection with a different size pipe, valve, or filterInstallastraightpipeaccordingtothetablebelow.*1Ifadevicethatisnotlistedinthetablebelowisinstalledeitherupstreamordownstream,contacttheazbilGroupfortherequiredlengthofthestraightpipesection.Ifreverseflowismeasuredinadditiontotheregularforwardflow,thelengthofthedownstreamstraightpipemustbethesameastheupstreamone.

Pipe and connected device Position Straight sectionWithin the specifications (±3 % FS) Within an accuracy of ±5 % FS

MFF25S filter *3

(for MCF0080/0150/0151/0250)Upstream 10D Not needed

MFF25L series filter *3

(for MCF0400/0500)Upstream 20D Not needed

Pipe one size larger in diameter(with a reducer) *4, *5

MCF0080: ⅜B → ¼BMCF0150/0151: ¾B → ½BMCF0250: 1¼B → 1BMCF0400: 2B → 1½B

Upstream 5D Not needed

Downstream Not needed Not needed

Pipe one size larger in diameter(with a reducer) *4, *5

MCF0500: 2½B → 2B

Upstream 10D 5D

Downstream 5D 5D

Pipe one size smaller in diameter(with a reducer] *4, *6

MCF0080: ⅛B → ¼BMCF0150/0151: ⅜B → ½BMCF0250: ¾B → 1BMCF0400: 1¼B → 1½B

Upstream 20D 5D

Downstream Not needed Not needed

Pipe one size smaller in diameter(with a reducer] *4, *6

MCF0500: 1½B → 2B

Upstream 25D 10D

Downstream 5D 5D

Single elbow *7 Upstream 10D Not neededDownstream Not needed Not needed

Double elbow *7 Upstream 10D 10DDownstream Not needed Not needed

Ball valve (full-bore, full open) *8 Upstream Not needed Not neededDownstream Not needed Not needed

Regulator *9

MCF0080Upstream 200D Not needed

Downstream 10D Not neededRegulator *9

MCF0150, MCF0151, MCF0250, MCF0400, MCF0500

Upstream 30D Not needed

Downstream 5D Not needed

Air filter Upstream 25D Not needed

*1 Connecting a carbon steel pipe for pressure service (JIS G 3454) or a stainless pipe (JIS G 3459) greater than schedule 40 will cause decreased accuracy. (The larger the schedule number, the smaller the inner pipe diameter. For this reason accuracy is affected.)

*2 The connection port size (D) is approximately 8 mm for the MCF0080 (¼B), 15 mm for the MCF0150/0151 (½B), 25 mm for the MCF0250 (1B), 40 mm for the MCF0400 (1½B), and 50 mm for the MCF0500 (2B).

*3 The table shows the straight pipe length required if the filter has the same size (bore) as the MCF.*4 MCF models and connecting pipe sizes are shown below.

Model / Pipe size ⅛B ¼B ⅜B ½B ¾BMCF0080 +

MCF0150/0151 +

Model / Pipe size ¾B 1B 1¼B 1½B 2B 2½BMCF0250 +MCF0400 +MCF0500 +

: Pipe one size smaller than the MCF : Pipe the same size as the MCF

 + : Pipe one size larger than the MCF

9

Page 10: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

*5 The figure below shows an example of the MCF0080 connected with reducers. The accuracy is within the specifications (±3 % FS). If the MCF is connected to a pipe more than one size larger (e.g., MFC0080 to a ½B pipe), the straight pipe length is the same as that shown for “Pipe one size larger in diameter (with a reducer)” in the “Pipe and connected device” table on the previous page.

MCF0080

3/8B 1/4B 3/8B

5D

*6 The figure below shows an example of the MCF0150 connected with reducers. The accuracy is within the specifications (±3 % FS).

MCF01501/2B3/8B

20D

3/8B

Do not connect a smaller size pipe to theMCFwithout a section of straight pipe. Even though there is a regu-lar forward f low in themain f low path, theremay be a reverse f low in themeasurementmodule, resulting in adisplay of “–0.”Alternatively, the displaymay show a f low rate that is considerably lower than the actual rate.If theMCF is connected to a pipemore than one size smaller (e.g.,MCF0150 to a¼Bpipe), add 5D to the speci-fied straight pipe length* before theMCF. The straight pipe length after theMCF is the same as that shown for“Pipe one size smaller in diameter (with reducer)” in the “Pipe and connected device” table on the previous page.*ThespecifiedstraightpipelengthisrequiredifapipeonesizesmallerindiameterisconnectedtotheMCF.

MCF01501/2B1/4B

25D

1/4B

*7 The figures below show examples of connections with a single elbow and with a double elbow.

10D

Single elbow

10D

Double elbow

*8 This valve does not have an internal constriction. Install flow control valves downstream of the MCF, if possible.*9 A regulator should be at least the specified distance away from the MCF. It does not matter if the piping from the regulator to the MCF is

tubing or contains an elbow, for example. However, in the case of an elbow, use the necessary straight pipe section before the MCF.

RegulatorElbow

10D or longer straight pipe sectionDistance from MCFMCF0080: 200D or moreOther models: 30D or more

10

Page 11: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

• Connection with a tube fitting for air supply pipingIfatubefittingisconnectedfortheairsupplypipingtotheMCF,installastraightpipesectionasshownbelow.ConnectingatubefittingtotheMCFwithoutastraightpipesectionmaycauseareverseflowinthemeasurementmodule,eventhoughthereisaregularforwardflowinthemainflowpath,resultinginadisplayof“–0.”Alternatively,thedisplaymayshowaflowratethatisconsiderablylowerthantheactualrate.Thespecificationsshownbelowapplytostraightpipesonly.Inthecaseofanelbow,add5Dtothestraightpipelength.Thisiswhenthetubeextendsabout300mmalmoststraightfromthefitting.

Tube fitting for air supply piping

TubeStraight pipe

Pipe and connected device Position Straight sectionWithin the specifications (±3 % FS) Within an accuracy of ±5 % FS

Tube fitting for air supply pipingTube size: 8 mm dia. (6 mm bore)(MCF800)

Upstream 15D 5D

Downstream Not needed Not needed

Tube fitting for air supply pipingTube size: 12 mm dia. (8 mm bore)(MCF800)

Upstream 5D Not needed

Downstream Not needed Not needed

Tube fitting for air supply pipingTube size: 12 mm dia. (8 mm bore)16 mm dia. (12 mm bore) (MCF0150)

Upstream 10D 5D

Downstream Not needed Not needed

Tube fitting for air supply pipingTube size: 16 mm dia. (12 mm bore)(MCF0151)

Upstream 20D 10D

Downstream Not needed Not needed

Tube fitting for air supply pipingTube size: 12 mm dia. (8 mm bore)16 mm dia. (12 mm bore) (MCF0250)

Upstream 10D 8D

Downstream 5D 5D

• Rotation of the display unitAsshownbelow,thedisplayunitcanberotated90˚counterclockwiseand180˚clockwisefromthedefaultposition.

Clockwise

Counterclockwise

11

Page 12: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Mounting OrientationThestandardwaytomountthisdeviceisonahorizontalpipewiththedisplayunitfacingupward.Althoughmountingwithanyorientationispossible,theremaybeameasurementerrordependingonthepositionofthedisplayunit.

· Vertical (orientation #5)

· Horizontal with the display facing upward (standard; = orientation #1)

· Horizontal with the display facing right when viewing the air inlet (orientation #2)

· Horizontal with the display facing left when viewing the air inlet (orientation #3)

Flow direction

Flow direction

Side view

Flow direction

Flow direction

Flow direction

Side viewView of air inlet and display

Side viewView of air inlet and display

mode

enter

ALEVLL/min

· Horizontal with with the display facing downward (orientation #4)

Side view

Flow direction

mod

e

ente

r

AL

EV

LL/

min

mode

enter

AL

EV

LL/m

in

12

Page 13: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

• Mounting on a horizontal pipe with the display facing right when viewing the air inlet (mounting orientation #2)Operating pressure Flow rate range Error in instantaneous flow rate

0 to 1 MPa 5 to 100 % of FS* flow rate 0.5 % FS / 0.1 MPa ± 1 digit or less-0.07 to 0 MPa 5 to 100 % of FS* flow rate 0.5 % FS / 0.01 MPa ± 1 digit or less

*FS:fullscaleExample:Ifthedeviceismountedonahorizontalpipewiththedisplayunitfacingrightwhenviewingtheairinlet,theinstan-

taneousflowrateerrorat0.3MPaisamaximumof1.5%FS±1digitascomparedwithinthestandardposition.0.5[%FS/0.1MPa]×0.3[MPa]=1.5[%FS]

Note:Errorcanbecorrectedbythekeys.

• Mounting on a horizontal pipe with the display facing right when viewing the air inlet (mounting orientation #3)Operating pressure Flow rate range Error in instantaneous flow rate

0 to 1 MPa 5 to 100 % of FS* flow rate -0.5 % FS / 0.1 MPa ± 1 digit or less-0.07 to 0 MPa 5 to 100 % of FS* flow rate -0.5 % FS / 0.01 MPa ± 1 digit or less

* FS: full scale Example: If the device is mounted on a horizontal pipe with the display unit facing left when viewing the air inlet, the instantaneous flow rate error

at 0.3 MPa is a maximum of -1.5 % FS ± 1 digit as compared with in the standard position. -0.5 [% FS / 0.1 MPa] × 0.3 [MPa] = -1.5 [% FS]

Note: Error can be corrected by the keys.

Handling Precautions• If the device is mounted on a horizontal pipe with the display facing right or left when viewing the air inlet, setting the

low-flow cutoff to "5" (±5 % of FS flow rate) or less is recommended. If the low-flow cutoff is not set, a flow rate may be displayed when there is no flow, and the amount of total flow may be increased by the totalizing/reverse-totalizing function.

• Mounting on a horizontal pipe with the display unit facing downward (orientation #4), mounting on a vertical pipe (orientation #5)Thecharacteristicsofthedevicedonotchangeascomparedwiththestandardposition.However,ifthedeviceismountedonahorizontalpipewiththedisplayfacingdownward,accuracymaydecreaseovertimeduetotheaccumulationwithinthesensorofmoisture,mist,ordustfromthemeasuredfluid.

13

Page 14: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

Pressure LossTypicalcharacteristicsareshownbelow.Characteristicsfor0–100%FSflowrateareshownontheleftandcharacteristicsfor100–200%FSflowrateareshownontheright.

MCF0080 (¼B)

0 50

Flow rate [L/min] Flow rate [L/min]

0 to 100 % of FS flow rate 100 to 200 % of FS flow rate

Pre

ssur

e lo

ss [k

Pa]

100kPa

Primary pressure

300kPa500kPa700kPa

0

2

4

6

8

100 150 200 0

Pre

ssur

e lo

ss [k

Pa]

100kPa

Primary pressure

300kPa

500kPa700kPa

0

20

15

10

5

25

35030025020015010050 400

MCF0150 (½B)

0 100

Flow rate [L/min] Flow rate [L/min]

0 to 100 % of FS flow rate 100 to 200 % of FS flow rate

Pre

ssur

e lo

ss [k

Pa]

100kPa

Primary pressure

300kPa

500kPa700kPa

0

2

4

6

8

200 300 400 500 0

Pre

ssur

e lo

ss [k

Pa] 100kPa

Primary pressure

300kPa

500kPa

700kPa

0

20

15

10

5

25

800600400200 1000

MCF0151 (½B)

0 200

Flow rate [L/min] Flow rate [L/min]

0 to 100 % of FS flow rate

Pre

ssur

e lo

ss [k

Pa] 100kPa

Primary pressure

300kPa

500kPa700kPa

0400 600 800 1000

Pre

ssur

e lo

ss [k

Pa] 100kPa

Primary pressure

300kPa500kPa700kPa

0

80

60

40

20

100

20

15

10

5

25100 to 200 % of FS flow rate

0 16001200800400 2000

14

Page 15: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

MCF0250 (1B)

0 500

Flow rate [L/min]

Pre

ssur

e lo

ss [k

Pa]

100kPa

300kPa

500kPa700kPa

1000 2500 30001500 20000

5

10

15

20Primary pressure

Flow rate [L/min]

0 to 100 % of FS flow rate 100 to 200 % of FS flow rate

0

Pre

ssur

e lo

ss [k

Pa]

100kPa

Primary pressure

300kPa

500kPa700kPa

0

80

60

40

20

100

50004000300020001000 6000

MCF0400 (1½B)

0 1000

Flow rate [L/min]

Pre

ssur

e lo

ss [k

Pa]

100kPa

300kPa

500kPa700kPa

2000 5000 60003000 40000

5

10

15

20Primary pressure

Flow rate [L/min]

0 to 100 % of FS flow rate 100 to 200 % of FS flow rate

0

Pre

ssur

e lo

ss [k

Pa]

100kPa

Primary pressure

300kPa

500kPa700kPa

0

80

60

40

20

100

100008000600040002000 12000

MCF0500 (2B)

0 2000

Flow rate [L/min]

Pre

ssur

e lo

ss [k

Pa]

100kPa

300kPa

500kPa700kPa

4000 10000 120006000 80000

5

10

15

20

25 Primary pressure

0 to 100 % of FS flow rate

0 4000

Flow rate [L/min]

Pre

ssur

e lo

ss [k

Pa]

100kPa

300kPa

500kPa700kPa

8000 20000 2400012000 160000

20

40

60

80

100 Primary pressure

100 to 200 % of FS flow rate

15

Page 16: Air Flow meter DC 24 V modelVibration: 10 to 500 Hz, 2with 1.5 mm amplitude or 98 m/s acceleration, whichever is smaller Shock: 490 m/s2 Package drop test: Drop height 60 cm (free

1st edition: Nov. 2017

(13)

Please read “Terms and Conditions” from the following URL before ordering and use.

http://www.azbil.com/products/factory/order.html

1-12-2 Kawana, FujisawaKanagawa 251-8522 Japan

http://www.azbil.com/

Specifications are subject to change without notice.

No part of this publication may be reproduced or duplicated without the prior written permission of Azbil Corporation.16