air handling unit 39g galaxy - hexacorp - site · air handling unit 39g ... in accordance to jis...

20
1 ® AIR HANDLING UNIT AIR HANDLING UNIT AIR HANDLING UNIT AIR HANDLING UNIT AIR HANDLING UNIT 39G GALAXY 39G GALAXY

Upload: vuonghanh

Post on 06-Sep-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

AIR

HAN

DLI

NG

UN

ITAI

R H

AND

LIN

G U

NIT

AIR

HAN

DLI

NG

UN

ITAI

R H

AND

LIN

G U

NIT

AIR

HAN

DLI

NG

UN

IT

39GGALAXY

39GGALAXY

Page 2: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

2

50mm NTB Features :50mm NTB Features :

CISB 39G offers...• Units are designed in accordance to

- ARI Standard for Coils (ARI 410)- ASHRAE Standard for Drain Pan (ASHRAE 62-89)

• Double Wall with 1”, 2” & 3” 40kg/m3 CFC-Free PU Insulation (HCFC 141b). Isolates Insulation Exposure to the Air Stream.

• Wide range of Coils offering – 4, 5, 6, 7, 8 Rows and 8, 10, 12, 14 FPI for Chilled Water. Optimized coil circuiting .DX Coil and Hot Water Coil are also available.

• All Chilled Water and DX Coils are Factory Pressure Tested at 400 psig as standard.

• Coil tracks enable easy coil removal for complete cleaning and assurance of a dry unit interior.

• Powder painted sloped galvanized steel drain pan with bottom drainage.

• Forward Curved and Backward Curved (Airfoil Blade) Fan- Forward Curved - Sizes 160 ~ 1000mm Diameter- Backward Curved (Airfoil Blade) – Sizes 225 ~ 1000mm Diameter

• Low leak construction with hex socket compression, type latch assemble and ribseals on mating panel perimeter.

• Factory installed unit base of 100mm height. constructed of 14 Gauge Galvanized Steel.

• Composite Corner Piece (Trileg) - Nylon 6 + 30% Glass filled.

• Non Thermal Bridge Aluminium Frame Extrusion.

• Non Thermal Bridge Sandwiched Panels and Access Doors.

• Non Thermal Bridge Quality Panel to Frame Fitting.

• No condensation problems in humid environments at low internal temperatures.

• Hygienic : due to smooth internal and external surface.

• Rigid construction with aluminium framework and machine injected rigid polyurethane foam panels.

• Spring-mounted fans for low vibration transmission.

• Dry, Corrosion Free construction.

Page 3: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

3

Chilled Water Coil With Steel Header (CU and Alu Fin)

Coils are of aluminium / copper plate fins with belled collarsand bonded to 12.7mm OD copper tubes by mechanicalexpansion. The coils have galvanised steel casing andsteel headers with male threaded connections.

Sloping Drain Pan and Drain Outlet

New drain pan assembly for better drainage, bottomaccess drain and sloping for rapid waterflow and betterInternal Air Quantity (IAQ). Ready to couple with femaleconnection.

Direct Expansion Coil (DX Coil)

Coils are of aluminium / copper with belled collars andbonded 12.7mm OD copper tubes by mechanicalexpansion. Coils are provided with brass distributors withsweat type connections.

Isolator Spring

As standard from the factory, the fan and motor assemblyare mounted on a common base with colour-codedinternally mounted spring isolators, which saves siteinstallation cost.

Assembly Fan Housing Motor and Base

FMB are made of painted heavy gauge galvanized steel(for 39G1422 and above) or power strut type (for 39G0508to 39G1319) to ensure proper and easy of installation fanhousing and motor.

Compression Latch (Hex Socket)

Only requires the use of haxagon wrench to open / closethe access door.

Page 4: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

4

Bearing Arm

Self aligning double row ball bearings mounted within acost iron housing supported on tubular bearing armassembly.

Taper Lock Pulley

Ability to change diameter of pulley according to fan shaft.Pulleys with taper lock bush allows for convenientdismantling and maintenance of drive package, besidesoffering flexibility in interchanging for different shaft sizes.

Fan Discharge Collar

Flanged discharge collar to provide easy ductingconnection.

Handle Grab

Large and Non-Conductive handles for easy panelremoval.

Accessory High Velocity Filter (HVF) Frame

For “free air return” application, factory supplied 75mmHVF track is an option instead of one module casingresulting in shorter overall unit length.

Dampers

Mixing boxes are equipped with parallel bladesinterconnected outside with return air dampers.

Page 5: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

5

• Panels shall be formed to produce solid 50mm double walled thermal break design of modular dimensions. Thereshall be a thermal break between the exterior and internal panels. Exterior panels shall be fabricated from 0.50mmthickness pre-painted steel, in accordance to JIS G3312 SGC570 Z18 or equivalent. The coating shall meet orexceed ASTM B117 Standard for Salt Spray Resistance at 500 hours. Interior panels shall be fabricated from solid1.00mm galvanized sheet steel, in accordance with JIS G3302 SGCC Z27 or equivalent [1.00mm SUS 304 StainlessSteel - optional]. Both exterior and interior panels shall be formed and reinforced to provide rigid construction.

• All panels to be insulated with machine-injected rigid polyurethane foam with a minimum density of 40kg/m3 andthermal conductivity K-factor of 0.019W/m.K in accordance with JIS A9514 (PU panel class 0).

• Panels shall be of one-piece design to facilitate removal. Panels shall be assembled with mechanical fastenerssuch that each panel is individually removable. The fasteners shall be zinc-chromate plated [SUS 304 stainlesssteel - optional].

• Panels shall have no exterior exposed raw edges that could lead to rust formation. The side perimeter of externalpanel shall include a built-in PVC gasket acting as air seal. Panels shall come with removable polyethylene protectivesheet to protect external surfaces from scratches and allow for removal at job site.

• Casing construction shall be Non-Thermal-Bridge (NTB) with no direct metal-to-metal contact between the internaland external surfaces. The unit frame construction shall consist of nylon glass-fiber reinforced corner-joints thatconnect extruded aluminium thermal break profiles. The extruded aluminium thermal break profiles shall consist ofa complete structure fabricated from high strength engineering thermoplastic bars that separates the aluminiumouter and inner profiles. The aluminium frames shall be gasketed along the perimeter with closed cell heavy dutyneoprene rubber gasket located in between panels and the aluminium frames. The frame shall be constructed topermit removal of the panels without affecting the structural integrity of the unit.

• Corner pieces (Tri-leg) molded of composite material forms the final integral part of the casing instruction. The non-metallic construction of the corner pieces enhances the Non-Thermal-Bridge feature of the AHU casing.

• Unit casing construction shall be tested to conform to the following standard:BS EN 1886:1998 or DIN EN 1886:1998 Ventilation for buildings – Air Handling Units – Mechanical performance

The construction shall satisfy the minimum requirements according to the classification in BS EN 1886:1998 orDIN EN 1886:1998 as shown below:

Guide Specifications for 39SR 50mm Non-Thermal Bridge (NTB) AHUGuide Specifications for 39SR 50mm Non-Thermal Bridge (NTB) AHU

Panel DesignPanel Design

Casing ConstructionCasing Construction

• Access doors shall be constructed from double walled thermal break panels insulated with the same material asthe casing panels. The four sides of the access door shall be covered permanently with extruded PVC to ensurenon-metallic thermal break.

• Door frames shall be constructed of a single-piece fiberglass construction for Non-Thermal-Bridging (NTB). Theinternal flange of the door frame shall be sealed along the perimeter with replaceable closed cell neoprene gasketof minimum 5.0mm thickness for air tightness and thermal performance.

• The door latch shall consist of a single-piece construction consisting of a handle with opening and closing mechanismfabricated from nylon glass fiber reinforced thermoplastic with thermal break design. The locking of the accessdoor shall be achieved via a single-piece gradiated cam-lock with stopper for air-tightness.

• Door hinges shall be fabricated from nylon glass fiber reinforced thermoplastic and installed with no direct contactwith the internal surface of the air handling unit. The hinges shall permit a complete 180° door swing

Access DoorsAccess Doors

Mechanical Characteristics ClassCasing strength 2Casing air leakage under –400 Pa BCasing air leakage under +700 Pa A/B *Filter bypass leakage F9Thermal transmittance T2Thermal bridging factor TB2

Note: Class B achievable upon request with special construction

Page 6: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

6

Basic ConstructionBasic Construction

39G 25mmFrame Construction

39G 50mmFrame Construction

39SR 50mm NTBFrame Construction

39G 25mmPanel (Double Skin)

39G 50mmPanel (Double Skin)

39SR 50mm NTBPanel (Sandwich)

39G 25mmFrame-Panel Construction

39G 50mmFrame-Panel Construction

39SR 50mm NTBFrame-Panel Construction

39G 25mmTrileg Construction

39G 50mmTrileg Construction

39SR 50mm NTBTrileg Construction

Injected Polyurethane�(40kg/m3)

Gasket

Double Skin Panel

25mm

Injected Polyurethane�(40kg/m3)

Gasket

Double Skin Panel

50mm

Injected Polyurethane�(40kg/m3)

Sandwich Panel

PVC Gasket

50mm

Page 7: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

7

Quic

k Se

lect

ion

Char

tQu

ick

Sele

ctio

n Ch

art

0508A

0508B

0511�

0612�

0713�

0813�

0914�

0916�

1018�

1118�

1319�

1422�

1522�

1722�

1724�

1725�

1926�

2127�

2230�

2234�

2434�

2636

0.1

7�

0.2

5�

0.3

4�

0.4

9�

0.7

0�

0.8

1�

1.0

5�

1.1

5�

1.4

4�

1.6

8�

2.0

8�

2.3

6�

2.5

5�

2.9

3�

3.3

0�

3.5

9�

3.9

6�

4.6

3�

5.4

8�

6.4

2�

6.9

9�

8.1

2

0.0

7

0.3

1

40.6

2

10.9

281.2

3

51.5

421.7

4

92.0

5

62.3

6

32.6

703.0

0�

2 4 6

8 10 12 1

4 16 18 20 22 2

4 26 2

8 30 32 3

4 36 38

CARRIER 39G UNIT SIZE

AIR

VO

LU

ME

, l/

s x

10

00

CA

PA

CIT

Y, K

W

COIL FACE AREA (sq.m)

0.3�0.4�0.8

0.4�0.6�1.1

0.5�0.9�1.5

0.7�1.2�

�2.2�

1.5

2.5

4.5

1.5

m/s

MIN

. CO

IL F

AC

E V

ELO

CIT

Y, C

OO

LIN

G O

R H

EAT

ING

2.5

m/s

MA

X. C

OIL

FA

CE

VE

LO

CIT

Y, C

OO

LIN

G W

ITH

OU

T E

LIM

INAT

OR

4.5

m/s

MA

X. C

OIL

FA

CE

VE

LO

CIT

Y, H

EAT

ING

1.1�

1.8���

3.2

1.2�

2.0���

3.6

1.6�

2.6����� 4.7

1.7�

2.9�����

5.2

2.2�

�3.6�

�����

6.5

2.5�

4.2� �����

7.6

3.1�

5.2� �����

9.4

3.5�

5.9� �����

3.8�

6.4� �����

4.4�

7.3����

5.0�

8.3���

5.4�

9.0���

5.9�

���

9.9���

6.9�����������������

10.6

11.5

13.2

14.9

16.2

17.8

20.8

24.7

28.9

31.5

36.5

11.6

8.2���������������� 13.7

9.6����������������

16.1

10.5���������������

17.5

12.2��������������

20.3

Not

e: F

or C

hille

d W

ater

app

licat

ion

betw

een

2.5

& 3

.15m

/sec

. fac

e ve

loci

ty, t

he u

se o

f Drif

t Elim

inat

or is

nec

essa

ry.

Page 8: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

8

DimensionDimension

UnitSize

Section Length

HVF (F)MXB (G) LVF (E) BF (D)Filter Access

(C) Coil (B) Fan (A)

UnitHH*

(mm)

UnitWidth(mm)

UnitHV**(mm)

RangeOf Hp

NominalCapacity

(kW)

NominalA/Flow

@2.5m m/s Fan Size

0508AFCG 02-160 1 ~ 1.5

7.9 425 600 300 600 600 600 500 500 500 800 1000FCG 02-180 1.5 ~ 2

0508B FCG 02-180 1.5 ~ 2 11.4 614 600 300 600 600 600 500 500 500 800 10000511 FCG 02-200 1.5 ~ 3 15.8 850 600 300 600 600 600 500 600 500 1100 1000

0612FCG 02-225 2 ~ 4

22.9 1227 600 300 600 600 600 500 600 600 1200 1200BCG 12-225 3 ~ 5

0713FCG 02-280 3 ~ 5

32.5 1746 600 300 600 600 600 500 700 700 1300 1400BCG 02-280 4 ~ 7.5

0813FCG 02-315 4 ~ 5

37.8 2030 600 300 600 600 600 500 800 800 1300 1600BCG 12-315 5 ~ 7.5

0914FCG 02-355 4 ~ 7.5

48.8 2620 600 300 600 600 600 500 900 900 1400 1800BCG 12-355 5 ~ 10

0916FCG 02-355 4 ~ 7.5

53.6 2879 600 300 600 600 600 500 900 900 1600 1800BCG 12-355 7.5 ~ 15

1018FCG 02-400 5 ~ 10

66.8 3587 600 300 600 600 600 500 1000 1000 18002000

BCG 15-400 7.5 ~ 15 2100

1118FCG 05-450 7.5 ~ 15

78.2 4201 600 300 600 600 600 500 1000 1100 1800 2200BCG 15-450 10 ~ 15FCG 05-450 7.5 ~ 15

96.7 5192600 300 600 600 600 500 1000 2400

1319 BCG 15-450 10 ~ 151300 1900FCG 05-500 10 ~ 20

600 300 600 600 600 500 1100 2500BCG 15-500 15 ~ 20FCG 05-500 10 ~ 15

900 300 600 600 600 500 1100 26001422

BCG 15-500 10 ~ 15109.8 5900 1400 2200

FCG 02-560 15 ~ 20900 300 600 600 600 500 1200 2700

BCG 15-560 15 ~ 20FCG 02-560 10 ~ 20

118.6 6372900 300 600 600 600 500 1200 2800

1522BCG 15-560 15 ~ 20

1500 2200FCG 02-630 15 ~ 25

900 300 600 600 600 500 1400 3000BCG 15-630 20 ~ 25FCG 02-630 15 ~ 20

136.2 7316900 300 600 600 600 500 1400 3200

1722BCG 15-630 15 ~ 25

1700 2200FCG 02-710 20 ~ 25

900 300 600 600 600 500 1500 3300BCG 15-710 20 ~ 30FCG 02-630 15 ~ 25

153.6 8280900 300 600 600 600 500 1400 3200

1724BCG 15-630 15 ~ 25

1700 2400FCG 02-710 20 ~ 30

900 300 600 600 600 500 1500 3300BCG 15-710 20 ~ 30FCG 05-630 15 ~ 25

166.9 8988900 300 600 600 600 500 1400 3200

1725BCG 15-630 15 ~ 25

1700 2500FCG 02-710 20 ~ 30

900 300 600 600 600 500 1500 3300BCG 15-710 25 ~ 40FCG 02-710 15 ~ 25

184.5 99121300 300 600 600 600 500 1500 3500

1926BCG 15-710 20 ~ 30

1900 2600FCG 05-800 25 ~ 40

1300 300 600 600 600 500 1700 3700BCG 15-800 25 ~ 40FCG 05-710 15 ~ 25

215.3 115641300 300 600 600 600 500 1500 3700

2127BCG 15-710 20 ~ 30

2100 2700FCG 05-800/GI 25 ~ 40

1300 300 600 600 600 500 1700 3900BCG 15-800/GI 30 ~ 50

FCG 05-800 20 ~ 30

254.8 136881300 300 600 600 600 500 1700 4000

2230BCG 15-800 20 ~ 30

2200 3000FCG 05-900 30 ~ 50

1300 300 600 600 600 500 1900 4200BCG 15-900 40 ~ 50

FCG 05-800/GI 20 ~ 40

298.7 160481300 300 600 600 600 500 1700 4000

2234 BCG 15-800/GI 20 ~ 40

2200 3400FCG 05-900/GI 30 ~ 60

1300 300 600 600 600 500 1900 4200BCG 15-900/GI 40 ~ 60

FCG 05-900 25 ~ 40

325.1 174641300 300 600 600 600 500 1900 4400

2434 BCG 15-900 25 ~ 402400 3400

FCG 05-1000 40 ~ 601300 300 600 600 600 500 2000 4500

BCG 15-1000 40 ~ 60FCG 05-900/GI 25 ~ 50

377.8 202961300 300 600 600 600 500 1900 4600

2636 BCG 15-900/GI 25 ~ 50

2600 3600FCG 05-1000 40 ~ 75

1300 300 600 600 600 500 2000 4700BCG 15-1000 40 ~ 75

*HH - Height Horizontal **HV - Height Vertical

Page 9: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

9

Note:

1) External AHU Length = (Section Length + K) mm

K = 110mm for 25mm casing thickness

160mm for 50mm casing thickness

2) External AHU Width = (Unit Width + K) mm

3) For Horizontal Unit, External AHU Height = (HH + K + 100*) mmFor Vertical Unit, External AHU Height = (HV + 2K + 100*) mm

*100mm is for unit base

4) If the External AHU Length is > 1900mm, section will be split into several casing for shipping purposes.

Note:

ACCESS

A

H

BCDG EF

HV

HH

Page 10: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

10

Fan

Disc

harg

e Ou

tlet D

imen

sion

(mm

)Fa

n Di

scha

rge

Outle

t Dim

ensi

on (m

m)

Unit

Fan

Size

AB

CD

E Di

men

sion

Size

(Mot

or L

ocat

ion)

ARR.

1 (T

HF)

ARR.

2 (B

HF)

ARR.

3/5

(U/D

BF)

ARR.

4/6

(U/D

BR)

2550

2550

2550

2550

2550

2550

2550

2550

0508

AFC

G 0

2-16

025

528

045

047

520

520

520

520

539

642

128

631

120

222

731

333

8FC

G 0

2-18

020

523

047

650

122

922

922

922

940

943

428

631

116

418

928

731

205

08B

FCG

02-

180

205

230

476

501

229

229

229

229

409

434

286

311

164

189

287

312

0511

FCG

02-

200

404

429

550

575

256

256

256

256

377

402

245

270

256

281

198

223

0612

FCG

02-

225/

BCG

12-

225

442

467

580

605

288

288

288

288

431

456

286

311

129

154

304

329

0713

FCG

02-

280/

BCG

12-

280

419

444

630

655

361

361

361

361

457

482

286

311

139

164

335

360

0813

FCG

02-

315/

BCG

12-

315

376

401

630

655

404

404

404

404

478

503

286

311

177

202

279

304

0914

FCG

02-

355/

BCG

12-

355

407

432

650

675

453

453

453

453

502

527

286

311

116

141

292

317

0916

FCG

02-

355/

BCG

12-

355

482

507

775

800

453

453

453

453

502

527

286

311

116

141

292

317

1018

FCG

02-

400/

BCG

15-

400

628

653

775

800

507

507

507

507

529

554

286

311

100

125

303

328

FCG

05-

450/

BCG

15-

450

566

591

775

800

569

569

569

569

569

582

286

311

105

130

366

391

1118

FCG

05-

450/

BCG

15-

450

566

591

775

800

569

569

569

569

569

582

286

311

105

130

366

391

1319

FCG

05-

450/

BCG

15-

450

610

635

831

856

569

569

569

569

569

582

286

311

105

130

366

391

FCG

05-

500/

BCG

15-

500

453

478

919

944

638

638

638

638

638

638

321

346

164

189

434

459

1422

FCG

05-

500/

BCG

15-

500

602

627

1070

1095

638

638

638

638

638

638

321

346

164

189

434

459

FCG

02-

560

496

521

1099

1124

715

715

715

715

715

677

321

346

142

167

473

498

BCG

15-

560

496

521

1099

1124

715

715

715

715

715

677

321

346

170

195

473

498

1522

FCG

02-

560

496

521

1099

1124

715

715

715

715

715

677

321

346

142

167

473

498

BCG

15-

560

496

521

1099

1124

715

715

715

715

715

677

321

346

170

195

473

498

FCG

02-

630

463

488

1046

1071

801

801

801

801

801

718

321

346

142

167

514

539

BCG

15-

630

463

488

1046

1071

801

801

801

801

801

718

321

346

167

192

514

539

1722

FCG

02-

630

463

488

1046

1071

801

801

801

801

801

718

321

346

142

167

514

539

BCG

15-

630

463

488

1046

1071

801

801

801

801

801

718

321

346

167

192

514

539

FCG

02-

710

509

534

903

928

898

898

898

898

898

772

321

346

142

167

568

593

BCG

15-

710

509

534

903

928

898

898

898

898

898

772

321

346

160

185

568

593

1724

FCG

02-

630

663

688

1046

1071

801

801

801

801

801

718

321

346

142

167

514

539

BCG

15-

630

663

688

1046

1071

801

801

801

801

801

718

321

346

167

192

514

539

FCG

02-

710

709

734

903

928

898

898

898

898

898

772

321

346

142

167

568

593

BCG

15-

710

709

734

903

928

898

898

898

898

898

772

321

346

160

185

568

593

1725

FCG

05-

630/

BCG

15-

630

678

703

1131

1156

801

801

801

801

801

718

321

346

167

192

514

539

FCG

02-

710

809

834

903

928

898

898

898

898

898

772

321

346

142

167

568

593

BCG

15-

710

809

834

903

928

898

898

898

898

898

772

321

346

160

185

568

593

1926

FCG

02-

710

681

706

1131

1156

898

898

898

898

898

772

321

346

142

167

568

593

BCG

15-

710

681

706

1131

1156

898

898

898

898

898

772

321

346

160

185

568

593

FCG

05-

800/

BCG

15-

800

572

597

1131

1156

1007

1007

1007

1007

1007

861

321

346

129

154

657

682

2127

FCG

05-

710/

BCG

15-

710

781

806

1131

1156

898

898

898

898

898

772

321

346

160

185

568

593

FCG

05-

800G

1/BC

G 1

5-80

0G1

672

697

1131

1156

1007

1007

1007

1007

1007

861

321

346

129

154

657

682

2230

FCG

05-

800/

BCG

15-

800

951

976

1152

1177

1007

1007

1007

1007

1007

861

321

346

129

154

657

682

FCG

05-

900/

BCG

15-

900

828

853

1152

1177

1130

1130

1130

1130

1130

922

321

346

133

158

718

743

2234

FCG

05-

800G

1/BC

G 1

5-80

0G1

1251

1276

1251

1276

1007

1007

1007

1007

1007

861

321

346

129

154

657

682

FCG

05-

900G

1/BC

G 1

5-90

0G1

1129

1154

1251

1276

1130

1130

1130

1130

1130

922

321

346

133

158

718

743

2434

FCG

05-

900/

BCG

15-

900

1158

1183

1222

1247

1130

1130

1130

1130

1130

922

321

346

133

158

718

743

FCG

05-

1000

/BC

G 1

5-10

0010

5310

7811

9012

1512

6712

6712

6712

6712

6794

832

134

610

613

170

773

226

36FC

G 0

5-90

0G1/

BCG

15-

900G

112

9013

1512

9013

1511

3011

3011

3011

3011

3092

232

134

613

315

871

874

3FC

G 0

5-10

00/B

CG

15-

1000

1153

1178

1290

1315

1267

1267

1267

1267

1267

948

321

346

106

131

707

732

Page 11: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

11

Horizontal Fan ArrangementsHorizontal Fan Arrangements

Side Elevation

Front Elevation

E

ARR 1 THF

D

ARR 3 UBF

DE

ARR 4 UBR

DE

E

ARR 2 BHF

D

ARR 5 DBFDE

ARR 6 DBRDE

SERVICE�DOOR

LEFTRIGHT

LEFT HAND

BCA

SERVICEDOOR

LEFTRIGHT

RIGHT HAND

ACB

Page 12: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

12

Base Unit Casing WeightBase Unit Casing Weight

Table below shows the base unit casing weight (Approximation) for 25mm, 50mm and 50mm NTB casing

Note: Weight in kg

Unit MXB Fan Coil HVF BF LVF ACCsize (mm) (mm) (mm) (mm) (mm) (mm) (mm)

25 50 25 50 25 50 25 50 25 50 25 50 25 50

0508A 51 61 25 30 25 30 10 12 34 40 35 41 30 36

0508B 51 61 25 30 25 30 10 12 34 40 35 41 30 36

0511 66 79 30 36 30 36 12 14 42 49 42 49 36 43

0612 70 84 40 48 33 39 13 16 46 54 54 62 40 48

0713 82 98 50 60 35 41 14 17 50 58 62 70 42 50

0813 94 113 60 72 37 45 15 18 54 64 64 74 44 54

0914 100 120 72 86 40 48 16 19 60 70 73 83 48 58

0916 110 132 78 94 43 51 17 20 65 76 78 89 52 63

1018 118 142 95 114 48 57 19 23 73 85 94 106 58 70

1118 120 144 100 120 50 59 20 24 75 87 98 110 60 72

1319 122 146 115 138 52 62 21 25 78 91 108 121 62 75

1422 131 157 151 181 56 66 22 26 82 96 117 131 65 79

1522 140 168 169 203 58 69 25 30 85 99 123 137 67 81

1722 147 176 183 220 60 71 27 32 91 103 139 151 71 83

1724 155 186 189 227 63 76 29 34 96 109 147 160 75 88

1725 167 200 201 241 66 79 31 37 100 115 159 174 77 92

1926 172 206 224 269 68 81 33 39 107 122 168 183 82 97

2127 185 222 260 312 72 90 35 41 114 129 180 195 87 102

2230 195 234 308 370 76 90 37 45 119 134 208 223 90 105

2234 215 258 342 410 80 95 39 47 126 141 222 237 95 110

2434 225 270 363 436 84 99 41 49 131 146 230 245 98 113

2636 240 288 419 503 89 106 43 51 139 154 245 260 104 119

Page 13: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

13

Fan Motor WeightFan Motor Weight

Table below shows the approximate fan motor weight

Notes :

• Motor weights based on 4 - pole 415/3∅/50Hz induction type TEFC motor foot mounted.

• Motor shall be of �, Y or D.O.L. wiring.

• Standard motor shall be per IEE standard IP54 enclosure with Class F insulation and B Temperature rise complyingwith BS2757.

• Maximum ambient temperature 40°C.

• For derivation of motor kW from fan BkW use

Motor kW = Fan BkW x A, where A = 1.20 if BkW<10kW A = 1.15 if BkW>10kW

• Please refer to your nearest Carrier representatives for special motor voltages or application.

Motor HP Motor kW Approx. Weight (kg) Frame Number

1 0.75 15 D80

1.5 1.1 20 D90S

2 1.5 22 D90L

3 & 4 2.2/3.0 30 D100L

5 & 5 1/2 3.7/4.4 42 D112M

7.5 5.5 65 D132S

10 7.5 76 D132M

15 11 118 D160M

20 15 139 D160L

25 18.5 189 D180M

30 22 203 D180L

40 30 290 D200L

50 37 320 D225SC

60 45 355 D225MC

75 55 520 D2250SA

Page 14: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

14

Fan Type Fan Size Maximum RPM Maximum BkW

FCG 02-160 4700 3.1

FCG 02-180 4200 4.5

FCG 02-200 3800 4.5

FCG 02-225 3400 4.5

FCG 02-280 2700 6.2

FCG 02-315 2400 6.2

FCG 02-355 2100 6.2

FCG 02-400 1900 6.2

Forward CurvedFCG 05-450 1700 16.0

FCG 05-500 1500 16.0

FCG 02-560 1200 13.0

FCG 02-630 950 13.0

FCG 05-630 950 26.0

FCG 02-710 850 16.0

FCG 05-710 850 39.1

FCG 05-800 750 39.1

FCG 05-800/G1 750 47.8

FCG 05-900 670 47.8

FCG 05-900/G1 670 47.8

FCG 05-1000 600 6.5

BCG 12-225 6640 6.5

BCG 12-280 5300 6.5

BCG 12-315 4730 6.5

BCG 12-355 4200 6.5

BCG 15-400 3600 20.0

BCG 15-450 3360 26.6

BCG 15-500 2050 26.6

Backward CurvedBCG 15-560 2400 30.0

BCG 15-630 1880 26.0

BCG 15-710 2000 49.9

BCG 15-800 1470 45.0

BCG 15-800/G1 1470 45.0

BCG 15-900 1430 62.0

BCG 15-900/G1 1430 62.0

BCG 15-1000 1140 60.0

Fan Size And RPM Limitation/BkW LimitationFan Size And RPM Limitation/BkW Limitation

Remark : A selection is valid provided if first reaches and not exceed either max. limits (RPM of BkW).

Page 15: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

15

Filte

r Typ

e, D

imen

sion

And

Qua

ntity

For

Eac

h AH

U Si

zeFi

lter T

ype,

Dim

ensi

on A

nd Q

uant

ity F

or E

ach

AHU

Size

PAR

T N

AM

EPA

RT

NO

.M

OD

EL

0508

A05

08B

0511

0612

0713

0813

0914

0916

1018

1118

1319

1422

1522

1722

1724

1725

1926

2127

2230

2234

2434

2636

a) H

EPA

Filte

r EU1

3 Pa

rticl

e Bo

ard

Fram

e (M

edia

Thi

ckne

ss 2

92m

m)

(H30

5 x

W30

5)m

m39

GA

509-

320

--

1-

--

--

--

--

--

--

--

--

--

(H30

5 x

W61

0)m

m39

GA

509-

321

11

1-

--

--

22

--

-3

--

--

--

5-

(H50

8 x

W50

8)m

m39

GA

509-

322

--

-2

22

--

--

6-

--

1212

12-

2024

--

(H61

0 x

W61

0)m

m39

GA

509-

323

--

--

--

22

22

-6

66

--

-9

--

1520

b) 1

” B

ag F

ilter

402

mm

L(H

289

x W

391)

mm

39G

A50

9-38

8-

-1

--

--

--

--

--

--

--

--

--

-(H

391

x W

595)

mm

39G

A50

9-38

4-

11

--

2-

--

--

--

--

--

--

--

-(H

289

x W

595)

mm

39G

A50

9-38

11

--

4-

22

33

3-

25

55

4-

47

84

4(H

595

x W

595)

mm

39G

A50

9-38

6-

--

-2

-2

23

36

66

66

812

1212

1520

20

c) 1

” B

ag F

ilter

450

mm

L(H

289

x W

391)

mm

39G

A50

9-39

6-

-1

--

--

--

--

--

--

--

--

--

-(H

391

x W

595)

mm

39G

A50

9-39

2-

11

--

2-

--

--

--

--

--

--

--

-(H

289

x W

595)

mm

39G

A50

9-38

91

--

4-

22

33

3-

25

55

4-

47

84

4(H

595

x W

595)

mm

39G

A50

9-39

4-

--

-2

-2

23

36

66

66

812

1212

1520

20

d) 1

” B

ag F

ilter

529

mm

L(H

289

x W

391)

mm

39G

A50

9-38

0-

-1

--

--

--

--

--

--

--

--

--

-(H

391

x W

595)

mm

39G

A50

9-37

6-

11

--

2-

--

--

--

--

--

--

--

-(H

289

x W

595)

mm

39G

A50

9-37

31

--

4-

22

33

3-

25

55

4-

47

84

4(H

595

x W

595)

mm

39G

A50

9-37

8-

--

-2

-2

23

36

66

66

812

1212

1520

20

e) 1

” H

VF

Filte

r W

asha

ble

(H28

9 x

W39

1)m

m39

GA

509-

130

--

1-

--

--

--

--

--

--

--

--

--

(H39

1 x

W59

5)m

m39

GA

509-

035

-1

1-

-2

--

--

--

--

--

--

--

--

(H28

9 x

W59

5)m

m39

GA

509-

032

1-

-4

-2

23

33

-2

55

54

-4

78

44

(H59

5 x

W59

5)m

m39

GA

509-

037

--

--

2-

22

33

66

66

68

1212

1215

2020

f) 2

” H

VF

Filte

r W

asha

ble

(H28

9 x

W39

1)m

m39

GA

509-

131

--

1-

--

--

--

--

--

--

--

--

--

(H39

1 x

W59

5)m

m39

GA

509-

041

-1

1-

-2

--

--

--

--

--

--

--

--

(H28

9 x

W59

5)m

m39

GA

509-

038

1-

-4

-2

23

33

-2

55

54

-4

78

44

(H59

5 x

W59

5)m

m39

GA

509-

043

--

--

2-

22

33

66

66

68

1212

1215

2020

g) 1

” H

VF

Filte

r D

ispo

sabl

e(H

289

x W

391)

mm

39G

A50

9-12

8-

-1

--

--

--

--

--

--

--

--

--

-(H

391

x W

595)

mm

39G

A50

9-02

3-

11

--

2-

--

--

--

--

--

--

--

-(H

289

x W

595)

mm

39G

A50

9-02

01

--

4-

22

33

3-

25

55

4-

47

84

4(H

595

x W

595)

mm

39G

A50

9-02

5-

--

-2

-2

23

36

66

66

812

1212

1520

20

h) 2

” H

VF

Filte

r D

ispo

sabl

e(H

289

x W

391)

mm

39G

A50

9-12

9-

-1

--

--

--

--

--

--

--

--

--

-(H

391

x W

595)

mm

39G

A50

9-02

9-

11

--

2-

--

--

--

--

--

--

--

-(H

289

x W

595)

mm

39G

A50

9-02

61

--

4-

22

33

3-

25

55

4-

47

84

4(H

595

x W

595)

mm

39G

A50

9-03

1-

--

-2

-2

23

36

66

66

812

1212

1520

20

No

te:

Dim

ensi

on

in m

m

Page 16: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

16

Coil

Wei

ght

Coil

Wei

ght

Not

e :

1. A

ll co

ils a

re o

f 13m

m O

D c

oppe

r tu

bes

with

allu

min

ium

pla

tee

fin c

onst

ruct

ion

2. T

o es

timat

e th

e w

eigh

t of w

ater

con

tent

(kg

) us

e: F

ace

area

(sq

.m)

x no

. of r

ows

x 7.

0kg/

sq.m

3. T

o es

timat

e dr

y co

il w

eigh

t (kg

) fo

r co

pper

pla

te fi

n co

nstr

uctio

n, u

se th

e ab

ove

data

(kg

) x

3.3

T

ype

Of

Co

il

Ho

t W

ater

Ch

illed

Wat

er

Dir

ect

Exp

ansi

on

No

Of

Ro

w

1

2

4

5

6

7

8

4

6

Fin

s/In

ch8

1012

148

1012

148

1012

148

1012

148

1012

148

1012

148

1012

148

1012

148

1012

14

Un

it S

ize

Fac

e A

rea

(sq

.m)

Est

imat

ed D

ry C

oil

Wei

gh

t (k

g)

0508

A0.

170

1414

1515

1616

1616

1818

1919

1920

2021

2121

2222

2222

2324

2324

2425

1818

1919

2121

2222

0508

B0.

246

1616

1717

1818

1919

2122

2223

2324

2425

2526

2627

2627

2829

2829

3031

2122

2223

2526

2627

0511

0.34

019

1919

1921

2122

2225

2627

2828

2930

3130

3132

3332

3435

3635

3638

3925

2627

2830

3132

33

0612

0.49

122

2223

2326

2627

2732

3435

3636

3738

4039

4142

4442

4446

4846

4850

5232

3435

3639

4142

44

0712

0.69

927

2728

2831

3132

3441

4244

4545

4749

5150

5255

5755

5860

6360

6366

6941

4244

4550

5255

57

0813

0.81

230

3031

3135

3637

3846

4850

5151

5456

5857

6062

6562

6569

7268

7175

7846

4850

5157

6062

65

0914

1.04

841

4242

4348

4951

5255

5860

6262

6568

7177

8083

8784

8892

9691

9510

010

455

5860

6277

8083

87

0916

1.15

243

4444

4551

5253

5459

6164

6667

7073

7682

8589

9389

9498

102

9710

210

711

259

6164

6682

8589

93

1018

1.43

648

4949

5058

5961

6277

8083

8686

9094

9896

101

105

110

105

111

116

122

115

121

128

164

7780

8386

9610

110

511

0

1118

1.68

153

5455

5664

6668

7087

9094

9898

103

107

112

109

115

120

126

120

127

133

140

132

139

146

154

8790

9498

109

115

120

126

1319

2.07

861

6264

6575

7780

8210

310

711

211

611

712

212

813

413

013

714

415

114

415

216

016

815

816

717

618

510

310

711

211

613

013

714

415

1

1422

2.36

6971

7274

8588

9093

117

122

127

132

133

139

145

152

148

156

164

171

164

173

182

191

179

190

200

210

117

122

127

132

148

156

164

171

1522

2.55

7577

7880

9295

9810

112

613

113

714

214

415

015

716

415

916

817

718

517

718

619

620

619

420

521

622

712

613

113

714

215

916

817

718

5

1722

2.93

8688

9092

106

109

112

115

145

151

158

163

165

172

180

189

183

193

203

213

203

214

225

237

222

235

248

260

145

151

158

163

183

193

203

213

1724

3.30

9799

107

103

119

123

126

130

164

170

178

184

186

194

203

213

207

218

229

240

229

242

254

267

251

265

280

294

164

170

178

184

207

218

229

240

1725

3.59

105

107

110

112

129

133

137

142

178

185

193

200

202

211

221

231

224

236

249

261

249

262

276

290

273

288

304

319

178

185

193

200

224

236

249

261

1926

3.96

116

119

121

124

143

147

152

156

196

204

214

221

223

233

244

256

248

261

275

288

275

290

305

320

301

319

336

353

196

204

214

221

248

261

275

288

2127

4.62

136

139

142

145

167

172

177

182

229

238

249

258

260

271

285

298

289

305

320

336

320

338

356

374

352

372

392

412

229

238

249

258

289

305

320

336

2230

5.47

161

164

167

171

198

204

210

216

271

282

295

306

308

321

337

353

342

361

379

398

379

400

421

443

416

440

464

487

271

282

295

306

342

361

379

398

2234

6.42

188

192

197

201

232

239

246

253

318

330

346

358

361

377

395

414

402

423

445

466

445

469

494

519

488

516

544

571

318

330

346

358

402

423

445

466

2434

6.99

205

209

214

218

252

260

265

276

346

360

376

390

393

410

430

450

437

461

484

508

484

511

538

565

531

561

592

622

346

360

376

390

437

461

484

508

2636

8.12

238

243

249

254

293

302

311

320

402

418

437

453

457

476

500

523

508

535

562

590

562

594

625

656

617

652

687

723

402

418

437

453

508

535

562

590

Page 17: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

17

Fan Housing Dimension And WeightFan Housing Dimension And Weight

Note: Width does not include both end of shaft.

Table below shows full details of 39G fan housing dimension and weight.

Fan Size Length (mm) Width (mm) Height (mm) Weight (kg)

Forward CurvedFCG 02-160 269 257 315 7FCG 02-180 299 282 352 9FCG 02-200 328 309 388 10FCG 02-225 366 350 433 12FCG 02-280 449 423 532 20FCG 02-315 502 465 596 23FCG 02-355 562 515 669 30FCG 02-400 632 578 750 45FCG 05-450 708 644 826 65FCG 05-500 827 713 952 80FCG 02-560 875 787 1046 97FCG 02-630 979 874 1173 115FCG 05-630 1028 876 1198 137FCG 02-710 1104 971 1324 175FCG 05-710 1152 973 1342 183FCG 05-800 1290 1092 1509 233FCG 05-800/G1 1290 1092 1509 233FCG 05-900 1448 1225 1697 316FCG 05-900/G1 1448 1225 1699 316FCG 05-1000 1573 1362 1889 376

Backward CurvedBCG 12-225 366 350 432 15BCG 12-280 449 423 532 23BCG 12-315 502 465 596 27BCG 12-355 562 515 699 36BCG 15-400 625 580 731 61BCG 15-450 708 644 826 73BCG 15-500 827 713 952 94BCG 15-560 921 789 1074 125BCG 15-630 1028 876 1198 149BCG 15-710 1152 973 1342 201BCG 15-800 1290 1092 1509 250BCG 15-800/G1 1290 1092 1509 250BCG 15-900 1448 1225 1697 358BCG 15-900/G1 1448 1225 1697 358BCG 15-1000 1573 1362 1889 416

W

L

H

Page 18: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

18

1.1 Furnish and install central station air handling unitsof the type, size and capacity shown on the equipmentschedule.

1.2 Equipment schedules and specifications are basedon Carrier 39G ‘Galaxy’ series. The design of the air-handling unit is based on the use of modular panelsand extruded aluminium perimeter frames withcomposite material for corner piece. Othermanufacturers of equal quality may be submitted tothe consulting engineers for approval. Whensubstitution of equipment is made, the contractor shallbe responsible for the cost of any item andengineering revision necessary to satisfy plans andspecifications.

1.3 Units shall be horizontal or vertical draw-through typeas shown on the drawings and shall consists (in thedirection of air flow) a mixing box section, a filtersection, a coil section and a fan section generally inaccordance with the attached equipment schedules.

1.4 Unit shall be supplied with welded unitbase with holesfor rigging located to suit optimum hoisting stability.The use of slings and spreader bars are recommendedfor large section.

2.1 The unit casing construction shall have double skinconstruction to allow access without damaging theinsulation and isolating it from the air stream.

2.2 The casing shall have extruded aluminium perimeterframe, with modular panels and composite materialcorner piece. The panels shall be constructed suchthat they shall comprise of two layers of steel sheetwith injected insitu CFC-Free Polyurethane insulationwith thermal conductivity factor of 0.019 w/mk anddensity of 40kg/m3 in between. The assembly of fixpanels to the perimeter frame shall be from insidethe unit. The removable panels should be providedon the both sides of the units with hex socketcompression type latch assembly and large & non-conductive handles. All external panels surface shallbe pre-painted zinc allume. Internal panels shall begalvanised steel sheet.

3.1 The fan shall be of the forward curved or backwardcurved DIDW centrifugal type. The blade of forwardcurved wheels shall be galvanised steel. The bladeof backward curved wheel shall be heavy gauge steel,treated and painted after manufacture. The fan assemblyshall be statically and dynamically balanced to the 80%of maximum fan speed as shown in the schedule.

3.2 Factory/field furnished and installed fan motors shallbe mounted inside the fan section on the mountingbase. The motors shall be of the totally enclosed fancooled (TEFC) type (or open drip proof type) suitablefor use with…Volts…Phase….Hz electrical supply.Motor speed shall be as per schedule.

3.3 The fan drive package shall consist of foxed pitchfan and motor pulleys and V-belts, adequately sizedto accommodate the application service factor.

3.4 The fan and motor assembly shall be mounted on anadjustable mounting base with factory supplied springanti-vibration mountings or rubber isolator. The fandischarge shall be square (for forward curved orbackward curved fans) in area and flanged and isolatedfrom the casing by a fire retardant grade flexibleconnection. Only on fan discharge shall be provided.

4.1 The coils shall be of the cartridge type, mounted overthe condensate drain pan (for cooling coil). Coils shallbe tested at 2760kPag air pressure while submergedin water. Coils performance shall be rated inaccordance to ARI standard 410.

4.2 Chilled Water coils shall have aluminium/copper finswith belled collars and bonded to 12.7mmm ODcopper tubes by mechanical expansion. Fins shallbe of the “Dual Sinewave” form. Coil shall havegalvanised steel casing and steel headers with malethreaded connections. Working pressure shall be2060kPag at 93oC. Coils shall be drainable and havenon-air-trapping circuits. No turbulence promotingdevices will be permitted inside the tubes. Headersshall have drain and vent connections. Note : copperheader shall be sweat type connection (braze).

4.3 Direct expansion coil shall have aluminium/copperfins with belled collars and bonded to 12.7mm ODcopper tubes by mechanical expansion. Fins shallbe of the “Dual Sinewave” form. Coils shall beprovided with brass distributors with sweat typeconnections. Coils shall have full-face active area withintertwined circuits for equal loading on each circuit.Suction and metering valve connection shall be onthe same end. After leak testing, coil shall be chargedwith dry air. Coils shall be designed and tested inaccordance to ARI standard.

4.4 Hot Water coils shall be constructed similar to thechilled water coil as per Section 4.3 except that themaximum working pressure shall be 1200kpag at205oC.

4.5 All coils shall have counter flow arrangement.4.6 The condensate drain pan shall be constructed by

16-gauge powder painted Galvanised Steel with40mm depth and 400mm in length. Slider shall bewelded at drain pan for easier coil installation andremoval. The condensate drain pan shall beconstructed in slope with one female threaded pipeconnection of 43mm OD routed through bottom fordrainage in accordance to ASHRAE 62-89 Standard.

Guide SpecificationGuide Specification

GeneralGeneral

Casing Construction (25mm and 50mm)Casing Construction (25mm and 50mm)

Fan SectionFan Section

CoilCoil

Page 19: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

19

Guide SpecificationGuide Specification

5.1 The filter section shall be supplied by the air handlingunit manufacturer with the same casing constructionas specified for the other unit sections. The type offilters to be housed within the filter section shall bethe type and efficiency indicated on the equipmentschedule.

5.2 High velocity filter section shall be capable ofreceiving 25mm or 50mm thick filters of standard size.Low velocity filter section shall be capable of receiving50mm deep filters mounted in 50mm width holdingframes.

5.3 Bag filter section shall be capable of accepting bagfilters with length up to 596mm and 22mm-filterheader thickness.

6.1 Mixing boxes shall be parallel bladed, interconnectedoutside air and return air dampers. Damper bladesshall be brake formed for stiffness and shall bemechanically secured to 13mm OD steel rods rotatingin nylon bushings and mounted in rigid powderpainted steel damper frames. Dampers shall besectionalised to limit blade length to not more than1480mm in order to prevent excessive blade warpingand ensure tight closure.

7.1 Access section shall be supplied by the air handlingunit manufacturer with the same casing constructionas specified for the other sections. The access panelsshall be ultra low leak construction with hex socketcompression type latch assembly and large & non-conductive handles for easy removal of the accesspanel. The access panel shall be double skinnedconstruction and internally insulated with injectedinsitu CFC-Free polyurethane insulation. The accesspanel perimeter shall be lined with ribseals.

Filter SectionFilter Section

Mixing BoxMixing Box

Access SectionAccess Section

8.1 Viewports shall be available as factory installed optionon access doors. The viewports shall be fabricatedfrom round, double plane, clear and rigid polycarbonatewith a minimum diameter of 200.0mm and installedwith screws that do not come into direct contact withthe internal surface of the air handling unit. Theviewport shall be gasketed on the internal andexternal surfaces with thermoplastic elastomer (TPE)gaskets to ensure air-tightness. The viewport shallbe capable of withstanding unit operating pressures.

9.1 Marine lamps shall be available as factory-installedoption on the fan and access sections of the airhandling unit. The construction shall be vapour andweather tight rated to IP44. The marine lamp shallconsist of a structural light fitting base with aluminiumreflector and receptacle, and a structural glass globeprotected by wire mesh. The marine lamp shall comefitted with a light bulb complete with factory installedwiring and conduits and terminated with an on/offswitch located external to the unit and near to theaccess door.

10.1 The drain pan shall be available fabricated in galvanizedsteel and powder painted to withstand ASTM B-117Salt Spray Test at 500 hours. The drain pan shall haveoption of being fabricated in Stainless Steel SUS 304.

10.2 The drain pan shall be constructed to have full width,single sloped drain pan to ensure positive condensatedrainage and shall extend downstream of the coil toprovide sufficient amount of space to contain moisturecarry-over. The coil shall not sit in the drain pan andshall be removable via coil tracks. The drain pan shallhave an integral FPT elbow for side discharge andtrapping.

10.3 The drain pan must be accessible for inspection andcleaning.

ViewPortsViewPorts

Marine LampMarine Lamp

Drain PanDrain Pan

Page 20: AIR HANDLING UNIT 39G GALAXY - Hexacorp - Site · AIR HANDLING UNIT 39G ... in accordance to JIS G3312 SGC570 Z18 or equivalent. ... 78.2 4201 600 300 600 600 600 500 1000 1100 1800

20

39G-E03-6SL supercedes 39G-D02-5SL

Manufacturer reserves the right to discontinue, orchange at any time, specifications or designswithout notice and without incurring obligations.

39G Rev. 3

05 2003

®

CarrierInternationalSdn. Bhd.Malaysia

Carrier International Sdn. Bhd. (3385-T)Lot 4, Jalan P/6, 43650 Bandar Baru Bangi,

Selangor, Malaysia.Tel: 03-8925 8001Fax: 03-8925 3578