Page 1: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

AIRAH Presentation Case studies in HVAC system noise issues

SLR Consulting Australia Pty Ltd 21 August 2013

Luke Zoontjens

Page 2: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

The client / documentation refers to a ‘soundproof’ or VIP space

Use of the prefix ‘acoustic’

Interior services are exposed / open / perforated ceiling

Residential building, or the site immediately borders residences

The site is next to major infrastructure such as rail or freeways

There are scientists, precision equipment, patients, lab animals

Green Star / ESD requirements

Encountered any of the following?

Page 3: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

The client / documentation refers to a ‘soundproof’ or VIP space

Use of the prefix ‘acoustic’

Interior services are exposed / open / perforated ceiling

Residential building, or the site immediately borders residences

The site is next to major infrastructure such as rail or freeways

There are scientists, patients or lab animals

Green Star / ESD requirements

Encountered any of the following?

Page 4: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Environmental Acoustics in WA

How big is the consulting industry here?

29+ private firms in Perth alone at last count In no particular order: AECOM, Aurecon, EcoAcoustics, EDC, GED, GHD, HSA, LGA, NDY, SLR, Vipac, ERM, 360Env, MDA, WGE, Precision, SVT/NVMS, Hewshott, WP, Coffey, AI, QuietAcoustics, NDE, URS, Dinglebird, VDM, Instrulabs, Sealhurst, Instrulabs.

Page 5: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

• www.acoustics.asn.au • ~600 members nationally, 60 in WA • ‘Learned’ society • Annual conferences and input into

professional standards • Acoustics Australia technical journal

Page 6: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

• The peak professional association in the industry; • Up-to-date technology and state of the art practices, Code of

Ethics; • Members work only within their nominated areas of competence

and maintain professional indemnity insurance cover; • Free of commercial activities which may affect their impartiality; • Commitment to undertake regular professional training and

development of all staff.

www.aaac.org.au

Page 7: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

WA Members

(Formerly Heggies)

www.aaac.org.au

Page 8: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

DESIGN FRAMEWORKS IN WA

Page 9: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Design Frameworks • State authorities - noise regulations, planning

policies • Local authorities / ‘Sound Attenuation’ policies • Australian standards – comfort, productivity,

fire/life safety, privacy • Industry Guidelines – AIRAH, AAAC etc. • National construction code • Green star / ESD rating tools • Client and user expectations of quality

Page 10: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

CASE STUDIES

Page 11: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

ADELAIDE

Page 12: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Domestic systems guidance • http://www.fairair.com.au • AIRAH Air Conditioning Residential Best

Practice Guideline (Western Australia) • Installers Guide to Air Conditioner Noise,

RACIRB / Dept Env, Water & Catchment Protection

Page 13: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Section 80 of EPA1986• 80(1) generally states that a person who installs

any equipment which, when operated, emits unreasonable noise commits an offence under the Act.

• The penalty for an offence under Section 80 (1) is $5,000 for an individual or body corporate.

Page 14: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Section 80 of EPA1986• 80(2) generally states that if an occupier is

convicted of committing an offence under the Act because of someone committing offence under 80(1), that occupier may recover the cost of the installation, together with the amount of any penalty imposed on him from the installer by action in court.

Page 15: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Environmental noise limits • Assigned levels for residential buildings under

state noise regulations vary due to ‘influencing factor’, assume LA10 35dB (10pm-7am)

• Note that 5-10dB adjustments are made if the noise has annoyance characteristics (e.g. tonal whine, deterioration over time)

• AIRAH guidelines of LAeq 45dB maximum during the day and LAeq 35dB maximum at night at property boundary – varies between states

Page 16: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

1. Distance factor – Assume boundary; within 15m of neighbouring building

2. Barrier factor – 0 if line of sight, 5 or 10 depending on fence – 0 for roof mounted (e.g. evaporative)

3. Reflection factor – 0, 3, 6 depending on surrounding structure – 0 for roof mounted (e.g. evaporative)

Basic approach

Page 17: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

57 0 0

Consider roof level installation 10m from boundary

57

Page 18: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

45 10 3

Consider ground level installation 2m from 1.8m wall

52

Page 19: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

ADELAIDE

Page 20: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

AS/NZS 2107 Reception areas target: ~40-45dB(A) Actual: ~61dB(A)

Page 21: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client
Page 22: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Lessons learnt

• Intake and discharge flow conditions

• Fan unit mounting arrangements

• Lightweight metalwork and panel mode responses

Page 23: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

ADELAIDE (again)

Page 24: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Mech Tender

Page 25: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Mech As-Built

AS/NZS 2107 target: ~35-40dB(A)Actual: ~52dB(A)

Page 26: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Lessons learnt

• Beware of areas where the architectural brief calls for perforated metal and feature/exposed ceilings.

• Identify small cellular shared offices and low density workspaces as among the most sensitive.

• Flexible ducting reduces opportunities for future noise control options.

Page 27: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client
Page 28: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client
Page 29: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

AS/NZS 2107 target: ~30dB(A) State Noise Regulations Assigned

Level: LA10 35dB(A) Actual: LA10 ~44dB(A) Add +5dB for tonality Add +15dB for indoor measurement =64dB(A) … 29dB exceedance

Page 30: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

Lessons learnt • Beware of extreme noise control requirements in

residential buildings, particularly those remote from busy roads and commercial areas, and involving mixed uses.

• There is always a physical limit to the performance of noise and vibration treatments; services cannot always be located where it is convenient.

• In a post construction phase of a building, achieving more than a 10-15dB noise reduction via path controls only is excellent.

Page 31: AIRAH Presentation Case studies in HVAC system …AIRAH Presentation Case studies in HVAC system noise issues SLR Consulting Australia Pty Ltd 21 August 2013 Luke Zoontjens The client

CLOSING DISCUSSION