al-ko easyair flat · rating and performance for units, components and sections din en 1886...

72
AL-KO EASYAIR ® flat Flat air handling unit OPERATING AND ASSEMBLY MANUAL 3059570 I 12/2013 GB

Upload: others

Post on 19-Mar-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

AL-KO eAsyAir®flatFlat air handling unit

OperAting And AssembLy mAnuAL

3059570 i 12/2013

gb

Page 2: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions2

AL-KO EASYAIR®flat

Contents

1. About this manual ..........................................................................................51.1 Legend........................................................................................................................................................5

1.2 Regulations and standards .........................................................................................................................5

1.3 Legal information .......................................................................................................................................5

2. Safety guidelines ...........................................................................................62.1 Proper use ..................................................................................................................................................6

2.2 Possible incorrect use ................................................................................................................................7

2.3 Residual hazards ........................................................................................................................................7

2.4 Delivery ......................................................................................................................................................7

2.5 Storage, transport ......................................................................................................................................7

2.6 Duties of operator .......................................................................................................................................8

2.7 Disposal of packaging ................................................................................................................................8

3. Product description ........................................................................................93.1 EC declaration of conformity / EC declaration of incorporation ..................................................................9

3.2 Product description ..................................................................................................................................11

3.3 Technical data ...........................................................................................................................................13

4. Transport / preparation .................................................................................. 154.1 Transport ..................................................................................................................................................15

4.2 Preparation ...............................................................................................................................................15

4.2.1 Space requirement ...................................................................................................................................15

4.2.2 Ceiling construction ..................................................................................................................................15

5. Assembly .................................................................................................. 175.1 Opening / removing the maintenance panel ..............................................................................................17

5.2 Assembling the modules ..........................................................................................................................17

5.2.1 Procedure .................................................................................................................................................17

5.2.2 Removing components.............................................................................................................................20

5.2.3 Duct connection .......................................................................................................................................22

5.2.4 Siphon connection ....................................................................................................................................23

5.3 Electrical connection.................................................................................................................................23

5.3.1 Cable list ...................................................................................................................................................23

5.3.2 Installation / connection of remote control (optional) ...............................................................................25

5.3.3 Installation / connection of temperature sensors for supply, outdoor and extract air ...............................25

5.3.4 Electrical air heater connection (optional ELE) .........................................................................................26

5.3.5 Hot water heater connection (optional WWE) ...........................................................................................27

5.3.6 Cooler module connection (option KWK) .................................................................................................28

5.3.7 Installation of bus cards (optional) ...........................................................................................................30

5.3.8 Connection control (optional) ...................................................................................................................30

Page 3: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

33059570

6. Commissioning ........................................................................................... 316.1 Basics .......................................................................................................................................................31

6.2 Before starting the system ........................................................................................................................31

6.3 Turning the system on and off ..................................................................................................................31

6.4 After starting the system ..........................................................................................................................32

6.4.1 Addressing damper actuator motors ........................................................................................................32

6.4.2 Addressing valve actuator motors ............................................................................................................33

7. Set-up menus ............................................................................................. 347.1 Control unit (optional remote control) ......................................................................................................34

7.2 Main display .............................................................................................................................................35

7.2.1 Turning the fans on and off .......................................................................................................................35

7.2.2 Setting the temperature from the main display .........................................................................................35

7.3 Menu levels ..............................................................................................................................................36

7.3.1 Setting the system parameters .................................................................................................................37

7.4 User level ..................................................................................................................................................38

7.4.1 "Settings" menu ........................................................................................................................................38

7.4.2 "Displays" menu ........................................................................................................................................39

7.4.3 "Time functions" menu ..............................................................................................................................40

7.5 Service level .............................................................................................................................................42

7.5.1 "Unoccupied mode" menu .........................................................................................................................42

7.5.2 "Night ventilation" menu............................................................................................................................44

7.5.3 "Supply air limitation" menu ......................................................................................................................45

7.5.4 "Compensation" menu...............................................................................................................................46

7.5.5 "AUTO operation" menu ............................................................................................................................47

7.5.6 "Sensor offset" menu ................................................................................................................................48

7.5.7 "Operating hours counter" menu ...............................................................................................................49

7.5.8 "Alarm recording" menu ............................................................................................................................49

7.5.9 "Presence detection" menu .......................................................................................................................50

7.5.10 "Miscellaneous" menu ...............................................................................................................................50

8. Maintenance .............................................................................................. 528.1 Safety .......................................................................................................................................................52

8.2 Consumables and replacement parts ........................................................................................................52

8.3 Fuses and terminals..................................................................................................................................52

8.4 Maintenance schedule ..............................................................................................................................53

8.5 Checking components ..............................................................................................................................55

8.5.1 WWE / KWK..............................................................................................................................................55

8.5.2 Plate heat exchanger ................................................................................................................................55

8.5.3 Dampers ...................................................................................................................................................56

8.5.4 Drip separator...........................................................................................................................................56

" Contents"

Page 4: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions4

AL-KO EASYAIR®flat

8.5.5 Fans ..........................................................................................................................................................56

8.6 Replacing components .............................................................................................................................56

8.6.1 Replacing filter bags .................................................................................................................................56

9. Trouble shooting.......................................................................................... 579.1 Contact .....................................................................................................................................................57

9.2 General faults ...........................................................................................................................................57

9.3 "AL" display fault .......................................................................................................................................57

9.4 "AL" fault table ..........................................................................................................................................58

10. Shutdown .................................................................................................. 5910.1 Decommissioning .....................................................................................................................................59

10.2 Dismantling ..............................................................................................................................................59

10.3 Disposal....................................................................................................................................................59

11. Annexe data point list ................................................................................... 6011.1 EASYAIR®flat (PF-01 – PF-03; GF-01 – GF-03) ........................................................................................60

11.2 EASYAIR®flat (PF-01 – PF-03; GF-01 – GF-03) with electric heater ..........................................................61

11.3 EASYAIR®flat (EF-01 – EF-03) ..................................................................................................................62

11.4 EASYAIR®flat (EF-01 – EF-03) with electric heater ...................................................................................63

12. Annexe data point list ................................................................................... 6412.1 LON-Bus ...................................................................................................................................................64

12.2 Mod-Bus ...................................................................................................................................................65

12.3 BACnet......................................................................................................................................................66

12.4 Ethernet ....................................................................................................................................................67

13. Sample commissioning protocol ...................................................................... 68

Page 5: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

53059570

1. About this manual

� Read this document thoroughly before installation and start-up. This is a prerequisite for safe work and fault-free use.

� Observe the safety instructions and warnings in this document and on the product.

� This document is an essential component of the described product and should be passed on to the buyer upon sale.

1.1 Legend

Warning!This symbol indicates safety activities which must absolutely be observed in order to avoid personal injury!

Attention!This symbol indicates safety activities which must absolutely be observed in order to avoid property damage!

Specific guidelines for easier comprehensibility and handling.

1.2 Regulations and standards

The following standards and regulations were applied during construction and are valid during installation, start-up, operation and maintenance:

DIN EN ISO 12100 Safety of machinery – General principles for design - Risk assessment and risk reduction

DIN EN ISO 13857 Safety of machinery - Safety distances to prevent hazard zones being reached by upper and lower limbs

DIN EN 61000-6 -1

-2 -3

-4

Electromagnetic compatibility (EMC) - Part 6: Generic standards– Immunity for residential, commercial and light-industrial

environments– Immunity for industrial environments– Emission standard for residential, commercial and light-industrial

environments– Emission standard for industrial environments

DIN EN 60204-1(DIN VDE 0113)

Safety of machinery - Electrical equipment of machines -Part 1: General requirements

DIN EN 13053 Ventilation for buildings - Air handling units -Rating and performance for units, components and sections

DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance

DIN EN 349 Safety of machinery - Minimum gaps to avoid crushing of parts of the human body

VDMA 24167 Fans – Safety requirementsVDMA 24168 Ventilation devices and systems;

Air outlets, determination of the air flow with the pressure compensation method (null method)

VDI 3801 Operating of air-conditioning systemsVDI 3803-1 Air-conditioning -

Central air-conditioning systems - Structural and technical principlesVDI 6022 Ventilation and indoor-air quality – Hygiene requirements for ventilation and air-

conditioning systems and units

"About this manual"

Page 6: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions6

AL-KO EASYAIR®flat

BGV A1 Principles of PreventionBGV D6 CraneBGR 500 Chapter 2.8 Operation of load-acceptance equipment in hoisting-equipment operation2006/42/EC Machinery Directive97/23/EC Pressure Equipment Directive2004/108/EC Electromagnetic Compatibility Directive (EMC)

1.3 Legal information

All given data applies only to the product description. A statement cannot be inferred from this information about a specific condition or suitability for a particular purpose. The information does not remove the responsibility of the user to employ his/her own judgments and checks.

2. Safety guidelines

Observe these points in order to avoid injury, fire and other hazards caused by improper use and operation of this equipment:

Attention!Assembly, electrical connection, supply connection, maintenance, commissioning, repairs etc. may only be performed by trained specialist personnel!

Prior to all work on the EASYAIR®flat ensure that the power supply is shut off (power off all poles) and safeguarded from unauthorized powering on.

Only operate EASYAIR®flat when it is completely installed.

If the assembly is performed contrary to our regulations, and the defect/damage which has occurred is causally associated with inappropriate modification, processing or any other treatment, all claims to damages compensation or warranty are thereby excluded. The ordering party must prove that incorrect assembly did not cause the defect which has occurred.

General maintenance guidelines in the Operation and assembly manual for EASYAIR®flat made by AL-KO THERM must absolutely be observed.

The design and method of construction of the EASYAIR®flat conforms to the norms indicated in the declaration of con-formity or declaration of incorporation in order to minimize any potential hazard posed by the EASYAIR®flat. The furthest possible avoidance of potential hazards can only be warranted upon compliance with the additionally valid norms for the total installation in its ready-to-install form is maintained by the equipment manufacturer/system builder.

Ensure that all authorized persons the operation and assembly manual have read and understood in its entirety and observe these!

In order to avoid hazards within the operation, all plant, operational and work procedures / instructions of the company / user shall apply in addition to this operation guide.

Work performed on the EASYAIR®flat requires personal protective equipment (PPE)!

2.1 Proper use

This equipment is to be exclusively used for the ventilation of rooms and buildings, the maintenance of necessary room climates, and the reduction of the amount of dust and other contaminants in the air. It may only be operated within the temperature range of - 25 °C to + 40 °C. Furthermore EASYAIR®flat units are exclusively designed for horizontal ceiling installation. Other scope of applications must be agreed by the manufacturer.

Page 7: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

73059570

2.2 Possible incorrect use

AL-KO EASYAIR®flat may only be operated within the scope of the technical data defined by AL-KO. Any other use devia-ting from that described under "2.1 Proper Use" is regarded as improper. The manufacturer is not liable for any damages resulting from improper use.

Possible misuse is e.g.:

� The transport of media with excessively high or low temperatures as well as aggressive media or media containing a large amount of dust.

� Use in explosive atmospheres

2.3 Residual hazards

The system may pose hazards if not used by trained personnel and/or is used improperly and not for its intended use.

Residual hazards are potential, non-obvious hazards, such as:

� Injury due to any failure to observe the safety guidelines, norms, guidelines or regulations,

� Injuries caused during inadequately coordinated work

� Endangerment from working on electrical systems, cables and connections

2.4 Delivery

� EASYAIR®flat units are delivered in modules. Please consider "5.2 Assembling the modules".

2.5 Storage, transport

� Store the individual functional parts in their original packaging in a dry place and protected from the weather.

� Cover open pallets with tarps and protect the functional parts from contamination (i.e. from shavings, stones, wire, etc.).

� For transport in harsh conditions (i.e. on open vehicles, unusual shaking, and sea transport or in subtropical coun-tries) additional packaging must be used to protect the product from these particular influences.

� Prevent constant and especially abrupt temperature changes during storage. It can be particularly harmful if humidity is able to condense.

� During transport, ensure sufficient visibility. (as necessary, possibly with a accompanying person etc.)

� No persons may be present in the transport area.

� The transport of the modules of the EASYAIR®flat may only be performed by trained, qualified and briefed personnel under the aspect of "Safety".

� When using transport devices which require an operator's license, it must be ensured that the personnel hold such a valid license.

� Ensure the use of suitable hoisting equipment.

� During transport, observe the relevant regulations on work safety and environmental protection.

� In order to avoid damage during storage, the fan must be turned once a month.

� For storage times of over one year, check the fans for ease of movement before assembly (turn them by hand).

� Avoid warping the housing or any other damage

� The initiator is at fault for any damage resulting from improper packaging, storage and transport.

"Safety guidelines"

Page 8: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions8

AL-KO EASYAIR®flat

2.6 Duties of operator

Operators of AL-KO THERM GMBH products are responsible for regularly training their personnel on the following topics:

� Compliance with and use of the operating- and assembly manual and the legal regulations.

� Proper operation of the ventilation unit.

� If applicable, compliance with the plant security directives and the operation instructions.

� Emergency procedures.

2.7 Disposal of packaging

Disposal of packaging must be performed according to the currently valid, local environmental and recycling regulations of your country and your municipality.

Page 9: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

93059570

3 Product description

3.1 EC declaration of conformity / EC declaration of incorporation

"Product description"

Page 10: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions10

AL-KO EASYAIR®flat

Page 11: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

113059570

3.2 Product description

Because of their low construction height, EASYAIR®flat air handling units are intended for ceiling installation.The unit design consists of functional modules (filter, fan, silencer, heater, cooler, heat recovery). The devices can be or-dered optionally as combined supply and exhaust air systems including heat recovery or simply as air supply and exhaust air systems.The units with heat recovery achieve a high degree of heat recovery. Thus the units make a considerable contribution to energy savings and a reduction of operation costs. All units can be ordered with the appropriate control devices. This ensures trouble-free unit operation.All field devices come ready assembled with the unit. The switch cabinet comes as a separate unit and can thus be installed wherever best suits the client. The wiring installation between the unit and switch cabinet must be supplied by the client.Optional extras allow the units to be extended.Optional components to extend use consist of: acoustically isolated unit connections, dampers, electrical or water-heated heater module, cooler module, silencer module, pressure sensors for pressure or constant volume regulation, air quality sensor, room temperature sensor, etc.When using the associated control system, filter replacements which become necessary are displayed by the pressure-difference filter monitoring device. All control functions are included in the control software and their parameters can be set. By means of pre-configured bus systems, the control system can easily be integrated into higher-level systems: the user can choose between Modbus, LON, BacNet/Ethernet.

Our products are subject to constant quality control and comply with the applicable regulations.

AUL Outdoor air (OA) ZUL Supply air (SA)

ABL Return air (RA) FOL Exhaust air (EA)

1 Cross flow-Plate heat exchanger-module 7 Cooling-module*

2 Fan-module supply air 8 Connecting piece*

3 Fan-module exhaust air 9 Damper*

4 Filter-module 10 Installation plates

5 Silencer-module* 11 Counter flow-Plate heat exchanger-module

6 Heating-module* (Warmwater or E-Heater)

* available as an option

heig

htw

idth

length(5)

2 mm per module connection distance for housing gasket note

Fig. EASYAIR®flat EF unit

"Product description"

Page 12: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions12

AL-KO EASYAIR®flat

heig

htw

idth

length(5)

2 mm per module connection distance for housing gasket note

Fig. EASYAIR®flat PF unit

heig

htw

idth

length(5)

2 mm per module connection distance for housing gasket note

Fig. EASYAIR®flat GF unit

Page 13: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

133059570

3.3 Technical data

Supply air / exhaust air unit EF

Type Air volume(1)(m³/h)/ Sound power level(3)(dB(A)) sFp(4) sA/rA Max. connection power(6)

min nominal max W/m³s kVA A V

eF 01 650 / 68 1.000 / 68 1.700 / 73 567 0,81 3,5 1x230

eF 02 900 / 69 1.800 / 79 2.750 / 87 654 1,12 2,8 3x400

eF 03 1.350 / 64 2.700 / 72 3.700 / 80 608 1,28 3,2 3x400

Type Basic unit (mm) Duct connection Basic unit

Length(5) Width Height Width Height Weight kg

eF 01 818 662 362 612 306 59

eF 02 818 662 464 612 408 69,5

eF 03 818 968 464 918 408 87

Options

Type WWe KWK eLe sd

kW(9) kg kW(8) kg kW(11) A kg kg

eF 01 11,4 22,5 5,0 29,5 8,1 11,7 29 49

eF 02 20,5 26 8,9 34,5 14,6 21,1 35,5 55

eF 03 30,8 34 13,8 45,5 21,9 31,6 44,5 74

Supply and exhaust air unit PF with Cross flow-Plate heat exchanger

Type Air volume(1)(m³/h)/ Efficiency(2)/ Sound power level(3)(dB(A)) sFp(4) sA-/rA Max. connection power(6)

min nominal max W/m³s kVA A V

pF 01 650 / 55 / 71 1.000 / 52 / 73 1.350 / 52 / 77 910 / 877 1,38 6,0 1x230

pF 02 900 / 59 / 70 1.800 / 57 / 80 2.200 / 57 / 84 948 / 814 1,84 4,6 3x400

pF 03 1.350 / 58 / 66 2.700 / 57 / 73 3.300 / 57 / 77 957 / 845 2,16 5,4 3x400

Type Basic unit (mm) A Duct connection (mm) Basic unit

Length(5) Width Height mm Width Height Weight kg

pF 01 1.738 1.326 362 918 612 306 219

pF 02 2.146 1.326 464 1.326 612 408 285

pF 03 2.350 1.938 464 1.530 918 408 403

Options

Type WWe KWK eLe sd

kW(7) kg kW(8) kg kW(10) A kg kg

pF 01 4,7 20 5,0 29,5 5,5 7,9 24 49

pF 02 8,4 22,5 8,9 34,5 9,5 13,7 31,5 55

pF 03 12,7 29 13,8 45,5 14,0 20,2 37 74

"Product description"

Page 14: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions14

AL-KO EASYAIR®flat

Supply and exhaust air unit PF with Counter flow-Plate heat exchanger

Type Air volume(1)(m³/h)/ Efficiency(2)/ Sound power level(3)(dB(A)) sFp(4) sA-/rA Max. connection power(6)

min nominal max W/m³s kVA A V

gF 01 650 / 84 / 70 1.000 / 82 / 71 1.350 / 80 / 73 614 / 599 1,38 6,0 1x230

gF 02 900 / 84 / 70 1.800 / 80 / 80 1.880 / 80 / 81 941 / 862 1,84 4,6 3x400

gF 03 1.350 / 84 / 66 2.700 / 80 / 73 2.840 / 80 / 74 791 / 731 2,16 5,4 3x400

Type Basic unit (mm) A Duct connection (mm) Basic unit

Length(5) Width Height mm Width Height Weight kg

gF 01 1.738 1.326 362 918 612 306 223

gF 02 1.942 1.326 464 1.122 612 408 274

gF 03 2.044 1.938 464 1.224 918 408 370

Options

Type WWe KWK eLe sd

kW(7) kg kW(8) kg kW(10) A kg kg

gF 01 4,7 20 5,0 29,5 5,5 7,9 24 49

gF 02 8,4 22,5 8,9 34,5 9,5 13,7 31,5 55

gF 03 12,7 29 13,8 45,5 14,0 20,2 37 74

(1) External pressure loss supply air 200 Pa, exhaust air 200 Pa(2) Efficiency of heat recovery according to DIN EN 308 (without condensation)(3) Sound power level in the supply air duct(4) Specific Fan Power (SFP) in accordance with EnEV 2009 at nominal air volume

and external duct pressure losses supply air 200 Pa, exhaust air 200 Pa, incl. filters (F7 / F5)(5) Basic unit length including 2 mm housing gasket per module connection(6) Without power for optional electric air heater(7) Heating capacity for temperature difference 14 K, medium 50 / 35 °C(8) Cooling capacity for temperature difference 10 K, medium 6 / 12 °C(9) Heating capacity for temperature difference 34 K, medium 50 / 35 °C

(10) Heating capacity for temperature difference 14 K, 400 V / 50 Hz(11) Heating capacity for temperature difference 22 K, 400 V / 50 Hz*Values based on nominal airflow

Page 15: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

153059570

4. Transport / preparation

4.1 Transport

� The system’s individual components may only be conveyed with the means of transport intended for this purpose.

� Only transport the system in modules; do not transport devices which have been connected together

� Do not leave or operate with suspended loads.

� Only approved hoisting equipment with sufficient load capacity may be used.

� The hoisting equipment must be in perfect condition.

� Lifting gear (slings, chains, etc) must be checked for load capacity and damage before use.

� Before lifting the devices, lock all maintenance doors!

4.2 Preparation

� Check the characteristics of the ceiling.

� Check the individual components for damage in transport.

� For the installation site, choose a place which allows easy access for servicing and maintenance.

� Care should be taken that the components and the connecting cable at the installation site can neither be damaged mechanically nor affected by oil or other aggressive substances.

� Check that security devices, contactors and circuit boards in the control cabinet are tightly secured.

� Push any loose assemblies in firmly.

� The fresh air intake is to be designed in line with the applicable standards and should be placed well away from ex-haust air or extractor outlets (kitchens, laundries, etc.)

� If possible, the expelled air should be exhausted via a roof outlet well away from fresh air intakes, windows, balconies, etc.

Attention!Components that become loose during transport can cause malfunctions or damage.

4.2.1 Space requirement

� Care should be taken to allow free access to the operating side (from underneath).

� The important thing is to allow sufficient distance so that the maintenance panel can be opened and the main components removed.

� The height of the siphon for condensate outflow tubes (optional) must be taken into account when suspending the unit from a ceiling; use a condensate pump if necessary.

4.2.2 Ceiling construction

� The devices may only be installed under horizontal, vibration-resistant ceilings.

� The design of the ceiling and the suspension construction must comply with the client's requirements on acoustics (sound insulation) and the correct drainage of the condensate.

� The ceiling construction must be able to bear the units’ structural load.

"Transport / preparation"

Page 16: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions16

AL-KO EASYAIR®flat

Example of ceiling construction:

EF devices require a suspension option at the distance B1, while GF and PF devices require it at the distance B1 or B2 respectively.

for max. M12

Fig.: Dimensions ceiling construction

in mm EF 01 EF 02 EF 03 GF 01 GF 02 GF 03 PF 01 PF 02 PF 03

B1 662 662 968 663 663 969 663 663 969

B2 – – – 663 663 969 663 663 969

Page 17: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

173059570

5. Assembly

� AL-KO EASYAIR®flat will be delivered in modules.

� The manufacturer‘s documents must be read before assembly or disassembly.

� The installation drawing supplied with the system must be adhered to during assembly of the modules, in particular the filter and fan modules!

� Assembly and disassembly are only to be undertaken by appropriately trained personnel with the requisite know-ledge and experience.

� Work on electrical and mechanical equipment or components may only to be conducted by personnel with appropriate training and authorization.

5.1 Opening / removing the maintenance panel

� EASYAIR®flat units are fitted with sufficiently large maintenance panels to make servicing and inspection easy. Operating and servicing is always performed from underneath.

� Specially designed hinges allow the maintenance panel to be opened but also completely unhooked and removed.

Closed state Partially opened state(between 15° and 26°)Operating lid can be detached

Opened stateOperating lid cannot be detached

Fig.: Door positions

� To open the maintenance panel, open both locks completely using the key included and while supporting the panel with one hand, let the panel open slowly downwards.

� To unhook the maintenance panel, open both locks completely using the key included and open the panel about 3 cm. Then by hand, lift the panel slightly along the hinge side and unhook the hinges.

Warning!Always keep the panel supported in your hand.When you unhook the panel, hold it firmly with both hands.Caution! The panel is not secured from falling in any way.

5.2 Assembling the modules

5.2.1 Procedure

� Unpack the modules.

� Attach the click connector supplied with delivery in the intended aperture on the front side of the module; see Fig.: Click connector / door lock.

� The sealing strip provided must always be glued flush with the inside edge of the device and past the click-in connector onto the front part of the module, see Fig.: Attaching the sealing strip

� Care must be taken that the sealing strip is not attached under tension (particularly at the corners)!

"Assembly"

Page 18: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions18

AL-KO EASYAIR®flat

� Fit the cover cap included on the interior of the housing. This way the inspection openings for the click connector are closed; see Fig.: click connector / door lock.

� Hook in the mounting straps at the top of the housing and attach them to the housing with the screws provided, see Fig.: Mounting straps

� Screw a Duo-Taptite M8X25 screw into the hole of the inner mounting bracket of the "left housing", see Figure: Con-nect modules

� The assembly of the GF and PF devices starts with the heat recovery module.

� Attach the modules to the ceilings in the appropriate assembling sequence (left housing before right housing!) using the mounting brackets and suitable mounting material (noise insulation to be provided by the customer). Take note of the device structures, see Fig.: Connect modules

� Once the modules have been installed on the ceilings, connect the modules with the click-in connectors by pressing them against each other. Care must be taken that the Duo-Tapite screw threads into the bracket of the "right housing".

In order to reduce the weight of the individual modules, the components can be removed from the housings.

After loosening the covers, using the special tool included, the click connectors can be opened at any time and removed from the housing; see Fig.: click connector / door lock.

� Establish potential equalisation of the modules by connecting them using a potential equalisation bolt; see Fig.: potential equalisation

� After that, fit cover; see Fig.: potential equalisation

� Connect the entire installation to the potential equalisation

1

4

23

1 Click connectors2 Covering cap3 Special tool4 Door lock

Fig.: Click connectors / door locks

Page 19: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

193059570

2

1

3

1

2

3

Fig.: Installation links

1 Installation link2 Fixing screws3 Housing

12

1 Screw for potential equalization2 Covering cap

Fig.: Potential equalization

"Assembly"

Page 20: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions20

AL-KO EASYAIR®flat

12

3b

a

2c

1 Installation link2 Sealing strip3 Duo-Taptite M8X25a PLT or GST Housingb Left Housingc Right Housing

Fig.: Connecting modules

1

2

1 Sealing strip2 Click connectors

Fig.: Sealing strip stick on

5.2.2 Removing components

Warning!The suspended parts have to be secured against falling down when they are extended. A second person may secure them as required.Falling down must be prevented by counter-action when the safeguards are removed.

Generally speaking, the following components can be removed from inside the housings:

Filter

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel".

� The filter can be removed from the housing by pulling at the frame of the filter bag.

Silencer

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel".

� Turn the safety latches (red) by 90° to longitudinal orientation.

� Carefully remove the silencer from the housing.

Fans

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel".

� Disconnect the electricity supply by loosening the snap coupling.

� Turn the safety plates (red) outwards.

� Carefully remove the fan from the housing.

Page 21: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

213059570

Plate heat exchanger (Cross flow)

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel".

� Remove the safety screws from the air guidance panels, see Fig.: Safety screws

� Detach the cross link by removing the screws, see Fig.: Cross link plate heat exchanger

� Turn the safety plates (red) outwards.

� Carefully remove the plate heat exchanger from the housing

1

23

4

2

1

Fig.: Safety screws Fig.: heat exchanger crosspiece

1 Safety screws 1 Fixing screws2 Washer 2 Crosspiece3 Plate heat exchanger (Cross flow)4 Air guidance panel

Plate heat exchanger (Counter flow)

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel".

� Support the door bar from the bottom

� Loosen the screws of the door bar, see Fig.: Door bar of the plate heat exchanger

� Carefully lower the door bar and modules of the plate heat exchanger (counter-current) out of the housing and remove separately.

Warning!It is important that the door bar is lowered horizontally to prevent sliding of the blocks resting on it.

34

12

5

1 GF module2 Door bar3 Cover flap4 Duo Taptite M5x105 Toothed disk

Fig.: Door bar for plate heat exchanger (counter-flow)

"Assembly"

Page 22: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions22

AL-KO EASYAIR®flat

Drip separator (cooler module)

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel".

� Carefully remove the drip separator from the housing by pushing it up and sidewards in the direction of the heat exchanger and then lowering it.

5.2.3 Duct connection

For PF- and GF units the duct system channels the outdoor air into the air handling unit and into the building as supply air. The extract air is passed through the unit for heat recovery and channeled outside as exhaust air.

For EF units the duct system channels the outdoor or room air (recirculation) to the ahu and into the building / room as supply air.

Equipotential bonding between the device and the drain must be established with the grounding strip supplied.

Duct connections (optional)

Sound-isolated duct connections are available for all EASYAIR®flat units, which use the entire available unit cross-section.

These duct connections must be fixed with enclosed drilling screws to the casing.

Connection of the ducts to the unit must be properly performed.

Requirements for the duct system

The ventilation system should be designed for slow air velocities and low pressure drop to boost efficiency, energy consumption and air output.

Pulleys near the device should be avoided.

All connections between ducts and air handling unit are to be executed accurately and securely.

Condensation protection / thermal insulation

For PF- and GF units the outside and exhaust air ducts must always be well insulated to prevent condensation. It is particularly important to carefully insulate all pipelines leading directly to the unit and to cold rooms/zones.

For EF units that are used for cooling issues the supply air duct must be insualted.

Generally speaking, all air ducts carrying cold air must be insulated.

5.2.4 Siphon connection

EASYAIR®flat heat recovery and cooler modules are provided with a condensate tray and a condensate pipe in the ope-rating panel. This condensate pipe comes in the form of a snap-on coupling. This allows quick and easy connecting / disconnecting of the condensate drainage pipe to the device.

It is possible to push-fit a 14 mm outside diameter drainage tube directly into this connector.

As delivered, a short length of plastic 14 mm outside diameter drainage tube is inserted in the connector, so that it is possible to simply fit a commercial hose with 14 mm inside diameter onto this plastic hose using a hose clip.

Condensate outflow pipes must be connected to the waste-water system using an s-bend (supplied by client).

If this is not possible because of lack of space, a condensate pump (supplied by client) should be used.

In order to prevent an intake or outtake of air from the closed drainage system, the height of each siphon must be designed for the negative or over pressure of the air handling unit.

Page 23: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

233059570

Fig: Tray with siphon connection

Height Over pressure Negative pressure

H1 25 mm 105 mm

H2 120 mm 65 mm

H3 = H1 + H2

The installation height of the siphon must be kept in mind when installing the unit.

5.3 Electrical connection

� EASYAIR®flat devices are delivered as standard without control devices and without field devices.

� As an option, the devices can be ordered with control and field devices ready installed.

� The switch cabinet is delivered as a separate unit and must be wired up by the client with the EASYAIR®flat devices.

� This enables the switch cabinet to be installed in any easily accessible place as per the client's preferences.

Warning!The electrical connection may only be performed by a licensed electrician in accordance with the regulations as well as the directives of the local power company. The connection is to be performed in exact accordance with the circuit diagram and assembly plan.

If necessary, connect the switch cabinet to the field devices on the EASYAIR®flat unit according to the wiring diagram which is included in the unit documentation (optionally with control system).

5.3.1 Cable list

No liability is assumed for the stated cable cross-sections.Type of installation and possible accumulations have not been taken into consideration!

Unit type CablePF-01; GF-01; EF-01 Supply line (230 VAC / 1 Ph), 3 x 1,5 mm2

Unit type CablePF-02; PF-03; GF-02; GF-03; EF-02; EF-03 Supply line (400 VAC / 3 Ph), 5 x 1,5 mm2

"Assembly"

Page 24: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions24

AL-KO EASYAIR®flat

Cables from the switch board to the field devices:

Field device CableActuator for dampers and bypass damper 3 x 0,75 mm2

External control element 6-wire Telefone ribbon cable for RJ12 connectorTemperature sensor 2 x 0,75 mm2

Frost protection thermostat 2 x 0,75 mm2

Valves (heating valve, cooling valve) 3 x 0,75 mm2

Pumps (heating pump, cooling pump) 3 x 1,5 mm2

Presence detector 2 x 0,75 mm2

Electrical heater

Cable from unit switch board to the electrical heater:

Control 0-10 V DC 2 x 0,75 mm2

Power supply (230 VAC / 1 PH) 3 x 1,5 mm2

Unit Supply Capacity Current consumption Supply linePF-01 400 VAC / 3 Ph 5,5 kW 7,9 A 4 x 1,5 mm2

PF-02 400 VAC / 3 Ph 9,5 kW 13,7 A 4 x 1,5 mm2

PF-03 400 VAC / 3 Ph 14,0 kW 20,2 A 4 x 2,5 mm2

GF-01 400 VAC / 3 Ph 5,5 kW 7,9 A 4 x 1,5 mm2

GF-02 400 VAC / 3 Ph 9,5 kW 13,7 A 4 x 1,5 mm2

GF-03 400 VAC / 3 Ph 14,0 kW 20,2 A 4 x 2,5 mm2

EF-01 400 VAC / 3 Ph 8,1 kW 11,7 A 4 x 2,5 mm2

EF-02 400 VAC / 3 Ph 14,6 kW 21,1 A 4 x 4 mm2

EF-03 400 VAC / 3 Ph 21,9 kW 31,6 A 4 x 4 mm2

Page 25: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

253059570

5.3.2 Installation / connection of remote control (optional)

You can control all settings on your ventilation system using the central control unit on the switch board.

If your system has the optional external control element, you can also control the settings from this control element that you can install away from the switch board.

� For connecting the remote control, use the supplied 6-wire ribbon cable (10 m) with a Western modular RJ12 plug. The maximum permissible cable length is 50 m.

� Connect the RJ12 plug with the J10 controller plug connection.

1

2

Fig.: Remote control connection

1 Control2 Connection of remote control

5.3.3 Installation / connection of temperature sensors for supply, outdoor and extract air

Outdoor air temperature sensor

� In order to measure the exact outside temperature, the sensor must be placed in the weatherproof grid or outdoors.

Temperature sensor extract air*

� In order to measure the exact extract air temperature, the extract air temperature sensor must be in the duct work in a way that a mixing temperature of all single zones can be detected.

* An external room temperature sensor may be optionally installed inside the heated rooms. This replaces the factory-fitted sensor and is connected to the controller.

Only a room or an extract air sensor may be connected! The connection of both sensors is not permitted.

"Assembly"

Page 26: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions26

AL-KO EASYAIR®flat

Supply air temperature sensor

� In order to measure the exact supply air temperature, the supply air sensors must be mounted in the duct be-hind the air handling unit. Mounting directly onto the outlet of the supply air duct is ideal, taking into account any interference influences within the ductwork.

Fig.: Temperature sensor location

1 Temperature sensor 3 Supply air* temperature sensor location

2 Extract air temperature sensor location 4 Outdoor air temperature sensor location

* Mount the temperature sensor for supply air at least 3 m behind the unit!

5.3.4 Electrical air heater connection (optional ELE)

For heating up the supply air an optional electrical heater is available.

Attention!Installation, electrical connection, maintenance and repair may only be conducted by trained personnel!

The air heater is included in the controller for the room and supply air temperature and is continually regulated according to the temperature requirement. The air heater is equipped with an integrated safety-temperature limiter and airflow switch.

� Connect the air heater electrically according to the circuit diagram.

Power consumption / cable list, see "5.3.1 cable list"

The power supply must be realised on site.

Page 27: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

273059570

Black

BlackRed

White

White

Blue

PE

X5

PE

LN

1 x 230V AC

A1

A2

L1L2L3PE

EFS 9252

3 x 400V

1

1 10

11

210V

Black

X5

X5

PE L1 L2 L3

Black Orange

Black

2

3

3

4

4

5

5 13

12

6GND

6

L1 L2 L3 PE

1 2

3

45

6

7

8

9

10

11

12

Fig.: Connection schematic for electric air heater

1 Ext. power supply 7 Power controller / pulser2 Release control voltage AL-KO 8 Duct sensor (NTC) in the air heater3 Miniature circuit breaker 9 Contactor 24 Contactor 1 10 Flow monitor (signaling contact)5 Ext. control by AL-KO 11 Safety temperature limiter6 Air heater 12 Flow monitor (power supply)

Attention!A flow monitoring device and a fan overrun must be installed on-site for units without integrated control!

5.3.5 Hot water heater connection (optional WWE)

A pump hot water heater (PHW) may be used to heat the supply air.

� Supply and return lines are to be connected according to professional standards.

Do not confuse the supply and return lines when connecting the pipes.The water intake is on the air outlet side (Fig.: counter-current principle).

Warning!When connecting the heat exchanger with an appropriate tool (i.e. pipe wrench), hold it firmly in order to avoid damage. Attach cables and connections to the heat exchanger so that it is readily accessible for maintenance.

� Maximum operating pressure: 6 bar � Maximum hot water flow temperature: 80 °C

� Valves and actuators must be professionally installed.

� Actuators must be connected in the control cabinet and registered in the controller, see "6.5.2 Addressing Valve Actuator Motors"

� Carefully ventilate the heat exchanger.

"Assembly"

Page 28: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions28

AL-KO EASYAIR®flat

1

1

2

2

3

3

4

4

1

1

2

2

3

3

4

4

Fig.: PHW air heater diagram Fig.: Counter-current principle

1 PHW heater2 Frost protection3 Valve4 Valve actuator (bulk delivery)5 Recirculation pump (on-site)

1 Air intake

2 Air outlet3 Media intake4 Media outlet

The figure only shows the schematic hydraulic connection of the heater. The exact hydraulic connection must be done acc. to the requirements of the heating system.

Access to the heat exchanger must be guaranteed on the duct side.

Function

The heater is included in the controller for the room and supply air temperature. Heat emission is metered through adjusting the appropriate control valve.

Attention!For temperatures below freezing point, in order to prevent frost and corrosion the heat exchanger must either be emptied and exhausted with pressurized air or filled with commercial antifreeze with corrosion protection.Emptying can be performed via the discharge screw intended for this purpose on the underside of the collector.

5.3.6 Cooler module connection (option KWK)

For an additional cooling of the supply air a chilled water cooling coil is available.

A drip separator (DS) is mounted behind the cooler in order to prevent condensate carry-over into the duct.

� Supply and return lines from both heat exchangers are to be connected according to professional standards.

Do not confuse the supply and return lines when connecting the pipes. The water intake is on the air outlet side (Fig.: counter-current principle).

Page 29: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

293059570

Attention!When connecting the heat exchanger with an appropriate tool (i.e. pipe wrench), hold it firmly in order to avoid damage.Attach cables and connections to the heat exchanger so that it is readily accessible for maintenance.

� Valves and actuators must be professionally installed.

� Actuators must be connected in the control cabinet and registered in the controller, see "6.4.2 Addressing Valve Actuator Motors"

� Carefully ventilate the heat exchanger.

1

1

2

2

3

3

4

4

1

1

2

2

3

3

4

4

Fig.: PCW air cooler diagram Fig.: Counter current principle

1 Cooler PCW

2 Valve3 Valve actuator (bulk delivery)4 Recirculation pump (on-site)

1 Air intake

2 Air outlet3 Media intake4 Media outlet

The figure only shows the schematic hydraulic connection of the cooler. The exact hydraulic connection must be done acc. to the requirements of the heating system.

Access to the heat exchanger and drip separator must be ensured on the duct side.

Function

The cooler is included in the controller for the room and supply air temperature. The temperature is set by regulating the cold water control valves.

Attention!For temperatures below freezing point, the heat exchangers must either be emptied and exhausted with pressu-rized air or filled with commercial antifreeze with corrosion protection in order to prevent frost and corrosion.Emptying can be performed via the discharge screw intended for this purpose on the underside of the collector.

"Assembly"

Page 30: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions30

AL-KO EASYAIR®flat

5.3.7 Installation of bus cards (optional)

The controller may be optionally integrated into a supra-ordinate network.

In addition, the following bus cards may be inserted into the available control slot:

� LON

� Modbus

� BACnet

� Ethernet

Fig.: Slot for optional bus cards

� The connection to the bus cable is directly performed with the optional plug-in card.

� Only one plug-in card is possible in each case.

� Data point lists, see "11 Appendix Data Point List"

5.3.8 Connection control (optional)

� Connect the supply air sensor (included in delivery) at the switch cabinet.

� Connect the outdoor air sensor (included in delivery) at the switch cabinet.

� Connect the extract air sensor (included in delivery) at the switch cabinet.

� In case of the "room temperature regulation" option, connect the room sensor (included in delivery) at the switch cabinet.

� Connect the installed damper actuator at the switch cabinet.

� For WWE modules, connect the frost protection thermostat at the switch cabinet.

� For filter modules, connect the pressure sensor to the filter monitoring at the switch cabinet.

� Connect the associated valves and pumps at the switch cabinet.

� Connect the main power supply and the control circuits for fresh and exhaust air units at the switch cabinet and to the plugs (included in delivery) as per the wiring diagram. Then insert the plugs into the sockets built into the ven-tilator module.

� In case of the pressure or constant volume regulation option, connect the two pressure transmitters at the switch cabinet (at constant pressure regulation: previous on-site installation of the transmitters on channels).

If, in additional, there is a remote control, it must be plugged into the adjustment control in position J10, using an RJ-12 plug.

� Connect the supply line according to the wiring diagram.

Page 31: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

313059570

6. Commissioning

6.1 Basics

For commissioning, AL-KO recommends proceeding according to the example commissioning protocol, see "12. Sample Commissioning Protocol."

Before commissioning, make sure:

� that the device was installed as described in this manual, see "5. Assembly."

� that all filter elements are properly installed.

� that the duct system and the water and drainage system are properly connected to the unit.

� that the fresh air intake is an adequate distance from sources of dirt etc. (kitchen extractor hood, central dust vacuum, etc.).

6.2 Before starting the system

� Check the mechanical function of the blind flaps by manually unlocking them at the actuator motor.

� Check the seals of all built-in filters.

AL-KO generally recommends replacing all of the filters after brief operation of the system in order to remove the contaminants from the construction and commissioning phases.

� Check the mechanical function of the by-pass flap (plate heat exchanger) by manually unlocking it at the actuator motor.

� Turn the fan impeller by hand several times and check for ease of movement.

� If necessary, remove foreign bodies from the fan enclosure.

� Check the heat exchanger for dirt and damage.

� Every condensate outflow pipe must be connected to the waste-water system using a separate s-bend. (see 5.2.4 Siphon connection)

� Complete the installation and put into operation in accordance with the commissioning protocol.

6.3 Turning the system on and off

� All control systems and modules are made ready for operation when the power supply is detected at the switch cabinet.

"Commissioning"

Page 32: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions32

AL-KO EASYAIR®flat

6.4 After starting the system

The indicated menu settings are described in detail in chapter "7. Settings Menu."

� Check the damper actuator motors for

� the correct rotation � the correct position � If this is not the case, the direction of rotation must be changed with the rotation direction switch of the flap

actuator motors.

� Address the damper actuator motors; see "6.5.1 Addressing Damper Actuator Motors."

� Check the correct direction of rotation of the fan motors by briefly switching on and off. The inlet valve is marked with a red arrow indicating the direction of rotation.

� With three-phase motors, the direction of rotation can be reversed by changing over 2 phases at the power supply input.

Attention!Risk of injury from running fan! Block off the fan prior to inspecting the motor direction! After the machine is switched off, the rotor still runs for approx. 1 to 3 more minutes. Never bring the rotor to a stop by hand or other object!

� Check to make sure that the valves are set as shown in the "display" menu. If this is not the case, the rotational direction of the valve actuator drive must be changed as required.

� Set the operating hours counter to zero.

� Set the date, time, medium and low air flow, and program the weekly schedule.

� Enter the address of the service company.

� Operational commissioning of the electric heater (optional)

6.4.1 Addressing damper actuator motors

The actuator motors of the dampers are connected to the MP-bus of the EASYAIR®flat air handling unit. They must be registered (addressed) using the controller during commissioning.

1

2

3

54

1 Rotation direction switch Switch over: Rotation direction changed

2 Press button and LED display green

Off: No voltage supply or faultGreen illuminated: OperationPress button: Activate the rotation angle adjustment, thereafter normal operation

3 Press button and LED display yellow

Off: Normal operation without MP busYellow illuminated: Adaptation or synchronisation process activeYellow flashing: Request for access by MP masterPress button: Confirm the accessYellow flickering: MP communication active

4 Button for gearbox disconnection

Press button: Gearbox disconnected, motor stops, manual adjustment possibleRelease button: Gearbox connected, start synchronisation, thereafter normal operation

5 Service connector For connection of the parameterisation and service tools

Fig.: Damper actuator motor

MP Bus modules may only be addressed when the system is in the "OFF" operating mode!

Page 33: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

333059570

Steps

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Select "Password Entry" using the < – > key.

5. Enter the password using the < + > and < – > keys and confirm by pressing <ENTER>.

The password "0005" is pre-set.

6. Select the "Other" menu using the < – > key.

7. Enter the "Other" menu by pressing <ENTER>.

8. Select "MP Bus Components" using the < – > key.

9. Select the MP Bus Module 1, "Supply Air Damper" using the < + > and < – > keys.

10. Confirm by pressing <ENTER>.

11. Press the "Address" button on the damper actuator motor.

The message "MP Bus module is addressed" appears.

12. Confirm by pressing <ENTER>.

13. Where present, address the second damper actuator motor in the same manner.

6.4.2 Addressing valve actuator motors

The valve actuator motors for the WWE or WKE options are connected to the MP bus of the EASYAIR®flat air handling unit. Heating and cooling valves must be addressed after installation. If the required Belimo module is not available, it must be configured at the manufacturer level.

MP bus modules may only be addressed when the system is in the "OFF" operating mode!

Steps

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Select "Password Entry" using the < – > key.

5. Enter the password using the < + > and < – > keys and confirm by pressing <ENTER>.

The password "0005" is pre-set

6. Select the "Other" menu using the < – > key.

7. Enter the "Other" menu by pressing <ENTER>.

8. Select "MP Bus components" using the < – > key.

9. Select the MP bus module that you would like to configure using the < + > and < – > keys.

10. Confirm by pressing <ENTER>.

11. Press the "address" button on the valve actuator motor.

The message "MP Bus module is addressed" appears.

12. Confirm by pressing <ENTER>.

13. If available, address the cooling valve in the same manner.

"Commissioning"

Page 34: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions34

AL-KO EASYAIR®flat

7. Set-up menus

7.1 Control unit (optional remote control)

Fig.: Remote control

1 Remote control 2 Main display

Operating element General function Function in the basic image

ALARM Showing a fault; Acknowledging a fault

Showing a fault Acknowledging a fault

Prg PRG Program display Shows the most common settings

Esc ESC Switches to the previous menu Switches to the main menu

+ Navigation in the menu Raises the target value displayed

- Navigation in the menu Lowers the target value displayed

ENTER Confirming values Selecting menu items

Adjusting the fan speed Turns the system OFF

1

2

Page 35: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

353059570

7.2 Main display

After being switched on, the controller starts a self-test. The main display then appears. The display automatically switches to the main display if a button is not pressed in the sub-menu within 60 seconds.

Fig.: Main display

1 Date 4 Time 2 Alarm - error display 5 Temperature-target value *3 Selected setting 6 Setting status

* If the "ventilation" mode is selected, the actual temperature value will be displayed.

7.2.1 Turning the fans on and off

� The system is connected to the power network via the main switch. Thereby, all regulation and control components are ready.

Attention!The main switch is NOT suitable for switching on and off during operation.

� Switch on by pressing <ENTER>.

Fig.: Switching on and off

7.2.2 Setting the temperature from the main display

� You can raise the target temperature value using the < + > key.

� You can lower the target temperature value using the < – > key.

If the time switch program is active, the programmed temperature can only be lowered or raised by 2 °C by using these keys.

1 4

2 5

3 6

"Set-up menus"

Page 36: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions36

AL-KO EASYAIR®flat

7.3 Menu levels

The controller is divided into 3 levels:

� User Level

� This level contains all important functions necessary for the system operator.

� Service Level

� This level contains all functions, which as a rule are only to be set during operational start-up and are necessary for the system start-up. Password: 0005

� Manufacturer level

� This level is only needed by the manufacturer for system parameterization and is no longer required in this manual.

Set PointTemperature

Main Menu

Set Point Fan

Settings

Display

Option WeekProgram Activ

Time Functions

Operation Mode

Service

Esc

Esc

Esc

Esc

Esc

Esc

Esc

Esc

Esc

Esc

Esc

see 7.4.1

see 7.4.2

see 7.4.3

see 7.5

UserLevel

Service Level

Example:Adjust OperationMode

Esc

Fig.: Menu Levels

Page 37: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

373059570

7.3.1 Setting the system parameters

General

� Select the menu item to be adjusted and confirm by pressing <ENTER>.

� Set the desired value using the < + > and < – > keys.

Setting the temperature

Fig.: Setting the temperature

1. Press <ESC> in the main display.

2. Enter the settings menu by pressing <ENTER>.

� You can raise the target temperature value using the < + > key. � You can lower the target temperature value using the < – > key.

� When several adjustable parameters are within the display field, you can toggle between these by using the <ENTER> button.

Setting the support function heating

Fig.: Support function heating

1. Press <ESC> in the main display.

2. Enter the "Service" menu by pressing <ENTER>.

� Navigate to "Password Entry" using the < – > key. � Enter the password using the < – > or < + > keys and confirm by pressing <ENTER>. � Then navigate to the "Support Function" menu by pressing <ENTER>. � Set the desired value using the < – > and < + > keys.

"Set-up menus"

Page 38: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions38

AL-KO EASYAIR®flat

7.4 User level

7.4.1 "Settings" menu

Fan

Operation Mode

Temperature

Week Program(only available with season switch clock)

Language

Set PointsSupply Air Fan

Set PointsExhaust Air Fan

Example:Set point adjustmentConstant pressure control:

Settings

Fig.: Menu tree settings

1. Press <ESC> in the main display.

2. Enter the "Settings" menu by pressing <ENTER>.

Setting the values, see "7.3 Setting the System Parameters"

Operating modes: Heating, cooling, ventilation, auto

� Heating: the system heats if the temperature target value is higher than the actual value. The system is otherwise in ventilation mode

� Cooling: The system cools if the temperature target value is lower than the actual value. The system is otherwise in ventilation mode

� Venting: The system ventilates. � Auto: The system heats, cools or ventilates automatically, see "7.5.5 Auto Operation Menu."

Page 39: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

393059570

7.4.2 "Displays" menu

1

2

3

Settings Sensor Values

Components

Miscellaneous

Fig.: Menu tree display

1 Current temperature values from the connected sensors, where applicable, pressures, flow rates, and air quality.

2 Current operational status of the respective field devices and the system.3 Supply air target temperature (automatically calculated by the controller with connected room and temperature

sensors and sets the target temperature of the incoming air).

1. Press <ESC> in the main display.

2. Navigate to the "Display" menu using the < – > key.

There you can retrieve the actual states.

"Set-up menus"

Page 40: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions40

AL-KO EASYAIR®flat

7.4.3 "Time functions" menu

Activating the time program

Time Functions Weekly Program

Daily Program

Date / Time

Fig.: "Time functions" menu tree.

1. Press <ESC> in the main display.

2. Navigate to the "Time Functions" menu using the < – > key.

3. Confirm by pressing <ENTER>.

4. Navigate as described below.

The time program is designed in such a way that one of 4 individually adjustable daily schedules can be assigned every weekday in the weekly schedule (Mon – Sun).

Each daily schedule has 6 switching times with separately assigned temperature target values and fan speeds.

Page 41: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

413059570

Setting the daily schedule

1. Navigate in the "Time Functions" menu to the "Daily Schedule" menu using the < – > key.

2. Confirm by pressing <ENTER>.

The respective switching times, temperature target values and fan speeds can be set by pressing the <ENTER> button several times.

3. Change the respective parameters by using the < + > and < – > keys.

After setting the first three time switching points, the cursor jumps back to the basic position.

4. Choose the time switching points 3 – 6 by using the < + > and < – > keys.

A maximum of 4 daily schedules are adjustable.

Example:

Switching point 1

Switching point 2

Switching point 3

Switching point 4

Switching point 5

Switching point 6

p15:00 Off 8:30 St.1 18:00 Off 20:00 Off 21:30 Off 22:00 Off

21,0 °C 21,0 °C 21,0 °C 21,0 °C 21,0°C 21,0 °C

p25:00 Off 8:00 St.1 10:00 St.1 12:00 St.1 14:00 Off 17:00 Off

21,0 °C 21,0 °C 21,0 °C 21,0 °C 21,0 °C 21,0 °C

p36:00 St.1 9:00 Off 17:00 St.1 19:00 St.1 22:00 St.1 23:00 St.1

21,0 °C 21,0 °C 21,0 °C 23,0 °C 19,0 °C 19,0 °C

p48:00 St.1 8:00 St.1 10:00 St.1 12:00 St.1 18:00 St.1 20:00 St.1

21,0 °C 21,0 °C 21,0 °C 21,0 °C 21,0 °C 19,0 °C

Fig.: Daily schedules

Setting the weekly program

P1

Fig.: Weekly program

1. Select the menu item "Weekly Program" in the "Time Functions" menu.

2. Confirm by pressing <ENTER>.

3. Select the respective days of the week by repeatedly pressing <ENTER>.

A daily schedule (P1-P4) can be assigned to every weekday by using the < + > and < – > keys.

"Set-up menus"

Page 42: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions42

AL-KO EASYAIR®flat

Setting the time

Fig.: Change the date / time

1. Select the menu item "Date/Time" in the "Time Functions" menu.

2. Confirm by pressing <ENTER>.

3. Pressing <ENTER> moves the cursor one position to the right.

4. The value can be changed using the < + > and < – > keys.

If the controller is connected to the power supply during the shift from summer to winter-time, or winter to summer-time, from 2:00 AM and 3:00 AM , the change takes place automatically.

Maintaining temperature

If no fan level is chosen for certain times on a day that is controlled by the time program, the system switches to maintai-ning the temperature.

In this case the fan will only be switched on if the room temperature drops below the target value set in the daily schedule and it heats the room back up.

The maintaining temperature function is only active with a connected room sensor and activated time switching program.

7.5 Service level

7.5.1 "Unoccupied mode" menu

(only available with room temperature sensor)

Fig.: Unoccupied Mode display

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Enter the "Unoccupied Mode" menu by pressing <ENTER>.

When the system is switched off, the temperature increases or decreases according to the prevailing outdoor weather conditions and the climate inside the room. The "Unoccupied Mode htg" and "Unoccupied Mode clg" are available to counteract this.

Page 43: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

433059570

Unoccupied Mode Cooling

Power up conditions

� If the temperature in the room increases beyond the unoccupied cooling limit, the "Unoccupied Mode Cooling" switches on.

It remains on until the room temperature is 1 °C less than the unoccupied cooling limit.

Afterwards, the system is switched off.

Unoccupied Mode Heating

Power up conditions

� If the temperature in the room decreases to under the unoccupied heating limit, the "Unoccupied Mode Heating" switches on.

It remains on until the room temperature is 1 °C more than the unoccupied heating limit.

Afterwards, the system is switched off.

Boundary conditions

� System "OFF"

� No fault

� "Heating," "Cooling" or "Auto" mode

� Time switching program "off" or non-active

� Room temperature sensor connected

� Unoccupied Mode Heating and Cooling approved

� No night ventilation (in Unoccupied Mode Cooling)

"Set-up menus"

Page 44: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions44

AL-KO EASYAIR®flat

7.5.2 "Night ventilation" menu

Fig.: Night ventilation

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "Night Ventilation" menu using the < – > key.

7. Enter the "Night Ventilation" menu by pressing <ENTER> and set the parameters.

Power up conditions:

� Room temperature > room temperature power-on value

� Delta outdoor temperature/room temperature < room temperature - outdoor temperature

� Daily maximum value (previous day) > daily minimum

� Outdoor temperature > night minimum

Power down conditions:

� Outdoor temperature < night minimum

� Room temperature < room temperature power-on value

Boundary conditions:

� Room temperature sensor and outdoor temperature sensor connected

� Night ventilation approved

� Timer available

� Timer program non-active

� No fault

� System "OFF"

� Operating mode "Cooling" or "Auto"

Night ventilation has the task of cooling the room in summer during operation-free times by using cool, outside air. This pushes the stored heat in the walls on hot summer days outside in the most energy efficient way possible.

Page 45: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

453059570

7.5.3 "Supply air limitation" menu

Fig.: Supply air limitation

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "Supply Air Limitation" menu using the < – > key.

7. Go into the "Supply Air Limitation" menu by pressing <ENTER> and set the parameters.

Maximum supply air temperature

� The supply air temperature calculated by the controller cannot rise above the set value.

Minimum supply air temperature

� The supply air temperature calculated by the controller cannot fall below the set value.

Supply air limitation Antifreeze limit / supply air temperature

� If the supply air temperature falls below the set value, the system goes into frost alarm.

The supply air temperature is limited by a minimum and maximum value. If a high incidence of extraneous heat enters the room, the supply air temperature is prevented from falling too low. Drafts caused by the low supply air temperatures would occur in the room without this limit.

"Set-up menus"

Page 46: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions46

AL-KO EASYAIR®flat

7.5.4 "Compensation" menu

Fig.: Compensation

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > key and confirm by pressing <ENTER>.

6. Navigate to the "Compensation" menu using the < – > key.

7. Enter the "Compensation" menu by pressing <ENTER> and set the parameters.

Summer and winter compensation are used to automatically switch the system between summer and winter operation. Due to the external temperature, the temperature target value is thus shifted.

Summer

� Here you can program how many °C higher or lower the temperature target value should shift.

Winter

� Here you can program how many °C higher or lower the temperature target value should shift.

Start at

� Here you can program the external temperature at which summer or winter compensation begins.

End at

� The fresh air rate can be limited here ("Settings" menu)

� Here you may program the external temperature at which summer or winter compensation ends and the tempera-ture target value shift has reached its maximum value.

1 42 3

Fig.: Summer / winter compensation

1 End of winter compensation 3 Start of summer compensation2 Start of winter compensation 4 End of summer compensation

Page 47: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

473059570

7.5.5 "AUTO operation" menu

1 2

Fig.: AUTO operation

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "AUTO Operation" menu using the < – > key.

7. Enter the "AUTO Operation" menu by pressing <ENTER> and set the parameters.

If "AUTO" is switched on, the controller will constantly compare the calculated supply air target value with the outdoor temperature.

� If the outdoor temperature / supply air actual value is the same as the supply air target value, ventilation will be switched on.

� If the outdoor temperature / the supply air actual value falls below the value set in "differential heating," the controller automatically recognizes that the heat must be switched on.

� If the outdoor temperature / supply air actual value rises to the value set in "differential cooling," the system goes into cooling operation.

The "differential heating" default value is set to 2K and the "differential cooling" value to 4K .

It is normal that the actual temperature for the 2K heat demand and for the 4K cooling demand differ from the tempera-ture target value.

These values must be smaller if a more exact temperature control is desired.

Example:

� Differential heating: 2K

� Differential cooling: 4K

� Adjusted basic target value: 20 °C

Outdoor temperature 19 °C: System ventsOutdoor temperature 17 °C: System heats because the outdoor temperature / supply air actual value has fallen

below the "differential heating" value.Outdoor temperature 25 °C: System cools because the outdoor temperature / supply air actual value has risen

above the "differential heating" value.

"Set-up menus"

Page 48: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions48

AL-KO EASYAIR®flat

7.5.6 "Sensor offset" menu

The "Sensor Offset" menu enables the sensor value to be compared if where the temperature is not being precisely dis-played. It allows you to measure the actual temperature of the sensor with a calibrated thermometer and compare this with the temperature in the control display.

The temperature value displayed can be corrected by up to ± 5K in this menu.

Fig.: Sensor Offset

1. Press <ESC> in the main display.

2. Select the "Service" menu using the button < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "Sensor Offset" menu using the < – > key.

7. Enter the "Sensor Offset" menu by pressing <ENTER> and set the parameters.

Page 49: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

493059570

7.5.7 "Operating hours counter" menu

The operating hours counter counts the hours of operation during which the system is switched on. By doing this, the service intervals can be maintained.

Fig.: Operating hours counter

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "Operating Hours Counter" menu using the < – > key.

7. Enter the menu by pressing <ENTER>.

8. The operating hours counter can be reset by pressing <ENTER>.

7.5.8 "Alarm recording" menu

The last 10 fault messages are saved here and can be displayed.

Shows the saved faults

Fig.: Alarm Recording

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "Alarm Recording" menu using the < – > key.

7. Enter the menu by pressing <ENTER>.

"Set-up menus"

Page 50: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions50

AL-KO EASYAIR®flat

7.5.9 "Presence detection" menu

Fig.: Presence detection 1

Fig.: Presence detection 2

Prerequisites:

� A presence detector must be connected and configured at the manufacturer level.

The presence detector has the highest priority.

Regardless of operating mode and current target value, the system will be driven at the set values during presence detection.

The follow-up time indicates how long the system should run in the set operation mode after a presence detection defects.

7.5.10 "Miscellaneous" menu

siehe 7.6.1

siehe 7.6.2

siehe 7.6.3

Miscellaneous

Fig.: Overview of "Miscellaneous"

1. Press <ESC> in the main display.

2. Select the "Service" menu using the < – > key.

3. Enter the "Service" menu by pressing <ENTER>.

4. Navigate to "Password Entry" using the < – > key.

5. Enter your password (standard: 0005) using the < + > and < – > keys and confirm by pressing <ENTER>.

6. Navigate to the "Miscellaneous" menu using the < – > key and perform one of the following steps.

Page 51: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

513059570

New password

The password for the service level may be changed here.

Fig.: New password

1. Enter the "Miscellaneous" menu by pressing <ENTER>.

2. Navigate to "Password Entry" using the < – > key and confirm with <ENTER>.

3. Enter a new password using the < + > and < – > keys.

4. Confirm by pressing <ENTER>.

Index: Service

You can enter the service company's address and telephone number here. This display appears in the "service" menu.

Fig.: Index Service

1. Go into the "Miscellaneous" menu by pressing <ENTER>.

2. Navigate to "Index: Service" using the < – > button and confirm by pressing <ENTER>.

Characters, letters and digits can be selected using the < + > and < – > keys.

Pressing <ENTER> moves the cursor one position over.

3. When everything is entered, press <ESC>.

Addressing MP bus modules

See "6.5.1 Addressing Damper Actuator Motors" and "6.5.2 Addressing Valve Actuator Motors".

"Set-up menus"

Page 52: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions52

AL-KO EASYAIR®flat

8. Maintenance

The air handling unit operator is obligated to ensure that the system undergoes routine maintenance by trained personnel.AL-KO recommends performing maintenance according to VDI 6022 and VDMA 24186.In addition, a hygiene inspection is required every 3 years according to VDI 6022.

The AL-KO THERM GMBH assumes these tasks upon conclusion of a maintenance contract.

8.1 Safety

Attention!Installation, start-up, maintenance and repairs may only to be carried out by trained personnel!

Attention! � As a general rule, when working on the device always disconnect the power supply (disconnect all

phases).

� Only open the inspection doors when the machine is off and the fans are at a standstill. After the machi-ne is switched off, the rotor still runs for approx. 1 to 3 more minutes. Never bring the rotor to a stop by hand or other object!

� After working on the unit, the person responsible is to ensure that no persons remain in the system and that all factory-fitted protection measures are working before powering the system back up.

8.2 Consumables and replacement parts

Attention!Only use original consumables and replacement parts. Only in this way is safe operation guaranteed! The war-ranty is void in the case of non-compliance. You can find a replacement parts list in the unit documentation.

8.3 Fuses and terminals

The fuses are time delay circuit breakers.

Fuse and terminal assignments can be found in the wiring diagram included in delivery.

Page 53: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

533059570

8.4 Maintenance schedule

no. Component / activity Action / note Inspections to be carried outat monthly intervals

1 3 6 12 241. Outdoor and exhaust air outlets

Check for dirt, damage and corrosion Completely clean and repair X2. Unit housing

Check for dirt, damage and corrosion on the air side

Clean and repair X

Check for water formation (condensate, leakages)

Clean and identify the cause X

Check that drains are functioning properly

Clean if needed X

Flexible connections Check for leak tightness X3. Air filter

Check for unacceptable levels of dirt, damage (leakages) and odors.(The air filters must exhibit their designated filter class separating efficiency across their entire lifetime)

The appropriate filter is to be changed out with indication of contamination or leakages. If the entire filter change is overdue by more than 6 months, change out the entire filter

X

"Filter change" warning message Replace the filter if the maximum pressure difference is exceeded X

Most recent filter change XInspection of the hygiene state X

4. Heat exchangers, general (optional)If cleaning in the installed state is insufficient, the heat exchanger must be removed and adequately cleaned.Check for contamination, damage and corrosion

Clean and repair X

Wet cooler, condensate pan and drip separator are to be checked for contamination, corrosion and proper functioning

Repair

X

Check the siphon for functioning Repair XInspection of the hygiene state XAir heaterCheck for dirt, damage and corrosion on the air side

Clean and repair X

Cleaning to maintain proper functio-ning (downstream) X

Ventilate XElectrical air heaterCheck there is no formation of scaling or corrosion X

Check for dirt, damage and corrosion on the air side

Clean and repair X

Check for proper functioning XCheck the controller and safety equipment for proper functioning X

"Maintenance"

Page 54: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions54

AL-KO EASYAIR®flat

no. Component / activity Action / note Inspections to be carried outat monthly intervals

1 3 6 12 24Cooler The siphon backflow is to be

dimensioned and arranged according to the pressure conditions so that the condensation can flow unimpaired

Check for dirt, damage and corrosion

Clean and repair X

Clean wet cooler, drip separator and pan X

Check the supply and return for proper functioning X

Ventilate XCheck the hygiene state XDrip separatorCheck for dirt, damage and formation of deposits

Cleaning to maintain functionality - all surfaces including pan and drip separa-tor, dismantling if necessary

X

Check drip separator to ensure not formation of deposits

Carry out cleaning to maintain functionality, if encrustation is visible X

Check the water drainage and siphon for proper functioning X

5. Heat recovery, generalHeat exchangers and their accessories must be regularly inspected for dirt, corrosion and damage downstream.Check for dirt, damage and corrosion

The heat exchangers can be cleaned with a hot-water, high-pressure cleaner, (sec. 8.5.2)

X

Check the exhaust and outdoor airflow for tightness

Repair X

Condensate pan is to be checked for dirt, corrosion and functioning

Repair X

Check the siphon for proper functioning

Repair X

Control of the hygiene state X6. Dampers

Check for dirt, damage and corrosion

Clean if necessary X

Check for proper mechanical functioning X

Damper actuator motors Check for proper functioning X7. Fans

Check fans for dirt, damage and corrosion.

Clean and repair X

Check rotor for dirt, imbalance and running noise.

Switch on motor briefly X

8. Electrical controlVisually inspect terminals and connectors.

Clean if needed and check tightness of fitting.

Page 55: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

553059570

8.5 Checking components

All installed components are to either be easily accessible for inspection or extractable after removing the maintenance doors from the unit.

The objective of regular hygiene checks is to detect and eliminate hygiene issues early on through frequent visual inspec-tions or random microbiological checks.

Regular hygiene control includes the following measures:

Visual inspection of the unit for hygiene issues such as bacterial growth or contamination, rust build-up, calcium deposits and damage.

Components identified as dirty during the hygiene inspections must immediately be cleaned.

8.5.1 WWe / KWK

Attention!The use of high-pressure washers with conventional jet nozzles is not permitted due to risk of damage!

Corrosion may occur in the heat exchangers after longer periods of downtime due to sulfate-reducing bacteria. These sulfides aggressively corrode welded joints and copper-based material.

We recommend the following measures to reduce this type of copper corrosion:

� Using sulphate-free water in the entire circuit

� Ensuring there are no leaks in the system.

� Avoiding long periods of downtime for filled circuits.

� Avoiding frequent re-filling with fresh water.

� Using material-tolerant inhibitors or biocides.

8.5.2 Plate heat exchanger

The heat exchanger can be cleaned with a hot-water, high-pressure cleaner. The following parameters must be met:

Nozzle: Flat jet nozzlePressure: max. 20 barAmount of water: max. 450 l/hWater temperature: max. 70 °CDistance from the heat exchanger: min. 30 cmNozzle direction: 90° offset to the foil stamping or blades

1

2

3

4 5

6

Fig.: Clean the plate heat exchanger

1 Plate heat exchanger 4 Supply air2 High-pressure flat spray nozzle 5 Extract air3 Outdoor air 6 Exhaust air

"Maintenance"

Page 56: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions56

AL-KO EASYAIR®flat

Attention!The specified values must be met, otherwise the plate heat exchangers may be damaged.

Cleaning agents (i.e. all-purpose cleaners, biodegradable) may be used to remove stubborn dirt. Plenty of fresh water must be used for rinsing afterwards!Do not use any aluminum cleaners! They are acidic and corrode the surfaces of the plate heat exchanger.

8.5.3 Dampers

Regularly clean dampers.

Attention!When the dampers close, do not reach inside the slats with your hand during operation or servicing. Danger of crushing!

8.5.4 Drip separator

The drip separator can be pulled out for maintenance reasons.

8.5.5 Fans

Regularly clean ventilation rotors, the motor and the motor base.

8.6 Replacing components

8.6.1 Replacing filter bags

Filter bags are generally to be replaced once they have reached the permissible end pressure difference.

Do not wash out and reuse used air filters. They must always be replaced with new air filters. The hygienic requirements will not be met otherwise!

� Open or unhook the operating panel; see "5.1 Opening / removing the operating panel"

� The filter can be pulled downwards out of the housing by pulling on the filter bag frame.

� Clean and inspect the filter seals. Replace any damaged seals.

� Insert new filter bags and hold them in place by spanning them across the filter frame.

Attention!Only use original consumables and replacement parts.

Safe operation can only be ensured in this way. The warranty may be invalidated!

Page 57: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

573059570

9. Trouble shooting

Attention!Diagnosis, fault elimination and restarts may only be carried out by trained personnel. This is especially applicable for work on electrical equipment within the control cabinet (i.e. test work, replacing fuses)!

9.1 Contact

For all questions regarding our products, please contact the manufacturer of your ventilation system, one of our branches, or us directly:

AL-KO tHerm gmbH Telephone: (+49) 82 25 / 39 - 0Hauptstraße 248-250 Fax: (+49) 82 25 / 39 - 211389343 Jettingen-Scheppach E-Mail: [email protected]

Web: www.al-ko.com

9.2 General faults

Fault Possible cause of fault / actionRemote control does not work Check the connection:

� Was a 6-wire telephone cable used? � Was a 6-pole Western plug (RJ12) used? � Was the Western plug correctly crimped to the flat telephone cable?

If the connection is OK, check the address of the remote control: � Simultaneously press the < + >, < – > and <ENTER> keys on the remote control for 3 seconds. A menu will open:

The address 32 must be entered in the "display address setting."Damper actuator motors or valve actuator motors are not moving.

Address the actuators. MP bus modules, see "6.5.1 Addressing Damper Actuator Motors" and "6.5.2 Addressing Valve Actuator Motors.

Damper actuator motors cannot be parameterized.

Set the fan speed to "OFF."Damper actuator motors are wrongly connected.

Temperature target value cannot be set.

Set the operating mode to AUTO, heating or cooling. See "7.5.5 AUTO operation menu"

9.3 "AL" display faultThe system has experienced a fault if the "AL" symbol appears in the main display.

1. Display the fault:

� Press the fault button. . The current fault is displayed.

2. Fix the cause of the fault.

3. Finally, acknowledge the fault by pressing the fault button 4 times. The "AL" symbol is no longer visible.

4. The system can be switched on again.

"Trouble shooting"

Page 58: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions58

AL-KO EASYAIR®flat

9.4 "AL" fault table

Fault display Cause of fault / action CategoryDirty filter Replace the filter as soon as possible. 1Frostschutz The temperature directly behind the heating coil briefly fell below 6 °C:

� The heating coil was not adequately supplied with hot water. � Particularly with roof units, the unit temperatures may fall below 6 °C when the outside temperature is low and the system is "OFF."

� Set the operating mode to AUTO or heating.

2

Fan motor protection switch

Safety device for the fan motor has been triggered. � Fan motor windings overheated: acknowledge alarm message; have the motor serviced if the fault occurs again.

3

Frost protection limit of the supply air temperature.

The temperature in the supply air has fallen below 6 °C: � To fix the problem see "frost protection."

2

Pump failure One of the pumps is indicating a fault 3STL (safety temperature limiter)

The temperature of the electric heater has reached a too high value. � Fix the cause and disengage the safety temperature limiter in the electric heater.

3

Electric air heater If the alarm cannot be acknowledged or the electric heater fails again, have it serviced by trained personnel.

1

1 These faults are only displayed, but they should be taken care of as quickly as possible. They will not lead to a system shutdown.

2 When these faults occur, the fresh air and exhaust air dampers close, the fans stop, the heating valve opens and the heating circuit pump starts

3 These faults lead to an immediate system shutdown.

Page 59: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

593059570

10. Shutdown

10.1 Decommissioning

Prior to starting work, disconnect the power supply to the installation (switch off all poles), and safeguard the unit from powering on without authorization.

Warning!Several parts of the installation are under pressure.

Attention!In the winter, the risk of freezing exists for several components. As necessary, take suitable activities (such as filling these parts with antifreezing medium).

Prior to the next start-up, observe the items in the chapter "Commissioning and Maintenance".

When the system is shut down for a prolonged period, the instructions for the individual components must be adhered to.

The information of the component manufacturers must be taken into account (request a copy as required)

10.2 Dismantling

Prior to the next start-up, observe the items in the chapter "Commissioning and Maintenance".

Warning!Several parts of the installation are under pressure.

The dismantling may only be performed by trained specialist personnel.

The dismantling process must be performed according to the work/accident prevention regulations valid at the time such work is performed.

10.3 Disposal

Do not dispose of any disused devices, batteries or accumulators in household rubbish! For disposal of the EASYAIR®flat, the operation materials and accessories should executed according the relevant local environmental and recycling regulations in your state/country and muncipality as valid at the time of disposal.

"Shutdown"

Page 60: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions60

AL-KO EASYAIR®flat

11. Annexe control diagrams

11.1 eAsyAir®flat (PF-01 – PF-03; GF-01 – GF-03)

Außenluft-fühler

Fros

tsch

utz-

ther

mos

tat

Zulu

ftfüh

ler

Abl

uftfü

hler

Rau

mfü

hler

Fig.: Control scheme EASYAIR®flat (PF-01 – PF-03; GF-01 – GF-03)

B1 Pressure transmitter (supply air) Y1 Control signal supply air fan

B2 Pressure transmitter (extract air) Y2 Control signal exhaust air fan

B3 Supply air temperature sensor Y3 Control signal heating

B4 Extract air / room temperature sensor Y4 Control signal cooling

B5 Outdoor air temperature sensor ID1 Failure fan motor

NO1 Release Fan ID2 Reserve

NO2 Reserve ID3 Filter supervision

NO3 Reserve ID4 Frost protection thermostat

NO4 Pump / release heating ID5 Failure pump

NO5 Pump / release cooling ID6 Motor protection fan motor

NO6 Reserve ID7 Reserve

NO7 Reserve ID8 Reserve

NO8 Collective fault MP Bus

All actuators and valve operating mechanism

Page 61: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

613059570

11.2 eAsyAir®flat (PF-01 – PF-03; GF-01 – GF-03) with electrical heater

Außenluft-fühler

Zulu

ftfüh

ler

Abl

uftfü

hler

Rau

mfü

hler

Fig.: Control scheme EASYAIR®flat (PF-01 – PF-03; GF-01 – GF-03) with electrical heater

B1 Pressure transmitter (supply air) Y1 Control signal supply air fan

B2 Pressure transmitter (extract air) Y2 Control signal exhaust air fan

B3 Supply air temperature sensor Y3 Control signal heating

B4 Extract air / room temperature sensor Y4 Control signal cooling

B5 Outdoor air temperature sensor ID1 Failure fan motor

NO1 Release Fan ID2 Reserve

NO2 Reserve ID3 Filter supervision

NO3 Reserve ID4 Frost protection thermostat

NO4 Pump / release heating ID5 Failure pump

NO5 Pump / release cooling ID6 Motor protection fan motor

NO6 Reserve ID7 Reserve

NO7 Reserve ID8 Reserve

NO8 Collective fault MP Bus

All actuators and valve operating mechanism

"Annexe control diagrams"

Page 62: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions62

AL-KO EASYAIR®flat

11.3 eAsyAir®flat (EF-01 – EF-03)

Außenluft-fühler

Fros

tsch

utz-

ther

mos

tat

Zulu

ftfüh

ler

Rau

mfü

hler

Fig.: Control scheme EASYAIR®flat (EF-01 – EF-03)

B1 Pressure transmitter (supply air) Y1 Control signal supply air fan

B2 Pressure transmitter (extract air) Y2 Control signal exhaust air fan

B3 Supply air temperature sensor Y3 Control signal heating

B4 Extract air / room temperature sensor Y4 Control signal cooling

B5 Outdoor air temperature sensor ID1 Failure fan motor

NO1 Release Fan ID2 Reserve

NO2 Reserve ID3 Filter supervision

NO3 Reserve ID4 Frost protection thermostat

NO4 Pump / release heating ID5 Failure pump

NO5 Pump / release cooling ID6 Motor protection fan motor

NO6 Reserve ID7 Reserve

NO7 Reserve ID8 Reserve

NO8 Collective fault MP Bus

All actuators and valve operating mechanism

Page 63: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

633059570

11.4 eAsyAir®flat (EF-01 – EF-03) with electrical heater

Außenluft-fühler

Zulu

ftfüh

ler

Rau

mfü

hler

Fig.: Control scheme EASYAIR®flat (EF-01 – EF-03) with electrical heater

B1 Pressure transmitter (supply air) Y1 Control signal supply air fan

B2 Pressure transmitter (extract air) Y2 Control signal exhaust air fan

B3 Supply air temperature sensor Y3 Control signal heating

B4 Extract air / room temperature sensor Y4 Control signal cooling

B5 Outdoor air temperature sensor ID1 Failure fan motor

NO1 Release Fan ID2 Reserve

NO2 Reserve ID3 Filter supervision

NO3 Reserve ID4 Frost protection thermostat

NO4 Pump / release heating ID5 Failure pump

NO5 Pump / release cooling ID6 Motor protection fan motor

NO6 Reserve ID7 Reserve

NO7 Reserve ID8 Reserve

NO8 Collective fault MP Bus

All actuators and valve operating mechanism

"Annexe control diagrams"

Page 64: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions64

AL-KO EASYAIR®flat

12 Annexe data point list

12.1 LON-busLON-bus SNVT-Name SNVT-Type Resolution Range i /oTemperature set point nvisetpoint SNVT_temp_p (105) 0,1°C 0,0 - 99,0°C inTemperature set point nvocurr_setpoint SNVT_temp_p (105) 0,1°C 0,0 - 99,0°C outSupply air temperature nvosplytemp SNVT_temp_p (105) 0,1°C -50,0 - 200,0°C outExtract air temperature nvoexhtemp SNVT_temp_p (105) 0,1°C -50,0 - 200,0°C outOutdoor air temperature nvoouttemp SNVT_temp_p (105) 0,1°C -50,0 - 200,0°C outHeating demand nvohtg_valve SNVT_lev-percent (81) 0,1% 0,0 - 100,0% outCooling demand nvoclg_valve SNVT_lev-percent (81) 0,1% 0,0 - 100,0% outHeat recovery demand nvohr SNVT_lev-percent (81) 0,1% 0,0 - 100,0% outSet point air quality nviset_airq SNVT_temp_p (105) 0,1dp 0,0 - 99,9dp inAir quality nvoairquality SNVT_temp_p (105) 0,1dp 0,0 - 99,9dp outFresh air damper nvoflap_fresh SNVT_lev-percent (81) 0,1% 0,0 - 100,0% outExhaust air damper nvoflap_exit SNVT_lev-percent (81) 0,1% 0,0 - 100,0% outHR bypass damper nvoflap_bypass SNVT_lev-percent (81) 0,1% 0,0 - 100,0% out

Fan step nvifanstep SNVT_count (8) 1 0 - 3 inFan step nvicurr_fanstep SNVT_count (8) 1 0 - 3 outSet point revolution supply air step 1 nvisply_rot_1 SNVT_count (8) 0,1% 0,0 - 100,0% inSet point revolution supply air step 2 nvisply_rot_2 SNVT_count (8) 0,1% 0,0 - 100,0% inSet point revolution supply air step 3 nvisply_rot_3 SNVT_count (8) 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 1 nviexh_rot_1 SNVT_count (8) 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 2 nviexh_rot_2 SNVT_count (8) 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 3 nviexh_rot_3 SNVT_count (8) 0,1% 0,0 - 100,0% inSet point supply air pressure step 1 nvisply_pres_1 SNVT_press_p (113) 1 Pa 0 - 2500 Pa inSet point supply air pressure step 2 nvisply_pres_2 SNVT_press_p (113) 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 1 nviexh_pres_1 SNVT_press_p (113) 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 2 nviexh_pres_2 SNVT_press_p (113) 1 Pa 0 - 2500 Pa inSet point supply air flow step 1 nvisply_flow_1 SNVT_count (8) 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 2 nvisply_flow_2 SNVT_count (8) 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 3 nvisply_flow_3 SNVT_count (8) 1 m³/h 0 - 20000 m³/h inSet point exhaust air flow step 1 nviexh_flow_1 SNVT_count (8) 1 m³/h 0 - 20000 m³/h inSet point exhaust air flow step 2 nviexh_flow_2 SNVT_count (8) 1 m³/h 0 - 20000 m³/h inSet point exhaust air flow step 3 nviexh_flow_3 SNVT_count (8) 1 m³/h 0 - 20000 m³/h inSupply air flow nvo_sply_flow SNVT_count (8) 1 m³/h 0 - 20000 m³/h outExhaust air flow nvoexh_flow SNVT_count (8) 1 m³/h 0 - 20000 m³/h outSupply air pressure nvo_sply_pres SNVT_press_p (113) 1 Pa 0 - 2500 Pa outExhaust air pressure nvoexh_pres SNVT_press_p (113) 1 Pa 0 - 2500 Pa out

Heating pump / heating release nvohtg_pump SNVT_switch (95) 1 0 / 1 outCooling pump / heating release nvoclg_pump SNVT_switch (95) 1 0 / 1 outCollective fault nvocentral_err SNVT_switch (95) 1 0 / 1 outFilter failure nvoerr_filter SNVT_switch (95) 1 0 / 1 outFrost protection failure nvoerr_antifreeze SNVT_switch (95) 1 0 / 1 outRunning control heat recovery nvoerr_run_control SNVT_switch (95) 1 0 / 1 outFan running control nvoerr_fan SNVT_switch (95) 1 0 / 1 outPump running control nvoerr_pump SNVT_switch (95) 1 0 / 1 outFire / Smoke nvoerr_fire SNVT_switch (95) 1 0 / 1 outControl of min. supply air temperature nvoerr_frost_temp SNVT_switch (95) 1 0 / 1 outIcing heat recovery nvoerr_hr_frost SNVT_switch (95) 1 0 / 1 outBurner failure nvoerr_burner SNVT_switch (95) 1 0 / 1 outCooling machine failure nvoerr_chiller SNVT_switch (95) 1 0 / 1 outSupply air temperature sensor failure nvoerr_sply_temp SNVT_switch (95) 1 0 / 1 outControl rotary heat exchanger nvoerr_rotor SNVT_switch (95) 1 0 / 1 outHeat recovery failure nvoerr_hr_frost SNVT_switch (95) 1 0 / 1 outMaintenance required nvoerr_service SNVT_switch (95) 1 0 / 1 outSafety temperature limiter failure nvoerr_stb SNVT_switch (95) 1 0 / 1 outAir stream control nvoerr_air_ctrl SNVT_switch (95) 1 0 / 1 outMotor control nvoerr_motor SNVT_switch (95) 1 0 / 1 outElectrical heater failure nvoerr_E_htg SNVT_switch (95) 1 0 / 1 out

Page 65: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

653059570

12.2 Mod-busFunction Data register Variabletype Resolution Range i /oTemperature set point Register 2 Analog 0,1°C 0,0 - 99,0°C inTemperature set point Register 3 Analog 0,1°C 0,0 - 99,0°C outSupply air temperature Register 4 Analog 0,1°C -50,0 - 200,0°C outExtract air / room air temperature Register 5 Analog 0,1°C -50,0 - 200,0°C outOutdoor air temperature Register 6 Analog 0,1°C -50,0 - 200,0°C outHeating demand Register 7 Analog 0,1°C 0,0 - 100,0% outCooling demand Register 8 Analog 0,1% 0,0 - 100,0% outHeat recovery demand Register 9 Analog 0,1% 0,0 - 100,0% outSet point air quality Register 10 Analog 0,1dp% 0,0 - 100,0dp inAir quality Register 11 Analog 0,1dp% 0,0 - 100,0dp outFresh air damper Register 12 Analog 0,0% 0,0 - 100,0% outExhaust air damper Register 13 Analog 0,1% 0,0 - 100,0% outHR bypass damper Register 14 Analog 0,1% 0,0 - 100,0% out

Outdoor air proportion Register 130 Integer 1% 0 - 100% inFan step Register 131 Integer 1 0 - 3 inOperation mode Register 132 Integer 1 0 - 3 inOutdoor air proportion Register 133 Integer 1% 0 - 100% outFan step Register 134 Integer 1 0 - 3 outOperation mode Register 135 Integer 1 0 - 3 outSet point revolution supply air step 1 Register 136 Integer 0,1% 0,0 - 100,0% inSet point revolution supply air step 2 Register 137 Integer 0,1% 0,0 - 100,0% inSet point revolution supply air step 3 Register 138 Integer 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 1 Register 139 Integer 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 2 Register 140 Integer 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 3 Register 141 Integer 0,1% 0,0 - 100,0% inSet point supply air pressure step 1 Register 142 Integer 1 Pa 0 - 2500 Pa inSet point supply air pressure step 2 Register 143 Integer 1 Pa 0 - 2500 Pa inSet point supply air pressure step 3 Register 144 Integer 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 1 Register 145 Integer 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 2 Register 146 Integer 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 3 Register 147 Integer 1 Pa 0 - 2500 Pa inSollwert Zuluft Volumenstr. Stufe 1 Register 148 Integer 1 m³/h 0 - 20000 m³/h inSollwert Zuluft Volumenstr. Stufe 2 Register 149 Integer 1 m³/h 0 - 20000 m³/h inSollwert Zuluft Volumenstr. Stufe 3 Register 150 Integer 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 1 Register 151 Integer 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 2 Register 152 Integer 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 3 Register 153 Integer 1 m³/h 0 - 20000 m³/h inSupply air flow Register 154 Integer 1 m³/h 0 - 20000 m³/h outExhaust air flow Register 155 Integer 1 m³/h 0 - 20000 m³/h outSupply air pressure Register 156 Integer 1 Pa 0 - 2500 Pa outExhaust air pressure Register 157 Integer 1 Pa 0 - 2500 Pa out

Heating pump / heating release Coil 2 Digital 1 0 / 1 outCooling pump / heating release Coil 3 Digital 1 0 / 1 outCollective fault Coil 4 Digital 1 0 / 1 outFilter failure Coil 5 Digital 1 0 / 1 outFrost protection failure Coil 6 Digital 1 0 / 1 outRunning control heat recovery Coil 7 Digital 1 0 / 1 outFan running control Coil 8 Digital 1 0 / 1 outPump running control Coil 9 Digital 1 0 / 1 outFire / Smoke Coil 10 Digital 1 0 / 1 outControl of min. supply air temperature Coil 11 Digital 1 0 / 1 outIcing heat recovery Coil 12 Digital 1 0 / 1 outBurner failure Coil 13 Digital 1 0 / 1 outCooling machine failure Coil 14 Digital 1 0 / 1 outSupply air temperature sensor failure Coil 15 Digital 1 0 / 1 outControl rotary heat exchanger Coil 16 Digital 1 0 / 1 outHeat recovery failure Coil 17 Digital 1 0 / 1 outMaintenance required Coil 18 Digital 1 0 / 1 outSafety temperature limiter failure Coil 19 Digital 1 0 / 1 outAir stream control Coil 20 Digital 1 0 / 1 outMotor control Coil 21 Digital 1 0 / 1 outElectrical heater failure Coil 22 Digital 1 0 / 1 out

"Annexe data point list"

Page 66: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions66

AL-KO EASYAIR®flat

12.3 BACnetFunction Resolution Range i /o

A001 Temperature set point 0,1°C 0,0 - 99,0°C in/outA002 Temperature set point 0,1°C 0,0 - 99,0°C outA003 Supply air temperature 0,1°C -50,0 - 200,0°C outA004 Extract air / room air temperature 0,1°C -50,0 - 200,0°C outA005 Outdoor air temperature 0,1°C -50,0 - 200,0°C outA006 Heating demand 0,1% 0,0 - 100,0% outA007 Cooling demand 0,1% 0,0 - 100,0% outA008 Heat recovery demand 0,1% 0,0 - 100,0% outA009 Set point air quality 0,1dp 0,0 - 99,9dp in/outA010 Air quality 0,1dp 0,0 - 99,9dp outA011 Fresh air damper 0,1% 0,0 - 100,0% outA012 Exhaust air damper 0,1% 0,0 - 100,0% outA013 HR bypass damper 0,1% 0,0 - 100,0% out

I001 Outdoor air proportion 1% 0 - 100% in/outI002 Fan step 1 0 - 3 in/outI003 Operation mode 1 0 - 3 in/outI004 Outdoor air proportion 1% 0 - 100% outI005 Fan step 1 0 - 3 outI006 Operation mode 1 0 - 3 outI007 Set point revolution supply air step 1 0,1% 0,0 - 100,0% in/outI008 Set point revolution supply air step 2 0,1% 0,0 - 100,0% in/outI009 Set point revolution supply air step 3 0,1% 0,0 - 100,0% in/outI010 Set point revolution exhaust air step 1 0,1% 0,0 - 100,0% in/outI011 Set point revolution exhaust air step 2 0,1% 0,0 - 100,0% in/outI012 Set point revolution exhaust air step 3 0,1% 0,0 - 100,0% in/outI013 Set point supply air pressure step 1 1 Pa 0 - 2500 Pa in/outI014 Set point supply air pressure step 2 1 Pa 0 - 2500 Pa in/outI015 Set point supply air pressure step 3 1 Pa 0 - 2500 Pa in/outI016 Set point exhaust air pressure step 1 1 Pa 0 - 2500 Pa in/outI017 Set point exhaust air pressure step 2 1 Pa 0 - 2500 Pa in/outI018 Set point exhaust air pressure step 3 1 Pa 0 - 2500 Pa in/outI019 Set point supply air flow step 1 1 m³/h 0 - 20000 m³/h in/outI020 Set point supply air flow step 2 1 m³/h 0 - 20000 m³/h in/outI021 Set point supply air flow step 3 1 m³/h 0 - 20000 m³/h in/outI022 Set point exhaust air flow step 1 1 m³/h 0 - 20000 m³/h in/outI023 Set point exhaust air flow step 2 1 m³/h 0 - 20000 m³/h in/outI024 Set point exhaust air flow step 3 1 m³/h 0 - 20000 m³/h in/outI025 Supply air flow 1 m³/h 0 - 20000 m³/h outI026 Exhaust air flow 1 m³/h 0 - 20000 m³/h outI027 Supply air pressure 1 Pa 0 - 2500 Pa outI028 Exhaust air pressure 1 Pa 0 - 2500 Pa out

D001 Heating pump / heating release 1 0 / 1 outD002 Cooling pump / heating release 1 0 / 1 outD003 Collective fault 1 0 / 1 outD004 Filter failure 1 0 / 1 outD005 Frost protection failure 1 0 / 1 outD006 Running control heat recovery 1 0 / 1 outD007 Fan running control 1 0 / 1 outD008 Pump running control 1 0 / 1 outD009 Fire / Smoke 1 0 / 1 outD010 Control of min. supply air temperature 1 0 / 1 outD011 Icing heat recovery 1 0 / 1 outD012 Burner failure 1 0 / 1 outD013 Cooling machine failure 1 0 / 1 outD014 Supply air temperature sensor failure 1 0 / 1 outD015 Control rotary heat exchanger 1 0 / 1 outD016 Heat recovery failure 1 0 / 1 outD017 Maintenance required 1 0 / 1 outD018 Safety temperature limiter failure 1 0 / 1 outD019 Air stream control 1 0 / 1 outD020 Motor control 1 0 / 1 outD021 Electrical heater failure 1 0 / 1 out

Page 67: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

673059570

12.4 EthernetFunction Variable No. Variabletype Resolution Range i /oTemperature set point 1 Analog 0,1°C 0,0 - 99,0°C inTemperature set point 2 Analog 0,1°C 0,0 - 99,0°C outSupply air temperature 3 Analog 0,1°C -50,0 - 200,0°C outExtract air / room air temperature 4 Analog 0,1°C -50,0 - 200,0°C outOutdoor air temperature 5 Analog 0,1°C -50,0 - 200,0°C outHeating demand 6 Analog 0,1% 0,0 - 100,0% outCooling demand 7 Analog 0,1% 0,0 - 100,0% outHeat recovery demand 8 Analog 0,1% 0,0 - 100,0% outSet point air quality 9 Analog 0,1dp 0,0 - 99,9dp inAir quality 10 Analog 0,1dp 0,0 - 99,9dp outFresh air damper 11 Analog 0,1% 0,0 - 100,0% outExhaust air damper 12 Analog 0,1% 0,0 - 100,0% outHR bypass damper 13 Analog 0,1% 0,0 - 100,0% out

Outdoor air proportion 1 Integer 1% 0 - 100% inFan step 2 Integer 1 0 - 3 inOperation mode 3 Integer 1 0 - 3 inOutdoor air proportion 4 Integer 1% 0 - 100% outFan step 5 Integer 1 0 - 3 outOperation mode 6 Integer 1 0 - 3 outSet point revolution supply air step 1 7 Integer 0,1% 0,0 - 100,0% inSet point revolution supply air step 2 8 Integer 0,1% 0,0 - 100,0% inSet point revolution supply air step 3 9 Integer 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 1 10 Integer 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 2 11 Integer 0,1% 0,0 - 100,0% inSet point revolution exhaust air step 3 12 Integer 0,1% 0,0 - 100,0% inSet point supply air pressure step 1 13 Integer 1 Pa 0 - 2500 Pa inSet point supply air pressure step 2 14 Integer 1 Pa 0 - 2500 Pa inSet point supply air pressure step 3 15 Integer 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 1 16 Integer 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 2 17 Integer 1 Pa 0 - 2500 Pa inSet point exhaust air pressure step 3 18 Integer 1 Pa 0 - 2500 Pa inSet point supply air flow step 1 19 Integer 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 2 20 Integer 1 m³/h 0 - 20000 m³/h inSet point supply air flow step 3 21 Integer 1 m³/h 0 - 20000 m³/h inSet point exhaust air flow step 1 22 Integer 1 m³/h 0 - 20000 m³/h inSet point exhaust air flow step 2 23 Integer 1 m³/h 0 - 20000 m³/h inSet point exhaust air flow step 3 24 Integer 1 m³/h 0 - 20000 m³/h inSupply air flow 25 Integer 1 m³/h 0 - 20000 m³/h outExhaust air flow 26 Integer 1 m³/h 0 - 20000 m³/h outSupply air pressure 27 Integer 1 Pa 0 - 2500 Pa outExhaust air pressure 28 Integer 1 Pa 0 - 2500 Pa out

Heating pump / heating release 1 Digital 1 0 / 1 outCooling pump / heating release 2 Digital 1 0 / 1 outCollective fault 3 Digital 1 0 / 1 outFilter failure 4 Digital 1 0 / 1 outFrost protection failure 5 Digital 1 0 / 1 outRunning control heat recovery 6 Digital 1 0 / 1 outFan running control 7 Digital 1 0 / 1 outPump running control 8 Digital 1 0 / 1 outFire / Smoke 9 Digital 1 0 / 1 outControl of min. supply air temperature 10 Digital 1 0 / 1 outIcing heat recovery 11 Digital 1 0 / 1 outBurner failure 12 Digital 1 0 / 1 outCooling machine failure 13 Digital 1 0 / 1 outSupply air temperature sensor failure 14 Digital 1 0 / 1 outControl rotary heat exchanger 15 Digital 1 0 / 1 outHeat recovery failure 16 Digital 1 0 / 1 outMaintenance required 17 Digital 1 0 / 1 outSafety temperature limiter failure 18 Digital 1 0 / 1 outAir stream control 19 Digital 1 0 / 1 outMotor control 20 Digital 1 0 / 1 outElectrical heater failure 21 Digital 1 0 / 1 out

"Annexe data point list"

Page 68: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions68

AL-KO EASYAIR®flat

13. Sample commissioning protocol

Commissioning ProtocolOrder no.:Project:

General:

Visual inspection of the air handling unit

Remove transport locks

Actuators for dampers installed Outdoor Exhaust HR bypass air damper air damper damper

Temperature sensor installed Outdoor air Supply air Extract air Room temperature temperature temperature temperature sensor sensor sensor sensor

Remote control installed

Checking of the controller settings:

Fan step adjusted 1-step 2-step 3-step

Operation mode adjusted Automatic Heating Cooling Ventilation

selectable damper and valve drives addressed

Page 69: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

693059570

"Sample commissioning protocol"

Commissioning ProtocolOrder no.:Project:

Functional test of the unit:

Function und direction of rotation of the actuators tested

Fan steps and direction of rotation tested

Correct connection of the sensor tested

Function heating valve and pump tested

Function control of the electrical heater tested

Function cooling valve and pump tested

Simulation of all failures on the unit

Page 70: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

Original operating instructions70

AL-KO EASYAIR®flat

Commissioning ProtocolOrder no.:Project:

Settings service level

Settings service level Release

Support operation cooling Release

Night ventilation Release

Switch on value room temperature Difference Delta outdoor air temp. / room air temp. Release beginning from outdoor air temp. daily min. Release beginning from outdoor air temp. night min.

Supply air limitation Maximum temperature Minimum temperature Frost protection limit value Minimum fresh air ratio

Set value compensation Summer Start with End with

Set value compensation Winter Start with End with

AUTO-Operation Difference Heating-><-Cooling Set value / Temp.out ventilation -><- Cooling

Sensor balancing Sensor balancing room air temperature Sensor balancing supply air temperature Sensor balancing extract air temperature Sensor balancing outdoor air temperature

No Yes 12 °C °C

No Yes 26 °C °C

No Yes

24 °C °C 2 °C °C 2 °C °C

28 °C °C 16 % °C

40 °C °C 16 °C °C

6 °C °C 30 % %

0,0 K K 24 °C °C 36 °C °C

0,0 K K 5 °C °C

-15 °C °C

1,0 K K 1,0 K K

0,0 0,0 0,0 0,0

Page 71: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

713059570

"Sample commissioning protocol"

Commissioning ProtocolOrder no.:Project:

Power consumption motors:

Supply air fan:

Exhaust air fan:

Adjustment of the pressure switches:

Filter control:

Measurement of the air flow (only for units with effective pressure device)

Differential pressure effective pressure: air flow:

Supply air:

Extract air:

Notes:

A V Hz

A V Hz

Supply air pa Extract air pa

Pa Pa m³/h

Pa Pa m³/h

Date

Location Signature

Page 72: AL-KO eAsyAir flat · Rating and performance for units, components and sections DIN EN 1886 Ventilation for buildings - Air handling units – Mechanical performance DIN EN 349 Safety

© Copyright 2013AL-KO THERM GMBH l Jettingen-Scheppach l GermanyAll rights, including the registration of intellectual property rights, are held by AL-KO THERM GMBH. This documentation or excerpts thereof may not be copied or forwarded to third parties without the explicit permission of AL-KO THERM GMBH. The right to technical changes that do not alter the function is reserved.

3059570/December 2013

AL-KO tHerm gmbH l Head Quarter l Hauptstraße 248 - 250 l 89343 Jettingen-Scheppach l GermanyFon +49 8225 39-0 l Fax +49 8225 39-2113 l [email protected] l www.al-ko.com