alternative testing techniques for current transformers...• an instrument transformer that is...
TRANSCRIPT
SEPTEMBER 5 - 7, 2018
Alternative Testing Techniques for Current Transformers
Dinesh Chhajer, PETechnical Support Group
MEGGER
SEPTEMBER 5 - 7, 20182
Agenda Current Transformer – Definition and Fundamentals
– Current Transformer Applicationso Metering / Revenueo Protection
– Accuracy Classification IEEE
Field Testing Practices
Alternative Testing Techniques– Concurrent Testing Method– DC Excitation Technique
Summary
SEPTEMBER 5 - 7, 20183
Applicable Standards
IEEE C57.13 IEEE Standard Requirements for Instrument Transformers
IEEE C57.13.1Field Testing of Relaying Current Transformers
IEC 60044-1 Instrument Transformers Part 1: Current Transformers
IEC 60044-6 Requirements for protective current transformers for transient performance
IEC 61869-2 Instrument transformers - Part 2: Additional requirements for current transformers
SEPTEMBER 5 - 7, 20184
Application & Classification (IEEE)
CURRENT TRANSFORMER DEFINITION & FUNDAMENTALS
SEPTEMBER 5 - 7, 20185
Current Transformer - Definition
• An instrument transformer in which the secondary current, under normal conditions of use, is substantially proportional to the primary current and differs in phase from it by an angle which is approximately zero for an appropriate direction of the connections.
• An instrument transformer that is intended to have its primary winding connected in series with the conductor carrying the current to be measured or controlled.
IEEE C37.110 - 2007 IEC 61869-2:2012 (IEC 60050-321:1986)
SEPTEMBER 5 - 7, 20186
Definition – Ideally, CT is a transformer with the secondary short-circuited. The secondary terminal voltage is zero and the magnetizing current is negligible.
Current Transformers
SEPTEMBER 5 - 7, 20187
Current Transformer – Ideal vs. Real
• Ideal CT
21 NIsNI p ×=×
• Real CT
IeIsIpNN
+=×2
1
SEPTEMBER 5 - 7, 20188
Current transformers (CTs) exhibit two primary errors:– Accuracy errors (related to gain or
linearity)– Phase angle errors
The error in the current reproduction from primary to secondary will be reflected in both amplitude and phase.
Current Transformer – Ideal vs. Real
SEPTEMBER 5 - 7, 20189
Current Transformer - Applications
SEPTEMBER 5 - 7, 201810
Metering CT - IEEE
High degree of accuracy at the specified standard burden at 10% and 100% of the rated primary current.
SEPTEMBER 5 - 7, 201814
Protective Relaying
– Protection class CTs provide input information for the protection of a power system.
– IEEE C57.13.1-2006 specifies that protection CTs must maintain a ratio error of no more than ±10% in a range from 1 to 20 times rated secondary current at the specified load.
Current Transformer - Protection
SEPTEMBER 5 - 7, 201815
Protection CTs – Classification IEEE
• Covers CTs in which the leakage flux in the core has a negligible effect on the ratio within the limits of current and burden, so that ratio can be Calculated.
• Covers CTs in which the leakage flux in the core creates a 1% difference between the actual ratio correction and the calculated ratio correction within the current and burden limits. In this case the ratio must be Tested.
Class T Class C
SEPTEMBER 5 - 7, 201816
Protection CTs - Standard Burden IEEE
Burden R (Ω) L (mH) Z (Ω)VA
(at 5A)PF
B – 1 0.50 2.30 1.0 25 0.5
B – 2 1.00 4.60 2.0 50 0.5
B – 4 2.00 9.20 4.0 100 0.5
B – 8 4.00 18.40 8.0 200 0.5
SEPTEMBER 5 - 7, 201817
FIELD TESTING PRACTICES
SEPTEMBER 5 - 7, 201818
Standard Field Electrical Tests for CTs
Saturation/ Excitation
Ratio and Phase Deviation
Polarity
Winding Resistance
Insulation Resistance
Burden
CT Demagnetization
SEPTEMBER 5 - 7, 201819
DC voltage applied across the insulation and IR is measured
CT Primary (H1-H2) – CT Secondary (X1-X2)
CT Primary (H1-H2) – Ground
CT Secondary (X1-X2) – Ground
CT Insulation Resistance Test
SEPTEMBER 5 - 7, 2018
Winding and Lead Resistance
– Static stress:• weight of the connected
conductor – Dynamic stress:
• wind / seismic activity• vibrations in CB operation
– Electrodynamic forces:• under short-circuit
conditions
– Forces in the system– This test confirms that:
• the DC resistance of the CT is within specification
• there is no high resistance connection in the CT or the wiring connected to it
– Temperature correction shall be made to meet 75°C.
WR test Factors Affecting WR
SEPTEMBER 5 - 7, 201821
The demagnetization of transformer cores can be performed in several ways:
– Variable Voltage Constant Frequency (VVCF) source
– Constant Voltage Variable Frequency (CVVF) source
– Decreasing the amplitude of an alternating DC current
CT Demagnetization
SEPTEMBER 5 - 7, 201822
Demagnetization needs to be done to eliminate the effects of residual magnetism due to DC current injection.
Achieved by slowly ramping the secondary RMS voltage and taking the CT to saturation region, then slowly decreasing the voltage back to zero.
CT Demagnetization
SEPTEMBER 5 - 7, 2018
Excitation / Saturation Curve
This test confirms that:– The CT is of the correct
accuracy rating– The CT has no shorted
turns– No wiring or physical
short circuits have developed in the primary or secondary windings of the CT after installation.
An AC voltage is applied to the secondary winding of the CT while the primary winding is left open circuited.
SEPTEMBER 5 - 7, 201824
Excitation / Saturation Curve
SEPTEMBER 5 - 7, 201825
Excitation / Saturation Curve
SEPTEMBER 5 - 7, 201826
Ratio Tests
Current Method Voltage Method
This test is not intended to prove the accuracy of the ratio, but simply to prove that the ratio, as installed, is as specified, and if taps are available, that they also have the correct ratio and have been wired to the correct terminals.
SEPTEMBER 5 - 7, 201827
Polarity Test
Polarity tests prove that the predicted direction of secondary current flow is correct for a given direction of primary current flow.
SEPTEMBER 5 - 7, 201831
External burden is measured by injecting AC current into the circuit connected to the CT and measuring the voltage drop across it.
Both resistive and reactive components are determined from the phase angle difference between V and I.
Burden Test
SEPTEMBER 5 - 7, 201832
Verifies that the CT will maintain its accuracy under a specified set of loading conditions.
Ensures that the CT is able to operate the devices linked within their operating characteristics.
Burden
SEPTEMBER 5 - 7, 201833
Protection CT Assessment
SEPTEMBER 5 - 7, 2018
Efficiency and AccuracyALTERNATIVE TESTING TECHNIQUES
SEPTEMBER 5 - 7, 201835
Multi-tap CT Field Testing
Traditional Non-Concurrent
CT Test Set
CT Test Set
SEPTEMBER 5 - 7, 201836
Concurrent Method of Testing
SEPTEMBER 5 - 7, 201837
Inject voltage on full secondary winding of a multi tap CT. Example X1–X5
Simultaneously measure voltage on all CT secondary taps
Simultaneously measure voltage on the CT primary
Measure current passing through CT secondary and phase angle between primary and secondary.
Alternative: Concurrent Measurement
SEPTEMBER 5 - 7, 201838
Various data points are measured as voltage applied to CT secondary is increased to saturate the CT
Ratio is still calculated as X1-X5/H1-H2
This same calculation is used for all other ratios (i.e. X1-X3/H1-H2)
Saturation curve is plotted as X1-X5 voltage vs current through secondary winding (Is)
Alternative: Concurrent Measurement
SEPTEMBER 5 - 7, 201839
Simultaneously measuring all values allows the calculation of saturation curves, knee points, ratio, polarity and winding resistance on all taps
The concurrent measurement on all other taps significantly reduces testing time
Alternative: Concurrent Measurement
SEPTEMBER 5 - 7, 201840
Concurrent Vs Non-Current Saturation Testing
SEPTEMBER 5 - 7, 201841
Inter-winding taps saturation and ratio’s (i.e. X2-X3) can be calculated from other measurements obtained.
Inter Winding Taps
SEPTEMBER 5 - 7, 201842
Multi-tap CT Test: Concurrent Method
SEPTEMBER 5 - 7, 201843
INSULATION RESISTANCE TEST
SEPTEMBER 5 - 7, 201844
WINDING RESISTANCE TEST
SEPTEMBER 5 - 7, 201845
Winding Resistance Test Results
Comparison Between Different Methods
X2-X3 X1-X4 X3-X5 X2-X5
Four Concurrent Measurements
50 405 454 504
50 405 454 504
50 406 455 505
51 405 454 505
Four Non-Concurrent Measurements
53 405 455 503
52 406 456 504
51 406 456 504
53 406 458 504
Readings in mohms
SEPTEMBER 5 - 7, 201846
Saturation Test Results
SEPTEMBER 5 - 7, 201847
Saturation Test Results
Comparison Between Different Methods
X1-X3 (V/I) X2-X3 (V/I) X2-X4 (V/I) X2-X5 (V/I)
Four Concurrent Measurements
68.363/0.1733 23.026/0.5252 136.61/0.0866 226.90/0.0519
69.049/0.1753 22.90/0.5233 138.40/0.0878 232.60/0.0532
68.472/0.1739 22.691/0.5187 137.57/0.0873 226.76/0.0519
69.604/0.1767 23.455/0.5359 139.15/0.0883 230.47/0.0528
Four Non-Concurrent Measurements
66.099/0.1680 23.852/0.5413 135.23/0.0849 231.46/0.0526
67.551/0.1716 23.804/0.5423 135.84/0.0851 237.84/0.0541
67.907/0.1724 23.644/0.5388 136.47/0.0856 232.95/0.0529
69.325/0.1761 23.766/0.5415 136.16/0.0854 225.68/0.0513
SEPTEMBER 5 - 7, 201848
Ratio & Polarity Test
SEPTEMBER 5 - 7, 201849
Ratio Test Results
Comparison Between Different Methods
X1-X2 (200:5) Error (%) X3-X4 (500:5) Error (%) X1-X4 (800:5) Error (%) X2-X5 (1000:5) Error (%)
Four Concurrent Measurements
200.095 : 5 0.048 500.156 : 5 0.031 800.386 : 5 0.048 1000.246 : 5 0.025
200.095 : 5 0.048 500.188 : 5 0.038 800.366 : 5 0.046 1000.257 : 5 0.026
200.088 : 5 0.044 500.144 : 5 0.029 800.247 : 5 0.031 1000.194 : 5 0.019
200.094 : 5 0.047 500.171 : 5 0.034 800.331 : 5 0.041 1000.263 : 5 0.026
Four Non-Concurrent Measurements
200.021 : 5 0.01 499.904 : 5 0.012 799.892 : 5 0.013 999.999 : 5 0
200.020 : 5 0.01 499.852 : 5 0.03 800.002 : 5 0 999.931 : 5 0.007
200.031 : 5 0.015 499.845 : 5 0.031 799.868 : 5 0.017 1000.073 : 5 0.007
200.025 : 5 0.012 499.878 : 5 0.024 799.904 : 5 0.012 999.858 : 5 0.014
SEPTEMBER 5 - 7, 201850
Concurrent Vs. Non-concurrent Ratio Method
SEPTEMBER 5 - 7, 201851
DC Excitation Technique
For Saturation Test
SEPTEMBER 5 - 7, 201852
An excitation test on protection class CTs requires to reach saturation of the core. A C800 CT will require a minimum of 400 V AC test voltage and under some instances can take around 1300V to achieve 1A of excitation current.
For transient type CTs, the test voltage can easily reach 4,000V or more to achieve 1A saturation
Issues during Saturation of Protection Class CTs
SEPTEMBER 5 - 7, 201853
The AC method - Core Saturation
0
2
4
6
8
10
12
0 50 100 150 200
Exci
tatio
n Vo
ltage
, V [k
V]
Excitation Current, Iexc [mA]
45 Hz 50 Hz 60 Hz 120 Hz
Effect of 𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 𝑣𝑣𝑣𝑣𝑓𝑓𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑓𝑓
B ∝ 𝑉𝑉𝑓𝑓
SEPTEMBER 5 - 7, 2018
Alternative method for Saturation
IEC 61869-2: 2012 – The most suitable
procedure for the determination of the saturation flux ψsat with the d.c. saturation method is given
DC method:– An alternative method to
obtain saturation / excitation curves of a CT is to use a low DC voltage.
– This method eliminates the need for dangerous high AC voltages during testing.
SEPTEMBER 5 - 7, 201855
DC Excitation Method
The core saturation can be achieved by applying DC voltage. IEC 60044-6“Instrument Transformers Part 6: Requirements for Protective Current Transformers for Transient Performance” in Annex B-3 explains this alternate way to perform CT excitation.
𝜑𝜑 = �𝑑𝑑𝑑𝑑 ∗ 𝑑𝑑𝑣𝑣
The integral of voltage over a period of time would be a measure of the flux produced. It can be generated by using AC or DC excitation voltage. The area under the curve reflects the flux produced.
SEPTEMBER 5 - 7, 201856
DC Excitation Method
The flux can be increased by utilizing either of the two methods.
Either the time can be kept constant as the voltage is increased, or the voltagecan be kept constant as the time increases.
The conventional method used over the years has been to keep the timeconstant (or fixed frequency at 50/60Hz) as the voltage is increased until itreaches saturation.
Alternatively, the voltage can be kept the same; thus DC voltage, and the timecan be prolonged until the core becomes saturated. By integrating theconstant DC voltage over time the core saturation can be determined.
This saturation can then be mathematically converted back to an equivalent 50Hz / 60 Hz saturation. This will achieve the same result as conventional ACexcitation test technique.
SEPTEMBER 5 - 7, 201857
DC Excitation Method
The advantage of DC Excitation method is:
Eliminates the need of high voltage AC and achieve thesame results by utilizing a DC voltage at or below theavailable line voltage. Safer operation !
The technique allows to test CTs with higher knee pointvoltages utilizing the same concept although with aslightly longer test duration.
SEPTEMBER 5 - 7, 201858
AC Vs DC Excitation Methods
SEPTEMBER 5 - 7, 201859
Concurrent DC Excitation Curves
Comparison of concurrent AC and DC excitation testing methods
SEPTEMBER 5 - 7, 201860
AC and DC Saturation Alternative DC Technique for Saturation/Excitation Testing
– AC Saturation up to 2kV – DC Saturation up to 30 kV
SEPTEMBER 5 - 7, 201861
DC Saturation Testing
SEPTEMBER 5 - 7, 201862
Recommended Testing Sequence
SEPTEMBER 5 - 7, 201863
New measurement techniques proposed utilize the concepts well described in electrical textbooks.
DC excitation and concurrent method of testing offer an alternative approach for testing CTs that provide same measurements and results as conventional techniques recommended in various international standards.
The comparative analysis between different methods indicate that DC excitation and concurrent method of testing can be utilized in place of AC excitation and individual tap by tap testing techniques without compromising the accuracy and reliability of the results.
Demagnetization is highly recommended after DC excitation to minimize any residual magnetism in the core of the CT.
Summary and Conclusions
SEPTEMBER 5 - 7, 201864
Questions?
Power onAt Megger, we understand that keeping the power on is essential for the success of your business. That is why we are dedicated to creating, designing and manufacturing safe, reliable, easy-to-use portable test equipment backed by world-leading support and expertise.
We can assist your acceptance, commissioning and maintenance testing for predictive, diagnostic or routine purposes. By working closely with electrical utilities, standards bodies and technical institutions, we contribute to the dependability and advancement of the electrical supply industry.