%108 efficiency
Small volume
Environmental friendly
16 pcs. cascade connectionopportunity
1/7 modulation ratio
Low flue gas temperature
(35°C - 65°C)
Possibility of control over
the internet with web server
Flue gas temperature andreturn water temperature difference 3°C - 5°C
The only one and first floor standing condensing boiler with aluminium and premix burner in all over Europe
1,100 kW within single boiler - 17,600 kW within single panel
HIGH EFFICIENCY CONDENSING BOILER WITH PREMIX BOILER
Condensing Boiler with Premix Burner540kW -
THE NEW PRODUCT OF CASTING AND CONDENSINGTECHNOLOGY ALUBOX FLOOR STANDING CONDENSING BOILER
ADVANTAGES OF ALUBOX FLOOR STANDING CONDENSING BOILERS
Heat exchanger with aluminium-silicon alloyand flexible cast iron bod .
Homogeneous heat distribution with metal fibercoated stainless steel burner.
High efficiency with premix technolog . Idealcombustion can be provided by using compatiblecomponents (gas valve, venturi and fan) with the help of optimum gas and air mixing.
Environmental friendly thanks to condensing technology. Alubox boilers provides class 5 NOx value which is excellent for nature. (2009/142 EEC).
Alubox 208 and 290kW model deserved class (according to 92/42 EEC) thanks to its high efficienc .
Thanks to 1:7 modulation ratio, Alubox boilers allowsto work from 162,7kW to 1107,6 kW depends on seasonal changes.
Due to 3°C - 5°C of flue gas and boiler return water temperature, it provides high energy saving.
It works with high efficiency even at high capacities.%108 at 50°C/30°C, %97,5 at 80°C/60°C.
Alubox boilers can work compatible with buildingautomation systems. Alubox boilers also providesto control with room thermostat, outdoor temperaturecontrol, zone control, cascade connection, hot water tank, swimming pool heating, solar and internet control with web server connection.
Alubox boilers can be cascaded up to 16 boiler(1 master boiler and 15 slave boilers)
Compact design; this system can find a place in yourarea thanks to small dimensions even its high power.
Condensing Boiler with Premix Burner540kW -
EXCELLENT THERMAL CONDUCTIVITY AND %108 EFFICIENCY WITH INNOVATIVE CASTING TECHNOLOGY AND SPECIAL FLEXIBLE ALUMINIUM ALLOY
Protec� e oxide coaa�ng on aluminium body ovides excellentcorrosion durability and long life.
Heat transfer area is increased by pins which is located oninterior surface of aluminium body. Pins has developed withperfect heat transfer technology and increases heat transfercoefficient than creates resistance and slow down high temperature flue gas when the gasses pass through them. This heat is transferred to the water op�mall.
Thanks to this applied technology to aluminium sec�ons, 180° C boiler temperature is transferred to water then flue gas spread with 56° C to atmosphere. With the help of this technology high efficiency can be achieved and nature is saved with low emissions.
High water pressure safety; the boiler safety is provided against in excess of 6 bar water pressure.
Superior safety systems;
The automa�c air ent; blows out the air which is jammed in the boiler in water circuit. This provides your system workingproperly and protect against corrosion.
Ionisa�on electode; checks the if combuss�on on burner or not, if th e is no flame on the burner, automaomally closethe gas inlet to make system safety.
Low water pressure safety; checks the boiler water pressure con�nuousl. If the pressure lower than 0,8 bar, closes the system.
Hot water temperature safety; if boiler water temperature exceeds 95°C, sensors will shut down system to protect itself.
Overhea�ng po�ec�on; this sens s will close the system when boiler water temperature exceeds 105°C as and in caseof failure with NTC sensors.
Flue gas temperature safety; this detects flue gas temperature with flue gas sensor. If flue temperature exceeds the limit, stops the system.
Frost protec�on; boiler orks automaatally to rise up temperature to 15°C when boiler water temperature down to 4°C soavoid frost risk of boiler. Boiler electrical supply must be on and boiler must be in stand-by state for using this func�on.
Pump protec�on; this potects the boiler against pump jamming and oxidaa�on. Boiler is orked certain day of the weekby control panel, if the boiler is not run long term.
Legionella protec�on; if domes�c hot ater in hot water tank stays lower than 60°C long term without use, this leads to form legionella bacteria. Boiler is worked certain day to rise up use water temperature 65°C for avoiding these bacterias.
High and low voltage protec�on; boiler is potected against voltage fluctuaua�on.
Domes�c hot ater frost pro�ec�on; if o mode chosen from control panel, the boiler water temperature keep fixed10° C to avoid frost risk. The electrical supply must be ac� e ffor using this func�on.
The control panel language is Turkish. Language also can be changed in English too.
Condensing Boiler with Premix Burner540kW -
GENERAL BOILER DIMENSIONS
M: Water outlet connection: 2"R: Water inlet connection : 2" G: Gas inlet : 1 ¼“
F: Flue diameter: 200 mm
M: Water outlet connection : 3"R: Water inlet connection : 3" G: Gas inlet : 2 ½“
F: Flue diameter: 250 mm
M: Water outlet connection : 4"R: Water inlet connection : 4" G: Gas inlet : 2 ½“
F: Flue diameter: 250 mm
Condensing Boiler with Premix Burner
540/
540kW -
OPTIONAL ACCESSORIES FOR COMFORT USE AND ENERGY SAVINGS AVS37 USER INTERFACE
Selection of DHW heating
Service connection (USB)
Escape
ResetRoom comfort temperature
adjustment and navigation button
Heating mode selection
LCD screen
Information button
Confirmation button for settings (OK)
Manuel control
Chimney sweeper button (STB test)
You can adjust day - week program - holiday program - comfort program - economy - boiler setting - pool setting - legionella function - solar collector - zone control - floor heating - cascade setting - winter and summer setting.
It has to be well placed where it can be
measure room temperature.
QAA55 Room Unit: QAA75 Wireless Room Unit:It has to be well palced where it can be measure
room temperature. You can adjust with this time
and day setting, operation unit (language selection),
time programming, holiday setting, heating unit,
DHW temperature, meintanence setting.
QAC345 Outside Air Sensor:
This is NTC type sensor. It can works between
-50°C to 70° C. Tolerance between +1 / -1K.
1,5mm² or 7,2mm copper cable mustdiameter
be use for connection. The allowed cable
lenght is 120 m.
QCI345 Cascade
Connection Unit
This is NTC type sensor.
It can work between 0 - 95°C
Tolerance is +0,5 / -0,5 K.
QAZ36 Immersion Type
SensorIt can work between
-30°C to 125° C.
Tolerance is +0,5 / -0,5 K.
QAD36 Clamp Type Sensor
AVS82 Interface
Connection Cable
It can work with computer or smart phone via web. You can
have a possiblities of control via smart phones
(iphone or android). You can put your system diagram into
OZW672 with ACS790 PC software. You will see trace the
system andinformations. You can control 1, 4 or 16
boilers depends on OZW model. There are a possibilities
of ethernet and USB port. There are 2 digital inlet for faulty
message. You can view faulty via web. It can sent a faulty
message up to 4 users. It can sent faulty massages with
e-mail to users via web periodically.
QZW672 Web Server
AVS75 Additional Module
Relay connections,
solar collector
connection, swimming pool
water heating and 3 way
valve connection can be
done with this unit.
Condensing Boiler with Premix Burner540kW -
HIGHER EFFICIENCY IN BOILER ROOM WITH SMALL VOLUME AND HIGH CAPACITY
Higher efficiency with higher capacity cascade system with premix burner
Cascade possiblities up to 16 within order of 1 master and 15 slave boilers.
This system allows you work continuously even in any boiler faulty.
Long lasting boilers thanks to equal ageing system to make equal working time for system boilers.
You can save fuel with wide range modulating and condensing technology.
Comfort heating with room thermostat and outside air tepmperature control.
You can control every boiler, all zones, swimming pool heating and solar collector via web server.
Condensing Boiler with Premix Burner540kW -
CASCADE CONNECTION SYSTEMS
Single boiler connection example scheme Single boiler, heat exchanger and DHW tank connection
Double boiler cascade system
Condensing Boiler with Premix Burner540kW -
TECHNICAL SPECIFICATIONS TABLE
PRODUCT TYPE
General
Flue installation type
Fuel type - gas category
Nominal heat output Pn (80-60) °C
Nominal heat input Qn
Nominal heat output Pn (50-30) °C
Working pressure
Maximum working temperature
Limit thermostat shut down temperature
Efficiency Q max (80-60) °C
Efficiency Q min (80-60) °C
Efficiency Q max (50-30) °C
Efficiency Q min (50-30) °C
Partial load %30 (return water 30) °C
Flue gas temperature (80-60) °C
Flue gas temperature (50-30) °C
CO emissions (80-60) °C
CO emissions (50-30) °C
CO emissions (80-60) °C
CO emissions (50-30) °C
Combustion and Efficiency
NO
Combustion products output mass
Gas consumption
Fan speed
Electric
Connections
Main supply
Boiler water outlet
Boiler water inlet
Boiler gas inlet
Condensation drainage
Air inlet connection
Chimney diameter
Dimensions
Weights
The distributor:
2
2
2
2
x class
NOx emissions G20
kW
kW
kW
kW
540
81,9