alubox cazan

8
%108 efficiency Small volume Environmental friendly 16 pcs. cascade connection opportunity 1/7 modulation ratio Low flue gas temperature (35°C - 65°C) Possibility of control over the internet with web server Flue gas temperature and return water temperature difference 3°C - 5°C The only one and first floor standing condensing boiler with aluminium and premix burner in all over Europe 1,100 kW within single boiler - 17,600 kW within single panel HIGH EFFICIENCY CONDENSING BOILER WITH PREMIX BOILER Condensing Boiler with Premix Burner 540kW -

Upload: sima-catalin-ionut

Post on 08-Apr-2016

237 views

Category:

Documents


2 download

DESCRIPTION

Cazan proiect

TRANSCRIPT

%108 efficiency

Small volume

Environmental friendly

16 pcs. cascade connectionopportunity

1/7 modulation ratio

Low flue gas temperature

(35°C - 65°C)

Possibility of control over

the internet with web server

Flue gas temperature andreturn water temperature difference 3°C - 5°C

The only one and first floor standing condensing boiler with aluminium and premix burner in all over Europe

1,100 kW within single boiler - 17,600 kW within single panel

HIGH EFFICIENCY CONDENSING BOILER WITH PREMIX BOILER

Condensing Boiler with Premix Burner540kW -

THE NEW PRODUCT OF CASTING AND CONDENSINGTECHNOLOGY ALUBOX FLOOR STANDING CONDENSING BOILER

ADVANTAGES OF ALUBOX FLOOR STANDING CONDENSING BOILERS

Heat exchanger with aluminium-silicon alloyand flexible cast iron bod .

Homogeneous heat distribution with metal fibercoated stainless steel burner.

High efficiency with premix technolog . Idealcombustion can be provided by using compatiblecomponents (gas valve, venturi and fan) with the help of optimum gas and air mixing.

Environmental friendly thanks to condensing technology. Alubox boilers provides class 5 NOx value which is excellent for nature. (2009/142 EEC).

Alubox 208 and 290kW model deserved class (according to 92/42 EEC) thanks to its high efficienc .

Thanks to 1:7 modulation ratio, Alubox boilers allowsto work from 162,7kW to 1107,6 kW depends on seasonal changes.

Due to 3°C - 5°C of flue gas and boiler return water temperature, it provides high energy saving.

It works with high efficiency even at high capacities.%108 at 50°C/30°C, %97,5 at 80°C/60°C.

Alubox boilers can work compatible with buildingautomation systems. Alubox boilers also providesto control with room thermostat, outdoor temperaturecontrol, zone control, cascade connection, hot water tank, swimming pool heating, solar and internet control with web server connection.

Alubox boilers can be cascaded up to 16 boiler(1 master boiler and 15 slave boilers)

Compact design; this system can find a place in yourarea thanks to small dimensions even its high power.

Condensing Boiler with Premix Burner540kW -

EXCELLENT THERMAL CONDUCTIVITY AND %108 EFFICIENCY WITH INNOVATIVE CASTING TECHNOLOGY AND SPECIAL FLEXIBLE ALUMINIUM ALLOY

Protec� e oxide coaa�ng on aluminium body ovides excellentcorrosion durability and long life.

Heat transfer area is increased by pins which is located oninterior surface of aluminium body. Pins has developed withperfect heat transfer technology and increases heat transfercoefficient than creates resistance and slow down high temperature flue gas when the gasses pass through them. This heat is transferred to the water op�mall.

Thanks to this applied technology to aluminium sec�ons, 180° C boiler temperature is transferred to water then flue gas spread with 56° C to atmosphere. With the help of this technology high efficiency can be achieved and nature is saved with low emissions.

High water pressure safety; the boiler safety is provided against in excess of 6 bar water pressure.

Superior safety systems;

The automa�c air ent; blows out the air which is jammed in the boiler in water circuit. This provides your system workingproperly and protect against corrosion.

Ionisa�on electode; checks the if combuss�on on burner or not, if th e is no flame on the burner, automaomally closethe gas inlet to make system safety.

Low water pressure safety; checks the boiler water pressure con�nuousl. If the pressure lower than 0,8 bar, closes the system.

Hot water temperature safety; if boiler water temperature exceeds 95°C, sensors will shut down system to protect itself.

Overhea�ng po�ec�on; this sens s will close the system when boiler water temperature exceeds 105°C as and in caseof failure with NTC sensors.

Flue gas temperature safety; this detects flue gas temperature with flue gas sensor. If flue temperature exceeds the limit, stops the system.

Frost protec�on; boiler orks automaatally to rise up temperature to 15°C when boiler water temperature down to 4°C soavoid frost risk of boiler. Boiler electrical supply must be on and boiler must be in stand-by state for using this func�on.

Pump protec�on; this potects the boiler against pump jamming and oxidaa�on. Boiler is orked certain day of the weekby control panel, if the boiler is not run long term.

Legionella protec�on; if domes�c hot ater in hot water tank stays lower than 60°C long term without use, this leads to form legionella bacteria. Boiler is worked certain day to rise up use water temperature 65°C for avoiding these bacterias.

High and low voltage protec�on; boiler is potected against voltage fluctuaua�on.

Domes�c hot ater frost pro�ec�on; if o mode chosen from control panel, the boiler water temperature keep fixed10° C to avoid frost risk. The electrical supply must be ac� e ffor using this func�on.

The control panel language is Turkish. Language also can be changed in English too.

Condensing Boiler with Premix Burner540kW -

GENERAL BOILER DIMENSIONS

M: Water outlet connection: 2"R: Water inlet connection : 2" G: Gas inlet : 1 ¼“

F: Flue diameter: 200 mm

M: Water outlet connection : 3"R: Water inlet connection : 3" G: Gas inlet : 2 ½“

F: Flue diameter: 250 mm

M: Water outlet connection : 4"R: Water inlet connection : 4" G: Gas inlet : 2 ½“

F: Flue diameter: 250 mm

Condensing Boiler with Premix Burner

540/

540kW -

OPTIONAL ACCESSORIES FOR COMFORT USE AND ENERGY SAVINGS AVS37 USER INTERFACE

Selection of DHW heating

Service connection (USB)

Escape

ResetRoom comfort temperature

adjustment and navigation button

Heating mode selection

LCD screen

Information button

Confirmation button for settings (OK)

Manuel control

Chimney sweeper button (STB test)

You can adjust day - week program - holiday program - comfort program - economy - boiler setting - pool setting - legionella function - solar collector - zone control - floor heating - cascade setting - winter and summer setting.

It has to be well placed where it can be

measure room temperature.

QAA55 Room Unit: QAA75 Wireless Room Unit:It has to be well palced where it can be measure

room temperature. You can adjust with this time

and day setting, operation unit (language selection),

time programming, holiday setting, heating unit,

DHW temperature, meintanence setting.

QAC345 Outside Air Sensor:

This is NTC type sensor. It can works between

-50°C to 70° C. Tolerance between +1 / -1K.

1,5mm² or 7,2mm copper cable mustdiameter

be use for connection. The allowed cable

lenght is 120 m.

QCI345 Cascade

Connection Unit

This is NTC type sensor.

It can work between 0 - 95°C

Tolerance is +0,5 / -0,5 K.

QAZ36 Immersion Type

SensorIt can work between

-30°C to 125° C.

Tolerance is +0,5 / -0,5 K.

QAD36 Clamp Type Sensor

AVS82 Interface

Connection Cable

It can work with computer or smart phone via web. You can

have a possiblities of control via smart phones

(iphone or android). You can put your system diagram into

OZW672 with ACS790 PC software. You will see trace the

system andinformations. You can control 1, 4 or 16

boilers depends on OZW model. There are a possibilities

of ethernet and USB port. There are 2 digital inlet for faulty

message. You can view faulty via web. It can sent a faulty

message up to 4 users. It can sent faulty massages with

e-mail to users via web periodically.

QZW672 Web Server

AVS75 Additional Module

Relay connections,

solar collector

connection, swimming pool

water heating and 3 way

valve connection can be

done with this unit.

Condensing Boiler with Premix Burner540kW -

HIGHER EFFICIENCY IN BOILER ROOM WITH SMALL VOLUME AND HIGH CAPACITY

Higher efficiency with higher capacity cascade system with premix burner

Cascade possiblities up to 16 within order of 1 master and 15 slave boilers.

This system allows you work continuously even in any boiler faulty.

Long lasting boilers thanks to equal ageing system to make equal working time for system boilers.

You can save fuel with wide range modulating and condensing technology.

Comfort heating with room thermostat and outside air tepmperature control.

You can control every boiler, all zones, swimming pool heating and solar collector via web server.

Condensing Boiler with Premix Burner540kW -

CASCADE CONNECTION SYSTEMS

Single boiler connection example scheme Single boiler, heat exchanger and DHW tank connection

Double boiler cascade system

Condensing Boiler with Premix Burner540kW -

TECHNICAL SPECIFICATIONS TABLE

PRODUCT TYPE

General

Flue installation type

Fuel type - gas category

Nominal heat output Pn (80-60) °C

Nominal heat input Qn

Nominal heat output Pn (50-30) °C

Working pressure

Maximum working temperature

Limit thermostat shut down temperature

Efficiency Q max (80-60) °C

Efficiency Q min (80-60) °C

Efficiency Q max (50-30) °C

Efficiency Q min (50-30) °C

Partial load %30 (return water 30) °C

Flue gas temperature (80-60) °C

Flue gas temperature (50-30) °C

CO emissions (80-60) °C

CO emissions (50-30) °C

CO emissions (80-60) °C

CO emissions (50-30) °C

Combustion and Efficiency

NO

Combustion products output mass

Gas consumption

Fan speed

Electric

Connections

Main supply

Boiler water outlet

Boiler water inlet

Boiler gas inlet

Condensation drainage

Air inlet connection

Chimney diameter

Dimensions

Weights

The distributor:

2

2

2

2

x class

NOx emissions G20

kW

kW

kW

kW

540

81,9