NOT FOR RESIDENTIAL USEThis Installation Manual provides the information required to install, install, troubleshoot and maintain
FIRE SENTINEL® RELEASE SYSTEM
FSBX-120VAC/24VFSCX-120VAC/24V
12/13 P/N 111995.502195
an FSBX and FSCX
www.overheaddoor.com 02/13
THIS PAGE LEFT BLANK
Fire Sentinel® Release System
Table of ContentsHow to use this manual ....................................................................... 2
Safety Information and Instructions................................................... 3
General Information ............................................................................ 4
Mechanical Installation (Mounting)................................................. 5-6
Electrical Connections .....................................................................7-19 High/Low Voltages .................................................................. 7 Smoke Detectors................................................................... 8-9 Supervised Annunciators ...................................................... 10 Remote Test and Trouble Silence ......................................... 10 Relay Outputs/Auxiliary Closed Limit .................................. 11 Control Circuit Sensing/Aux Open Limit ............................. 12 Safety Edge Connections/Wall Button Connections........... 13 Battery/Clock Backup Battery .............................................. 14 System Wiring ...................................................................15-17 Dip Switches/LEDs ................................................................. 18 Trouble Codes ........................................................................ 19
Maintenance ..................................................................................20-21 Specifications ......................................................................... 21
Testing ............................................................................................22-25
Release Device Compatibility Identifier/Replacement Parts ......... 25
Installation Notes ............................................................................... 26
Test Records ........................................................................................ 27
Warranty ............................................................................................. 28
How to use this manualThis Installation Manual provides the information required to install, troubleshoot and maintain an FSBX and FSCX Fire Sentinel® Release System.
This information includes:
• Important defining information related to safety terminology used throughout this manual, as well as safety related instructions which must be followed at all times while doing any steps/tasks/instructions detailed in this manual.
• Step by step installation, set-up and testing instructions for the FSBX and FSCX units.
• Important features and troubleshooting information for typical installation and normal operations that may occur.
• Important warranty and returned goods policy information.
DO NOT ATTEMPT TO INSTALL, REPAIR OR SERVICE THIS RELEASE DEVICE UNLESS YOU ARE A TRAINED SERVICE TECHNICIAN USING PROPER TOOLS AND INSTRUCTIONS.
www.overheaddoor.com 12/13 2Fire Sentinel® Release System
www.overheaddoor.com 12/13 3Fire Sentinel® Release System
Safety Information and Instructions
WARNINGOverhead Doors are large, heavy objects that move with the help of springs under high tension and electricmotors. Since moving objects, springs under tension, and electric motors can cause injuries, your safety and thesafety of others depend on you reading the information in this manual. If you have any questions or do not under-stand the information presented, call your nearest service representative. For the number of your local OverheadDoor distributor, call 800-929-3667, and for Overhead Door Factory Technical Advice, call 800-275-6187.
IMPORTANT
POTENTIAL HAZARD EFFECT PREVENTION
HIGH SPRING TENSION
WARNING
ELECTRICAL SHOCK
READ PRIOR TO ANY DOOR OPERATION
1. Read manual and warnings carefully.
2. Keep the door in good working condition. Periodically lubricate all moving parts of door.
3. If door has a sensing edge, check operations monthly. Make any necessary repairs to keep it functional.
door by disconnecting it from the operator. The Door should open and close freely. If it does not, the door must be taken out of service and a trained service representative must correct the condition causing the malfunction.
5. Keep instructions in a prominent location.
MOVING DOOR
Could result inSerious Injury
or Death
WARNING
WARNING
Could result inSerious Injury
or Death
Could result inSerious Injury
or Death
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING CAUTION
The word NOTE is used to indicate important steps to be followed or important considerations.
In this Manual, the words Danger, Warning, and Caution are used to stress important safety information. The word:
indicates an potentially hazardous situation which, if not avoided, could result in death or serious injury.indicates a potentially hazardous situation which, if not avoided, may result in injury or property damage.
Do Not operate unless the doorway is in sight and free of obstructions. Keep people clear of opening while door is moving.Do Not allow children to play with the door operator.Do Not change operator control to momentary contact unless an external reversing means is installed.Do Not operate a door that jams or one that has a broken spring.
Turn off electrical power before opening front cover. When replacing the cover, make sure wires are not pinched or near moving parts.Fire Sentinel® must be electrically grounded.
Do Not try to remove, repair or adjust springs or anything to which door spring parts are fastened, such as, wood block, steel bracket, cable or any other structure or like item.Repairs and adjustments must be made by a trained service representative using proper tools and instructions.
4. Each month, manually operate
General InformationThe Overhead Door Fire Sentinel® Release Systems (FSBX and FSCX) are intended for use on rolling, single-slide and center parting level and inclined track doors. All models are normally energized Fail-Safe Sentinels incorporating an internal battery pack and proprietary control circuitry. All comply with UL864 9th Edition, December 31, 2008 requirements and ULC S527-99. The Devices respond to emergency conditions generated by manual or automatic initiating devices and shall be installed in accordance with NFPA and UL 864 9th Edition Standards effective 12.31.08 and ULC S527-99.
The available FSBX and FSCX features* include exclusive, annual test standard compliance technology, coded test plate diagnostics, selectable ,stuptuo yaler C-mrof ,scitsongaid metsys lortnoc lanretxe ,srotceted ekoms dna esaeler rof troppus yrettab ruoh 42 muminim ,syaled emit
supervised annunciator and limit switch outputs and troubleshooting capabilities. The system incorporates an Annual Internal Clock/Calendar which generates a Test Trouble Signal if the system has not been tested within 365 days per National Fire Code requirements. Motorized and
.)noitcidsiruJ gnivaH ytirohtuA( DJHA/JHA yb deriuqer snoitacificeps etadommocca ot ledom yb desserdda era snoitallatsni launam * Check model label on unit to be installed to verify applicable features and options.
CAUTION: REVIEW ALL INSTALLATION INSTRUCTIONS, PROCEDURES, CAUTIONS AND WARNINGS CONTAINED WITHIN THIS MANUAL PRIOR TO INSTALLING AND/OR SERVICING THIS PRODUCT. AS WITH ALL RELEASING DEVICE SYSTEMS, MAXIMUM FIRE PROTECTION IS PROVIDED WHEN INSTALLED IN ACCORDANCE WITH FACTORY SPECIFICATIONS AND USED WITH FUSE LINK SYSTEMS.
CAUTION: PROPER OPERATION CAN ONLY BE PROVIDED ONCE PROPERLY INSTALLED AND INPUT POWER HAS BEEN APPLIED.
CAUTION: TEST SYSTEM REGULARLY TO ENSURE PROPER OPERATION! (TESTING SHOULD BE DONE AT LEAST MONTHLY.)
For Technical Support, please call 1-800-275-6187
www.overheaddoor.com 02/13 4 Fire Sentinel® Release System
Mechanical InstallationMounting Procedure:
WARNING: TO PREVENT SERIOUS INJURY OR DEATH - DO NOT INSTALL THIS UNIT ON A MOTORIZED DOOR WITHOUT A REVERSING ELECTRIC SAFETY EDGE.
Typical installation configuration may not accurately depict door manufacturer’s recommendations. See door manufacturer’s recommendations for use of this product with the door being installed. All hardware must be supplied by the door manufacturer or installer. Use only hardware approved and recognized by the appropriate testing or listing agencies in conjunction with the installation of this product. Only properly trained technicians, using proper tools and instructions, are to perform installation and testing as described herein. 1) The Release Device may be mounted on a vertical surface or optionally on a horizontal surface as illustrated in Figure 1.
WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL INPUT CONNECTIONS MUST BE MADE WITH POWER SOURCES DISCONNECTED. DO NOT INSTALL THIS UNIT WITHOUT REVIEWING AND UNDERSTANDING ALL WARNINGS AND INSTRUCTIONS CONTAINED HEREIN, AND IN THE DOOR MANUFACTURERS INSTRUCTIONS AND MANUALS.
CAUTION: THESE INSTALLATION PROCEDURES MUST BE FOLLOWED TO ENSURE PERFORMANCE OF THE FSBX OR FSCX TO APPROPRIATE STANDARDS AND CODES.
www.overheaddoor.com 12/13 5
FIGURE 1
continued on next page
Fire Sentinel® Release System
NO LESSTHAN 12”
NO LESSTHAN 12”
Mounting Procedure (continued):
3) Complete hardware installation by connecting fuse links, sash chain, S-hooks and turnbuckles per door manufacturer specifications. Place Armature in Supervisory Retaining Bracket (Figure 2) and attach cable or sash chain to the armature. Remove sash chain slack by adjusting turnbuckle. Do Not exceed 40 lbs maximum pull rating on device. The retaining bracket is meant to hold the armature and cable/sash until input power is supplied. The armature will be removed from the retainer and aligned with the supervised electromagnet when input power is supplied.
www.overheaddoor.com 02/13 6
Supervised Electromagnet
SupervisedRetaining Bracket
Armature inserted into retainer*.
S-hook & sash chain/cableto door
*Supports sash chain/cable until power is supplied
Supervised Electromagnet
Armature removed from retainer and affixed to electromagnet when input power is supplied.
2) The Release Device Enclosure must be mounted with minimum #10 size fastening screws or bolts for securing to structures other than masonry. • Masonry applications shall use 1/4" or greater anchors or studs as required to ensure proper mounting strength. Release device and associated hardware (sash chain [provided and preferred] or 1/16" cable, eyebolts, fuse links and turnbuckles) shall be installed as per door manufacturer recommendations.
FIGURE 2
Fire Sentinel® Release System
Electrical Connections
High Voltage/Low Voltage:Installation of all wiring and connections, including Class 1 and Class 2 circuits, must be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part1, with respect to wiring material type, wiring gauge related to power capacity requirements, circuit length and wiring methods. This unit is designed so that it may be used on automated motorized doors which incorporate appropriate safety features (see options below).
Current UL Recognized Monitored Reversing Devices 1) MillerEdge ME/MT series edge sensors 2) Overhead Door Photocells Kit P/N OPAKPE.S
3) Safe-T-Beams®:
Model OSTB-BX P/N 37221R (OHD)
Figure 3 1) BEFORE BEGINNING, turn off and disconnect power supply sources for the
Control Panel as well as motor where applicable. 2) Verify voltage rating of Control Panel to power source being used. Model voltage is indicated on the side of the unit. 3) C
4) For 120 VAC, connect L1/HOT to terminal 1. Connect L2/NEUT to terminal 3.Connect GROUND to terminal 2.
5) For 24 VDC, connect +24V to terminal 1, COMMON to termminal 3 and GROUND to terminal 2.
onnect power source inputs to TBX (chassis mount) screws 1 and 3. • Screw 2 of any model shall be utilized for earth ground where applicable.
• DO NOT connect battery at this time!
112087.0001
1-(L1) or (AC) or (DC-)2-(Earth GND)3-(L2) or (AC) or (DC+)
www.overheaddoor.com 12/13 7
PowerVoltage
LowVoltage
Fire Sentinel® Release System
WARNING: FAILURE TO DISCONNECT POWER SOURCES COULD RESULT IN ELECTRICAL SHOCK, SEVERE INJURY OR DEATH.
FIGURE 3
TBX
Smoke Detectors:
1) When installing smoke detectors with this unit, refer to NFPA 72 and NFPA 80 and any other applicable codes or regulations for instructions concerning proper placement and detection coverage. See Electrical Connections pages 8, 9, 11 and 12 for information. • End of line devices and supervisory resistors shall be installed for electrical supervision of smoke detectors and annunciators.NOTE: 1. DO NOT interface this unit to 4-wire smoke detectors that do not incorporate electrical supervision! 2. Field and System Wiring shall consist of 22-18 AWG wiring. Use only 350 VAC, 125VDC, 2 Amp, 2 AG Fast Acting fuses. All circuits are not power limited. All End -of-Line devices must be installed adjacent to the last initiating device.Typical wiring: See compatibility list on page 25 and instructions provided with detector for additional information. Field wiring shall consist of 22-18 AWG wire. Do not mix and match 2-wire smoke detectors from different manufacturers.
Normally Open 2-wire Initiating Devices: 1) 2)
Connect wiring from N/O smoke loop to TB-1, screws 1 and 2.
End-of-line supervisory resistor shall be connected at the end-of-line
detector as shown in Figure 4A or 4B base wiring. Two Class B Style A
detectors maximum @ 0.060 Amp/14VDC-28.6VDC maximum.
(continued next page)
WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL FIELD CONNECTIONS MUST BE MADE WITH POWER DISCONNECTED TO ALL COMPONENTS.
Electrical Connections
31/20 moc.rooddaehrevo.www 8
FIGURE 4A FIGURE 4B
Fire Sentinel® Release System
2W-B & 2WT-B
112228.0001 (5) + OUT(4) – OUT(3) – IN(2) + IN(1)
(5) + OUT(4) – OUT(3) – IN(2) + IN(1)
112228.0001
P/N 608964.0005(SLR835BH-2)
112228.0001
Smoke Detectors (continued)
Electrical Connections
Normally Open 4-wire Initiating Devices: erus gnikam ,2 dna 1 swercs ,1-BT ot pool ekoms O/N morf gniriw tcennoC )1
end of line supervisory resistor (112228.0001) is installed as indicated. 2) Auxiliary power (+28.6VDC) for smoke detectors may be obtained from TB1 positions 3 and 4. Observe proper polarity — TB1-3 (+), TB1-4 (-). 3) (2) detector maximum @ 0.075 Amp/28.6VDC maximum. 4) Electrical power supervision in the form of an end-of-line device (EOLR-1) shall be provided on all smoke detectors. See information
6 dna 5 serugiF ,rerutcafunam rotceted morf snoitacificeps dna base wiring.
NOTE: TB1 initiating device loops are supervised and cannot be directly series or parallel connected between release devices or shared with other alarm equipment. Incorrect wiring from unit to unit may cause damage to FIRE SENTINEL®..
www.overheaddoor.com 12/13 9
FIGURE 5 FIGURE 6
112228.0001 112228.0001
(5) COM(4) N.O.(3) - IN/OUT(2) + OUT + IN(1)
(+)
(- )
(+)
(- )
(+)
(- )
(5) COM(4) N.O.(3) - IN/OUT(2) + OUT + IN(1)
EOLR-1
Fire Sentinel® Release System
4W-B & 4WT-B
1
2
SUPERVISORY RESISTOR *
COM
N/O
FIRE ALARM PANEL
(-)
(+)
Alarm Relay Module Installation
* A supervisory resistor must be installed at the Relay Module.
ALARM RELAY MODULE
112228.0001
Supervised Annunciators:
Remote Test and Trouble Plate:
• (+24VDC output), connect annunciator (optional) observing polarity to TB1-10 (+) and TB1-11 (-).
• Install resistor as illustrated. Figure 7. • DO NOT connect a speaker to this output.
WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL FIELD CONNECTIONS MUST BE MADE WITH POWER DISCONNECTED TO ALL COMPONENTS.
Electrical Connections
The Remote Test and Trouble Plate provides convenient test and trouble silencing capabilities. The Trouble Silence function allows a user to temporarily silence the Trouble Sounder with a keyed function. The plate includes an LED Trouble Indicator, which illuminates indicating that trouble still exists. If the trouble condition is not corrected after 24 hours the trouble sounder will commence again and a manual intervention for reset is required. • Connect wiring from remote test plate to TB1 positions 15, 16, 17 and 18. • Observe wiring sequence as indicated in Figure 8. • Trouble Code table located on page 19.
DC + DC -
112228.0001
www.overheaddoor.com 02/13 10
FIGURE 7
FIGURE 8
Fire Sentinel® Release System
ANNUNCIATOR
REMOTE TEST PLATE
Com
mon
Test
Rese
t
Rem
ote
Trou
ble
(BLK
)
(WH
T)
(GRN
)
(RED
)
Relay Outputs: Two separate
NOTE: Relay contacts 2A @ 28 VDC resistive, common mode
SPDT dry contact relay outputs (resistive) are provided for switching or signaling of supplementary devices. A non-delayed output(relay toggles on alarm- beginning of time delay) is provided on TB1-12 (C), 13 (N/C), and 14 (N/O) and a Trouble Relay output for supplementary trouble annunciating devices is provided on TB1-19 (C), 20 (N/C), and 21 (N/O). The Trouble Relay toggles
indicating a fault in any of the supervised connections including initiating devices, signalling devices and supervised
option modules. See figure 9.
AOM Auxiliary Closed Limit:Required for FSCX – optional for FSBX Connect a normally open dry
to position TB-1, 8 and 9. See figure 10. FSBX is not intended for use with external automation. Wiring connections are to be made within 20 feet (6.1 m) and are to be enclosed in conduit.
Electrical Connections
www.overheaddoor.com 12/13 11
Alarm Relay TSystem rouble Relay
10 11 12 13 14 15 16 17 18 19 20 21FIGURE 9
FIGURE 10
112228.0001
112228.0001
112228.0001
112228.0001
112228.0001
112228.0001
Remote TestReset Station
Com
mon
Annunciator
AUX
Ope
n Li
mit
Switc
h
AUX
Clos
e Li
mit
Switc
h
AUX
Com
mon
Ann
unci
ator
+
Ann
unci
ator
–
AuxiliaryOpenLimit
AuxiliaryClosed
Limit
Test
Rese
t
Rem
ote
Trou
ble
EOLR-1
Smoke Power TB1-3 (+) and TB1-4 (–)
Alarm Relay System TroubleRelay
Fire Sentinel® Release System
(On circuit board.) (On circuit board.)
contact (Contacts close when door is at down limit)
AOMRefer to Operator manufacturer’s wiring instructions for proper
Control Circuit Sensing: FSCX ONLY This option is used to detect the presence of control voltage on motor driven doors for automated fire alarm closure. When control circuit voltage is not present (24V-30V AC or DC) the FSCX will sound a trouble, indicating the loss of door operator control voltage. In alarm, if control voltage is not present FSCX will mechanically release the door after the factory set 10 second delay (or longer optional delay). Connect control
circuit voltage to position 30 (–) and 31(+).
Electrical Connections
www.overheaddoor.com 02/13 12
Auxiliary Open Limit: FSCX ONLY
• Connect a normally open dry contact (Contacts close when door is at up limit) .8 dna 7 ,1-BT snoitisop ot
WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL FIELD CONNECTIONS MUST BE MADE WITH POWER DISCONNECTED TO ALL COMPONENTS.
Control Sense (+)
Control Sense Out (–)
Monitored Operator Safety Edge CommonMonitored Operator Safety Edge InCloseOpen
Stop
3-Button Common
Open
Close
Stop
3-Button Common Station
Monitored Safety Edge
Remote TestReset Station
Annunciator
AUX
Ope
n Li
mit
Switc
h
AUX
Clos
e Li
mit
Switc
h
AUX
Com
mon
Ann
unci
ator
+
Ann
unci
ator
–
EOLR-1
Smoke Power TB1-3 (+) and TB1-4 (–)
Alarm Relay System Trouble Relay
FIGURE 11
Fire Sentinel® Release System
(On circuit board.) (On circuit board.)
Com
mon
Test
Rese
t
Rem
ote
Trou
ble
ELECTRIC OPERATOR
AuxiliaryOpenLimit
AuxiliaryClosed
Limit
AOM
112228.0001
112228.0001
112228.0001
112228 0001
112228 000
112228 0001
BLUE
YELLOW
Safety Edge Connection: FSCX ONLY— Figure 11 • Connect safety edge across the operator’s “safety edge” sense terminal
and the FSCX “Safety Edge” TB-1, 26 and 27.
• Connect operator’s “open” terminal to FSCX “open” TB-1, no. 24.
• C
WALL BUTTON CONNECTION FSCX ONLY
onnect operator’s “close” terminal to FSCX “close” TB-1, no. 25.
• Connect operator’s “common” terminal to FSCX “operator common” TB-1, no. 22.
• Connect operator’s “stop” terminal to the “stop” terminal on the 3-button control.
• Connect operator’s “open” terminal to the “open” terminal on the 3-button control.
• C• Connect 3 button common to TB-1, no. 23.
onnect operator’s “close” terminal to the “close” terminal on the 3-button control.
Electrical Connections
www.overheaddoor.com 02/13 13Fire Sentinel® Release System
Control Sense (+)
Control Sense (–)
Monitored Operator Safety Edge CommonMonitored Operator Safety Edge InCloseOpen
3-button Common
Operator Common
Open
Close
Stop
3-Button Common Station
MONITOREDSAFETY EDGE
MONITORED EDGEINTERFACE MODULE
Remote TestReset Station
Annunciator
AUX
Ope
n Li
mit
Switc
h
AUX
Clos
e Li
mit
Switc
h
AUX
Com
mon
Ann
unci
ator
+
Ann
unci
ator
–
EOLR-1
Smoke Power TB1-3 (+) and TB1-4 (–)
Alarm Relay System Trouble Relay
FIGURE 11 (repeated)
ELECTRICOPERATOR
(On circuit board.) (On circuit board.)
Com
mon
Test
Rese
t
Rem
ote
Trou
ble
AuxiliaryOpenLimit
AuxiliaryClosed
Limit
AOM
no.
112228.0001
112228.0001
112228.0001
112228 000
112228 0001
112228 0001
BLUE
YELLOW
Electrical ConnectionsBattery: Must be connected at this time,
s*eirettab elbaegrahcer-non eht tcennoC )2(112087.0001) to the
FSBX or FSCX observing Figure 12 for proper mounting
and connection.
NOTE: The transformer is used only in 120VAC models
* Batteries must be replaced with P/N 112087.0001. Standard AA batteries will not work and may cause damage to the unit and will void the factory warranty.
and
.sledom CDV42 no dedivorp ton si
www.overheaddoor.com 02/13 14
Replaceable fuses 2A @ 350VAC,125VDC, 2AG Fast Acting
Power
LowVoltage
Voltage112087.0001
1-(L1) or (AC) or (DC-)2-(Earth GND)3-(L2) or (AC) or (DC+)
FIGURE 12
Fire Sentinel® Release System
Red wire
SYSTEMBACKUP
BATTERIES
to Red terminal
Black wire to Black terminal
TBX
1) Install System Backup Batteries.• Connect + lead of left battery to – lead of right battery using jumper wire provided.• Connect black wire to black terminal on left battery.• Connect red wire to red terminal on right battery.
Electrical ConnectionsReplaceable fuses 2A @ 350VAC,125VDC, 2AG Fast Acting
REMOTE TEST PLATE
2JQ2-RFUSE
PARTS KIT
BA
T+
BA
T-
AC
-2A
C-1
www.overheaddoor.com 12/13 15
FIGURE 13
Fire Sentinel® Release System
RESISTOR
112228.0001
TROUBLE
NORMAL
TEST RESET
(-) (+)
)+( )-( (-)(+)
(-) (+)
(-)
(+)
TERM-2
DOWN LIMIT PROXIMITY SWITCH
OPTIONAL EQUIPMENT NOT INCLUDED WITH THE RELEASE DEVICE.
TERM
-7TE
RM-8
TERM
-9
TERM
-21
TERM
-20
TERM
-19
TERM
-14
TERM
-13
TERM
-12
120V
AC
112228.0001
112228.0001
112228.0001
AD
WH
T
BLK
GRN
RED
WH
TG
RN
WHITE
BLK
TERM
-11
TERM
-10
TERM
-18
TERM
-17
TERM
-16
TERM
-15
TERM-4TERM-3TERM-2TERM-1
TWO-WIREINITIATING DEVICE
FOUR-WIREINITIATING DEVICE
TERM-1SYSTEMTROUBLERELAY
ALARMRELAY
FIRE SENTINEL®MODEL FSBX120VAC
ON
F I R E
Remote Test Reset Station
1 2
3 4
5 6
7 8
—OR—
Field and System Wiring shall consist of 22-18 AWG wiring. Use only 350 VAC, 125VDC, 2 Amp, 2 AG Fast Acting fuses. All circuits are not power limited. SYSTEM WIRING NOTES: 1. Supervised, 35 Ohm maximum line impedance. 11228.0001 end of line resistor required for supervision. 2. Not supervised, 75 Ohm maximum line impedance. 3. 4 Class B Style A detectors maximum 112228.0001 end of line resistor required for supervision. 4. 2 Class B Style W notification appliances maximum @ 0.16 Amp/28.6VDC maximum Supervised 20 Ohm maximum line impedance. Place 112228.0001 at positions 10 and 11 if appliances are not used. 5. Form C dry contacts, relay contacts 2A @ 28.6VDC resistive, common mode. 6. End of line relay (EOLR-1) shall be installed with 4-wire detectors. Do Not loop wire under terminals for connections. 7. Smoke power TB1-3 (+) and TB1-4 (–). Supervised, see items 2, 6 above. 8. (2) Class B Style A detectors maximum @ 0.075 Amp/28.6VDC maximum Supervised, see item 1 above. 9. All wiring connections are
10. Replace batteries every 2 years.
to be made within 20 feet (6.1 m), enclosed in conduit and in the same room. GROUND FAULT: 20 kOhms maximum from one conductor to earth ground.
WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL INPUT CONNECTIONS MUST BE MADE WITH THE UNIT POWERED DOWN. ALL AUXILIARY LIMIT SWITCHES MUST BE DRY CONTACTS.
Electrical Connections
FIGURE 13A
All information on this page applies to both Figure 13A and 14.
www.overheaddoor.com 12/13 16Fire Sentinel® Release System
A SOUNDER/STROBE **
**
*
*
ORANGE
3 1
(–) (+)
(–)(+) )+( )–(
(–) (+)
(–)
(–)(+)
(+)
(+)TERM
-2
TERM-7TERM-8TERM-9TERM-21
TERM-20TERM-19
TERM-14TERM-13TERM-12
120VAC
112228.0001
ADASOUNDER/STROBE
BLUE
YELLOW
BLUE
YELLOW
PURPLE
208V230V
SINGLE PHASE
THREE PHASE
GND GND
GND GND
NEUTRAL
LINE 3LINE 2LINE 1
LINE(HOT)
L NE 2
L NE 1
SPLICE
SPLICE
SPLICE
YELLOWORANGERED
OPEN
CLOSE
STOP
MONITOREDEDGE
INTERFACEMODULE
SENSINGEDGE
RED
WHITEGREEN
BLACK
TERM-11
TERM-10
1
3
TERM-18TERM-17TERM-16TERM-15
TERM-22
AUX OUTPUTBOARD
TERM-23TERM-24
115V
TERM-25
TERM-4
TERM-3
TERM-2
TERM-1
TWO-WIREINITIATING DEVICEFOUR-WIRE
INITIATING DEVICE
TERM-1
UP1
DN1**
OPENCLOSE
SystemTroubleRelay
RMX® / RSX® / RHX® / CDX™OPERATOR
ON
FIRE
Remote TestReset Station
1 2 3 4 5 6 7 8
L2L1
L3L2L1
NL1
STOP
GND1-BTNODC STBODC STB
NO SAFETYNO SAFETYEXT INTLKEXT INTLK
AlarmRelay
ExternalRadio
—OR—
GREENPURPLEPINKBLACK
GREYWHITEORANGE
TERM-30TERM-31
BLA
WHITE(N)
L1 CKGREEN
FIRE SENTINEL®MODEL
FSCX120V
TERM-27TERM-26
**
*
*
**
*
TERMINAL LEGEND AND HOOKUPS: 1. Smoke Alarm Return 2. Smoke Alarm Power 3. Smoke Alarm Power 4. Power Return (System Ground)
5. N/A 6. N/A 7. Auxiliary Open Limit Switch (must be dry switch contact) 8. Limit Switch Common 9. Auxiliary Close Limit Switch (must be dry switch contact)
10. Annunciator Output (+) 11. Annunciator Return (–) 12. Alarm Relay Common (dry contact) 13. Alarm Relay Normally Closed (dry contact) 14. Alarm Relay Normally Open (dry contact)
15. Remote Common (System Ground) 16. Remote Test (must be dry switch contact) 17. Remote Reset (must be dry switch contact) 18. Remote Trouble Indicator (red LED anode) 19. Trouble Relay Common (dry contact) 20. Trouble Relay Normally Closed (dry contact) 21. Trouble Relay Normally Open (dry contact)
RELAY BOARD TERMINALS FROM LEFT: 22. 3-button Common 23. Stop 24. Open 25. Close 26. Analog Operator Safety Edge 27. Analog Operator Safety Edge Common 28. Digital Operator Safety Edge 29. Digital Operator Safety Edge 30. Control Sense Out 31. Control Sense In
Electrical ConnectionsFIGURE 14All information on this page applies to Figures 13A and 14.
www.overheaddoor.com 12/13 17Fire Sentinel® Release System
* ** OPTIONAL EQUIPMENT N DOWN LIMIT—USE PROXIMITY SWITCHOT INC LUDED WITH THE RELEASE DEV IC E. FSBX.
*
112228.0001
112228.0001
(–)BROWNTAN
Electrical ConnectionsDip Switches:
LED Indications when lit:
.51 erugiF ot refeR
ON1 2 3 4 5 6 7 8
FIGURE 15
www.overheaddoor.com 02/13 18
1. Delay Alarm Time (OFF: 10s, ON: 20s.) 2. Delay Alarm Time Extended (OFF: as set by 1, ON: 60s.)
3. Safety Timer (OFF: 2 minutes, ON: 4 minutes.)
4. Annunciator Down Limit (if set ON: notification appliances
will shut off when automated door reaches down limit in
tests only.)
5. Auto Open on Reset (if set ON: automated doors will open
when the alarm is reset in tests only.)
6. Relay Board Present (OFF: Board not present ON: Board
present [use to enable/disable relay board functions.])
7. Stop on Obstruction (ON: in alarm, automated doors will
stop at the obstruction on the third closing cycle.)
(See
Test Procedures, page 24) 8. Alarm on Power Loss (ON: loss of external power will trigger
an alarm sequence.)
Three LEDs in the upper left corner of the board are:
Green: AC Present - LED 9
Yellow: Battery OK - LED 10
Yellow: Trouble - LED 11
Next to the JP16 header connector:
Yellow: Magnet open/not present - LED 2
Green: Magnet on- LED19
Upper Right:
Green: 5V Power on - LED 23
LEDs along the Terminal Block—left to right:
Yellow: Smoke detector loop open - LED 22
Red: Smoke detector alarm or short - LED 21
Green: Open Limit - LED 6
Green: Down Limit - LED 4
Yellow: Alarm annunciator loop open - LED 7
Red: Alarm annunciator loop short - LED 8
LED11
LED10
LED9
RESET
TESTJP9 JP8 JP4 JP6 JP10 JP2
JP26
JP3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
LED8
LED7
LED20
LED4
LED6
LED21
LED22
LED19
LED23
LED2
JP16
JP21
JP23
16
JP19
JP25
S6
S5
S4ON
1
Fire Sentinel® Release System
NOTE: Relay Board LEDs are not shown.1 2 3 4 5 6 7 8
www.overheaddoor.com 12/13 19Fire Sentinel® Release System
Electrical Connections (Trouble Code Chart)The Trouble LED on the Main Board will flash out these codes in sequence. Each trouble present is counted out in sequence separated by a distinct pause.After all uncleared troubles have been counted out, the sequence repeats.
(1) FLASH
TROUBLE LED (YELLOW)
TROUBLE CODE
REQUIRED ACTION
MAGNET FAULT
(3) FLASHES
(5) FLASHES
(6) FLASHES
(7) FLASHES
(8) FLASHES
(9) FLASHES
(10) FLASHES
(11) FLASHES
(12) FLASHES
(15) FLASHES
(16) FLASHES
(17) FLASHES
(18) FLASHES
(22) FLASHES
(29) FLASHES
GROUND FAULT
BATTERY NOT CHARGING
CHARGER VOLTAGE FAIL
BATTERY LOW
EXTERNAL POWER LOSS
RETAINER SWITCH
ANNUNCIATOR CIRCUIT OPEN
ANNUNCIATOR CIRCUIT SHORT
ALARM LOOP OPEN
TEST REQUIRED
REAL-TIME CLOCK ERROR
STUCK RESET
CONTROL SENSING VOLTAGE NOT PRESENT
NON-RECHARGEABLE BATTERY RUN TIME EXCEEDED
SAFETY EDGE FAULT
Check electromagnet cable and terminal JP3
Check all low voltage �eld wiring especially insulation
Check SLA battery cables
Check AC voltage and wiring
Check AC voltage and wiring; Check fuse F3; replace with known good battery
Check AC voltage and wiring; Check fuse F2
Remove armature from bracket and place on magnet
Check annunciator (Horn/Strobe) wiring; Verify EOL resistor is installed
Check annunciator (Horn/Strobe) wiring
Check smoke alarm wiring and smoke alarm EOL (resistor/relay termination)
Perform drop or close test
Replace non-rechargeable battery and perform drop or close test
Check reset button and keyswitch; Check keyswitch wiring
Check terminals 30, 31 and pigtail - Check operator has power
Replace non-rechargeable battery
Check safety edge and safety edge wiring
WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH DURING MAINTENANCE: • PLACE DOOR IN FULLY CLOSED POSITION • DISCONNECT ANY AND ALL POWER FROM SYSTEM AND SYSTEM COMPONENTS INCLUDING MOTORS WHERE APPLICABLE
Maintenance
System batteries must be changed a minimum of every two years or upon generation of system battery trouble. Included is a pair of sealed lead acid
fo riap a sa llew sa ,pukcab yrettab metsys rof dezilitu seirettab elbaegrahceron-board lithium battery used for the System Annual Test Clock. All batteriesshould
be replaced simultaneously by a properly trained technician using proper
tools and instructions. For proper replacement parts, see list on page 25.
Batteries should be disposed of in accordance with Federal, State and Local Regulations.
System fuses are all 2A @ 350V, 125VDC, 2AG Fast Acting. Reference pages 14, 15 (Figures 12 and 13).
www.overheaddoor.com 02/13 20Fire Sentinel® Release System
ELECTRICALOPERATING VOLTAGES: CURRENT REQUIREMENTS: 24 VDC .....................................................SUPERVISORY (non-alarm) .385 A/Alarm .610 A maximum. 120 VAC................................................. 0.430 A maximum.INPUT POWER SUPERVISED: NOTE: 1. Initial power up inrush current shall not exceed 3 times rated current on any model.
DOOR POSITION INPUTS: MAXIMUM LOOP RESISTANCE: 35 Ohms.
MAXIMUM CURRENT: Not to exceed .002 A maximum.
MAXIMUM VOLTAGE: 5VDC.FORM C OUTPUT (MAXIMUM CONTACT RATING):
2 A @ 28VDC resistive, common mode.SMOKE DETECTOR POWER:
18.6–28.8VDC @ .021 A STANDBY, .075 A ALARM. (See pages 8 & 9.) FUSES: ALL FUSES: 2A @ 350V, 125VDC, 2AG, Fast Acting Type (See figure 12 & 13).
NOTIFICATION APPLIANCES: 28.8VDC @ .160 A ALARM (See figures 7). BATTERY BACKUP: 12VDC, 5AH, QTY=2, 24hr. supervised circuit. GROUND FAULT: 20 kOhms maximum from one conductor to earth ground.
MECHANICALLOAD RATING: SUPPORT AND RELEASE–40lb. maximum.PHYSICAL DIMENSIONS: 10.250" x 9.750" x 4.750" (H x W x D) I.D.WEIGHT: 19 lbs. w/batteries.
Electrical and Mechanical SpecificationsMODEL FSBX MODEL FSCX
ELECTRICALOPERATING VOLTAGES: CURRENT REQUIREMENTS: 24 VDC .....................................................SUPERVISORY (non-alarm) .385 A/Alarm .610 A maximum. 120 VAC ............................................... 0.430 A maximum.INPUT POWER SUPERVISED: NOTE: 1. Initial power up inrush current shall not exceed 3 times rated current on any model.
CONTROL SENSE-ALL MODELS: Input voltage: 24VAC / DC typical Input Current—Not to exceed .005 A.DOOR POSITION INPUTS: MAXIMUM LOOP RESISTANCE: 35 Ohms. MAXIMUM CURRENT: Not to exceed .002 A maximum. MAXIMUM VOLTAGE: 5VDC.FORM C OUTPUT (MAXIMUM CONTACT RATING): 2 A @ 28VDC resistive, common mode.SMOKE DETECTOR POWER: 18.6–28.8VDC @ .021 A STANDBY, .075 A ALARM. (See pages 8 & 9.) FUSES: ALL FUSES: 2A @ 350V, 125VDC, 2AG, Fast Acting Type (See figure 12 & 13).NOTIFICATION APPLIANCES: 28.8VDC @ .160 A ALARM (See figures 7).BATTERY BACKUP: 12VDC, 5AH, QTY=2, 24hr. supervised circuit. GROUND FAULT: 20 kOhms maximum from one conductor to earth ground.REMOTE TEST/RESET STATION: SPDT, 1A @ 125VAC. Position 1-test, Position 2-normal, Position 3-trouble/alarm reset. Indicators—Red LED - trouble indication (see Trouble Codes pg. 19) On the reset of a trouble, the sounder will turn off, but the LED will remain lighted until the troubles are fixed and a reset is performed. The sounder will reactivate within 24 hours if the trouble is not cleared.
REMOTE TEST/RESET STATION: SPDT, 1A @ 125VAC. Position 1-test, Position 2-normal, Position 3-trouble/alarm reset. Indicators—Red LED - trouble indication (see Trouble Codes pg. 19) On the reset of a trouble, the sounder will turn off, but the LED will remain lighted until the troubles are fixed and a reset is performed. The sounder will reactivate within 24 hours if the trouble is not cleared.
MECHANICALLOAD RATING: SUPPORT AND RELEASE: 40lbs. maximum.PHYSICAL DIMENSIONS: 10.250" x 9.750" x 4.750" (H x W x D) I.D. WEIGHT: 20 lbs. with batteries.
www.overheaddoor.com 12/13 21Fire Sentinel® Release System
NOTE: TESTING MUST BE PERFORMED AND WITNESSED FOR NORMAL OPERATION AFTER INSTALLATION. A “Test Required” trouble will occur until a complete test cycle is performed. This is a normal condition and part of the Internal Annual Test Clock/Calendar. The annual test is a National Fire Code requirement. More frequent tests may be required by the local Authority Having Jurisdiction (AHJ). Refer to test procedures contained herein, as well as other testing programs recommended by door manufacturer.
Test Procedures
The following tests as described using the Remote Test Plate (RTP) may alternatively be performed by the chassis mounted push button test and reset switches. It is recommended that test and reset functions be performed utilizing the RTP provided with the unit.Test steps 1-5 verify a mechanical release to a non-motorized door or a motorized door with external power normal. Test steps 6-10 verify a mechanical release under battery power with external power loss. 1) Turn ON power to the FSBX or FSCX and turn OFF power to the motor operator (if applicable). • A "Test Required" trouble and "Retainer Switch" trouble will be generated at power up. This is normal.
Mechanical Door Drop Test for Models BX and CX:
WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING THE MECHANICAL OR ELECTRICAL DOOR DROP TEST, KEEP YOURSELF AND ANY OTHERS CLEAR OF THE DOOR AND ANY MOVING PARTS.
• CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.
• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.
• Turn RTP to RESET, then NORMAL, to silence the troubles. • Remove the Armature from the Retaining Bracket (Figure 2, page 6) and align it with the Supervised Electromagnet. WARNING: CLEAR THE DOOR OPENING BEFORE BEGINNING STEP 2. 2) Turn RTP to the TEST position. The annunciator will sound indicating a door closure is about to occur and after a 10 second factory set alarm verification delay (or longer optional delay) the device will mechanically release the door. 3) Turn RTP to RESET position and then back to the NORMAL position. This test verifies a mechanical release for a non-motorized door or in absence of power to the motor for externally automated doors. 4) Mechanically reset the door and reattach Armature to the Supervised Magnet. • Make sure the door is fully raised. 5) DO NOT restore power to the motor. WARNING: CLEAR THE DOOR OPENING BEFORE BEGINNING STEP 6. 6) Turn OFF power to the FSBX or FSCX. 7) The power LED (red) will turn off and "External Power Loss" and "Battery Not Charging" troubles will be generated in approximately 10 seconds. This is a normal condition. • Turn the RTP to the TEST position. The annunciator will sound indicating a door closure is about to occur and after a 10 second factory set alarm verification delay (or longer optional delay) the device will mechanically release the door. 8) Turn the RTP to the RESET position and then back to NORMAL. This test verifies a mechanical release in absence of power to the FSBX or FSCX and motor (if applicable). 9) Mechanically reset the door and reattach the armature to the release magnet. 10) Restore power to the Release System and Motor operator and raise the door
to the fully open position.
• Turn the RTP to RESET and back to NORMAL to clear trouble indicator on the RTP.
www.overheaddoor.com 02/13 22Fire Sentinel® Release System
WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING THE MECHANICAL OR ELECTRICAL DOOR DROP TEST, KEEP YOURSELF AND ANY OTHERS CLEAR OF THE DOOR AND ANY MOVING PARTS. • CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.
Test ProceduresAutomatic Door Closure Tests (Motorized Doors/FSCX only):
THREE CYCLE OBSTRUCTION TEST with release on obstruction
1) Make sure the DIP switch at position 6 (relay board PRESENT)
is set in the ON position on the Main Circuit Board. • Make sure the door is open and there are no obstructions in its path.
1) Make sure the DIP switch at position 6 (relay board PRESENT) is set in the ON position on the Main Circuit Board. • Place a chair or other suitable obstruction in the normal path of the door.
WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)
WARNING: THIS EQUIPMENT IS DESIGNED TO BE USED IN CONJUNCTION WITH AN OPERATOR INCORPORATING A MONITORED REVERSING FEATURE SAFETY EDGE. DO NOT
EXECUTE THIS TEST WITHOUT A SAFETY EDGE INSTALLED!
2) Turn the key switch to TEST and leave it there. The annunciator will turn on indicating that a door closure is about to occur. After the factory set 10 second delay (or longer optional delay), the device will turn on the motor initiating a closure.
2) hctiws yek nruT
3) Allow the door to fully close.4) Reset the FSCX by turning the key switch to the RESET position, then back to NORMAL.
5) Open the door.back to NORMAL.
no nrut lliw rotaicnunna ehT ereht ti evael dna TSET ot
indicating that a door closure is about to occur. After the factory set 10 second delay (or
.erusolc a gnitaitini rotom eht no nrut lliw ecived eht ,)yaled lanoitpo regnol
Upon contact with the obstruction, the safety edge will reverse the motor and raise the door to the fully open position. The FSCX will make three attempts to close the door with the motor, after which the FSCX will release the door through the drop release mechanism. STAND CLEAR OF ANY PATH THE OBSTRUCTION MIGHT TAKE AFTER BEING STRUCK BY THE DROPPED DOOR. The door will drop onto the obstruction and will fully close once the obstruction is removed. The annunciator will continue to sound until the alarm condition is cleared. 3) Reset
4) Reset the door sash chain and armature. *N-O REV INPUT will not allow “STOP ON OBSTRUCTION.”
the FSCX by turning the key switch to the RESET position and then back to NORMAL.
THREE CYCLE OBSTRUCTION TEST WITH STOP ON OBSTRUCTION 1) Make sure the DIP switches at position 6 (relay board PRESENT) and
eht no noitisop NO eht ni tes era )noitcurtsbo no pots( 7 noitisop .draoB tiucriC niaM
• Place a chair or other suitable obstruction in the normal path of the door.
no nrut lliw rotaicnunna ehT ereht ti evael dna TSET ot hctiws yek eht nruT )2 dnoces 01 tes yrotcaf eht retfA .rucco ot tuoba si erusolc rood a taht gnitacidni delay (or longer optional delay), the device will turn on the motor initiating .erusolc a CONTINUED NEXT PAGE
www.overheaddoor.com 02/13 23Fire Sentinel® Release System
WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)
WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)
Test ProceduresAutomatic Door Closure Tests (Motorized Doors/FSCX only) (continued):
THREE CYCLE OBSTRUCTION TEST WITH STOP ON OBSTRUCTION CONTINUEDIf the obstruction is removed, the FSCX will wait 10 seconds and then close the door. Should the door contact a second obstruction, the FSCX will fully open the door, then attempt to close the door again. If the obstruction is still there, the FSCX will open the door to the up limit and mechanically release the door. STAND CLEAR OF ANY PATH THE OBSTRUCTION MIGHT TAKE AFTER BEING CONTACTED BY THE DROPPED DOOR. The annunciator will continue to sound until the alarm condition is cleared. 3) Reset
4) Reset door sash chain and armature.5) Open the door.
the FSCX by turning the key switch to the RESET position and then back to NORMAL.
AUTO OPEN
ON RESET
TEST
1) Make sure the DIP switches at position 5 (auto open on reset, test only) and position 6 (relay board PRESENT) are set in the ON position on the .draoB tiucriC niaM
THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)
2) Turn the key switch to TEST and leave it there. • Make sure there are no obstructions in the path of the door. 3) Allow the door to fully close. 4) Reset the FSCX by turning the key switch to the RESET position and back to NORMAL. • After the reset is complete the door will automatically start to open to
.timil pu eht
NOTIFICATION
NOTE: If Dip Switch 5 is not set to ON—the door will automatically re-open.
OFF ON CLOSE LIMIT TEST ,timil nwod no ffo noitacifiton( 4 noitisop ta sehctiws PID eht erus ekaM )1 noitisop NO eht ot tes era )TNESERP draob yaler( 6 noitisop dna )ylno tset
on the Main Circuit Board.
THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the Device Enclosure.)
timil nwod eht ni ton si rotarepo eht erus ekaM )2 • If in the down limit, press the open button on the 3-button station to open the door. 3) Turn the key switch to TEST and leave it there. • Make sure there are no obstructions in the path of the door. 4) Allow the door to fully close. • When the door reaches the down limit, the notification appliances will shut off. If the open button on the 3-button station is pressed and the door leaves the down limit, the notification appliances will turn back on. 5) Reset the FSCX by turning the key switch to RESET and then back to NORMAL.
www.overheaddoor.com 02/13 24Fire Sentinel® Release System
WARNING
WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.
: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING THE MECHANICAL OR ELECTRICAL DOOR DROP TEST, KEEP YOURSELF AND ANY OTHERS CLEAR OF THE DOOR AND ANY MOVING PARTS.• CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.
WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.
Upon contact with the obstruction, the safety edge will reverse the motor and raise the door to the fully open position. The FSCX will make three attempts to close through the motor. On the third up limit the FSCX will close the door and stop at the obstruction.
Test ProceduresAutomatic Door Closure Tests (Motorized Doors/FSCX only) (continued):
www.overheaddoor.com 12/13 25
ALARM ON POWER LOSS TEST 1) Make sure the DIP switch at position 8 (alarm on power loss) is set in the ON position on the Main Circuit Board. 2) UNPLUG the unit from the AC power source OR DISCONNECT the DC power input to the unit. • After the factory set 10 second time delay (or longer optional delay) the device will close the door. 3) Re-apply AC or DC power to the unit. 4) Reset the FSCX by turning the key switch to RESET and back to NORMAL.
After completing all tests, verify the door is in normal operating condition (open or closed) and that all power required for normal operation has been restored to the unit and operator. This equipment is designed to operate with its power source applied.
SET DIP SWITCHES AS DESIRED.
Release Device Compatibility IdentifierPhotoelectric Smoke DetectorsSystem Sensor Model No ............Description 2W-B ..............................................2-wire smoke detector, compatibility identifier A 2WT-B ............................................2-wire smoke detector w/135°F thermal sensor, compatibility identifier A 4W-B ..............................................4-wire smoke detector 4WT-B ............................................4-wire smoke detector w/135°F thermal sensorHochiki Model No ...........................Description SLR835BH-2 ................................2-wire smoke detector w/135°F thermal sensor, compatibility identifier HD-6
Heat DetectorsSystem Sensor Model No ............Description 5603 ...............................................135°F fixed temperature 5604 ...............................................194°F fixed temperature
Notification DevicesSystem Sensor Model No ............Description SR ...............................................Strobe. Set for 15 cd per System Sensor Instructions HR ...............................................Horn. Set for non-temporal horn per System Sensor Instructions P2R ...............................................Horn/Strobe. Set for 15 cd and non-temporal horn per System Sensor instructions
End of Line Devices System Sensor Model No ..........Description EOLR-1 ..........................................End of line relay
Replacement PartsOverhead Door Part No ... ........... ..Qty ..................................... ..Description 111658.0001.S ...........................1 .......................................... Sytem backup battery (12 Volt) 112087.0001.S ...........................1 ...........................................System non-rechargeable battery (NRB2.4-7.2)
as req'd ..............................End of line relay etalP/w.........................as req'd ..............................End of line resistor etalP/w 112249.0001.S
111995.XXXXXX .....................as req'd ..............................Installation Manual 112012.0001.S ...........................1 ..........................................Armature Assembly 112007.0001.S ...........................1 ...........................................Remote Test Plate
112228.0001.S ...........................10 pack..............................Supervisory Resistor
112226.000 S.1 ...........................10 .kcap ............................. Fuse 2A
WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING A MECHANICAL OR ELECTRICAL DOOR DROP TEST, STAY CLEAR OF THE DOOR AND ANY MOVING PARTS.
• CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.
• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.
Fire Sentinel® Release System
112325.0001.S ......................
Hochiki Model No ...........................Description DFE-135 ..................................... 135˚F fixed temperature
Installation Notes
www.overheaddoor.com 02/13 26Fire Sentinel® Release System
Test RecordsDATE SERIAL # INSTALLER/TESTER NAME WITNESS NAME PASS FAIL
www.overheaddoor.com 02/13 27
Make copies of this page as needed for additional testing. Keep records of all tests in a permanent file.
Fire Sentinel® Release System
Overhead Door Corporation Fire Sentinel® Release System
Limited Warranty The Distributor of Overhead Door Corporation products whose name appears below (”Seller”) warrants to the original purchaser of the Fire Sentinel® Release System specified below(”Product”), subject to all terms and conditions hereof, that the Product and all components thereof will be free from defects in material and workmanship under normal use and service for the following period, measured from the date of the installation:
• One (1) year
its option,the Product or any part thereof which is determined by Seller to be defective during the applicable warranty period. Any labor charges are excluded and will be the responsibility of the purchaser. This warranty is made to the original purchaser of the Product only, and is not transferable or assignable.
This warranty applies only to the Product which is installed in commercial or industrial building applications. This warranty does not apply to any unauthorized alteration or repair of the Product, or to any Product or component which has been damaged or deteriorated due to misuse, neglect, accident or failure to provide necessary maintenance, normal wear and tear, or acts of God or other causes beyond the resonable control of Seller and does not cover batteries, or repairs and maintenance to the operator or door components.
THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
IN NO EVENT SHALL SELLER BE RESPONSIBLE FOR, OR LIABLE TO ANYONE FOR, SPECIAL, INDIRECT, COLLATERAL, PUNITIVE, INCIDENTAL OR CONSEQUENTIAL DAMAGES, even if Seller has been advised of the possibility of such damages. Such excluded damages include,
MODEL #:
SERIAL #:
ORIGINAL PURCHASER:
INSTALLATION ADDRESS:
DOOR NUMBER (MULTIPLE DOOR INSTALLATIONS):
DOOR TYPE:
SELLER:
SELLER’S ADDRESS:
DATE OF INSTALLATION:
SIGNATURE OF SELLER:
28
Claims under this warranty must be made promptly after discovery, within the applicable warranty period, and in writing to the authorized distributor or installer whose name and address appeared below. (Proof of purchase and identification as the original purchaser maybe required.) The purchaser must allow Seller reasonable opportunity to inspect any Productclaimed to be defective prior to removal or any alteration of its condition.
www.overheaddoor.com
THIS PAGE LEFT BLANK
Fire Sentinel® Release System
www.overheaddoor.com
THIS PAGE LEFT BLANK
Fire Sentinel® Release System
1 Door DriveMt. Hope, Ohio 44660
800-275-6187www.overheaddoor.com
top related