Ammonia Chillers Stefan S. Jensen,

B.Sc.Eng, F.AIRAH, FIEAust, CPEng, NPER

Scantec Refrigeration Technologies

3/13/2014 2 scantec refrigeration technologies Pty Ltd

Introduction

Ammonia

• Admirable safety record (statistically <2 fatalities per 1 billion inhabitants of 14 countries per year; source: IIAR Dallas, 2009)

• Natural refrigerant (used for >130 years)

• Very favourable transport properties

The case studies will provide an overview of actual operating air conditioning systems using NH3 as working fluid.

3/13/2014 3 scantec refrigeration technologies Pty Ltd

Why NH3?

Global HFC emissions by 2050 are ~9-19% (CO2e basis) of projected global CO2 emissions in the BAU scenario.

Source: Velders et al

This rises to 28-45% in a 450 ppm CO2 stabilization scenario.

3/13/2014 4 scantec refrigeration technologies Pty Ltd

Why NH3?

• 16th of December 2013 EU agrees to phase down HFC’s by 79% by 2030

• June 2013 agreement between Presidents Xi and Obama to work together towards an HFC phase-down

• 6th of September 2013 Australia commits internationally to HFC phase-down by 2030

3/13/2014 5 scantec refrigeration technologies Pty Ltd

Why NH3? Climate change legislation 1997 & 2013

3/13/2014 6 scantec refrigeration technologies Pty Ltd

Why NH3? Climate change legislation 1997 & 2013

Source: The Globe Climate Legislation Study: “A review of climate change legislation in 66 countries, 4th edition”

3/13/2014 7 scantec refrigeration technologies Pty Ltd

Chiller Plant with NH3

Engine Room

Location Brisbane CBD

3/13/2014 8 scantec refrigeration technologies Pty Ltd

Chiller Plant with NH3

Engine Room

Location CBD

3/13/2014 9 scantec refrigeration technologies Pty Ltd

Chiller Plant with NH3

BEFORE

R134A Centrifugal Chillers

3/13/2014 10 scantec refrigeration technologies Pty Ltd

Condensers

Evaporators

NH3 accumulator

Receiver

HP float

Screw compressors

Chiller Plant with NH3

AFTER

3/13/2014 11 scantec refrigeration technologies Pty Ltd

Condensers

NH3 accumulator

Receiver

HP float

Screw compressors

NH3 charge = 1300 kg or ~0.2 kg/kW

Evaporators

Chiller Plant with NH3

AFTER

3/13/2014 12 scantec refrigeration technologies Pty Ltd

Chiller Plant with NH3

Evaporators

Compressor

Relief valve

Condensers

3/13/2014 13 scantec refrigeration technologies Pty Ltd

Chiller Plant with NH3

NH3 Scrubbers

465 kW VFD’s

MCC A/C

Annual reduction from 40% to <30%

3/13/2014 14 scantec refrigeration technologies Pty Ltd

Public building with NH3

BEFORE

Two Air Cooled R22 Water Chillers for Office Air Conditioning, 1200 kW

3/13/2014 15 scantec refrigeration technologies Pty Ltd

Public building with NH3

Condenser

HCFC 22 Compressors

HCFC 22 DX AHU

BEFORE

3/13/2014 16 scantec refrigeration technologies Pty Ltd

AFTER

Two Water Cooled R717 Water Chillers, 1200 kW

Annual Energy Saving

500 MWh

Public building with NH3

3/13/2014 17 scantec refrigeration technologies Pty Ltd

Public building with NH3

AFTER

Connection of Basement AHU

Roof top plant room

3/13/2014 18 scantec refrigeration technologies Pty Ltd

Public building with NH3

AFTER

3/13/2014 19 scantec refrigeration technologies Pty Ltd

Public building with NH3

Emergency Ventilation – 41.4 m3/s

<20% of LEL or <30,000 ppm

3/13/2014 20 scantec refrigeration technologies Pty Ltd

Future Heat Recovery System

Edwards GXC50 indirect, open vented, high pressure water tank to AS3498

Existing 613315 hot water system used as booster

Cold water

NH3 compressor

Desuperheater

~66 m

Public building with NH3

AFTER

3/13/2014 21 scantec refrigeration technologies Pty Ltd

Commercial offices

Completed

During Construction

3/13/2014 22 scantec refrigeration technologies Pty Ltd

Commercial offices

Design Refrigeration Capacities

System LT HT Refrigerant NH3 NH3 PGB CHW System temperature, [°C] -24 -10 -7 5 Capacity, [kW] 160 0 719 619

Legend: LT: Low Temperature HT: High Temperature PGB: Propylene Glycol Brine CHW: Chilled Water

Chilled water system services >50 air conditioned office spaces

3/13/2014 23 scantec refrigeration technologies Pty Ltd

Commercial offices

CHW

LT

SBY PGB

3/13/2014 24 scantec refrigeration technologies Pty Ltd

Commercial offices

3/13/2014 25 scantec refrigeration technologies Pty Ltd

Conclusions

▪ No HFC Levy (GWP for NH3 = 0) ▪ No environmental impact of fugitive gas loss ▪ Superior COP

▪ Annual NH3 leakage rate <1%

▪ Suitable for high grade heat recovery

▪ Enables elimination of all SGG’s

3/13/2014 26 scantec refrigeration technologies Pty Ltd

Conclusions

Plant room design – HFC versus NH3 • Unobstructed escape routes – lack of same eliminates NH3 • Charge cost of HFC plant 10-20 times higher than NH3 • Change of image by factory packaging of NH3 systems • Increased production numbers of factory assembled NH3

packages ⇒ lower capital costs • Barriers: Legislation (policies, standards),

technology/safety, supply/availability (components etc.), psychology (perceptions, acceptance), funding/costs (subsidies, tax etc.), markets (competition, demands etc.), training/know-how