caleffi academy hydronic design // inregelen
Post on 16-Oct-2021
7 Views
Preview:
TRANSCRIPT
CALEFFI ACADEMY HYDRONIC DESIGN // INREGELEN 23 & 24 AUGUSTUS 2016 – Patrick Hagen
ECOLOGIE ECONOMIE HVAC-SECTOR
BUSINESS AS USUAL
Eu-richtlijnen, Ecodesign, EPB àverplichtingen, andere aanpak, nieuwe systemen
CONSUMENT
COMFORT OP DE EERSTE PLAATS
Duurzaamheid & ecologie = filosofie. Doet enkel verplichte investering.
GEBREK AAN OVERHEIDSINITIATIEVEN KORTE TERMIJN-DENKEN VERKEERDE PERCEPTIE
Comfort
Budget
Duurzaamheid
DUURZAAMHEID EFFICIENTIE COMFORT
HYDRAULISCH CONCEPT COMPONENTSELECTIE INREGELING HAALBARE BUDGETTEN
SYSTEEMOPTIMALISATIE
DUURZAAM INGEREGELDE INSTALLATIES
HOOGST MOGELIJK COMFORT
LAAGST MOGELIJK VERBRUIK
HOOGST MOGELIJK RENDEMENT
WAAROM INREGELEN?
INSTALLATIE IN ONBALANS • HOOG ENERGIEVERBRUIK • MOGELIJK KOUDE RUIMTES • SLECHT COMFORT
• LAAG ENERGIEVERBRUIK • HOOG COMFORT
NIET INGEREGELD
INGEREGELD
SYSTEEMOPTIMALISATIE WHAT’S IN IT FOR YOU?
EINDGEBRUIKER
• COMFORT • DUURZAME EN EFFICIËNTE
INSTALLATIE • ZEER KORTE TERUGVERDIENTIJD • KLEINE INVESTERING
INSTALLATEUR
• SOLIDE BASIS VAN CONCEPT • COMPONENTSELECTIE IN DETAIL • MINIMALE FOUTMARGE • OPSPOORBARE STORINGEN
Systeemoptimalistie is beste oplossing naargelang de wens van de klant, volgens budget, waarbij foutenmarges in de uitvoering ervan geminimaliseerd worden.
BASISTHEORIE INREGELEN
KV-WAARDE ▪ Geleidingsvermogen klep Kv-waarde ▪ Tegenovergestelde van weerstand
▪ Geeft het debiet aan waarbij een drukverschil van 100 kPa (1 bar) ontstaat
▪ Uitgedrukt in m3/h
▪ Temperatuur water: tussen 5°C en 40°C (gewoonlijk 15-16°C)
▪ Speciaal geval van Kv-waarde ▪ Geeft het debiet aan bij de volledig geopende klep
waarbij een drukverschil van 100 kPa (1 bar) ontstaat ▪ Uitgedrukt in m3/h
▪ Temperatuur water: tussen 5°C en 40°C (gewoonlijk 15-16°C)
KVS-WAARDE
G = [m3/h] Debiet Δp =[bar] Drukverschil Kvs = [m3/h] Hydraulische kenmerken van het ventiel
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KV-WAARDE
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // CIRCUIT CURVE
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KLEPKARAKTERISTIEK
Lineair gedrag indien Δpklep = constant
BASISTHEORIE INREGELEN VAN INSTALLATIE MET RADIATOREN // KLEPKARAKTERISTIEK
Lineair gedrag indien Δppomp = constant en ∆pklep ≠ constant klepautoriteit β (reactie debiet op gedrag van klep)
Stel: Klep sluit, debiet verkleint
∆Ppomp = ∆Prest + ∆P klep
cte ↘ ↗
BASISTHEORIE POMPGEGEVENS // VERSCHUIVING WERKINGSPUNT
BASISTHEORIE POMPGEGEVENS // VERSCHUIVING WERKINGSPUNT
van A naar C
Sluiten van de klep (Kv1 < Kv)
Klep
sluit
van A naar B
Openen van de klep (Kv2 > Kv )
Klep
opent
BASISTHEORIE POMPGEGEVENS // TOERENTALGEREGELDE POMP
BASISTHEORIE POMPGEGEVENS // TOERENTALGEREGELDE POMP KENMERKEN
Automatische drukverschilregeling op Δp-c (drukconstant modus)
Opvoe
rhoo
gteH[m
]
VolumestroomV[m³/h]
nmax
1
2
nregel
3
1. Toerengeregelde pomp ingesteld op setpunt opvoerhoogte (punt 1).
2. De elektronica meet het verschil tussen het setpunt (punt 1) en actuele meetwaarde (punt 2).
3. De regelaar reduceert het toerental en brengt de opvoerhoogte weer op setpuntwaarde (punt 3).
H2
V2
nregel
nregel
nregel
nregel
V1
H1
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
(Ventilator)convector nominaal debiet G 330 l/h
Drukverlies veroorzaakt bij nominaal debiet ΔP 1500 Pa
Lengte van de stijgleidingen – aansluitingen (ventilator)convectoren l 4 m
Bochten tussen stijgleidingen en (ventilator)convectoren nr. 2 (90°)
8 SECUNDAIRE CIRCUITS
8 SECUNDAIRE CIRCUITS
Leidingen h8 790 Pa
Hulpstukken z8 960 Pa
Afgifte k8 1500 Pa
TOTAAL h8 3250 Pa = 3,25 kPa
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
SECTIE VAN STIJGLEIDING 8 - 7
SECUNDAIR CIRCUIT 7
Leidingen h8-7 287 Pa
Hulpstukken z8-7 57 Pa
TOTAAL ∆P8-7 344 Pa
H8 3250 Pa
∆P8-7 344 Pa
DRUKVERLIES H7 3594 Pa = 3,59 kPa
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
G7 = gebalanceerd debiet H7 = nieuw drukverlies van het circuit G8 = te balanceren debiet H8 = drukverlies van het te balanceren circuit
SECUNDAIR CIRCUIT 7
Debiet G7-8
Debiet 8 G8 330 l/h
Debiet 7 G7 348 l/h
TOTAAL G7-8 678 l/h
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
SECTIE VAN STIJGLEIDING 7 - 6
Drukverlies ∆P7-8
Leiding h7-6 1096 Pa
Hulpstukken z7-6 250 Pa
TOTAAL ∆P7-6 1346 Pa = 1,37 kPa
SECUNDAIR CIRCUIT 6
H7 3250 Pa
∆P7-6 1350 Pa
DRUKVERLIES H6 4940 Pa = 4,94 kPa
NIET-INGEREGELD CIRCUIT HOE ONTSTAAT DRUKVERLIES
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN
VOLLAST
G8 = 330 l/h Ø8 = ½” V8 = 0,44 m/s G7 = 330 l/h Ø7 = ½” V7 = 0,44 m/s G6 = 330 l/h Ø6 = ½” V6 = 0,44 m/s G5 = 330 l/h Ø5 = ½” V5 = 0,44 m/s G4 = 330 l/h Ø4 = ½” V4 = 0,44 m/s G3 = 330 l/h Ø3 = ½” V3 = 0,44 m/s G2 = 330 l/h Ø2 = ½” V2 = 0,44 m/s G1 = 330 l/h Ø1 = ½” V1 = 0,44 m/s
G8-7 = 330 l/h Ø8-7 = ¾” G7-6 = 660 l/h Ø7-6 = ¾” G6-5 = 990 l/h Ø6-5 = 1” G5-4 = 1320 l/h Ø5-4 = 1 ¼” G4-3 = 1650 l/h Ø4-3 = 1 ¼” G3-2 = 1650 l/h Ø3-2 = 1 ¼” G2-1 = 1980 l/h Ø2-1 = 1 ¼” G1-0 = 2310 l/h Ø1-0 = 1 ½”
VOLLAST
(Ventilator)convector nominaal debiet G 330 l/h Drukverlies veroorzaakt bij nominaal debiet ΔP 1500 Pa Lengte van de stijgleidingen – aansluitingen (ventilator)convectoren l 4 m
Bochten tussen stijgleidingen en (ventilator)convectoren nr. 2 (90°)
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
DEBIETBEREKENING
SECUNDAIR CIRCUIT 8
Leidingen h8 790 Pa
Hulpstukken z8 960 Pa
Afgifte k8 1500 Pa
Inregelventiel ∆Pv8 1110 Pa
TOTAAL h8 4360 Pa = 4,36 kPa
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
Inregelventiel ingesteld op POSITIE 6
SECUNDAIR CIRCUIT 8
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
Sectie van stijgleiding 8 - 7
Debiet G8-7 = G8 = 333 l/h
Leiding h8-7 287 kPa
Hulpstukken z8-7 57 kPa
TOTAAL ∆P8-7 344 kPa
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
3250 Pa SECUNDAIR CIRCUIT 7
Drukverlies
H8 4360 Pa
∆P8-7 344 Pa
H7 EFF 4704 Pa = 4,70 kPa
Inregelstand
H7EFF 4704 Pa
H8 3250 Pa
∆PREG.VENT 1454 Pa = 1,45 kPa
Inregelventiel ingesteld op POSITIE 4.5
SECUNDAIR CIRCUIT 7
INGEREGELD CIRCUIT DRUKVERLIES OPLOSSEN: inregelventiel – gekalibreerde opening
Statisch inregelen
Inregelventiel met debietmeter serie 132
Inregelventiel met venturi serie 130
Inregelventiel met flensaansluiting serie 130
Dynamisch inregelen
Drukonafhankelijk ventiel Flomatic® serie 145
Automatische debietregelaar Autoflow®
serie 121-126 serie 127 serie 120-125 serie 103
∆p regelen
Drukverschilregelaar serie 140
Inregelventiel met voorinstelling serie 142
Drukverschilregelaar serie 519
INREGELEN // toepassingen & componenten
Statisch inregelen Dynamisch inregelen ∆P inregelen
Serie 130 Serie 132
Serie 145 Flomatic®
Serie 120 / 121 /125 / 126 / 107 / 103
Autoflow®
Serie 140 Serie 142 Serie 519
Solar Geothermie Tapwater
Radiatoren Vloerverwarming Satellietunit
Koelplafonds Luchtverhitter Stralingspanelen Convectoren Luchtgroep Cascade
INREGELEN // toepassingen
INREGELEN // toepassingen RADIATOREN
INREGELEN // toepassingen RADIATOREN
INREGELEN // toepassingen VLOERVERWARMING
INREGELEN // toepassingen VLOERVERWARMING
INREGELEN // toepassingen VLOERVERWARMING
INREGELEN // toepassingen DISTRIBUTIE-UNITS
INREGELEN // toepassingen DISTRIBUTIE-UNITS
INREGELEN // toepassingen DISTRIBUTIE-UNITS
INREGELEN // toepassingen DISTRIBUTIE-UNITS
INREGELEN // toepassingen VENTILOCONVECTOREN | KOELBALKEN | LUCHTVERHITTERS | STRALINGSPANELEN
INREGELEN // toepassingen VENTILOCONVECTOREN | KOELBALKEN | LUCHTVERHITTERS | STRALINGSPANELEN
INREGELEN // toepassingen LUCHTGROEPEN
INREGELEN // toepassingen LUCHTGROEPEN
INREGELEN // toepassingen LUCHTGROEPEN
INREGELEN // toepassingen CASCADE