ci supraloft panel filters loft sl-1a, sl-2a, sl-3a, sl-3 ... · ci supraloft® panel filters...
Post on 04-Jun-2020
27 Views
Preview:
TRANSCRIPT
CI Supraloft® Panel FiltersSL-1A, SL-2A, SL-3A, SL-3, SL-4, SL-5A, SL-5MERV 6, 7, 8, & 10
SL-2AMERV 7
SL-1AMERV 6
SL-3AMERV 8
SL-3MERV 8
SL-4MERV 8
SL-5AMERV 8
SL-5MERV 10
Quick FactsDescription and BenefitsBest ValueCI Supraloft® line of Panel Filters are one of the industry’s best values in filtration. CI uses polyester media produced in CI-owned and operated facilities to make panel filters. In fact, CI’s environmentally responsible panel filters are manufactured with recycled products whenever possible. The CI Supraloft® Panel Filters are available in a wide variety of filtration performance options to meet the needs of today’s varied and challenging HVAC environments.
Removes ContaminantsCI Supraloft® Panel Filters help to improve indoor air quality and remove contaminants from HVAC environments. Each panel filter is engineered to protect both expensive HVAC equipment and workers from dirty air and its damaging effects. The CI Supraloft® Panel Filters will also extend the life of costly secondary filters. Equally important, the user-friendly filters are lightweight, durable and easy to install.
Self-Sealing to Prevent Air BypassWith their self-sealing design, the CI Supraloft® Panel Filters prevent air bypass and increase efficiency performance. Each panel is heat-sealed around a sturdy internal grid that provides durability and structural integrity. The CI Supraloft® Panel Filters use a progressive density fiber structure and incorporate a non-migrating tackifier for optimum filter performance in airflow, efficiency and depth loading. The filter’s synthetic media is unaffected by ambient temperature changes or excess humidity.
Various ConfigurationsCI Supraloft® Panel Filters are available in both single panel and linked configurations, and are a suitable replacement for all commonly used pre-filters. The filters provide the best performance in both pre-filtration and standalone applications.
Looking for LEED certification? CI Supraloft® Panel Filters SL-3A, SL-3, SL-4, SL-5A and SL-5 can be used to meet new construction phase requirements for the Green Building Council’s LEED certification program.
Features:• Provides lower in class initial resistance• Provides higher holding capacity and
longer service life• Provides lower operating cost• SL-3A, SL-3, SL-4, SL-5A and SL-5 meet
requirements for new construction phase of LEED’s program
• Self-sealing design to prevent air bypass• Select filters consist of recycled components• Some made with antimicrobial fibers
Applications:• Commercial and industrial facilities• Pharmaceutical • Government and educational facilities• Hospitals• Paint booth/finishing
Technical:• Available in a variety of standard and
custom sizes, in both individual panel and linked configurations
• Available in MERV 6, 7, 8 and 10• Tested in accordance with ASHRAE Test
Standard 52.2-2007• UL Standard 900 tested and approved• 100% synthetic media• Temperature rated up to 175°F
CI Supraloft® Panel Filters are engineered with superior performance criteria in all facets of filtration including efficiency, resistance and dust holding capacity to address today’s challenging HVAC system requirements. As part of the most advanced and innovative line of HVAC filtration products, the CI Supraloft® Panel Filter combines an excellent initial and life cycle resistance with a high dust-holding capacity. This combination provides optimum filter performance—creating the energy and operating cost savings desired in the demanding HVAC market. The CI Supraloft® Panel Filter is backed by the outstanding customer service and on-time delivery that customers have come to expect from Columbus Industries.
CI Supraloft® Panel FiltersSL-1A, SL-2A, SL-3A, SL-3, SL-4, SL-5A, SL-5
SL-5A is the new PLEAT COMMANDER® Panel Filter which combines efficiency and holding capacity in a low initial resistance filter.
Filter Type MERVRated Face Velocity (FPM) Initial Airflow Resistance (in w.g.)
Med High Med HighSL-1A 6 300 500 0.19 0.40SL-2A 7 300 500 0.18 0.38SL-3A 8 300 500 0.18 0.36SL-3 8 300 500 0.22 0.45SL-4 8 300 500 0.25 0.52SL-5A 8 300 500 0.16 0.30SL-5 10 300 500 0.28 0.58
Filter Size Nominal
(W X H X D)
Filter Size Exact
(W X H X D)
Rated Airflow Capacity (CFM) Med High
10 X 20 11-1/4 X 21-1/2 420 700
12 X 12 13-1/4 X 13-1/2 300 50012 X 20 13-1/4 X 21-1/2 500 80012 X 24 13-1/4 X 25-1/2 600 100014 X 16 15-1/4 X 17-1/2 470 78014 X 20 15-1/4 X 21-1/2 580 97014 X 25 15-1/4 X 26-1/2 730 122015 X 20 16-1/4 X 21-1/2 630 104015 X 24 16-1/4 X 25-1/2 750 1250
16 X 16 17-1/4 X 17-1/2 530 89016 X 18 17-1/4 X 19-1/2 600 100016 X 20 17-1/4 X 21-1/2 670 111016 X 22 17-1/4 X 23-1/2 730 122016 X 24 17-1/4 X 25-1/2 800 133016 X 25 17-1/4 X 26-1/2 830 139018 X 20 19-1/4 X 21-1/2 750 125018 X 24 19-1/4 X 25-1/2 900 150018 X 25 19-1/4 X 26-1/2 940 156020 X 20 21-1/4 X 21-1/2 830 1390
20 X 22 21-1/4 X 23-1/2 920 1530
20 X 24 21-1/4 X 25-1/2 1000 167020 X 25 21-1/4 X 26-1/2 1040 174022 X 24 23-1/4 X 25-1/2 1100 183022 X 25 23-1/4 X 26-1/2 1150 191024 X 24 25-1/4 X 25-1/2 1200 200025 X 25 26-1/4 X 26-1/2 1300 2170
f:user:paintlab:data:air:New-Panel Filter Charts-1.xls
SL2A SL3A SL3 SL4 SL5 SL5A0.35 0.20 0.60 1.10 2.60 3.90 3.600.47 1.00 5.90 5.30 8.10 6.90 8.100.62 2.60 17.10 12.80 18.20 12.60 16.200.85 4.40 29.70 27.80 35.70 26.40 26.201.15 10.40 40.10 41.60 48.10 39.30 38.601.45 19.50 47.10 47.60 55.30 48.50 45.301.90 32.70 54.00 53.60 61.90 58.30 51.902.60 52.40 61.50 59.80 68.00 71.20 58.303.50 59.90 67.10 64.50 71.80 80.90 64.204.75 62.70 71.20 70.50 74.50 86.30 68.306.25 63.70 72.80 75.50 75.10 90.00 72.608.50 63.60 74.00 81.60 75.50 93.10 76.00
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.35 0.47 0.62 0.85 1.15 1.45 1.90 2.60 3.50 4.75 6.25 8.50
SL2A
SL3A
SL3
SL4
SL5
SL5A
Par0cal Size Re
moval Efficien
cy (%
)
Par0cal Size (um)
Composite Minimum Efficiency Curve
f:user:paintlab:data:air:New-Panel Filter Charts-1.xls
ResistanceVelocity (cfm) Δ P (in w.g.)
SL2A SL3A SL-3 SL4 SL5 SL5A0 0.000 0.000 0.000 0.000 0.000 0.000
492 0.045 0.063 0.067 0.100 0.080 0.043984 0.140 0.159 0.173 0.210 0.222 0.1171968 0.375 0.437 0.480 0.544 0.626 0.3042460 0.500 0.613 0.653 0.780 0.874 0.427
0.000
0.100
0.200
0.300
0.400
0.500
0.600
0.700
0.800
0.900
0 492 984 1968 2460
Filte
r Res
ista
nce
(in w
.g.)
Air Flow Rate (cfm)
SL2A
SL3A
SL-3
SL4
SL5
SL5A
Resistance Curve
Panel Filters can provide DOUBLE THE LIFE guarantee over a traditional pleated air filter.