CONTENTS
2
Introduction
Technical Information
13mm Module WidthQA Mini Rail Mounted MCB’sQA Mini Rail Mounted Switch Disconnectors and Earth LeakagesQA DIN Rail Mounted MCB’sQA DIN Rail Mounted Switch Disconnectors and Earth LeakagesQF Dual Mounted MCB’sQF Dual Mounted Switch Disconnectors and Earth LeakagesQF DIN Rail Mounted MCB’sQF DIN Rail Mounted Switch Disconnectors and Earth LeakagesQL Dual Mounted MCB’sQY Dual Mounted MCB’s (DC)
18mm Module WidthQF DIN Mounted MCB’s
19,5mm Module WidthQF Dual Mounted MCB’s
Accessories
Mounting
Wiring and Installation
Tripping Characteristics
Auxiliary ProductsElectronic Time SwitchesGapped Surge ArrestorsLatching Unit and Controller
Mounting and InstallationHandle Lock
3
4
6789
101112131415
16
17
18
19
20
21
25262728
2930
October 2000
INTRODUCTION
3
1. APPLICATION
Note that the IEC60898 products are not for use in the sub-Saharan Africa market.
The QA and QF range of miniature circuit breakers are for use against overloads and short circuits in residential andcommercial electrical installations.
The standard products are for use in 240V AC systems or 125V DC systems. The QA and QF earth leakage units arefor protection against fire and shock hazards in residential and commercial installations, and have a number of newfeatures.
The Q range is complemented by a number of auxiliary products for energy management, switching of loads, andprotection against surges.
2. PRINCIPLE OF OPERATION
2.1. Time Delay OperationAt an overcurrent flow, the magnetic force produced bythe coil overcomes the core spring, the core closes to thepole piece, attracts the armature, and actuates the tripbar. The delay is obtained by the viscosity of the oil.
2.2. Instantaneous OperationIf the overcurrent is excessive, the armature is instantlyattracted, without the influence of the moving core.
MAGNETIC-MAGNETIC CIRCUIT BREAKER
3. CONSTRUCTION
3.1. Operating Handle -ON / TRIP / OFF operation. Resetting after tripping isperformed by returning the handle to the “OFF” position andthen “ON” again.
Trip Free Operation - Even if the handle is held in the “ON”position, the breaker will trip if an overcurrent flows.
Positive “ON” and Positive “OFF” mechanism - Shouldthe contacts weld in the closed position due to an abnormalcondition, the tripping mechanism will trip but the handle willremain in the “ON” position indicating that the circuit is stillclosed. Under these conditions, the handle cannot bemoved to the “OFF” position.
3.2. Arc Extinguishing Device - Comprises a set ofspecially shaped steel grids isolated from each other. Amagnetic field is induced in the grids by the current flow anddraws the arc into the grids so that it is lengthened, cooledand split into a series of smaller arcs which are more easilyextinguished.
MINIATURE CIRCUIT BREAKER (MCB)
Normal Operation
Movement OperatesTripping Mechanism
ArmatureFrame
Line
Tube
Contacts
Trip Latch
CoilSpring
Core
Flexible LoadPole
Oil
Load
ARC EXTINCTION
Magnetic Flux
Arc
GridMagnetic Force
Line Terminal
Fixed Contact
Handle
MechanismAssembly
CoilMagneticFrame
Load Terminal
Contact Tips
Arc RunnerLine Side
Arc RunnerLoad Side
Arc GridsArmature
Clip-in Spring
Moving Contacts
TECHNICAL INFORMATION
4
4.2 Earth Leakage Units
• 3 Year warranty.• Current ratings up to 63A.• Guaranteed operation for voltages down to 50V AC.• Immune to pulsating DC.• Detects and trips if the neutral is not present.• Detects and trips if the neutral potential rises above 50V over earth potential.• Detects and trips if line and neutral are reversed.• Detects and trips if the line to neutral voltage exceeds a predetermined value (special types only).• Detects if the earth potential is not present.• Short time delay to avoid nuisance tripping.• One device covers all nominal voltages from 100 - 240V AC.• Operates normally even if reverse fed.• Insulation resistance testing can be done with the handle in either the ON or OFF position. When the
handle is in the ON position, the functional earth wire should be disconnected. The test voltage appliedwith the megger must not exceed 500V.
• Indication for ON - OFF - overload trip - earth leakage trip.• Although a functional earth connection is used, there is no current flow to earth during normal operation.• Current limiting on overload type.
4. FEATURES
4.1. Circuit breakers and switch disconnectors
• Handle trips to mid position, on circuit breaker and earth leakage units to indicate that the unit has trippedfor an electrical fault and has not been switched off manually.
• Convenient rail mounting for mini-rail, USA rail, DIN rail and surface mounting.• Circuit breakers can carry 100% of rated current and always trip within pre-determined percentage of rated current irrespective of ambient temperature conditions.• The operation is not dependent on thermal action to activate the tripping mechanism, therefore the
predetermined trip current is not changed by a variation in temperature. The tripping characteristic ismainly determined by the number of turns of the solenoid coil.
• No thermal de-rating of current necessary up to a maximum of 60°C ambient.• Non-standard current ratings are available - even fractions of ampere rating.• A wide variety of tripping characteristics are available to suit particular needs and giving reliable protection.• No nuisance tripping caused by high ambient temperatures.• Immediate reset after fault has been cleared.• No ageing or deterioration of sensing mechanism which is hermetically sealed.• 10 Year warranty.• Current ratings up to 63A.• Compact size, 13mm, 18mm and 19,5mm module widths.• Single phase loading does not affect the tripping characteristic of a multipole circuit breaker.• Circuit breakers have been tested and conform to the requirements to be used as disconnectors.• Magnetic-magnetic principle, with internal and external linkage to a common trip of multipole units, to ensure all poles trip simultaneously.• Easy to connect box terminals (25mm2 cable maximum), to a torque of 2,5Nm.
5. TECHNICAL DATA
5.1. All Q Range circuit breakers, switch disconnectors and earth leakage units have been fully tested in accordance withnational and international standards.
5.2. The Q Range of circuit breakers are current limiting - When an overcurrent causes the breaker to trip an arc is drawnand is quickly extinguished. A magnetic field is introduced in the grids by the current flow and draws the arc into the gridsso that it is lengthened, cooled and split into a series of smaller arcs which are more easily extinguished.
TECHNICAL INFORMATION
5
5.3. Overcurrent Trip Curve Selection
6. Circuit Breakers and Switch Disconnectors
6.1 Handle Colour Circuit Breakers - White Switch Disconnectors - Green Single pole and neutral - White / Green
6.2. Interrupting Capacity Ratings (kA)
Note:SABS 156 tests are carried out at 110% of nominalvoltage and power factor 0,45 - 0,5.
6.3. Rated Service Life (Operations) AC only
CURVE No.
MCB RATEDCURRENT
(AMP)
No. OF OPERATING CYCLES(Cycle = ON / OFF
6 times per minute)
TIME DELAYINSTANTANEOUS
(Short circuit)NON TRIPPING
CURRENTTRIPPINGCURRENT
123BCD
KM
QA(13) up to 50QF(13) up to 25
QF(18) / QF(19) up to 63A
Mechanical4 000
Electrical6 000
Total10 000
LongMedium
ShortShort
MediumLong
Medium
1.05 x In1.05 x In1.05 x In1.13 x In1.13 x In1.13 x In1.00 x In
1.30 x In1.30 x In1.30 x In1.45 x In1.45 x In1.45 x In1.25 x In
HighMediumLowLowMediumHighMedium
10 - 15 x In5 - 10 x In3 - 5 x In3 - 5 x In
5 - 10 x In10 - 15 x In6 - 12 x In
Note:The tripping and the non-tripping current are not affected by the ambient temperature.In = Rated current of the MCB.
.4. As per SABS 156, MCB’s have to comply with theoverload test which is 50 operations at 6 times ratedcurrent.
6.5. Reverse Connection - MCB ’s and switchdisconnectors have been tested for, and comply with therequirements to be reverse connected.
6.6. Frequency - MCB’s are suitable for 50/60Hzsystems.
6.7. Switch disconnectors - All Q Range small frameswitch disconnectors are non-automatic circuit breakers,are fully rated and carry the associated circuit breakerfault current for 10ms. Protection must be provided by adevice upstream.
7. RCCB and RCBO (Earth Leakage Units)
7.1. Specifications IEC 61008 / 61009 and SABS 767
7.2. Supply Voltages 220 / 240V AC single phase 220 / 240V AC single phase and neutral 380 / 415V AC three phase
7.3. Clearance and Creepage Distances To IEC, SABS and UL.
7.4. Frequency 50/60Hz
7.5. Earth Leakage Unit Type NumberSuffix 15A = Single phase RCBO (white handle) -Single phase with two fully rated current paths, onefitted with overload.Suffix 15C = Single phase RCCB (green handle) -Single phase with two fully rated current paths, nooverload protection, which must be provided by adevice upstream.
7.6. Sensitivity (mA) 30mA
7.7. Vibration Resistance IEC 60571-1977.
QA 13mm MCB’s
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curves (3 Standard)
Wiring Diagrams
QA-1(13)
-1
0,1
QA-2(13)
-2
0,2
QA-3(13)
-3
0,3
Magnetic-Magnetic
QA-N-2(13)
-1Pole + Neutral
0,2
QA-N-4(13)
-3Pole + Neutral
0,4
1* - 2* - 5 - 10 - 15 - 20 - 25 - 30 - 35 - 40 - 45 - 50 - 63*
Mini RailDIN RailSurface ClipUSA Rail
2 Breaking capacityto
SABS156 andIEC60947-2
2, 3(3), 2DC, 3DC(3) 2, 3(3),2DC, 3DC(3)
2, 3(3) 2, 3(3)
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489-A
230AC
2,5
400AC
2,5
400AC
2,5
230AC
2,5
400AC
2,5
240AC3
415AC3
415AC3
240AC3
415AC3
Miniature Circuit Breaker277AC
2
480AC
1
480AC
1
277AC
480AC
125DC
2
250DC
2 2
125DC
125DC
QA-(13) MCB’s and Switch Disconnectors
13
13
26 39 527466
869315
15
519
16
57
6
*Subject to availability
HWD
1P861366
2P862666
3P863966
4P865266
2
1x
42 6
5x x x
31x
2 N
N1x x x
42 6
531 N
N2 4
31x x
QA 13mm SWITCH DISCONNECTORS, RCCB / RCBO’S
QA-S-1(13)
-1
0,1
QA-S-2(13)
-2
0,2
Manual
QA-S-3(13)
-3
0,3
QA-S-4(13)
-4
0,2
QA15A*10 - 15 - 20 - 30
40 - 50 - 6030
1Pole + NeutralEarth Leakage
0,26Magnetic-
Magnetic andEarth Leakage
QA15C
301Pole + NeutralEarth Leakage
0,24Manual
andEarth Leakage
63 63
230AC
2,5
230AC
2,5
240AC
3
240AC
3
230AC
2,5
400AC
2,5
400AC
2,5
400AC
2,5
QA15A / QA15C Earth Leakages
L
L
N
N
16
39
86
1517
,593 57
15
6675
255
2, 3, B, C---- -
*Subject to availability
7
HWD
E/L863966
Switch Disconnector
2 4
31
2
1
62 4
3 51
2 64 8
1 3 5 7
N2
1 N
V
1
N2
Nx
V
QA 13mm DIN MCB’s
QA-1(13)-D
-1
0,1
QA-2(13)-D
-2
0,2
QA-3(13)-D
-3
0,3
Magnetic-Magnetic
QA-N-2(13)-D
-1Pole + Neutral
0,2
QA-N-4(13)-D
-3Pole + Neutral
0,4
1* - 2* - 6 - 10 - 16 - 20 - 25 - 32 - 40 - 45 - 50 - 63*
Mini RailDIN RailSurface ClipUSA Rail
2, 3(3), B, C, 3DC(3) 2, 3(3), B, C 2, 3(3), B, C2, 3(3), B, C,3DC(3)
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489-A
230AC
2,5
400AC
2,5
400AC
2,5
230AC
2,5
400AC
2,5
240AC3
3*
415AC3
3*
415AC3
3*
240AC3
3*
415AC3
3*
277AC
2
480AC
1
480AC
1
277AC
480AC
125DC
2
250DC
2
125DC
125DC
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curves (3 Standard)
Wiring Diagrams
7365
869315
15
519
16
QA-(13)-D MCB’s and Switch Disconnectors
45
13
13
26 39 52
*Subject to availability
8
2 Breaking capacityto
SABS156 andIEC60947-2
HWD
1P861365
2P862665
3P863965
4P865265
Miniature Circuit Breaker
42 6
5x x x
31x
2 N
N1x x x
42 6
531 N
N2
1x
2 4
31x x
QA 13mm DIN SWITCH DISCONNECTORS, RCCB / RCBO’S
QA-S-1(13)-D
-1
0,1
QA-S-2(13)-D
-2
0,2
Manual
QA-S-3(13)-D
-3
0,3
QA-S-4(13)-D
-4
0,2
QA15A-D*10 - 16 - 20 - 32
40 - 50 - 6330
1Pole + NeutralEarth Leakage
0,26Magnetic-
Magnetic andEarth Leakage
QA15C-D
301Pole + NeutralEarth Leakage
0,24Manual
andEarth Leakage
-
63
Switch Disconnector
63
230AC
2,5
230AC
2,5
240AC
3
240AC
3
240AC
3
415AC
3
415AC
3
415AC
3
QA15A-D / QA15C-D Earth Leakages
L
L
N
N
36
8645
1517
.515
93
7565
165
25
*Subject to availability
9
2, 3(3), B, C
HWD
E/L863665
----
2 4
31
62 4
3 51
2 64 8
1 3 5 7
2
1
N2
1 N
V
1
N2
Nx
V
QF 13mm MCB’s
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curves (3 Standard)
Wiring Diagrams
QF-1(13)
-1
0,1
QF-2(13)
-2
0,2
QF-3(13)
-3
0,3
Magnetic-Magnetic
QF-N-2(13)
-1Pole + Neutral
0,2
QF-N-4(13)
-3Pole + Neutral
0,4
1* - 2* - 5 - 10 - 15 - 20 - 25
Miniature Circuit Breaker
Mini RailDIN RailSurface ClipUSA Rail
2(3), 3, 2DC(3) 2(3), 3, 2DC(3) 2(3), 3, 2DC(3)2(3), 3 2(3), 3
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489-A
230AC
5
400AC
5
400AC
5
230AC
5
400AC
5
240AC6
415AC6
415AC6
240AC6
415AC6
277AC
2
480AC
1
480AC
1
277AC
480AC
125DC
3
250DC
3
125DC
3
125DC
7466
869315
1517
.5
525 16
QF-(13) MCB’s and Switch Disconnectors
57
13
13
26 39 52
10
2 Breaking capacityto
SABS156 andIEC60947-2
*Subject to availability
HWD
1P861366
2P862666
3P863966
4P865266
2
1x
42 6
5x x x
31x
2 N
N1x x x
42 6
531 N
N2 4
31x x
QF 13mm SWITCH DISCONNECTORS, RCCB / RCBO’S
QF-S-1(13)
-1
0,1
QF-S-2(13)
-2
Switch Disconnector
0,2
Manual
QF-S-3(13)
-3
0,3
QF-S-4(13)
-4
0,2
QF15A*10 - 15 - 20 - 30
40 - 50 - 6030
1Pole + NeutralEarth Leakage
0,26Magnetic-
Magnetic andEarth Leakage
QF15C
301Pole + NeutralEarth Leakage
0,24Manual
andEarth Leakage
63 63
230AC
5
230AC
5
240AC
6
240AC
6
230AC
5
400AC
5
400AC
5
400AC
5
QF15A / QF15C Earth Leakage
L
L
N
N
16
39
86
1517
,593 57
15
6675
255
2(3), 3
*Subject to availability
11
HWD
E/L863966
---- -
2 4
31
2
1
62 4
3 51
2 64 8
1 3 5 7
N2
1 N
V
1
N2
Nx
V
QF 13mm DIN MCB’s
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curves (3 Standard)
Wiring Diagrams
QF-1(13)-D
-1
0,1
QF-2(13)-D
-2
0,2
QF-3(13)-D
-3
0,3
Magnetic-Magnetic
QF-N-2(13)-D
-1Pole + Neutral
0,2
QF-N-4(13)-D
-3Pole + Neutral
0,4
1* - 2* - 6 - 10 - 16 - 20 - 25
Mini RailDIN RailSurface ClipUSA Rail
2(3), 3, B, C(3),2DC(3)
2(3), 3, B, C(3),2DC(3)
2(3), 3, B, C(3) 2(3), 3, B, C(3),2DC(3)
2(3), 3, B, C(3),
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489-A
230AC
5
6
230AC
5
6
400AC
5
6*
400AC
5
6*
400AC
5
6*
240AC6
240AC6
415AC6
415AC6
415AC6
277AC
277AC
480AC
480AC
480AC
125DC
3
250DC
3
125DC
3
125DC
7365
869315
15
519 16
QF-(13)-D MCB’s and Switch Disconnectors
45
13
13
26 39 52
12
2 Breaking capacityto
SABS156 andIEC60947-2
*Subject to availability
Miniature Circuit Breaker
HWD
1P861365
2P862665
3P863965
4P865265
2
1x
42 6
5x x x
31x
2 N
N1x x x
42 6
531 N
N2 4
31x x
QF 13mm DIN SWITCH DISCONNECTORS, RCCB / RCBO’S
QF-S-1(13)-D
-1
0,1
QF-S-2(13)-D
-2
0,2
Manual
QF-S-3(13)-D
-3
0,3
QF-S-4(13)-D
-4
0,2
QF15A-D*10 - 16 - 20 - 32
40 - 50 - 6330
1Pole + NeutralEarth Leakage
0,26Magnetic-
Magnetic andEarth Leakage
QF15C-D
301Pole + NeutralEarth Leakage
0,24Manual
andEarth Leakage
63
Switch Disconnector
63
230AC
5
230AC
5
240AC
6
240AC
6
240AC
6
415AC
6
415AC
6
415AC
6
QF15A-D / QF15C-D Earth Leakages
L
L
N
N
36
8645
1517
.515
93
7565
165
25
2(3), 3
*Subject to availability
13
HWD
E/L863665
---- -
2 4
31
2
1
62 4
3 51
2 64 8
1 3 5 7
N2
1 N
V
1
N2
Nx
V
QL 13mm MCB’s
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curve (3 Standard)
Wiring Diagrams
QL-1(13)
-1
MCB120AC
10
0,1
Magnetic-Magnetic
KM(3)
QL-2(13)*
-2
MCB240AC
10
0,2
1 -2 - 5 - 1015 - 20 - 25
5 - 1015 - 20 - 25
Mini RailDIN RailSurface ClipUSA Rail
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489A
QL-(13) MCB’s
13 267466
20
45
935771.4
82.4
*Subject to availability
14
2 Breaking capacityto
SABS156 andIEC60947-2
HWD
1P861366
2P862666
2
1x
2 4
31x x
13
QY 13mm MCB’s (DC)
QY-N10-1(13)
-1
80DC
10
0,1
U2(3)
QY-N-N10-2(13)
-1Pole + Neutral
80DC
10
0,2
U2(3)
QY-IS-N10-1(13)*
-1
80DC
10
0,1
Magnetic-Magnetic
OP(3)
QY-N10-1(13)-D
-1
80DC
10
0,1
U2(3)
QY-N-N10-2(13)-D
-1Pole + Neutral
80DC
10
0,2
U2(3)
QY-IS-N10-1(13)-D*
-1
80DC
10
0,1
OP(3)
1 - 2 - 6 - 10 - 16 - 2025 - 32 - 40 - 50
6 - 10 - 16 - 20 25 - 32 - 40 - 50
1 - 2 - 6 - 10 - 16 - 20 25 - 32 - 40 - 50
1 - 2 - 6 - 10 - 16 - 20 25 - 32 - 40 - 50
6 - 10 - 16 - 20 25 - 32 - 40 - 50
1 - 2 - 6 - 10 - 16 - 20 25 - 32 - 40 - 50
7365
869315
15
519
16QY-(13)-D MCB’s
45
13
1313
267466
869315
1517
.5
525 16
QY-(13) MCB’s
57
13 26
*Subject to availability
15
HWD
HWD
1P861365
1P861366
2P862665
2P862666
Miniature Circuit Breaker
2
1x
2
1x
2
1x
2
1x x
2 N
N1x
2 N
N1
QF 18mm DIN MCB’s
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curves (3 Standard)
Wiring Diagrams
QF-1(18)-D
-1
0,1
QF-2(18)-D
-2
0,2
QF-3(18)-D
-3
0,3
Magnetic-Magnetic
QF-N-2(18)-D
-1Pole + Neutral
0,2
QF-N-4(18)-D
-3Pole + Neutral
0,4
1 - 2 - 6 - 10 - 16 - 20 - 25 - 32 - 40 - 50 - 63
Mini RailDIN RailSurface ClipUSA Rail
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489-A
230AC
5
230AC
5
400AC
5
400AC
5
400AC
5
240AC6
6*
240AC6
6*
415AC6
6*
415AC
6
6*
415AC
6
6*
277AC
277AC
480AC
480AC
480AC
125DC
3
250DC
3
125DC
3
125DC
36 54 72186860
71.4
7282.4
45
4419
5 18
QF-(18)-D MCB’s
86
16
2 Breaking capacityto
SABS156 andIEC60947-2
1, 2(3), 3, 2DCB, C
(3), D*1, 2(3), 3, 2DC
B, C(3), D*
1, 2(3), 3,B, C
(3), D*1, 2(3), 3, 2DC
B, C(3), D*
1, 2(3), 3,B, C
(3), D*
Miniature Circuit Breaker
HWD
1P861865
2P863665
3P865465
4P867265
2
1x
42 6
5x x x
31x
2 N
N1x x x
42 6
531 N
N2 4
31x x
*Subject to availability
QF 19,5mm MCB’s
Product TypeStandard Ampere Ratings (A)
Sensitivity (mA)Number of PolesEquipment TypeRated Voltage (V)
RatedInterrupting/WithstandCapacity(kA)
Mounting Options
Weight (kg)Mechanism
Tripping Curves (3 Standard)
Wiring Diagrams
QF-1(19)
-1
0,1
QF-2(19)
-2
0,2
QF-3(19)
-3
0,3
Magnetic-Magnetic
QF-N-2(19)
-1Pole + Neutral
0,2
QF-N-4(19)
-3Pole + Neutral
0,4
1 - 2 - 5 - 10 - 15 - 20 - 25 - 30 - 35 - 40 - 45 - 50 - 60
Mini RailDIN RailSurface ClipUSA Rail
IEC60947-2SABS156IEC60947-3SABS152IEC61008IEC61009SABS767UL1077IEC60934(2)
IEC60898UL489UL489-A
230AC
5
230AC
5
400AC
5
400AC
5
400AC
5
240AC
6
240AC
6
415AC
6
415AC
6
415AC
6
277AC
277AC
480AC
480AC
480AC
125DC
3
250DC
3
125DC
3
17
2 Breaking capacityto
SABS156 andIEC60947-2
1, 2(3), 3, 2DC(3) 1, 2(3), 3, 2DC(3) 1, 2(3), 3 1, 2(3), 3, 2DC(3) 1, 2(3), 3
74 19.5 7858.53966
1213
5 1625
5786
QF-(19) MCB’s
Miniature Circuit Breaker
HWD
1P861866
2P863666
3P865466
4P867266
2
1x
42 6
5x x x
31x
2 N
N1x x x
42 6
531 N
N2 4
31x x
ACCESSORIES
18
Accessory Type
QA-(13)
QA-S-(13)
QA15AQA15C
QA-(13)-D
QA-S-(13)-D
QA15A-DQA15C-D
QF-(13)
QF-S-(13)
QF15AQF15C
QF-(13)-D
QF-S-(13)-D
QF15A-DQF15C-D
QL-(13)
QY-(13)
QF-(18)-D
QF-(19)
Note:(1) Available for single pole units only, with different pitches.(2) Available for single, double and triple pole units only, with different pitches.(3) 13mm Modules.(4) Subject to availability.
Busbar singlephase 54 pole
(1) (3)
Busbar 3 phaseinsulated
(2)
Escutcheonblanks Handle lock
Shrouds(1 to 8 pole)
(3)
Surfacemounting clip
/ screws
SafetyBlanks
(4)
MOUNTING
19
To install:Insert the topof the unit intothe mini raillip. Push theyellow clip atthe base ofthe unit toengage intothe mini rail.
To remove:Use a screwdriverto pull the yellowclip down todisengage theunit.
Pull unit slightlydown to withdrawunit from the minirail.
Mini Rail Mounting
DIN Rail Mounting
ResidualCurrentDevice(Earth Leakage)
MiniatureCircuitBreaker
ResidualCurrentDevice(Earth Leakage)
MiniatureCircuitBreaker
To install:When the unit is inthe correct position,push yellow clip atthe base of the unitto engage the unit onthe DIN rail.
To remove:Use screwdriver topull yellow clipdown to disengagethe unit.
WIRING AND INSTALLATION
20
1. Supply on the top, load on the bottom and RCCB/RCBO mounted on the right.
Supply
Supply
Supply
Supply
Supply
Load
Load
Load
Load
Load
2. Supply on the top, load on the bottom and RCCB/RCBO mounted on the left.
3. Supply on the bottom, load on the bottom andRCCB/RCBO mounted on the right.
4. Supp ly on the top, load on the top and RCCB/RCBO mounted on the right.
5. Supply on the bottom, load on the top and RCCB/RCBO mounted on the right.
TRIPPING CHARACTERISTICS
21
Sec
onds
Min
utes
(%) Rated Current
1000
100
10
1
10
1
0.1
0.01
0.001
100
105
130
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
Trip
ping
Tim
e
Operating CharacteristicsAmbient Temperature 30°C
Curve 2
Sec
onds
Min
utes
(%) Rated Current
1000
100
10
1
10
1
0.1
0.01
0.00110
010
513
015
0
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
Trip
ping
Tim
e
Operating CharacteristicsAmbient Temperature 30°C
Curve 3
Operating CharacteristicsAmbient Temperature 30°C
Curve 1
Sec
onds
Min
utes
(%) Rated Current
1000
100
10
1
10
1
0.1
0.01
0.001
100
105
130
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
Trip
ping
Tim
e
Operating CharacteristicsAmbient Temperature 30°C
Curve B
Operating CharacteristicsAmbient Temperature 30°C
Curve C
Sec
onds
Sec
onds
Min
utes
Min
utes
(%) Rated Current (%) Rated Current
1000 1000
100 100
10 10
1 1
10 10
1 1
0.1 0.1
0.01 0.01
0.001 0.001
100
100
113
113
145
145
200
200
300
300
400
400
500
500
1000
1000
1500
1500
2000
2000
2500
2500
3000
3000
4000
4000
5000
5000
Trip
ping
Tim
e
Trip
ping
Tim
e
TRIPPING CHARACTERISTICS
22
Operating CharacteristicsAmbient Temperature 30°C
Curve D
Sec
onds
Min
utes
(%) Rated Current
1000
100
10
1
10
1
0.1
0.01
0.001
100
113
145
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
Trip
ping
Tim
e
23
TRIPPING CHARACTERISTICS
1000
100
10
1
10
1
0.1
0.01
0.001
100
125
150
200
300
400
500
1000
1500
2000
2500
3000
4000
5000
100
10
5
1
0.5
0.1
0.05
0.01
0.005
0.001
50 100
150
200
300
400
500
1000
Operating CharacteristicsAmbient Temperature 40ºC
Curve KM
Operating CharacteristicsRCCB/RCBO
Ambient Temperature-10 to +60ºC
Sec
onds
Sec
onds
Min
utes
(%) Rated Current (%) Rated Sensitivity
Trip
ping
Tim
e
Trip
ping
Tim
e
500
400
300250
200175150125
100
75
50
40
3025
2017.5
1512.5
10-10-20 0 10 20 30 40 50 60 70 80
Trip Time -Ambient Temperature
Compensation forMagnetic-Magnetic
Circuit Breakers
Ambient Temperature
Ambient Temperature30ºC
(%)
Ope
ratio
n T
ime
TRIPPING CHARACTERISTICS
24
Sec
onds
Sec
onds
Min
utes
Min
utes
(%) Rated Current (%) Rated Current
Trip
ping
Tim
e
Trip
ping
Tim
e
Operating CharacteristicsAmbient Temperature 30°C
Curve OP(DC)
(4% Ripple Factor)
0.01
0.1
1
10
1
10
100
1000
150
130
130
100
105
105
200
300
255
400
500
1000
1500
2000
2500
3000
4000
5000
Operating CharacteristicsAmbient Temperature 30°C
Curve U2(DC)
(4% Ripple Factor)
0.01
0.1
1
10
1
10
100
1000
150
100
200
300
255
400
500
1000
1500
2000
2500
3000
4000
5000
(%) Rated Current(%) Rated Current
Trip
ping
Tim
e
Trip
ping
Tim
e
Min
utes
Min
utes
Seco
nds
Seco
nds
0.010.01
10001000Operating Characteristics
Ambient Temperature 30°C
Curve 3-DC
(4% Ripple Factor)
Operating CharacteristicsAmbient Temperature 30°C
Curve 2-DC
(4% Ripple Factor)
0.10.1
11
1010
11
1010
100100
145
150
113
145
100
100
113
200
200
300
300
255
400
400
500
500
1000
1000
1500
1500
2000
2000
2500
2500
3000
3000
4000
4000
5000
5000
AUXILIARY PRODUCTS
25
Latching Unit and Controller
• Compact size
• Service Life: Minimum 10 000 operations at full load (0,75pf)
• Degree of protection: IP41
• Operating range: -20°C to +60°C
• High current ratings
• Robust (few moving parts)
• Easy to install and connect
• Indication shows when the main contacts are in the closed position
FEATURES
Electronic Time Switches
• Compact size
• Simple setting of Times and Programs
• Units suitable for use in Residential, Commercial and Industrial applications
• Non-reserve units have capacitors on the PCB’s to ride through any voltage dips or short interruptions
• Service life: 25 000 operations at full load
• Degree of protection: IP41
• Protective lift-up cover
• Display on main screen serves as a real time clock
• All time switches have a by-pass / override switch
• Type of contact: Single pole normally open on load side (Note: Not potential free contacts)
• Low power consumption
• Temperature range: -20°C to +55°C
• 30 Minute time interval settings
Gapped Surge Arrestors
• Compact size
• Convenient mounting
• Outdoor type GSAW resistant to environmental conditions
• Gapped type with non-linear silicon carbide resistor
• No leakage current and potential thermal runaway problems
AUXILIARY PRODUCTS: ELECTRONIC TIME SWITCHES
QAT-DM30 Minutes
-
Mini + DIN Rail39mm x 57mm
220/240V rms 50Hz21 Amps RESISTIVE at 230V AC10 Amps INDUCTIVE at 230V AC
DIN Rail36mm x 45mm
QAT-R-DM30 Minutes12 Hours
QAT-D30 Minutes
-
QAT-R-D30 Minutes12 Hours
Product TypeDaily setting intervalsPower failure reserveRated VoltageRated Current(Do not exceed)MountingEscutcheon (W x H)Installation Wiring Diagram
SUPPLY
(230V)LOAD
TIME SWITCH
MAX LOAD: 21A RESISTIVE 10A INDUCTIVE
N
L
L
L230V ONLY
QAT-R-DM
LOAD
L
L L N
N
NE
UT
RA
L B
AR
SUPPLY
(230V)LOAD
TIME SWITCH
MAX LOAD: 21A RESISTIVE 10A INDUCTIVE
N
L
L
L230V ONLY
QAT-R-D
LOAD
L N
NE
UT
RA
L B
AR
Alternative “N”connection
57.0
82.0
66.0
45.0
QAT-DM & QAT-R-DM Escutcheon
QAT-D & QAT-R-D Escutcheon
Electronic Time Switches - Mini and DIN Rail mounted39.0 - Mini Rail
36.0 -Din
SUPPLY
(230V)LOAD
TIME SWITCH
MAX LOAD: 21A RESISTIVE 10A INDUCTIVE
N
L
L
L230V ONLY
QAT-R-DM
26
HWD
Mini823966
DIN823666
NOTE:4 - Terminal device can be wired as a3 - terminal device
4 - Terminal wiring
N
3 - Terminal wiring
540*
Surface2,5mm2
Product Type
Nominal discharge current (8/20us) kA
MountingMaximum cable sizeRated VoltageNumber of PolesMin. power frequency sparkover voltageMax. power frequency sparkover voltageMax. front wave impulse sparkover voltageInstallation Wiring Diagrams
QA
L-10
QA
L-25
QA
L-40
GS
AW
-10
GS
AW
-25
GS
AW
-40
GS
AE
-25
GS
AE
-40
GS
AE
-65
1,510
2,525
Mini and DIN Rail25mm2
540*
1,510
2,525
Bracket2,5mm2
Single pole800V (50Hz) rms
1 200V (50Hz) rms2 500V (Peak)
540*
2,525
565*
Indoor Boards Outdoor Use Equipment
QAL GSAE
Dia. 4 41 17
12
58 57
2
35.5
19.6
Dia. 43.3
41.8
GSAW
INDOORSURGE
ARRESTER
26.5
INDOORSURGE
ARRESTER
11.4
66
16 21.7
8269 57
Peak value high impulse current (4/10us) kA
AUXILIARY PRODUCTS: GAPPED SURGE ARRESTORS
27
*Excluding bracket
*Subject to availability
L L
L N
HWD
HDia.
HWD
454117
41*46
822666
Single pole800V (50Hz) rms1 200V (50Hz)2 500V (Peak)
Single pole800V (50Hz) rms1 000V (50Hz)2 500V (Peak)
240V AC 50/60Hz (280V rms maximum continuous) 440V AC
QLUC-L-M230V rms 50Hz
160 - 253V 50Hz100A RESISTIVE
1 Operating Cycle per Minute230V rms 50Hz
1mAMini Rail
39mm x 57mm
Product TypeSupply VoltageOperating RangeMaximum LoadMaximum Operating FrequencyTrigger signal
MountingEscutcheon (W x H)
Typical Installation Wiring Diagrams
AUXILIARY PRODUCTS: LATCHING UNIT AND CONTROLLER
28
LOAD
L
N
Latching UnitandController
QLUC
LED
Trigger Signal
ControlSwitch
Nominal Voltage Rated Current
Latching Unit and Controller
L1
L2
L3
N
Latching UnitandController(3 off QLUC units)
QLUC QLUC QLUC
LED LED LED
Individual load circuits
Trigger signals
Relay switch(LA/230V)
Control switch(Daylight or
Time Switch)
50Hz 400V
Multi-circuit configuration with common trigger
HWD
863966
7.8
67.2
2039
57 86
1666
AUXILIARY PRODUCTS: MOUNTING AND INSTALLATION
29
Mini Rail
Slide yellow clip up anddown as indicated
to install and removethe unit.
DIN Rail
HANDLE LOCK
FEATURES• Moulded in self extinguishing yellow thermoplastic.• Can accommodate up to three padlocks with a 3mm
shank diameter.• Can be used on single and multipole units.• Can be fitted to switches as well as MCB’s.• Locking mechanism does not impede the internal
tripping action of the breaker of RCD.
ApplicationThe handle lock can be used to lock the Q Range circuit breakers and earth leakage units (RCD’s) in either the “ON” or“OFF” position.
Installation
1. Open the locking lever by hinging it outwards.2. Push the lever towards the main body so that thewires protrude.
To lock the breaker in the “OFF” position3. Squeeze the locking wires between the thumb andforefinger and clip wires into holes of handle guard.4. Move the main body towards the breaker until it fitssnugly in the recess above the handle. (Handle is in“OFF” position).5. Hinge the locking lever back into place.6. Insert up to three padlocks with a 3mm shankdiameter.
To lock the breaker in the “ON” position3. Rotate handle lock 180°.4. Squeeze the locking wires between the thumb andforefinger and clip wires into holes of handle guard.5. Move the main body towards the breaker until it fitssnugly in the recess below the handle. (Handle is in“ON” position).6. Hinge the locking lever back into place.7. Insert up to three padlocks with a 3mm shankdiameter.
Locking wire
Main body
Locking lever
30
Fit locking wirethrough handle guardholes
Locking breaker in the “OFF” position
Locking breaker in the “ON” position