home | idaho transportation department · 2018. 5. 30. · panel amp rating: 225a with 200acb...
Post on 28-Aug-2020
3 Views
Preview:
TRANSCRIPT
ABBREVIATIONS
GENERAL STRUCTURAL NOTES (G.S.N.)
SPECIAL INSPECTION REQUIREMENTS
270
Nor
th 2
7th
St.
Boi
se, I
daho
. 837
02
(2
08) 3
38-1
212
fax
(208
) 338
-001
1
AHJ ENGINEERS, PCSTRUCTURAL CONSULTANTS
PROJECT #
5418 N. EAGLE RD. #140BOISE, IDAHO 83713
(208) 323-0199
18055.00
1 2 3 4 5 6 7
A
B
C
D
PLAN NOTES
GRID
GRID
270
Nor
th 2
7th
St.
Boi
se, I
daho
. 837
02
(2
08) 3
38-1
212
fax
(208
) 338
-001
1
AHJ ENGINEERS, PCSTRUCTURAL CONSULTANTS
PROJECT #
5418 N. EAGLE RD. #140BOISE, IDAHO 83713
(208) 323-0199
18055.00
PANEL LS1 (EXISTING) VOLTAGE: 240 / 120 V DIMENSION: PER NEC LOCATION:
PANEL AMP RATING: 225A WITH 200A CB MOUNTING: NEMA ENCLOSURE: 1
WIRES: 3 PHASE: 1 FEED: TYPE: SQUARE D NQOD
LOAD DESCRIPTION PH LOAD BKR CKT LOAD CKT BKR LOAD PH LOAD DESCRIPTION
WATT AMPS NO A B NO AMPS WATT
LTS - EXTERIOR A 324 20 1 1500 2 20 1176 A GARAGE DOOR OPERATOR
LTS - INTERIOR B 420 20 3 780 4 20 360 B REC - INTERIOR
LTS - NORTH ENTRANCE, CENTER DRIVE A 264 20 5 624 6 20 360 A REC - EXTERIOR
LTS - SOUTH ENTRANCE, TANKS B 264 20 7 744 8 20 480 B IRRIGATION CONTROLLER
SPARE A 20 9 0 10 20 A SPARE
SPARE B 20 11 0 12 20 B SPARE
SPARE A 20 13 0 14 20 A SPARE
SPARE B 20 15 0 16 20 B SPARE
SPARE A 20 17 0 18 A BUSSED SPACE
BUSSED SPACE B 19 0 20 B BUSSED SPACE
BUSSED SPACE A 21 0 22 A BUSSED SPACE
BUSSED SPACE B 23 0 24 B BUSSED SPACE
BUSSED SPACE A 25 0 26 A BUSSED SPACE
SAND SHED B 360 70 27 6360 28 100 6000 B MAG TANK PUMP
A 518 ** 29 6518 30 ** 6000 A 2 POLE
FEEDER BREAKER TOTAL LOAD PER PHASE-WATTS 8642 7884 FEED FROM: METER
RATING: 200A TOTAL LOAD PER PHASE-AMPS 73 66 PANEL ISC RATING 10,000
WIRE SIZE: 3-250 KCMIL AL & 1#4 AL GND CONDUIT SIZE: 2 1/2" C
PANEL SS (NEW) VOLTAGE: 240 / 120 V DIMENSION: PER NEC LOCATION: SAND SHED
PANEL AMP RATING: 100A WITH 70A CB MOUNTING: SURFACE NEMA ENCLOSURE: 3R
WIRES: 3 PHASE: 1 FEED: BOTTOM TYPE: SQUARE D NQOD
LOAD DESCRIPTION PH LOAD BKR CKT LOAD CKT BKR LOAD PH LOAD DESCRIPTION
WATT AMPS NO A B NO AMPS WATT
LIGHTS A 208 20 1 518 2 20 310 A LIGHTS
RECEPTACLES B 360 20 3 360 4 20 B SPARE
BUSSED SPACE (PFB) A 5 0 6 20 A SPARE
BUSSED SPACE (PFB) B 7 0 8 20 B SPARE
BUSSED SPACE (PFB) A 9 0 10 20 A SPARE
BUSSED SPACE (PFB) B 11 0 12 20 B SPARE
FEEDER BREAKER TOTAL LOAD PER PHASE-WATTS 518 360 FEED FROM: PANEL LSI CKTS 27,29
RATING: 70A TOTAL LOAD PER PHASE-AMPS 5 3 PANEL ISC RATING 10,000 AVAILABLE ISC 4.8kA
WIRE SIZE: 3#3 AL & 1#6 AL GND CONDUIT SIZE: 1 1/4" C