instrument list-50t eaf rev03
Post on 14-Dec-2014
209 Views
Preview:
TRANSCRIPT
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 1 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
PNEUMATIC SYSTEM OF 50T EAF - DRG.NO.- 5.4.2.02039 REV 03
1 PI501
A N Instruments / equivalent 4 Kg/cm2
Air Inlet line
6SSPG AD / equivalent35° C
2 PI502
A N Instruments / equivalent 4 Kg/cm2
Air Inlet line 6SSPG AD / equivalent
35° C
COOLING WATER SYSTEM OF 50T EAF - DRG.NO.- 5.4.2.01986 REV 04
3 PI101
A N Instruments / equivalent 4 Kg/cm2
6SSPG AD / equivalent35° C
4 PI103
A N Instruments / equivalent 4 Kg/cm2
6SSPG AD / equivalent
35° C
5 PI102
A N Instruments / equivalent 4 Kg/cm2
6SSPG AD / equivalent
35° C
5A PI104
A N Instruments / equivalent 4 Kg/cm2
6SSPG AD / equivalent
35° C
5B PI105
A N Instruments / equivalent 4 Kg/cm2
6SSPG AD / equivalent
35° C
6 PSL104 Pressure Switch
INDFOSS / equivalent 4 Kg/cm2
PLC 35° C
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
Pressure Measurementfor incoming air before
PRV
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2 3 way gauge cocks etc
Pressure Measurementfor incoming air after
PRV
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2 3 way gauge cocks etc
Pressure Measurementfor incoming water of
manifold 1
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2Cooling Water Incoming line
3 way gauge cocks etc
Pressure Measurementfor incoming water of
manifold 5
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2Soft Water
Incoming line
3 way gauge cocks etc
Pressure Measurementfor incoming water of
manifold 3
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2Cooling Water Incoming line
3 way gauge cocks etc
Pressure Measurementfor incoming water of
manifold 7
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2Cooling Water Incoming line
3 way gauge cocks etc
Pressure Measurementfor incoming water of
manifold 8
Pr. Gauge, 6" dial, ± 1% accuracy
0-10 kg/cm2Cooling Water Incoming line
3 way gauge cocks etc
Pressure Measurementfor incoming water of
manifold 1
0.35-7 kg/cm2Cooling Water Incoming lineB4 64 S7 Kg/cm2 / equivalent
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 2 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
7 PSL106 Pressure Switch
INDFOSS / equivalent 4 Kg/cm2
PLC 35° C
7A PSL106A Pressure Switch
INDFOSS / equivalent 4 Kg/cm2
PLC 35° C
8 PSL105 Pressure Switch
INDFOSS / equivalent 4 Kg/cm2
PLC 35° C
9 TI107
A N Instruments / equivalent 3 Kg/cm2
0-100° C 6RMST AV/equivalent
50° C
10 TI208
A N Instruments / equivalent 3 Kg/cm2
0-100° C 6RMST AV/equivalent
50° C
11 TI209
A N Instruments / equivalent 3 Kg/cm2
0-100° C 6RMST AV/equivalent
50° C
11A TI110
A N Instruments / equivalent 3 Kg/cm2
0-100° C 6RMST AV/equivalent
50° C
11B TI111
A N Instruments / equivalent 3 Kg/cm2
0-100° C 6RMST AV/equivalent
50° C
12 FS161 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC
SH0500 / equivalent50° C
117m3/Hr
13 FS162 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
Pressure measurementfor incoming water of
manifold 5
0.35-7 kg/cm2Cooling Water Incoming lineB4 64 S7 Kg/cm2 / equivalent
Pressure measurementfor incoming water of
manifold 7
0.35-7 kg/cm2Cooling Water Incoming lineB4 64 S7 Kg/cm2 / equivalent
Pressure Measurementfor incoming water of
manifold 3
0.35-7 kg/cm2Soft Water
Incoming lineB4 64 S7 Kg/cm2 / equivalent
Temperature Measurement
for outgoing water of manifold 2
Mercury in steel type Temp. Gauge, ± 1% accuracy
Outgoing water manifold 2
Temperature Measurement
for outgoing water of manifold 6
Mercury in steel type Temp. Gauge, ± 1% accuracy
Outgoing water manifold 6
Temperature Measurement
for outgoing water of manifold 4
Mercury in steel type Temp. Gauge, ± 1% accuracy
Outgoing water manifold 4
Temperature Measurement
for outgoing water of manifold 9
Mercury in steel type Temp. Gauge, ± 1% accuracy
Outgoing water manifold 4
Temperature Measurement
for outgoing water of HPP heat exchanger
Mercury in steel type Temp. Gauge, ± 1% accuracy
Outgoing water manifold 4
Flow Measurementfor outgoing water of
w.c.roof
0- 135 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of w.c.roof
0- 135 m3/Hr
Cooling Water
Return line
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 3 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO13 FS162 Flow Switch SH0500 / equivalent
117m3/Hr
PLC
14 FS163 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
100m3/Hr
15 FS164 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
100m3/Hr
16 FS175 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
6m3/Hr
17 FS176 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
6m3/Hr
18 FS177 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
6m3/Hr
19 FS178 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
6m3/Hr
20 FS196 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
21 FS197 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
22 FS198 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
23 FS208 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
40 m3/Hr
Flow Measurementfor outgoing water of w.c.roof
0- 135 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of w.c.side panel
0- 150 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of w.c.side panel
0- 150 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
bay panel
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
bay panel
0- 7m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
bay panel
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
bay panel
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
door cylinder
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
door frame
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
slag door
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
oxygen lance
0- 50 m3/Hr
Cooling Water
Return line
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 4 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
24 FS209 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
40 m3/Hr
25 FS210 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
40m3/Hr
26 FS185 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
22m3/Hr
27 FS186 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
22m3/Hr
28 FS179 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
Flow Measurementfor outgoing water of
oxygen lance
0- 50 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
oxygen lance
0- 50 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of Trx
HE
0- 25 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of Trx
HE
0- 25 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of LT
bustube
0- 6 m3/Hr
Cooling Water
Return line
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 5 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
29 FS180 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
30 FS181 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
5m3/Hr
31 FS182 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
5m3/Hr
32 FS183 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
5m3/Hr
33 FS184 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
5m3/Hr
34 FS187 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
35 FS188 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
36 FS189 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
37 FS190 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
38 FS191 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
Flow Measurementfor outgoing water of LT
bustube
0- 6 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of LT
bustube
0- 6 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of LT
bustube
0- 6 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of LT
bustube
0- 6 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of LT
bustube
0- 6 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
WC Cables
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
WC Cables
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
WC Cables
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
WC Cables
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of
WC Cables
0- 7 m3/Hr
Cooling Water
Return line
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 6 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
39 FS192 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLC SH0500 / equivalent
50° C
5m3/Hr
40 FS199 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3m3/Hr
41 FS200 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3 m3/Hr
42 FS201 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3m3/Hr
43 FS202 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3m3/Hr
44 FS203 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3m3/Hr
45 FS204 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3 m3/Hr
46 FS205 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3m3/Hr
47 FS206 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3m3/Hr
48 FS207 Flow Switch
IFM / equivalent 2.0 Kg/cm2
PLCSH0500 / equivalent
50° C
3 m3/Hr
Flow Measurementfor outgoing water of
WC Cables
0- 7 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 1
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 1
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy1
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 2
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 2
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 2
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 3
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 3
0- 5 m3/Hr
Cooling Water
Return line
Flow Measurementfor outgoing water of electrode arm assy 3
0- 5 m3/Hr
Cooling Water
Return line
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 7 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
49 TE109 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
50 TE110 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
51 TE111 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
52 TE112 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
53 TE113 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
54 TE114 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
55 TE115 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
56 TE116 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
57 TE117 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
58 TE118 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
Temp.Measurement
Element of Cooling
Water Return Lineof w.c. roof
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c. roof
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 8 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
59 TE119 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
60 TE120 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
61 TE121 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
62 TE122 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
63 TE123 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
64 TE124 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
65 TE125 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
66 TE126 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI150° C
67 TE144 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
68 TE145 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof w.c.side panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof bay panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof bay panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof bay panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof bay panel
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof door cylinder
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof door frame
Cooling Water
Return Line
thermowell of suitable material
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 9 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
69 TE146 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
70 TE215 RTD-Pt-100 NAGMAN / equivalent
3.5 Kg/cm2
0 - 100° C TJI235° C
70A TE216 RTD-Pt-100 NAGMAN / equivalent
3.5 Kg/cm2
0 - 100° C TJI235° C
70B TE217 RTD-Pt-100 NAGMAN / equivalent
3.5 Kg/cm2
0 - 100° C TJI235° C
71 TE156 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
72 TE157 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
73 TE158 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
74 TE133 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
75 TE134 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
77 TE127 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
Temp.Measurement
Element of Cooling
Water Return Lineof slag door
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling Water Incoming Line
to manifolds 1,5
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Incoming manifolds 3
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Incoming manifolds 7
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof Oxygen lance
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof Oxygen lance
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof Oxygen lance
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof trafo heat exchanger
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof trafo heat exchanger
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof LT bustube
Cooling Water
Return Line
thermowell of suitable material
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 10 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
78 TE128 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
79 TE129 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
80 TE130 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
81 TE131 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
82 TE132 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI250° C
83 TE135 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
84 TE136 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
85 TE137 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
86 TE138 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
87 TE139 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
88 TE140 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI3
Temp.Measurement
Element of Cooling
Water Return Lineof LT bustube
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof LT bustube
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof LT bustube
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof LT bustube
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof LT bustube
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 11 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
88 TE140 RTD-Pt-100 NAGMAN / equivalent 50° C 0 - 100° C TJI3
Temp.Measurement
Element of Cooling
Water Return Lineof W.C. cable
Cooling Water
Return Line
thermowell of suitable material
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 12 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
89 TE147 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
90 TE148 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
91 TE149 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
92 TE150 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
93 TE151 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
94 TE152 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
95 TE153 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
96 TE154 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 1
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 1
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 1
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 2
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 2
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 2
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 3
Cooling Water
Return Line
thermowell of suitable material
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 3
Cooling Water
Return Line
thermowell of suitable material
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 13 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
97 TE155 RTD-Pt-100 NAGMAN / equivalent
2.0 Kg/cm2
0 - 100° C TJI350° C
98 TJI1
MASIBUS/equivalent 2.0 Kg/cm20 - 100° C Instrument Panel PLC
50° C
99 TJI2
MASIBUS / equivalent 2.0 Kg/cm20 - 100° C Instrument Panel PLC50° C
100 TJI3MASIBUS / equivalent 2.0 Kg/cm2
0 - 100° C Instrument Panel PLC50° C
Temp.Measurement
Element of Cooling
Water Return Lineof electrode arm assy 3
Cooling Water
Return Line
thermowell of suitable material
Temp. Scanner of
Water Return Line (24 channel)
Temp Scanner 85XX 24-00-1-R-0-0-2-0 /
equivalent
Temp. Scanner of
Water Return Line (8 channel)
Temp Scanner 85XX 08-00-1-R-0-0-2-0 /
equivalentTemp. Scanner of
Water Return Line
(8 channel)
Temp Scanner 85XX 08-00-1-R-0-0-2-0 /
equivalent
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 14 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
WEIGHING SYSTEM OF 50T EAF
103 LS901 0.25-3 m Field PLC
104 LS902 0.25-3 m Field PLC
105 LS903 0.25-3 m Field PLC
106 LS904 0.25-3 m Field PLC
107 LS905 0.25-3 m Field PLC
108 LS906 0.25-3 m PLC PLC
109 WE905 Compression type load cell
SARTORIUS / equivalent
0-10 T Field WT801
PR 6201/14D1 / equivalent
110 WE906 Compression type load cell
SARTORIUS / equivalent
0-10 T Field WT801
PR 6201/14D1 / equivalent
Level switch of ferro alloy feeding bunker 1
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of ferro alloy feeding bunker 2
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of ferro alloy feeding bunker 3
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of ferro alloy feeding bunker 4
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of ferro alloy feeding bunker 5
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of ferro alloy feeding bunker 6
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Load cell of weigh hopper trolly for ferro
alloy feeding
Load cell of weigh hopper trolly for ferro
alloy feeding
CLIENT: EMIRATES STEELFOR : 50 TON EAF
HARDWARE SPECIFICATION FOR INSTRUMENTATION GA DANIELI INDIA LTD.
document.xls PAGE 15 OF 15 04/10/2023
TAG NO.PRESSURE
RANGE LOCATION ACCESSORIESTYPE MAKE / MODEL TEMPERATUREFLOW
SL. NO.
SERVICE DESCRIPTION
CONNECTED
TO
111 WE907 Compression type load cell
SARTORIUS / equivalent
0-10 T Field WT801PR 6201/14D1 / equivalent
112 WT908
SARTORIUS equivalent
PLCPR 1613/00 equivalent
113 LS801 0.25-3 m Field PLC
114 LS802 0.25-3 m Field PLC
115 LS803 0.25-3 m Field PLC
116 LS804 0.25-3 m Field PLC
117 LS805 0.25-3 m Field PLC
118 LS806 0.25-3 m Field PLC
Load cell of weigh hopper trolly for ferro
alloy feeding
Load Transmitter of weigh hopper trolly for
ferro alloy feeding
Microprocessor based transmitter unit
Hopper weighing Panel
Level switch of DRI charging bunker 1
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of DRI charging bunker 2
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of DRI charging bunker 3
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of DRI charging bunker 4
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of DRI charging bunker 5
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent
Level switch of DRI charging bunker 6
Ultrasonic type level switch(both high level & low level controls
provided)
SIEMENS(MILLITRONICS) / equivalent
POINTEK ULS 200 / equivalent