- 161 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 2
BGD 2740 lot 4.1 v ol 2 2019 03 13.docx
– Inter cabling between signal box, control box and Fire Extinguishing Cubicle (FEC).
– Butterfly valves /Gate valves on oil drain pipe and nitrogen injection pipe which should be able
to withstand full vacuum.
– Supports, signal box etc. which are to be painted with enamelled paint.
Technical Particulars
Fire extinction period from commencement of nitrogen injection: 30 s. (max.)
Total duration from activation of fire protection system to com-
plete cooling:
30 minutes (max.)
Fire detectors' heat sensing temperature: 141 °C
Heat sensing area per detector: Up to R = 800 mm
Transformer Conservator Isolation valve setting (minimum): 60 litre / min
Capacity of nitrogen cylinder (minimum water capacity): 68 litre
Capacity of nitrogen cylinder (minimum gas capacity, at
150 kg/cm² pressure:
10 m³
Power supply, for control box and for fire extinguishing cubicle
for lighting:
110 V DC / 240 V AC
Mandatory Spare Parts - Per Substation
Cylinder filled with nitrogen of required capacity per substation: 1 piece
Fire detectors: 3 pieces
Regulator assembly: 1 piece
Tests
Reports of all type tests conducted as per relevant IEC standards including test reports for the degree
of protection for FEC / control box / signal box shall be submitted with the bid.
The performance test of the complete system shall be carried out after installation of the system on
site. Detailed layout drawings, equipment drawing along with 4 sets of the operation and maintenance
manual along with soft copies (on CDs) shall be submitted by the Contractor.
4.12.4 Water Spray System
The new power transformers shall be equipped with Water Spray System made in EU/USA/Japan
One transformer water spray system.
To the water spray system is to be allowed one valve station including necessary control and monitor-
ing cabinet, to be designed for manual, automatic and electrical remote operation and must be provid-
ed in free-standing and self-supporting design, with the following basic equipment:
the required number of triggering and fire extinguishing nozzles, with galvanized pipes and mount-
ings,
the necessary galvanized connecting lines from the appropriate valve station to the nozzles pipe
network,
the necessary drainage valve, struts, diaphragms, sleeve valve, single chamber valve stations with
all fittings and connections, pressure sensitive switches for signalling and air pressure drop with the
possibility of extension by three transformer,
- 261 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 2
BGD 2740 lot 4.1 v ol 2 2019 03 13.docx
The Bidder shall be responsible for all negotiations with local authority/WASA where a connection to a
public sewer is proposed. Where high water levels in public sewers may cause effluent to back up into
a site, non-return valves shall be fitted. The Bidder shall provide all protection required to existing
sewers and shall deepen foundations, including boundary wall foundations, where required to ensure
all foundations are below adjacent sewers. The Bidder shall draw longitudinal sections of all pipelines.
Main control building shall be provided with a septic tank designed for 10 users and a soakaway of
open brick construction 11m deep by 2.2m diameter filled with broken bricks. The septic tank shall be
located at least 15 metres from buildings. Other buildings shall have septic tanks designed for the re-
quired number of users. All foul drains shall be vented by a vent pipe to above roof level. The inner
surface of all manholes and septic tanks shall be painted with 2 coats of bitumastic paint to protect it
against sulphate attack. The septic tank shall have access holes directly over the inlet pipes and outlet
pipes. Where public sewers exist alongside a site, the Bidder shall connect directly to the foul sewer,
provided effluent from the sewer is treated.
The Bidder shall construct the drainage first to ensure that at no stage is rainwater ponded on any part
of the site. All rainwater shall be able to run off the site or shall be immediately pumped off site by the
Bidder. The Bidder shall complete all necessary drains before casting any roof and large concrete ar-
ea which will create large run off. The condensate drains for the air conditioning shall also be connec t-
ed to the drainage. Two vents of minimum height 2.2m shall be provided on each septic tank.
10.1.3.4 Surfacing
For the whole of the switchyard outdoor equipment area the ground shall be surfaced with gravel or
other readily available local stone as approved by the Engineer. The switchyard surfacing shall be
clean, thoroughly washed when necessary, and free from clay, soil or contaminating material and shall
be graded from 20 - 45mm, laid and lightly compacted to a finished thickness of 175mm. Below the
gravel layer there shall be a 75mm brick layer with cement mortar (1:6), laid over a 75mm level of fine
sand spread over the finished fill site.
The substation plot, outside of the designated switchgear equipment areas, shall be turfed. Turf shall
be of good quality, free from weeds and shall be a minimum of 40mm thick. Samples of the turf which
is proposed to use shall be submitted to the Engineer for his approval. The turfs shall be laid to even
surfaces on a bed of vegetable soil, which shall be raked and consolidated to provide a suitable bed.
On sloping surfaces the Bidder shall provide and fix wooden pegs to retain turfs.
All areas to be surfaced shall first be treated with a total weed killer in accordance with the Manufac-
turer's instructions. Weed killer shall only be applied in dry weather when there is no risk of it being
washed out to adjacent agricultural areas.
10.1.3.5 Roads
Access road from outside of the site boundary that connects adjacent public road and all roads within
the site boundary shall be provided by the Bidder. The road surface shall be finished by concrete pav-
ing or equivalent. All roads shall be of reinforced slabs of minimum 15 cm thickness fitted with con-
struction joints at distances not exceeding 6.0 m. Paving schedule and methodology shall be approved
by the Employer. The extent of roads required is shown approximately on Bid drawings but the scope
Maungdaw
Agartala
Shillong
Nowgong
Ingraj Bazar
Farakka
Baharampur
Santipur
Rangaon
Calcutta
Habra
Haora
Barasat
Diamond Harbour
Kabirpur
Padm
a Br
idge
50.0
92
49.973
Kaliakor
JAMU
NA
GANGES
BAY OF BENGAL
KarnaphuliReservoir
Brahm
aputra
Karatoya
Atrai
Madhum
at
Baul
ai
Kaln
i
Bra
a
h
rm
utap
Tista
PADMA
MEGHNA
I N D I A( A S H A M )
I N D I A( W E S T B E N G A L )
I N D I A( T R I P U R A )
MYANMAR
0
0
20 40
60 mi20
60
40
80 km
N
© Magellan GeographixSMSanta Barbara, CA (800) 929-4627
Palashbari
Joypurhat
Lalmanirhat
Natore
Bottail
Jhenaidah
Manikganj Savar
Joydevpur
Tongi
Kishorganj
Sherpur
RPCL
Fenchu P/S
Srimangal
Ag
Sikalbaha
Dohazari
Panchagarh
Khulna Central
Gallamari
Satkhira
Patuakhali
Chuadanga
Magura
Bhandaria
BarisalBagherhat
Chowmuhani
Shahjadpur
Sirajganj
Feni
DaudkandiSonargaon
Kulaura
Shahmirpur
Niamatpur
Amnura
Brahmanbaria
Shahjibazar
Maduaghat
Bera PP
Bhola IPP
Jam
una
Brid
ge
Chhatak
Sylhet
Faridpur
Gopalganj
Netrokona
MonglaChandraghona
Kaptai
Thakurgaon
Saidpur
Rangpur
BograJamalpur
Chapai Nawabganj
Rajshahi
Mymensingh
Tangail
Pabna
Jessore
Noapara
Comilla(S)Chandpur
Madaripur
Goalpara
Cox’s Bazar
Narsingdi
Noagaon
Purbasadipur
AminbazarNarsingdi
DHAKA
CTG
POWER GRID COMPANY OF BANGLADESH LTD. (PGCB)OPTICAL FIBER (OPGW) NETWORK
Raozan
Hathazari
Khulna(S)
Ishwardi
Bogra(S)
Barapukuria
BaghabariAshuganj
BibiyanaFenchuganj
Comilla(N)
Meghnaghat
Feni
Sirajganj
Ghorasal
BSRM
APSCL
Kamta
Shahbazpur
Begumganj
Kutubdia
Sangu
Semutang
Feni
Saldanodi
Bakhrabad
Meghna
Belabo Titas
Habiganj
Rashidpur
Chhatak
Moulovibazar
Fenchuganj
Kailashtila
Bianibazar
Sylhet
Bibiyana
Ashuganj
Bibiyana
Baharampur,India
Borhanuddin
Barisal (N)
SurjyamaninagarIndia
Kaliakoir
47.5
6
45.96
25.4342.59
36.00
110.46
53.4251.48
45.1146.74
46.00
62.08
37.17
49.00
42.68
18.72
42.36
05.69
39.1757.30
75.00
02.0
0
38.00
01.2
8
01.20
Bheramara
11.00
10.70
24.14
44.1249.23
28.83
23.68
02.45
44.68
28.32
40.11 50.98
39.7
1
02.4465.00
60.79
67.28
107.78
48.0504.30
10.71
27.88
39.90
175.
00
149.07
Kabirpur
15.00
56.33 34.81
60.81
05.1
7
53.56
53.50
59.50
15.50
37.26
50.1
2
03.92
29.2
3
34.00
33.87 45.00
175.5
61.83
7
99.1
6
12.9
8
63.47
69.93
33.46
54.91
87.32
24.04
47.29
89.38
150.15
45.17
27.46
22.97
15.58
49.97350.092
33.19
8 FIBERS
12 FIBERS
24 FIBERS
32 FIBERS
48 FIBERS
UNDERGROUND CABLE WITH 24 FIBERS
UNDERGROUND CABLE WITH 12 FIBERS
Dhaka-1 Dhaka-2 Chittagong Bogra Khulna
EXISTING SUB-STATIONS WITHOUT OPTICAL FIBERS
PROPOSED SUB-STATIONS
NOT PRESENT NOT PRESENT
NOT PRESENT
NOT PRESENT
NOT PRESENT
LEGEND
Halishahar
Baraulia
Kulshi
Madunaghat
Shahmirpur
Julda
Agrabad
M.st
TKC
to Dohazari
Bakulia
Sholoshahar
Uttara
Joydebpur
Kabirpur
Savar
Manikganj
Mirpur
ShampurKeraniganj RPP
Madanganj
B.bhaban
Maghbazar
Sitalakhya
Dhanmondi
Narinda
Munshiganj
to Tangail
Gulshan
Narsingdhi
K. char
Basundhara
Satmasjid.
Vasantek(Cantonment)
Kallyanpur
Matuail
Bhulta
Abul Khair
New Tongi
Lalbagh
Kaptai
Chanadraghon
Jigatola
Sikalbaha
to Comilla(N) to Raozan
to Ashuganj
Charged at 230kV
CHITTAGONG RING
DHAKA RING
Aminbazar
Agargaon (Old Airport)
Hasnabad
Shampur 230 kV
Haripur
Maniknagar
Siddhirganj
Rampura
Ghorasal
Ullon
Tongi
Hathazari
WAPDA Bhaban
HQ
NLDC
16.23
56.13
21.4504.49
3.30
13.23
19.89
18.65
03.8
7
4.5725.571
12.35
27.35(100.85)
71.30
7.70
Sylhet South
Biyani bazar57.00
30.00
Sunamganj
Rangamati
Khagrachari
13.3028.13
10.91
Bandarban
32.08
59.26
Aminbazar
16.23
100.0
0
10.31
15.95
04.37
12.8812.50
10.91
17.68
32.08
10.00
5.00
5.00
07.00
17.00
13.50
07.18
47.29
24.04
150.15
28.13
13.3
0
Meghnaghat
12.16
02.5511.0602.01
04.51
04.4
4
2.10
03.9903.47
05.00
04.80
06.00
07.93
00.9
6
10.3616.05
17.8
5
09.24
27.36
50.2
7
21.92
15.58
33.19
22.97
8.05 07.6
9
4.712
Thermal Power Plant Existing
Thermal Power Plant Planned
Hydro Power Plant Existing
Renewable Plant
Thermal Power Plant U/C
HVDC BtB Station Existing
June 2016
39.68
42.74
46.17
17.00
15.8465.08
17.59
TRANSMISSIONLINES HAVING
132 KV 230 KV 400 KV
Gas Field
59.60
82.16
10.00
02.95
PROPOSED TRANSMISSION LINES
01.95RCT
References: 1. TMCC,
Power Grid Company of Bangladesh Ltd. 2. System Planning,Power Grid Company of Bangladesh Ltd.
HVDC10
.70
0.50
82.16
Padm
a Br
idge
- 7 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
B8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 132 kV switchgear
Lot 1
B9.X Gantry steel structures and equipment supports required for complet-
ing 132 kV switchgear
Lot 1
B10.X All other necessary material and equipment required for completing
132 kV switchgear
Lot 1
C 33 kV Switchgear, equipment connection and steel structures
One (1) set of complete equipment for switchgear 33 kV shall be de-
signed, supplied, delivered, installed, tested and commissioned, under this
contract, comprise the following:
Set 1
C1 Circuit Breaker 36 kV, 2000 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
vacuum type, for outdoor installation with one spring-stored energy oper-
ating mechanism
Set 2
C2.1 Disconnector 36 kV, 2000 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
centre break, post type, manually operated
Set 3
C2.2 Disconnector 36 kV, 100 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
centre break, post type, manually operated, with integrated fuse of 10 A
Set 2
C3.1 Current transformer 36 kV, 25kA, 50Hz, 170/70 kV BIL, single phase,
2000/1/1/1/1 A/A, 4-core, single ratio, post type
Set 6
C3.2 Current transformer 36 kV, 25kA, 50Hz, 170/70 kV BIL, single phase,
10/1/1/1 A/A, 3-core, single ratio, post type
Set 6
C4 Voltage transformer 36 kV, 50Hz, 170/70 kV BIL, single phase, 33/V3 /
110/V3 / 110/V3 kV/V/V, 2 secondary windings, inductive type
Set 12
C5 Surge arrester 36 kV, 30 kV continuous operating voltage, 10 kA nominal
discharge current, 50 Hz, single phase, gapless, metal oxide type
Set 6
C7.X Conductors for single busbar system and for connection of the 33 kV
switchgear, 36 kV, 2000 A & 630 A, 25 kA
Lot 1
C8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 33 kV switchgear
Lot 1
C9.X Gantry steel structures and equipment supports required for complet-
ing 33 kV switchgear
Lot 1
C10.X All other necessary material and equipment required for completing
33 kV switchgear
Lot 1
D Transformers
D2 Power transformer 132/33 kV three phase 80/120 MVA, Dyn1,
ONAN/ONAF
Set 2
D9.2 Water Spray System Set 2
D10.X All other necessary material and equipment required for completing
transformers
Lot 1
F Earthing / Auxiliary Power Transformers
F1 Earthing / Auxiliary Power Transformer 33/0.4 kV, three phase
200 kVA, Dyn11, ONAN
Set 2
F10.X All other necessary material and equipment required for completing
Earthing / Auxiliary Power transformers.
Lot 1
- 8 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
G Control, Protection, SCADA System and Metering
One (1) lot of complete equipment for control, protection, SCADA System
and metering for 132, 33 kV as well as LV AC and LV DC system (for
complete substation) shall be designed, calculated, supplied, delivered,
installed, tested and commissioned, under this contract.
Lot 1
The control and protection panels shall mirror the switchyard layout.
Enough space shall be reserved for future circuits.
The system comprise the following:
G1.1 Control, Protection and SAS set for 132 kV Overhead Line circuit, (in-
cluding the other end)
Set 2
G2.2 Control, Protection and SAS set for 132/33 kV Power Transformer cir-
cuits
Set 2
G3.2 Control, Protection and SAS set for Busbar 132 kV Set 1
G4 Control, Protection and SAS set for complete Switchgear 33 kV Set 1
G4.X Tariff metering panel(s) to accommodate programmable & recordable
digital 3-phase, 4-wire import and export MWh and MVArh meters (accu-
racy class 0.2) for each line and transformer feeder. For each feeder, min-
imum two (2) meters (main-1 & main-2) shall be provided
Lot 1
G5.X Digital Fault and Disturbance Recorder (DFDR) to accommodate all
feeders
Lot 0
G6.X Tele-control & Teleprotection & Tele-metering facilities, Lot 1
A complete lot of hardware and software, extension of the existing equip-
ment, necessary adjustment, adaptation, modification, integration and
configuration of new and existing equipment, all necessary modification
works in the hardware and software of the master stations, shall be pro-
vided both at the National Load Despatch Centre (NLDC) at Aftabnagar
and at the back-up station at Biddut Bhaban, for integration of the com-
plete substation
All required electrical signals shall be transmitted to the NLDC and the
back-up station through the industrial gateway of the substation automa-
tion system. All HV circuit breakers, disconnectors, tap changer, etc., shall
be controlled from the NLDC through the gateway of the substation auto-
mation system using the IEC 60870-5-104 protocol.
G10.X All other necessary material and equipment required for completing
control, protection, substation automation and metering system.
Lot 1
H Fibre Optic Multiplexer Equipment for Tele-prot. and Communication
H1.X Fibre Optic Multiplexer Equipment, a complete lot of fibre optic multi-
plexer equipment for protection & communication at substation shall be
designed, supplied, delivered, installed, tested and commissioned, under
this contract. Fibre optic multiplexer equipment is to be provided for.
Lot 1
Distance relay carrier signal (main and back-up)
Bus protection / breaker failure relay
SCADA data from switchgear and control system
VOIP system (2-IP Phone)
2-W remote subscriber ( 10 telephone sets)
Hot-line telephone system
- 13 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
The control and protection panels shall mirror the switchyard layout.
Enough space shall be reserved for future circuits.
The system comprise the following:
G1.1 Control, Protection and SAS set for 132 kV Overhead Line circuit, (in-
cluding the other end)
Set 2
G2.2 Control, Protection and SAS set for 132/33 kV Power Transformer cir-
cuits
Set 0
G3.2 Control, Protection and SAS set for Busbar 132 kV Set 0
G4.XE Extension of the existing Tariff Metering Lot 1
Tariff metering panel(s) to accommodate programmable & recordable
digital 3-phase, 4-wire import and export MWh and MVArh meters (accu-
racy class 0.2) for each line and transformer feeder, for required part of
substation. For each feeder, minimum two (2) meters (main-1 & main-2)
shall be provided
G5.XE Digital Fault and Disturbance Recorder (DFDR) to accommodate all
feeders, for required part of substation
Lot 0
G6.XE Tele-control & Teleprotection & Tele-metering facilities, Lot 1
A complete lot of hardware and software, extension of the existing equip-
ment, necessary adjustment, adaptation, modification, integration and
configuration of new and existing equipment, all necessary modification
works in the hardware and software of the master stations, shall be pro-
vided both at the National Load Despatch Centre (NLDC) at Aftabnagar
and at the back-up station at Biddut Bhaban, for integration of the re-
quired part of substation
All required electrical signals shall be transmitted to the NLDC and the
back-up station through the industrial gateway of the substation automa-
tion system. All HV circuit breakers, disconnectors, tap changer, etc., shall
be controlled from the NLDC through the gateway of the substation auto-
mation system using the IEC 60870-5-104 protocol.
G10.X All other necessary material and equipment required for completing
control, protection, substation automation and metering system.
Lot 1
H Fibre Optic Multiplexer Equipment for Teleprotection and Communi-
cation
H1.XE Fibre Optic Multiplexer Equipment, a complete lot of equipment for ex-
tension of existing fibre optic multiplexer equipment for protection &
communication, for required part of substation, shall be designed, sup-
plied, delivered, installed, tested and commissioned and integrated into
the existing system, under this contract. Fibre optic multiplexer equip-
ment is to be provided for.
Lot 1
Distance relay carrier signal (main and back-up)
Bus protection / breaker failure relay
SCADA data from switchgear and control system
Hot-line telephone system
H3.XE A lot of underground optical fibre (48 cores) cables from terminal box
at gantry structure to MDF (Main distribution Frame) shall be designed,
supplied, delivered, installed, tested and commissioned, including supply
and installation of MDF and digital cables, for required part of substa-
Lot 1
- 17 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
Q1, Q2, Q9 - Three (3) sets of three pole, three positions, motor operated,
insulated disconnector with earthing switch
Q8 - One (1) set of three pole, make-proof, motor operated earthing switch
T1-Three (3) single-phase, 5-core, multi ratio, 3200-1600-800/1/1/1/1/1 A,
GIS type current transformers
T5 - Three (3) single-phase, 2-secondary winding, 132/V3 / 110/V3 /
110/V3 kV/V/V, GIS type voltage transformers
T6 - One (1) set of three-phase, GIS type, hand operated disconnector link
SA - Three (3) single-phase outdoor surge arresters, GIS type
Z1 - One (1) set of three-phase, GIS type, cable compartment
or
Z2 - One (1) set of three phase indoor and outdoor GIB with three outdoor
GIS/AIR bushings
GIS.X - Control cabinet, cables, metal support structure, grounding, etc.
and all accessories for complete bay
BG.2 A complete indoor and partly outdoor GIS transformer feeder 145 kV,
3150A busbars / 2000 A feeder, 40 kA, 50Hz, 650/275 kV BIL, equipped
with:
Set 2
Q0 - One (1) set of three pole, GIS type, SF6 gas circuit breaker with one
spring-stored energy operating mechanism
Q1, Q2, Q9 - Three (3) set of three pole, three position, motor operated,
insulated disconnector with earthing switch
Q8 - One (1) set of three pole, make-proof, motor operated earthing switch
T1-Three (3) single-phase, 5-core, multi ratio, 3200-1600-800/1/1/1/1/1 A,
GIS type current transformers
SA - Three (3) single-phase outdoor surge arresters, GIS type
Z1 - One (1) set of three-phase, GIS type, cable compartment
or
Z2 - One (1) set of three phase indoor and outdoor GIB with three outdoor
GIS/AIR bushings
X - Control cabinet, cables, metal support structure, grounding, etc. and all
accessories for complete bay
BG.3 A complete indoor GIS bus coupler bay 145 kV, 3150A busbars / 3150 A
feeder, 40 kA, 50Hz, 650/275 kV BIL, equipped with:
Set 1
Q0 - One (1) set of three pole, GIS type, SF6 gas circuit breaker with one
spring-stored energy operating mechanism
Q1, Q2 - Two (2) sets of three pole, three position, motor operated, insu-
lated disconnector with earthing switch
T1-Three (3) single-phase, 5-core, multi ratio, 3200-1600-800/1/1/1/1/1 A,
GIS type current transformers
X - Control cabinet, cables, metal support structure, grounding, etc. and all
accessories for complete bay
BG.4 A complete indoor GIS metering bay 145 kV, 3150A busbars, 40 kA,
50Hz, 650/275 kV BIL, equipped with:
Set 1
Q21, Q22 - Two (2) sets of three pole, three position, motor operated, in-
sulated disconnector
T5 – Two (2) sets of three (3) single-phase, 2-winding, 132/V3 / 110/V3 /
110/V3 kV/V/V, GIS type voltage transformers
- 18 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
X - Control cabinet, cables, metal support structure, grounding, etc. and all
accessories for complete bay
BG.5 A complete indoor GIS busbars earthing bay 145 kV, 3150A busbars, 40
kA, 50Hz, 650/275 kV BIL, equipped with:
Set 1
Q81, Q82 - Two (2) sets of three pole, make-proof, motor operated earth-
ing switch
B5 Surge arrester 145 kV, 120 kV continuous operating voltage, 10kA nomi-
nal discharge current, 50Hz, single phase, heavy duty, station class, gap-
less, metal oxide type
Set 12
B7.X Conductors for connection of the 132 kV switchgear, 145 kV, 2000 A, 40
kA
Lot 1
B8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 132 kV switchgear
Lot 1
B9.X Gantry steel structures and equipment supports required for complet-
ing 132 kV switchgear
Lot 1
B10.X All other necessary material and equipment required for completing
132 kV switchgear
Lot 1
C 33 kV Switchgear, Equipment Connection and Steel Structures
One (1) set of complete equipment for switchgear 33 kV shall be de-
signed, supplied, delivered, installed, tested and commissioned, under this
contract, comprise the following:
Set 1
C1 Circuit Breaker 36 kV, 2000 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
vacuum type, for outdoor installation with one spring-stored energy operat-
ing mechanism
Set 2
C2.1 Disconnector 36 kV, 2000 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
centre break, post type, manually operated
Set 3
C2.2 Disconnector 36 kV, 100 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
centre break, post type, manually operated, with integrated fuse of 10 A
Set 2
C3.1 Current transformer 36 kV, 25kA, 50Hz, 170/70 kV BIL, single phase,
2000/1/1/1/1 A/A, 4-core, single ratio, post type
Set 6
C3.2 Current transformer 36 kV, 25kA, 50Hz, 170/70 kV BIL, single phase,
10/1/1/1 A/A, 3-core, single ratio, post type
Set 6
C4 Voltage transformer 36 kV, 50Hz, 170/70 kV BIL, single phase, 33/V3 /
110/V3 / 110/V3 kV/V/V, 2 secondary windings, inductive type
Set 12
C5 Surge arrester 36 kV, 30 kV continuous operating voltage, 10 kA nominal
discharge current, 50 Hz, single phase, gapless, metal oxide type
Set 6
C7.X Conductors for single busbar system and for connection of the 33 kV
switchgear, 36 kV, 2000 A & 630 A, 25 kA
Lot 1
C8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 33 kV switchgear
Lot 1
C9.X Gantry steel structures and equipment supports required for complet-
ing 33 kV switchgear
Lot 1
C10.X All other necessary material and equipment required for completing
33 kV switchgear
Lot 1
- 19 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
D Transformers
D2 Power transformer 132/33 kV three phase 80/120 MVA, Dyn1,
ONAN/ONAF
Set 2
D9.2 Water Spray System Set 2
D10.X All other necessary material and equipment required for completing
transformers
Lot 1
F Earthing / Auxiliary Power Transformers
F1 Earthing / Auxiliary Power Transformer 33/0.4 kV, three phase
200 kVA, Dyn11, ONAN
Set 2
F10.X All other necessary material and equipment required for completing
Earthing / Auxiliary Power transformers.
Lot 1
G Control, Protection, SCADA System and Metering
One (1) lot of complete equipment for control, protection, SCADA System
and metering for 132, 33 kV as well as LV AC and LV DC system (for
complete substation) shall be designed, calculated, supplied, delivered,
installed, tested and commissioned, under this contract.
Lot 1
The control and protection panels shall mirror the switchyard layout.
Enough space shall be reserved for future circuits.
The system comprise the following:
G1.1 Control, Protection and SAS set for 132 kV Overhead Line circuit, (in-
cluding the other end)
Set 2
G2.2 Control, Protection and SAS set for 132/33 kV Power Transformer cir-
cuits
Set 2
G3.2 Control, Protection and SAS set for Busbar 132 kV Set 1
G4 Control, Protection and SAS set for complete Switchgear 33 kV Set 1
G4.X Tariff metering panel(s) to accommodate programmable & recordable
digital 3-phase, 4-wire import and export MWh and MVArh meters (accu-
racy class 0.2) for each line and transformer feeder. For each feeder, min-
imum two (2) meters (main-1 & main-2) shall be provided
Lot 1
G5.X Digital Fault and Disturbance Recorder (DFDR) to accommodate all
feeders
Lot 0
G6.X Tele-control & Teleprotection & Tele-metering facilities, Lot 1
A complete lot of hardware and software, extension of the existing equip-
ment, necessary adjustment, adaptation, modification, integration and
configuration of new and existing equipment, all necessary modification
works in the hardware and software of the master stations, shall be pro-
vided both at the National Load Despatch Centre (NLDC) at Aftabnagar
and at the back-up station at Biddut Bhaban, for integration of the com-
plete substation.
All required electrical signals shall be transmitted to the NLDC and the
back-up station through the industrial gateway of the substation automa-
tion system. All HV circuit breakers, disconnectors, tap changer, etc., shall
be controlled from the NLDC through the gateway of the substation auto-
mation system using the IEC 60870-5-104 protocol.
G10.X All other necessary material and equipment required for completing
control, protection, substation automation and metering system.
Lot 1
- 25 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
G5.XE Digital Fault and Disturbance Recorder (DFDR) to accommodate all
feeders, for required part of substation
Lot 0
G6.XE Tele-control & Teleprotection & Tele-metering facilities, Lot 1
A complete lot of hardware and software, extension of the existing equip-
ment, necessary adjustment, adaptation, modification, integration and con-
figuration of new and existing equipment, and all necessary modification
works in the hardware and software of the master stations shall be provided,
both at the National Load Despatch Centre (NLDC) at Aftabnagar and at the
backup station at Biddut Bhaban, for integration of the required part of the
substation
All required electrical signals shall be transmitted to the NLDC and the back-
up station through the industrial gateway of the substation automation sys-
tem. All HV circuit breakers, disconnectors, tap changer, etc., shall be con-
trolled from the NLDC through the gateway of the substation automation
system using the IEC 60870-5-104 protocol.
G10.X All other necessary material and equipment required for completing con-
trol, protection, substation automation and metering system.
Lot 1
H Fibre Optic Multiplexer Equipment for Teleprotection
and Communication
H1.XE Fibre Optic Multiplexer Equipment, a complete lot of equipment for ex-
tension of existing fibre optic multiplexer equipment for protection & com-
munication, for required part of substation, shall be designed, supplied,
delivered, installed, tested and commissioned and integrated into the ex-
isting system, under this contract. Fibre optic multiplexer equipment is to
be provided for.
Lot 1
Distance relay carrier signal (main and back-up)
Bus protection / breaker failure relay
SCADA data from switchgear and control system
Hot-line telephone system
H3.XE A lot of underground optical fibre (48 cores) cables from terminal box at
gantry structure to MDF (Main distribution Frame) shall be designed, sup-
plied, delivered, installed, tested and commissioned, including supply and
installation of MDF and digital cables, for required part of substation
Lot 1
I Multicore Low Voltage Auxiliary Power and Control Cables
I1.XE A complete lot of multicore low voltage auxiliary power and control ca-
bles, including all other necessary material and equipment, between all
items of equipment supplied under the contract, and connection and
integration of new equipment with existing equipment, shall be de-
signed, supplied, delivered, installed, tested and commissioned
Lot 1
J LV DC, Batteries, Chargers and DC Distribution
J1.XE Extension of existing LV DC 110 V Auxiliary Power Supply Lot 1
A complete lot, including all necessary material and equipment, including a
set of LV DC distribution switchboards, shall be designed, supplied, deliv-
ered, installed, tested and commissioned, under this contract, to provide ex-
tension of the existing LV DC 110 V Auxiliary Power Supply and for con-
nection of new equipment and integration with the existing equipment
- 30 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
Q0 - One (1) set of three pole, GIS type, SF6 gas circuit breaker with one
spring-stored energy operating mechanism
Q1, Q2 - Two (2) sets of three pole, three position, motor operated, insu-
lated disconnector with earthing switch
T1-Three (3) single-phase, 5-core, multi ratio, 3200-1600-800/1/1/1/1/1 A,
GIS type current transformers
X - Control cabinet, cables, metal support structure, grounding, etc. and all
accessories for complete bay
BG.4 A complete indoor GIS metering bay 145 kV, 3150A busbars, 40 kA,
50Hz, 650/275 kV BIL, equipped with:
Set 1
Q21, Q22 - Two (2) sets of three pole, three position, motor operated, in-
sulated disconnector
T5 – Two (2) sets of three (3) single-phase, 2-winding, 132/V3 / 110/V3 /
110/V3 kV/V/V, GIS type voltage transformers
X - Control cabinet, cables, metal support structure, grounding, etc. and all
accessories for complete bay
BG.5 A complete indoor GIS busbars earthing bay 145 kV, 3150A busbars, 40
kA, 50Hz, 650/275 kV BIL, equipped with:
Set 1
Q81, Q82 - Two (2) sets of three pole, make-proof, motor operated earth-
ing switch
B5 Surge arrester 145 kV, 120 kV continuous operating voltage, 10kA nomi-
nal discharge current, 50Hz, single phase, heavy duty, station class, gap-
less, metal oxide type
Set 24
B7.X Conductors for connection of the 132 kV switchgear, 145 kV, 2000 A, 40
kA
Lot 1
B8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 132 kV switchgear
Lot 1
B9.X Gantry steel structures and equipment supports required for complet-
ing 132 kV switchgear
Lot 1
B10.X All other necessary material and equipment required for completing
132 kV switchgear
Lot 1
C 33 kV Switchgear, Equipment Connection and Steel Structures
One (1) set of complete equipment for switchgear 33 kV shall be de-
signed, supplied, delivered, installed, tested and commissioned, under this
contract, comprise the following:
Set 1
C1 Circuit Breaker 36 kV, 2000 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
vacuum type, for outdoor installation with one spring-stored energy oper-
ating mechanism
Set 3
C2.1 Disconnector 36 kV, 2000 A, 25 kA, 50 Hz, 170/70 kV BIL, three pole,
centre break, post type, manually operated
Set 5
C3.1 Current transformer 36 kV, 25kA, 50Hz, 170/70 kV BIL, single phase,
2000/1/1/1/1 A/A, 4-core, single ratio, post type
Set 9
C4 Voltage transformer 36 kV, 50Hz, 170/70 kV BIL, single phase, 33/V3 /
110/V3 / 110/V3 kV/V/V, 2 secondary windings, inductive type
Set 18
C5 Surge arrester 36 kV, 30 kV continuous operating voltage, 10 kA nominal
discharge current, 50 Hz, single phase, gapless, metal oxide type
Set 9
- 31 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
C7.X Conductors for single busbar system and for connection of the 33 kV
switchgear, 36 kV, 2000 A & 630 A, 25 kA
Lot 1
C8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 33 kV switchgear
Lot 1
C9.X Gantry steel structures and equipment supports required for complet-
ing 33 kV switchgear
Lot 1
C10.X All other necessary material and equipment required for completing
33 kV switchgear
Lot 1
D Transformers
D2 Power transformer 132/33 kV three phase 80/120 MVA, Dyn1,
ONAN/ONAF
Set 2
D9.2 Water Spray System Set 2
D10.X All other necessary material and equipment required for completing
transformers
Lot 1
F Earthing / Auxiliary Power Transformers
F1 Earthing / Auxiliary Power Transformer 33/0.4 kV, three phase
200 kVA, Dyn11, ONAN
Set 2
F10.X All other necessary material and equipment required for completing
Earthing / Auxiliary Power transformers.
Lot 1
G Control, Protection, SCADA System and Metering
One (1) lot of complete equipment for control, protection, SCADA System
and metering for 132, 33 kV as well as LV AC and LV DC system (for
complete substation) shall be designed, calculated, supplied, delivered,
installed, tested and commissioned, under this contract.
Lot 1
The control and protection panels shall mirror the switchyard layout.
Enough space shall be reserved for future circuits.
The system comprise the following:
G1.1 Control, Protection and SAS set for 132 kV Overhead Line circuit, (in-
cluding the other end)
Set 5
G2.2 Control, Protection and SAS set for 132/33 kV Power Transformer cir-
cuits
Set 3
G3.2 Control, Protection and SAS set for Busbar 132 kV Set 1
G4 Control, Protection and SAS set for complete Switchgear 33 kV Set 1
G4.X Tariff metering panel(s) to accommodate programmable & recordable
digital 3-phase, 4-wire import and export MWh and MVArh meters (accu-
racy class 0.2) for each line and transformer feeder. For each feeder, min-
imum two (2) meters (main-1 & main-2) shall be provided
Lot 1
G5.X Digital Fault and Disturbance Recorder (DFDR) to accommodate all
feeders
Lot 0
G6.X Tele-control & Teleprotection & Tele-metering facilities, Lot 1
A complete lot of hardware and software, extension of the existing equip-
ment, necessary adjustment, adaptation, modification, integration and
configuration of new and existing equipment, all necessary modification
works in the hardware and software of the master stations, shall be pro-
vided both at the National Load Despatch Centre (NLDC) at Aftabnagar
and at the back-up station at Biddut Bhaban, for integration of the com-
plete substation
- 37 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
Q0 - One (1) set of three pole, GIS type, SF6 gas circuit breaker with one
spring-stored energy operating mechanism
Q1, Q2 - Two (2) sets of three pole, three position, motor operated, insu-
lated disconnector with earthing switch
T1-Three (3) single-phase, 5-core, multi ratio, 3200-1600-800/1/1/1/1/1 A,
GIS type current transformers
X - Control cabinet, cables, metal support structure, grounding, etc. and
all accessories for complete bay
BG.4 A complete indoor GIS metering bay 145 kV, 3150A busbars, 40 kA,
50Hz, 650/275 kV BIL, equipped with:
Set 1
Q21, Q22 - Two (2) sets of three pole, three position, motor operated, in-
sulated disconnector
T5 – Two (2) sets of three (3) single-phase, 2-winding, 132/V3 / 110/V3 /
110/V3 kV/V/V, GIS type voltage transformers
X - Control cabinet, cables, metal support structure, grounding, etc. and
all accessories for complete bay
BG.5 A complete indoor GIS busbar earthing bay 145 kV, 3150A busbars, 40
kA, 50Hz, 650/275 kV BIL, equipped with:
Set 1
Q81, Q82 - Two (2) sets of three pole, make-proof, motor operated earth-
ing switch
B5 Surge arrester 145 kV, 120 kV continuous operating voltage, 10kA nom-
inal discharge current, 50Hz, single phase, heavy duty, station class, gap-
less, metal oxide type
Set 18
B6 Post Insulator 132 kV, 50 Hz, 650/275 kV BIL, 10 kN Set 18
B7.X Conductors for connection of the 132 kV switchgear, 145 kV, 2000 A, 40
kA
Lot 1
B8.X Insulators and fittings incl. all necessary clamps and connectors re-
quired for completing 132 kV switchgear
Lot 1
B9.X Gantry steel structures and equipment supports required for complet-
ing 132 kV switchgear
Lot 1
B10.X All other necessary material and equipment required for completing
132 kV switchgear
Lot 1
G Control, Protection, SCADA System and Metering
One (1) lot of complete equipment for control, protection, SCADA System
and metering for 132, 33 kV as well as LV AC and LV DC system (for
complete substation) shall be designed, calculated, supplied, delivered,
installed, tested and commissioned, under this contract.
Lot 1
The control and protection panels shall mirror the switchyard layout.
Enough space shall be reserved for future circuits.
The system comprise the following:
G1.1 Control, Protection and SAS set for 132 kV Overhead Line circuit, (in-
cluding the other end)
Set 4
G2.2 Control, Protection and SAS set for 132/33 kV Power Transformer cir-
cuits
Set 2
G3.2 Control, Protection and SAS set for Busbar 132 kV Set 1
G4 Control, Protection and SAS set for complete Switchgear 33 kV Set 1
G4.X Tariff metering panel(s) to accommodate programmable & recordable
digital 3-phase, 4-wire import and export MWh and MVArh meters (accu-
Lot 1
- 38 -
Tender Documents for 132/33 kV Substations, Package 4.1, Volume 3
BGD 2740 lot 4.1 v ol 3 2019 03 13.docx
No. Equipment Unit Qty.
racy class 0.2) for each line and transformer feeder. For each feeder,
minimum two (2) meters (main-1 & main-2) shall be provided
G5.X Digital Fault and Disturbance Recorder (DFDR) to accommodate all
feeders
Lot 0
G6.X Tele-control & Teleprotection & Tele-metering facilities, Lot 1
A complete lot of hardware and software, extension of the existing
equipment, necessary adjustment, adaptation, modification, integration
and configuration of new and existing equipment, all necessary modifica-
tion works in the hardware and software of the master stations, shall be
provided both at the National Load Despatch Centre (NLDC) at Aftabna-
gar and at the back-up station at Biddut Bhaban, for integration of the
complete substation
All required electrical signals shall be transmitted to the NLDC and the
back-up station through the industrial gateway of the substation automa-
tion system. All HV circuit breakers, disconnectors, tap changer, etc.,
shall be controlled from the NLDC through the gateway of the substation
automation system using the IEC 60870-5-104 protocol.
G10.X All other necessary material and equipment required for completing
control, protection, substation automation and metering system.
Lot 1
H Fibre Optic Multiplexer Equipment for Teleprotection
and Communication
H1.X Fibre Optic Multiplexer Equipment, a complete lot of fibre optic multi-
plexer equipment for protection & communication at substation shall be
designed, supplied, delivered, installed, tested and commissioned, under
this contract. Fibre optic multiplexer equipment is to be provided for.
Lot 1
Distance relay carrier signal (main and back-up)
Bus protection / breaker failure relay
SCADA data from switchgear and control system
VOIP system (2-IP Phone)
2-W remote subscriber ( 10 telephone sets)
Hot-line telephone system
H3.X A lot of underground optical fibre (48 cores) cables from terminal box
at gantry structure to MDF (Main distribution Frame) shall be designed,
supplied, delivered, installed, tested and commissioned, including supply
and installation of MDF and digital cables
Lot 1
I Multicore Low Voltage Auxiliary Power and Control Cables
I1.X A complete lot of multicore low voltage auxiliary power and control
cables, including all other necessary material and equipment, between all
items of equipment supplied under the contract shall be designed, sup-
plied, delivered, installed, tested and commissioned
Lot 1
J LV DC, Batteries, Chargers and DC Distribution
J1.X A complete lot consists of two (2) sets of 110 V Ni-Cd batteries, complete
with chargers and distribution switchboards, including all other necessary
material and equipment, shall be designed, supplied, delivered, installed,
tested and commissioned, under this contract, to provide complete LV DC
110 V supplies for the substation.
Lot 1