AL802ULADANAC Power Extender
Installation Guide(See Application Guide for additional information)
- 2 - AL802ULADA
Agency Listings:• ULListedControlUnitsforFireProtective SignalingSystems(UL864).• MEA-NYCDepartmentofBuildingsApproved.• CSFM-CaliforniaStateFireMarshalApproved.• FM-FactoryMutualApproved.• NFPA72Compliant.Input:• Powerinput120VAC60Hz,5amp.• Two(2)ClassA,StyleZortwo(2)ClassB, StyleW,X,YFACPinputs.• Two(2)NCdrycontacttriggerinputs.Output:• Class2Ratedpowerlimitedoutputs.• 24VDC@8ampmaxtotalalarmcurrent.• 2.5ampmaxcurrentperoutput.• Separate1.0ampauxiliaryoutput.• Two(2)outputsmaybeparalleledformorepoweronan indicatingcircuit(see Application Guide).• Programmablesupervisedindicatingcircuitoutputs: Four(4)ClassB,StyleW,X,YorTwo(2)ClassA, StyleZorOne(1)ClassA,StyleZandTwo(2) ClassB,StyleW,X,Y(see Application Guide).•Thermalandshortcircuitprotectionwithautoreset.Battery Backup:•Built-inchargerforsealedleadacidorgeltypebatteries.•Automaticswitchovertostand-bybatterywhen ACFails.• Zerovoltagedropwhenswitchingoverto batterybackup.
Supervision:•ACfailsupervision(form“C”contact,1amp/28VDC). Factorysetfor30secondswithoptional2.5to3hour delaysetting(fieldselectable).• InstantlocalACtroublereportingrelay (form“C”contact,1amp/28VDC).•Batterypresenceandlowbatterysupervision (form“C”contact,1amp/28VDC).Visual Indicators:•InputandoutputstatusLEDindicators.Special Features:• 2-wirehorn/strobeSyncmodeallowsaudible notificationappliances(horns)tobesilenced whilevisualnotificationappliances(strobes) continuetooperate.• TemporalCode3,SteadyMode,InputtoOutput FollowerMode(maintainssynchronizationof notificationappliancescircuit).• Compatiblewith12VDCor24VDCfirepanels.•Outputloopsupervisionsteeredtoinput1orinput2.• Signalcircuittroublememory(helpsidentify intermittentloopproblems).• Commontroubleinputandoutput.• Groundfaultdetection.Added Features:•Unitincludespowersupply,redenclosure,camlock, andbatteryleads.Enclosure Dimensions and Descriptions:AL802ULADA15.5”Hx12.23”Wx4.5”DProduct Weight:17lbs.
Overview:TheAltronixAL802ULADAisanextremelycosteffective8ampremotepowersupply/batterycharger.Itmaybecon-nectedtoany12or24voltFireAlarmControlPanel(FACP).PrimaryapplicationsincludeNotificationApplianceCircuit(NACsuchasstrobesandhorns)expansionsupporttomeetADArequirements.Italsoprovidesauxiliarypowertosupportsystemaccessories.Theunitdeliverselectronicallyregulatedandfiltered24voltpowertoClassB,StyleW,X,YorClassA,StyleZNACloopcircuits.Additionally,aseparate1.0Aauxiliaryoutputforfour(4)-wiresmokedetectorsisavail-able.The8ampmax.alarmcurrentcanbedividedbetweenthefour(4)outputsforpoweringNACdevices.Eachoutputisratedat2.5ampmax.,andcanbeindependentlyprogrammedforSteady,TemporalCode3orStrobeSynchronization.AlloutputsmaybeprogrammedforInputtoOutputFollowerMode(outputwillfollowinput).Anindividualoutputof4ampisachievedbyparalleling2outputs.Innon-alarmconditionindependentloopsupervisionforClassA,StyleZand/orClassB,StyleW,X,YFACPNACcircuitsisprovided.Intheeventofalooptrouble,theFACPwillbenotifiedviathesteeredinput(input1orinput2).Inaddition,therearecommontroubleoutputterminals(NC,C,NO)whichareusedtoindicategeneralloop/systemtrouble.AcommontroubleinputisprovidedforoptionalNC(normallyclosed)devicestoreporttroubletotheFACP.Two(2)FACPsignalingoutputscanbeemployedanddirectedtocontrolsupervisionandpowerdeliverytoanycombinationofthefour(4)outputs.
Specifications:
AL802ULADA - NAC Power Extender
AL802ULADA - 3 -
Power Supply Specifications:AC Input: 120VAC60Hz,5amp,suppliedbyamaximum15ampdedicatedbranchcircuit.
Output: Four(4)regulatedsupervisedNACoutputcircuits,24VDC,2.5ampmaximumcurrent.One(1)aux.specialapplication24VDCpoweroutputcircuit1amp,non-supervisedtotaloutputcurrentmustnotexceedcurrent8ampinAlarmCondition.
Battery: Usetwo(2)12VDC/12AHortwo(2)12VDC/7AHbatteriesconnectedinseries.
Stand-by/Alarm Current Consumption:
90mA/175mA
EOL Resistor (end of line):
2.2K(2200ohm),AltronixModel#AL-EOL22(included).
Ground fault maximumtest impedance:
1000ohm.
Stand-by Specifications:Stand-by Batteries Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output
24VDC/7AH 24Hours 8amp/5minutes ---
24VDC/12AH(usetwo(2)12VDCbatteriesinseries)
24Hours 8amp/5minutes 50mA
24VDC/36AH 24Hours 8amp/5minutes 1amp
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may, not exceed 8 amp total alarm current (example: AUX = 1 amp, outputs up to 7 amp).
Installation Instructions:WiringmethodsshallbeinaccordancewiththeNationalElectricalCode/NFPA70/NFPA72/ANSI,andwithalllocalcodesandauthoritieshavingjurisdiction.Productisintendedforindooruseonly. Carefully review: Application Guide for AL602ULADA, AL802ULADA, AL1002ULADA Power Supply Specifications (pg. 3) Stand-by Specifications (pg. 3) Output Programming Selection Table (pg. 4) Sync Mode Selection Table (pg. 4) Terminal Identification Table (pgs. 5-6) LED Status Indication Table (pg. 6)1.Mounttheunitindesiredlocation.Markandpredrillholesinthewalltolineupwiththetoptwokeyholesinthe enclosure.Installtwoupperfastenersandscrewsinthewallwiththescrewheadsprotruding.Placetheenclosure’s upperkeyholesoverthetwoupperscrews,levelandsecure. Markthepositionofthelowertwoholes.Removetheenclosure.Drillthelowerholesandinstallthetwofasteners. Placetheenclosure’supperkeyholesoverthetwoupperscrews.Installthetwolowerscrewsandmakesuretotighten allscrews(Enclosure Dimensions, pg. 12).Secureenclosuretoearthground(Fig. 1, pg. 3).2.Connecttheline(L),ground(G),andneutral(N),terminalstoaseparateunswitchedACcircuit(120VAC,60Hz) dedicatedtotheFireAlarmSystem.3.Measureoutputvoltagebeforeconnectingdevices.Thishelpsavoidpotentialdamage.4.Connectbatterytoterminalsmarked[+BAT--]onthePowerSupplyBoard(batteryleadsincluded). Usetwo(2)12VDCbatteriesconnectedinseries.5.Setoutputselectionswitchesmarked[OUT1throughOUT4]tofollowcorrespondinginput[IN1&IN2]and desiredoutputsignaltype (Output Programming Selection Table, pg. 4).6.ConnectFACPoutputtodesiredAL800LGK9Elogicboardinputs,andnotificationappliancestodesired AL800LGK9Elogicboardoutputs(see Application Guide). Note:The2-wirehorn/strobesyncmodewillonlysynchronizehorns,horn/strobes,strobeswith synchronizationcapability.
L G Nline
groundneutral
Fig. 1
- 4 - AL802ULADA
7.Forconnectionofsmokedetectors,digitaldialer(Optional Hookup Diagram, pg. 7).
Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:• ForallClassB,StyleW,X,Y,hookupsSW1&SW2ontheAL800LGKlogicboardmustbeopen. ForallClassA,StyleZhookupsSW1&SW2ontheAL800LGKlogicboardmustbeclosed.
Output Programming Selection Table: Outputs must be programmed independently (OUT1 - OUT4)
Function Switch Positions Descriptions
ON OFF
InputtoOutputFollowerMode
1 2,3 Outputfollowssignalitreceivesfromthecorrespondinginput(i.e.FACPSyncmodule-maintainssynchronizationofnotificationappliancecircuit).
TemporalCode3Mode 3 1,2 EnablesTemporalCode3signalgenerationoutput.Thismodewillacceptasteadyorapulsinginput.
SteadyMode 1,2,3 Asteadyoutputsignalwillbegenerated.Thismodewillacceptsteadyorpulsinginput.
For the above modes Dip Switch 4 determines which Input controls the corresponding output:Switch 4 in the ON position causes output(s) to be controlled by input 1.Switch 4 in the OFF position causes output(s) to be controlled by input 2.
Sync Mode Selection Table:
FunctionSwitch Positions
DescriptionsON OFF
AmsecoSyncMode*
1,3,4
2
ThismodeisdesignedtoworkwiththeAmsecoseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
FaradaySyncMode* 2,4 1,3
ThismodeisdesignedtoworkwiththeFaradayseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
Gentex®
SyncMode*GentexisaregisteredtrademarkofGentexCorporation.
1,2,3,4
ThismodeisdesignedtoworkwiththeGentex®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchro-nizingtheflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
SystemSensor®SyncMode*SystemSensorisaregisteredtrademarkofHoneywell.
1,2,4 3
ThismodeisdesignedtoworkwiththeSystemSensor®seriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
CooperWheelock®
SyncMode*CooperWheelockisaregisteredtrademarkofCooperWheelock.
2,3,4 1
ThismodeisdesignedtoworkwiththeCooperWheelockseriesofhorns,strobes,andhorn/strobestoprovideameansofsynchronizingtheTemporal-codedhorns,synchronizingtheone-secondflashtimingofthestrobe,andsilencingthehornsofthehorn/strobecombinationoveratwo-wirecircuitwhileleavingstrobesactive.
*Note:TheAL802ULADAwillonlysynchronizehorns,horn/strobesandstrobesthatcontainsynchronizationcapability.Contactsignalmanufacturerformoredetailedinfo.Thesamesynchronizationmodemustbeselectedforalloutputs
Note: It is required to control visual notification appliances (strobes) via input 1 (IN1) and audible notification appliances (horns) via input 2 (IN2). This allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate.
(AL800LGK Board)Output Dip Switches
INPUT SELECTTEMPORAL
STROBE SYNCIN>OUT SYNC
AL802ULADA - 5 -
Amount of Notification Appliances per NAC:Amseco 27perNAC* SystemSensor® 32perNAC*
Faraday 39perNAC* CooperWheelock® 32perNAC*
Gentex® 32perNAC*
*Not to exceed a maximum of 2.5 amp per NAC.
Terminal Identification Table:AL800LGK9E - Logic BoardTerminalLegend Function/Description
IN1+,IN1-IN2+,IN2-(Supervised)
Theseterminalsconnecttothe12VDCor24VDCFACPnotificationappliancecircuitoutputs.(ClassA,StyleZorClassB,StyleW,X,Y)Inputtriggervoltageis8-33VDC@5mAmin.Terminalpolarityisshowninalarmcondition.Duringanalarmconditiontheseinputswillcausetheselectedoutputschosentodrivenotificationappliances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4). AtroubleconditiononanoutputloopwillcausethecorrespondinginputtotriptheFACPbyopeningtheFACPloop.Analarmconditionwillalwaysoverridetroubletodrivenotificationappliances.
RET1+,RET1-RET2+,RET2-(Supervised)
For(ClassA,StyleZhookupstheseterminalpairsreturntoFACPNAC1and/orNAC2.ForClassB,StyleW,X,YhookupstheFACPEOLresistorfromtheNAC1and/orNAC2outputsareterminatedattheseterminals.
C“DRY1”NCC“DRY2”NC(Dryinputtrigger)
Anopenacrosstheseinputs,willcausetheselectedoutputschosentodrivenotificationappli-ances.Thedesignatedoutputsaresetbyoutputswitches[OUT1throughOUT4](Output Programming Selection Table, pg. 4).NotetheseinputsareunidirectionalandwillnotreportatroubleconditiontotheFACP.
+OUT1--+OUT2--+OUT3--+OUT4--(Supervised)
Notificationappliancesareconnectedtotheseregulatedoutputs (see Application Guide pg. 2-4). Eachpower-limitedoutputwillsupply2.5amp.Two(2)outputsmaybeconnectedinparallelforamaximumNACoutputcapabilityof4amp.Totalsupplycurrentis8amp(see note below).Outputsarecontrolledbydesignatedinput1[IN1]orinput2[IN2](Output Programming Selection Table, pg. 4). Maximumlinelossorvoltagedrop(testedwith2.5V).
C“FAULT”NC(Commontroubleinput)
Anopencircuitacrossthispairofterminalswillcause[IN1andIN2]tosimultaneouslysignalatroubleconditionbacktotheFACP(TypicallyusedtoreportACorBATFail).(form“C”contact1amp/28VDC)(Fig. 2, pg. 7).
NC,C,NO(Commontroubleoutput)
Thesearedrycontacttroubleoutputsthatfollowanygeneralloop/systemtroubleconditions.(Typicallyusedtotriggeradigitalcommunicatororotherreportingdevice).(form“C”contact1amp/28VDC0.35PowerFactor)(Fig. 2, pg. 7) .
--AUX+Thisseparate1ampmaxauxiliarySpecialApplicationPoweroutputcircuitistypicallyusedto power4-wiresmokedetectors.Seeattachedlistofdevices(Appendix A, pgs. 10-12).
+DC-- 24VDCfrompowersupply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may, not exceed 8 amp total alarm current (example: AUX = 1 amp, outputs up to 7 amp).
- 6 - AL802ULADA
Terminal Identification Table:AL800ADA Power Supply Board*Terminal Legend Function/Description
L,G,N Connect120VACtotheseterminals:Ltohot,Ntoneutral,Gtoground.
-DC+ 24VDC@8ampinalarmnon-powerlimitedoutput.
ACFAILNO,C,NC
Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.
ACLOCALNC,NO,C
Form“C”drycontactsusedtoinstantaneouslysignalthelossACtolocalannunciationdevices,withACpresentterminalsmarkedNOandCareopen,NCandCareclosed.WhenlossofACoccursterminalsmarkedNOandCareclosed,NCandCareopen.
BATFAILNO,C,NC
Form“C”drycontactsusedtosignallowbatteryvoltageorlossofbatteryvoltage.UndernormalconditionsterminalsmarkedNOandCareopen,NCandCareclosed.DuringatroubleconditionterminalsmarkedNOandCareclosed,andNCandCareopen(Fig. 2, pg. 7).
+BAT- Stand-bybatteryinput(leadsprovided)(Fig. 2, pg. 7).
*Power Board Parameter Specifications:• ACFailconditionwillreportapproximately30secondsafterlossofAC.Todelayreportfor2.5to3hourscut jumperACDELAYonthePowerSupplyBoard(ACtroubleoutputdelayoption).IfthismodeisselectedthePower SupplyBoardmustberesetbyremovingallpowertoitfor30seconds.• Lowbatteryconditionwillreportatapproximately21VDC.• Batterypresencedetectionwillreportwithin180secondsafterbatteryremainsundetected(missingorremoved). Arestoredbatterywillreportwithin30seconds.
LED Diagnostics:AL800ADA - Power Supply BoardRed (DC) Green (AC) Power Supply Status
ON ON Normaloperatingcondition.
ON OFF LossofAC,Stand-bybatterysupplyingpower.
OFF ON NoDCoutput.
OFF OFF LossofAC.Dischargedornostand-bybattery.NoDCoutput.
AL800LGK9E - Logic BoardLED OFF ON BLINK (LONG)* BLINK (SHORT)**
ON Normal AlarmCondition TroubleCondition TroubleConditionMemory
ON Normal AlarmCondition TroubleCondition TroubleConditionMemory
OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory
OFF Normal AlarmCondition TroubleCondition TroubleConditionMemory
Input1 Normal AlarmCondition TroubleCondition ---
Input2 Normal AlarmCondition TroubleCondition ---
Fault Normal AlarmCondition --- ---
* Indicatescurrenttroublecondition.Whentrouble(open,shortorground)occursonaspecificoutput,the correspondingredoutputLED,[OUT1-OUT4]willblink.ThecorrespondinggreeninputLEDwill blinkaswell.Looptroublewillreportwithin30seconds.
**Indicatestroubleconditionmemory.Whenatroubleconditionrestores,theunitsredoutputLED,[OUT1-OUT4] willblinkwithashorteranddistinctlyadifferentduration.ThegreeninputLEDswillbeoff(normalcondition). Toresetthememorydepresstheresetbutton(Fig. 2c, pg. 7).TheLED(s)willextinguish.
Note:Ifindicatingcircuitshavebeenrestored,memoryresetisnotrequiredfornormaloperationoftheunit.
AL802ULADA - 7 -
These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2
Digital Communicator orLocal Annunciator Dry output Contact(Form "C" contacts)
4-wire SmokeDetector
+
--
+
--
4-wire SmokeDetector
FireAlarmControlPanel(FACP)
EOL PowerSupervision Relay
(Not Supplied)
EOLResistor
fromFACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NCC
NOC
"FA
ULT"
NC
OUT1 OUT3
OUT2 OUT4INPUT SELECT
TEMPORALSTROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--IN2+ C "DRY1" NCRET1+ RET1-- RET2--RET2+ C "DRY2" NC
+ OUT2 -- + OUT3 -- + OUT4 --
INPUT SELECTTEMPORAL
STROBE SYNCIN > OUT SYNC
-- AUX +
UPPER TERMINALSLOWER TERMINALS
AddressableControl ModuleTrigger OutputSee Note 2
lineground
neutralGreenLead
Use separate knockout. Keep 1/4" spacing from non power limited wiring
Power-LimitedOutputs2.5ampperoutputinalarm(total=8amp)(Supervised)
Supervised Non-Supervised
Non-Supervised
Non-Supervised
RESET
unswitched 120VACpower mains
(non-power limited) NC C NO NC C NO NC C NO
AC Local AC D
ELAY
BAT FAIL AC FAIL
AC LED
VR1
Fig. 2
These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2
Digital Communicator orLocal Annunciator Dry output Contact(Form "C" contacts)
4-wire SmokeDetector
+
--
+
--
4-wire SmokeDetector
FireAlarmControlPanel(FACP)
EOL PowerSupervision Relay
(Not Supplied)
EOLResistor
fromFACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NCC
NOC
"FA
ULT"
NC
OUT1 OUT3
OUT2 OUT4INPUT SELECT
TEMPORALSTROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--IN2+ C "DRY1" NCRET1+ RET1-- RET2--RET2+ C "DRY2" NC
+ OUT2 -- + OUT3 -- + OUT4 --
INPUT SELECTTEMPORAL
STROBE SYNCIN > OUT SYNC
-- AUX +
UPPER TERMINALSLOWER TERMINALS
AddressableControl ModuleTrigger OutputSee Note 2
lineground
neutralGreenLead
Use separate knockout. Keep 1/4" spacing from non power limited wiring
Power-LimitedOutputs2.5ampperoutputinalarm(total=8amp)(Supervised)
Supervised Non-Supervised
Non-Supervised
Non-Supervised
RESET
unswitched 120VACpower mains
(non-power limited) NC C NO NC C NO NC C NO
AC Local AC D
ELAY
BAT FAIL AC FAIL
AC LED
VR1
NC
CN
OC
"FA
ULT
" N
C
Fig. 2b
Fig. 2a
These circuits are used tomonitor AC and Bat Fail andwill cause a simultaneous trouble condition to the FACP's IN1 and IN2
Digital Communicator orLocal Annunciator Dry output Contact(Form "C" contacts)
4-wire SmokeDetector
+
--
+
--
4-wire SmokeDetector
FireAlarmControlPanel(FACP)
EOL PowerSupervision Relay
(Not Supplied)
EOLResistor
fromFACP
SW1
-- DC +
SW2
+ OUT1 --
OUT1 OUT2 OUT3 OUT4
INP1 INP2
FAULT
NCC
NOC
"FA
ULT"
NC
OUT1 OUT3
OUT2 OUT4INPUT SELECT
TEMPORALSTROBE SYNC
IN > OUT SYNC
IN1+ IN1-- IN2--IN2+ C "DRY1" NCRET1+ RET1-- RET2--RET2+ C "DRY2" NC
+ OUT2 -- + OUT3 -- + OUT4 --
INPUT SELECTTEMPORAL
STROBE SYNCIN > OUT SYNC
-- AUX +
UPPER TERMINALSLOWER TERMINALS
AddressableControl ModuleTrigger OutputSee Note 2
lineground
neutralGreenLead
Use separate knockout. Keep 1/4" spacing from non power limited wiring
Power-LimitedOutputs2.5ampperoutputinalarm(total=8amp)(Supervised)
Supervised Non-Supervised
Non-Supervised
Non-Supervised
RESET
unswitched 120VACpower mains
(non-power limited) NC C NO NC C NO NC C NO
AC Local AC D
ELAY
BAT FAIL AC FAIL
AC LED
VR1
Fig. 2cTroubleMemoryResetButton
CommontroubleInput/Output
Optional Hookup Diagram:
- 8 - AL802ULADA
Optional hookups:1- BatteryandACmonitoring:ACorBatteryFailconditionwillcausethecommontroubleinput[C“FAULT”NC]toreportbacktotheFACPviainput1andinput2.Thecommontroubleinputmayalsobeusedforotheroptional supervisorymonitoring.
ToreportACandBatteryTroubleconnectthebatteryandACFailrelayoutputshownin(Fig. 2a)tothe commontroubleinput.
2- Drycontactinput(C“DRY1”NC)(C“DRY2”NC)canbeusedtoalarmoutputfroman addressablemodule(theseinputsareunidirectionandcannotreportbacktotriggermodule).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.
3- Auxiliaryoutput(-AUX+)24VDCat1ampmax.
4- ACLocal[NC,C,NO]shouldconnecttothehostcontrolpanelforlocalannunciationof thetroublecondition.
Note: Ifcommontroubleinput,terminalsmarked[C“FAULT”NC]arenotused,theseterminalsmustbe shorted(connectjumper)toremaininactive.Foroptionalhookups(Fig. 2b).
Maintenance:Unitshouldbetestedatleastonceayearfortheproperoperationasfollows:
Output Voltage Test:Undernormalloadconditions,theDCoutputvoltageshouldbecheckedforpropervoltagelevel(26.2-26.4VDC recommended range).Battery Test:Undernormalloadconditionscheckthatthebatteryisfullycharged.Checkspecifiedvoltagebothatbatteryterminalandattheboardterminalsmarked[+BAT--]toinsurethereisnobreakinthebatteryconnectionwires.Fuses:Checkinputandoutputfusesonthepowersupplyboard,replaceifnecessary.Inputfuseratingis5amp@250V.Note:Maximumchargingcurrentis3.2amp.Note:Expectedbatterylifeis5years,howeveritisrecommendedchangingbatteriesin4yearsorlessifneeded.
AL802ULADA - 9 -
Battery Calculation Worksheet
Unitsarecapableofrecharging40AHbatterymax.Iftotalampere-hourrequiredexceeds40AH,decreaseAUXcurrenttoprovideenoughstand-bytimefortheapplication.
DeviceNumber of Devices
Current per DeviceStand-by Current
Alarm Current
Foreachdeviceusethisformula: Thiscolumn x Thiscolumn = Equals Currentpernumberofdevices.
AL802ULADA(Currentdrawfrombattery)
1Stand-by: 90mA 90mA
Alarm: 175mA 175mA
A AL802 Current 90mA 175mA
AuxiliaryDevices Refertodevicemanualforcurrentratings.
Alarm/Stand-by mA mA mA
Alarm/Stand-bymA
mA mA
Alarm/Stand-by mA mA mA
B Auxiliary Devices Current (must not exceed 1 amp)
Refertodevicemanualforcurrentratings.
Alarm: mA 0mA mA
Alarm:mA
0mA mA
Alarm: mA 0mA mA
Alarm: mA 0mA mA
C NotificationAppliancesCurrent must notexceed8amp(8000mA) 0mA mA
D Totalalarmcurrent mA mA
E Totalcurrentratingsconvertedtoamperes(lineDx.001) A A
F Numberofstandbyhours(24forNFPA72,Chapter1,1-5.2.5). H
G MultiplylinesEandF. Totalstand-byAH AH
HAlarmsoundingperiodinhours.(Forexample,5minutes=.0833hours.)
H
I MultiplylinesEandH. TotalalarmAH AH
J AddlinesGandI. Totalstand-byandalarmAH AH
KMultiplylineJby1.30.(30%extrainsurancetomeetdesiredperformance)Totalampere-hoursrequired
AH
- 10 - AL802ULADA
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
TableA-1belowlistsfour(4)wiresmokedetectorscompatiblewithAL802ULADAAUXoutput.
Smoke Detector/Base Detector TypeMax StandbyCurrent (mA)
AlarmCurrent (mA)
SystemSensorB112LP Base 0.12 36
SystemSensorB114LP Base * *
SystemSensorB404B Base * *
SystemSensorDH100ACDC Photoelectric 0.15 0.70
SystemSensorDH100ACDCLP Photoelectric 0.15 0.70
SystemSensorDH100ACDCLPW Photoelectric 0.15 0.70
SystemSensorDH400ACDCI IonizationDuct 25 95
SystemSensorDH400ACDCP PhotoelectricDuct 25 95
SystemSensor1112/24/D Ionization 0.05 50
SystemSensor1424 Ionization 0.10 41
SystemSensor1451(w/B402BBase) Ionization 0.10 39
SystemSensor2112/24ATR Photoelectric 0.50 60/70
SystemSensor2112/24AITR Photoelectric 0.50 60/70
SystemSensor2112/24/D Photoelectric 0.05 50
SystemSensor2112/24R Photoelectric 0.50 60/70
SystemSensor2112/24TR Photoelectric 0.50 60/70
SystemSensor2112/24T/D Photoelectricw/135oThermal 0.05 50
SystemSensor2112/24TSRBPhotoelectricw/135o
ThermalSupervisoryRelay15 45
SystemSensor2312/24TB Photoelectric 0.12 50
SystemSensor2412(12volt) Photoelectric 0.12 77
SystemSensor2412AT(12volt) Photoelectric 0.12 58
SystemSensor2412TH(12volt) Photoelectric 0.12 77
SystemSensor2424 Photoelectric 0.10 41
SystemSensor2424TH Photoelectric 0.10 41
SystemSensor2451 Photoelectric 0.10 39
SystemSensor2451TH(with/B402BBase) Photoelectric 0.10 39
SystemSensor2W-MOD LoopTest/MaintenanceMod. 30 50
AL802ULADA - 11 -
A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base Detector TypeMax StandbyCurrent (mA)
AlarmCurrent (mA)
SystemSensor4W-B(12/24volt) PhotoelectricI3 .05 23
SystemSensor4WT-B(12/24volt) PhotoelectricI3w/Therm .05 23
SystemSensor4WTA-B(12/24volt) I3Photow/Therm/Sounder .05 35
SystemSensor4WTR-B(12/24volt) I3Photow/Therm/Relay .05 35
SystemSensor4WTR-B(12/24volt)I3Photow/Therm/Sounder/Relay
.05 50
SystemSensor4WITAR-B(12/24volt)I3Photow/IsolatedTherm/
Sounder/Relay.05 50
SystemSensor2W-MOD2I3LoopTest/Maintenance
Mod..05 *
SystemSensorRRS-MODI3ReversingRelay/Sync
Module.05 *
SystemSensor6424 ProjectedBeam 10 28.4
SystemSensorBeam1224(S) ProjectedBeam 17 38.5
*Contactmanufacturerforcurrentdraws
A.2 Relays
TableA-3belowlistsrelayscompatiblewithAL802ULADAAUXoutput.
Manufacturer Model Current (mA)
SystemSensor
PR-1 PR-2 PR-3 EOLR-1 R-10T R-14T R-20T R-24T R-10E R-14E R-20ER-24E
15 30 30 30 23 23 40 40 23 23 40 40
- 12 - AL802ULADA
12.230"
15.500"
1.100"
0.910"
1.100"
0.910"
0.790"
1.100"
1.500"
1.250"
5.000"
1.250"
1.500"4.615"4.615"1.500"
1.750"
1.500"4.615"4.615"1.500"
1.750"
4.500"4.500"1.250"
1.500"
5.000"
2.000"
2.000"
1.250"
1.375"
1.125"
Enclosure Dimensions:15.5”Hx12.23”Wx4.5”D
MEMBER
Altronixisnotresponsibleforanytypographicalerrors.
14058thStreet,Brooklyn,NewYork11220USA,718-567-8181,fax:718-567-9056website:www.altronix.com,e-mail:info@altronix.com,LifetimeWarranty,MadeinU.S.A.IIAL802ULADA L27K