Asset: BEDFORD ACADEMY - BROOKLYN, 1119 BEDFORD AVENUE, New York, 11216
Inspection Id Inspection Type Time In Last Edited
SA : K994 Architectural - Senior 2020-08-06 7:44 AM 2020-09-11 12:06 PM
AA : K994 Architectural - Associate 2020-08-06 8:44 AM 2020-08-06 1:25 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Adofo Muhammad
Organization Bedford Academy - Brooklyn
Did you meet with this Principal? No
Did this Principal provide feedback? Yes
Summary of Principal's Feedback A Principal questionnaire form was returned with the followingcomment. The HVAC system does not properly function.
Custodian Was not present
Fireman Jerry Jones
Building Square Footage 23000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B+PH
Comments on the Number of Classrooms 12
Comments on the Year Built 1920
Student Population 361
Staff Population 45
Weather Fair
Facade Photo
Corner of Bedford Avenue and MonroeStreet - Northeast View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 1 of 24
Main Entrance Photo
Facade A - Bedford Avenue
Roof Photo
Roof 1 - North View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Limited Parapet repairs
Year: 2017
Systems: Limited Window repairs; limited Ceiling replacement(Rooms 101, 107, 204 and Entrance Lobby)
Year: 2016
Systems: Parapet reconstructed including Coping along BedfordAvenue; Cornice removed
Year: 2014
Systems: Structural crack repairs at Basement
Year: 2010
Systems: Complete Exterior and Interior Modernization andBuilding conversion project including Roof Barriers
Year: 2006
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? Yes
Year Leased 2005
Inspection Full Inspection
Priority Condition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 2 of 24
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? Yes
Are all floors of the building accessible through compliant means? Yes
Accessible classrooms exists on each floor? Yes
Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes
If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings Yes Yes
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware No No
Interior Corridors and Lobbies Yes
Interior Elevators Yes Yes
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria Basement Yes Yes Yes Yes
Classrooms 1st - 3rd Floor Yes Yes
Computer Rooms No
Gymnasium No
Library No
Main Office Room 106 Yes Yes
Multi-purpose Room No
Nurse's Room Room C04 Yes Yes
Pool No
Science Lab Room 304 Yes Yes
Toilet Rooms (Boys) Basement and 2nd Floors Yes Yes
Toilet Rooms (Girls) Basement, 1st and 3rd Floors Yes Yes
Toilet Rooms (Staff) Basement and 1st Floors Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 3 of 24
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CHIMNEY Inspected
Material Type(s) Metal
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 4 of 24
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Roof Plan reference
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Exit 2
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Steel
Replacement Quantity 8,000
Replacement Uom S.F.
InspectedInstance on Facades A, C - F
Instance Condition 3 - Fair
Instance Quantity 8,000
Instance Quantity Uom S.F.
Deficiency BRICK: OPEN JOINTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 5 of 24
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: MAJOR / THRU CRACKS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 6 of 24
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPOINT
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 7 of 24
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry, Metal
Replacement Quantity 3,000
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 3,000
Instance Quantity Uom C.F.
Deficiency BRICK: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 8 of 24
Question Response
EXTERIOR
PARAPETS
Deficiency Photo1
Facade A - Roof 1
Violations No violations recorded.
Deficiency BRICK: EFFLORESCENCE
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 1
Deficiency Photo1
Facade A - Roof 1
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 8,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 9 of 24
Question Response
EXTERIOR
ROOF
Roofing
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on IRMA: All Roofs
Instance Condition 4 - Between Fair and Poor
Instance Quantity 8,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2005
Source of Installation Custodial Staff
Deficiency IRMA: ROOFING: LOSS OF GRAVEL
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency IRMA: ROOFING: DAMAGED INSULATION
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 10 of 24
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1
Violations No violations recorded.
Deficiency IRMA: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 11 of 24
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Deficiency Photo1
Roof 1 - Room 305 shown, Roof 1 - Room 304 similar
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 12 of 24
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Main Entrance
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 4,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: Facades A, C, E
Instance Condition 3 - Fair
Instance Quantity 4,000
Instance Quantity Uom S.F.
Installation Year 2005
Source of Installation Custodial Staff
Deficiency ALUMINUM - OTHER: BROKEN PANE
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 13 of 24
Question Response
EXTERIOR
WINDOWS
WINDOWS
Elevation
Deficiency Quantity 160
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - Room 305 shown, Facade A - Room 304 similar
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 3 - Fair
Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING
Deficiency Location/Instance Basement - Boiler Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 14 of 24
Question Response
INTERIOR
STRUCTURAL
COLUMNS/BEAMS/BEARING WALLS Inspected
Basement - Boiler Room
Violations No violations recorded.
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CONCRETE SLAB ON GRADE: MINOR CRACKS
Deficiency Location/Instance Basement - Boiler Room
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Boiler Room, Electric Service Room C10A, WaterSprinkler Room C10C
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 3 - Fair
Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED
Deficiency Location/Instance Basement - Boiler Room
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 15 of 24
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on Basement (600 SF)
Ceiling
InspectedInstance on Basement (600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Basement (600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Equipment
Does not ExistInstance on Basement (600 SF)
Floor Finish
InspectedInstance on Basement (600 SF)
Condition 5 - Poor
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Center
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 16 of 24
Question Response
INTERIOR
CAFETERIA
Floor Finish
Deficiency Photo1
Center
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Entrance
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Entrance
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on Basement (600 SF)
Stage
Does not ExistInstance on Basement (600 SF)
Walls
InspectedInstance on Basement (600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement (600 SF)
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Rooms 304, 305
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 17 of 24
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Room 304
Violations No violations recorded.
Deficiency GYPSUM BOARD: DAMAGED/DETERIORATED
Deficiency Location/Instance Corridor near Room 106, 104A
Deficiency Quantity 15
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 106
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Room 302A
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 18 of 24
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling Inspected
Room 302A
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Main Entrance Lobby, Corridor near Room C10C, C01
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Main Entrance Lobby
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Corridor near Room 302A, 106, 104A, 103, 102, C10C
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 103
Violations No violations recorded.
Specialties Inspected
Classroom Locker(s) Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 19 of 24
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Specialties
Classroom Locker(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Fixed Seating Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement
Ceiling
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Servery, Back of the Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Servery
Violations No violations recorded.
Door(s)
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency QUARRY TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Near stove
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 20 of 24
Question Response
INTERIOR
KITCHEN
Floor Finish
Purpose of Action LEVEL 2
Deficiency Photo1
Near stove
Violations No violations recorded.
Walls
InspectedInstance on Basement
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIBRARY Does not Exist
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Does not Exist
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Inspected
InspectedInstance on Room 304
Alternative use No
Fixed Equipment
InspectedInstance on Room 304
Condition 5 - Poor
Deficiency CABINETRY: MISSING/DAMAGED
Deficiency Location/Instance Room 304
Deficiency Quantity 40
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 304
Violations No violations recorded.
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 21 of 24
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Does not Exist
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Partition Does not Exist
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stair B/Basement
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair B/Basement
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Does not Exist
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GYPSUM BOARD: DETERIORATED
Deficiency Location/Instance Rooms C10D, C10,E, Kitchen
Deficiency Quantity 15
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 22 of 24
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room C10D
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Does not Exist
Drainage System for Concrete Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Does not Exist
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Does not Exist
Student Use Does not Exist
Site Sidewalks & Walkways Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 23 of 24
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Bedford Avenue
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Bedford Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
PLAYING SURFACE Does not Exist
RETAINING WALLS Does not Exist
SEATING Does not Exist
SITE WALLS (NOT RETAINING WALLS) Does not Exist
STAIRS/RAMPS: EXTERIOR Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K994
PB/A&W Print Date: 9/13/2020Page 24 of 24