presented byMinnesota Electrical Association

Copyright © 2018 Minnesota Electrical Association, Inc.All rights reserved. No part of the contents of this PowerPoint may be reproduced or transmitted in any form or by any means without the written permission of the publisher.

1

This class has been approved for 2 hours continuing education code credits

DISCLAIMER:“Through the presentation of this course and/or these

materials no representation actual or implied is made that the trainer or MEA/ETN is setting or enforcing specific standards or is providing peer review, certification, accreditation, or product testing”.

The material is adapted from the 2017 NEC® NFPA 70. Actual code articles in their entirety are required to

maintain compliance.

2

Residential branch circuit requirementsGFCI/ AFCI requirementsRequired outlets Branch Circuit Sizing Branch circuit loads Dryer Calculations

3

Review of branch circuit requirements in residential installations

4

Branch circuits shall be rated with the maximum permitted ampere rating of the overcurrent device.

Rating for other than individual branch circuits shall be 15, 20, 30, 40, & 50 A.

The Ampere rating of the Overcurrent device shall determine the circuit rating

See exception for industrial premises

5

Presenter
Presentation Notes
Exceptions for industrial premises

A load where the maximum current is expected to continue for 3 hours or more.

Typically requires overcurrent and conductors to be sized at 125% of the anticipated load

6

A) General.

Branch circuits shall be permitted as multiwire circuits. – and are permitted to be considered multiple circuits

All conductors of a multiwire branch circuit shall originate from the same panelboard or similar distribution equipment.

7

8

(B) Disconnecting Means.

Each multiwire branch circuit shall be provided with a means that will simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates.

(C) Mulitwire branch circuits shall supply only line to neutral loads.

Exception for one utilization equipment - or where the ungrounded conductors are disconnected simultaneously

9

Presenter
Presentation Notes
IN: See 240.15B for use of single pole breakers

10

(D) Grouping. Ungrounded and grounded conductors of each multiwire branch circuit shall be grouped as per 200.4 (B) - by wire ties or similar means in at least one location within an enclosure.

Exceptions to 200.4 (B) : grouping shall not apply (1) If the circuit enters from a cable or raceway unique to the circuit

that makes the grouping obvious. (2) or if the branch circuits pass though a box without loops for

future termination s or splices.

11

12

(A) Grounded conductors are identified as per 200.6 (Grounded conductors)

(B) Equipment grounding conductors are identified as per 250.119 (Grounding conductors)

(C) Ungrounded conductors – (1) If there are different voltage systems within the premises, identify and post the wiring systems marking system. If adding a new system to an existing system, only the new system is required to be marked (2) Tag or color code the DC systems

13

(A) In dwelling units and guest suites of hotels- etc. the voltage that supplies luminaires and cord and plug connected loads 1440VA or ¼ HP or less shall not exceed 120V.

(B) 120 Volts maximum for terminals of lampholders with in their voltage rating, auxiliary equipment of electric discharge lamps, cord or permanently connected utilization equipment.

(C) 277V to ground as listed in 1-6 (D) 600 volts between conductors in 1-3

14

Multiple Branch Circuits. Where two or more branch circuits supply devices or equipment on the same yoke or mounting strap, a means to simultaneously disconnect the ungrounded supply conductors shall be provided at the point at which the branch circuits originate.

Note: 300.13 (B) requires that the continuity of the grounded conductor for a multi-wire branch circuit shall not depend on the connection through a device .

15

Presenter
Presentation Notes
Multi pole breaker or breaker with approved handle ties

Section IIFault detection

16

(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles:

(1) Bathrooms(2) Garages & accessory buildings that have a floor located at or below grade level (3) Outdoors (4) Crawl spaces: at or below grade level (5) Unfinished basements- not intended as habitable rooms (6) - (10) ContinuedFor purposes of this section- the distance shall be the shortest path a cord , connected to the receptacle will follow without piercing a floor, wall, ceiling, fixed barrier, or passing through a doorway , window...

17

Exception to (3): Receptacles that are not readily accessible and are supplied by a branch circuit dedicated to electric snow-melting, deicing, or pipeline and vessel heating equipment shall be permitted to be installed in accordance with 426.28 or 427.22, as applicable.Exception to (5): A receptacle supplying only a permanently installed fire or burglar alarm system shall not be required to have ground-fault circuit-interrupter protection.

18

19

(A) Dwelling Units- continued

(6) Kitchens : countertop receptacles (7) all Sinks: within 6’ of top inside edge of the bowl(8) Boathouses(9) Bathtubs or shower stalls: within (6’) of outside edge (10) Laundry areas

20

(B) is for non-dwelling units (C) Boat houses All occupancies – for circuits

not exceeding 240 volts (D) Kitchen dishwasher circuits in dwelling

occupancies NEW (E) All lighting outlets in crawl spaces

21

22

Branch circuits for lighting and for appliances, including motor-operated appliances, shall be provided to supply the loads calculated in accordance with 220.10.

Branch circuits shall be provided for specific loads not covered by 220.10 where required elsewhere in this Code and for dwelling unit loads as specified in 210.11(C).

23

A) Number of Branch Circuits. Minimum number of branch circuits shall be determined from the total calculated load and the size or rating of the circuits used. In all cases the number of circuits shall be sufficient to supply the load served. The circuit shall not exceed the maximum specified in 220.18

B) Load Evenly Proportioned Among Branch Circuits. This load shall be evenly proportioned among multi-outlet branch circuits within the panelboard(s).

24

Presenter
Presentation Notes
Multi outlet branch circuit should divide the load proportionally . There is no maximum number of outlets defined by the NEC .

C) Dwelling Units.(1) Small-Appliance Branch Circuits.

In addition to the number of branch circuits required by other parts of this section, -

Two or more, 20-ampere small-appliance branch circuits shall be provided for all receptacle outlets specified by 210.52(B). (Kitchen, pantry, dining room)

25

C) Dwelling Units.(2) Laundry Branch Circuits.

In addition to the number of branch circuits required by other parts of this section,

At least one additional 20-ampere branch circuit shall be provided to supply the laundry receptacle outlet(s) required by 210.52(F). This circuit shall have no other outlets. This is not the electric dryer receptacle

26

C) Dwelling Units.

(3) Bathroom Branch Circuits. In addition to the number of branch circuits

required by other parts of this section, at least one 20-ampere branch circuit shall be

provided to supply bathroom receptacle outlet(s). Such circuits shall have no other outlets.Exception: Where the 20-ampere circuit supplies a

single bathroom, --outlets for other equipment within the same bathroom shall be permitted to be supplied in accordance with 210.23(A)(1) and (A)(2).

27

28

(C) Dwelling Units.

NEW (4) Garage Branch Circuits. • In addition to the other required branch circuits, one 20A

-120V branch circuit shall be installed to supply receptacle outlets. This circuit shall have no other outlets

• EXCEPT that this circuit can supply readily accessible outdoor receptacles

29

Dedicated 20A circuit

Arc Fault circuit interruption shall be as in 210.12 A-B-C and the AFCI shall be readily accessible

30

A) Dwelling Units.All 120-volt, single phase, 15- and 20-ampere branch

circuits supplying outlets installed in dwelling unit kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas shall be protected by any of the means described in 210.12(A)(1)-(6):Not in bathrooms, rooms not intended as habitable rooms, garages, or outdoors

31

Presenter
Presentation Notes
Bathrooms were not included in the 2014 changes for requiring AFCI for most of the rest of the dwelling.

(A) Dwelling Units. (1) A listed combination-type arc-fault circuit

interrupter, provide protection of entire branch circuit (2) A listed branch/feeder-type AFCI installed at the

origin of the branch-circuit in combination with a listed outlet branch-circuit type arc-fault circuit interrupter installed at the first outlet box on the branch circuit. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit.

32

Presenter
Presentation Notes
Combination type is both series and parallel circuit protection . # 1 is traditional AFCI Breaker # 2 A “Listed Branch/ feeder” breaker provides parallel protection and the OBC receptacle style provides series protection … As of 2014 a breaker that provides a “DUAL” function rated panel breaker both AFCI and GFCI is available

For circuits that need GFCI and AFCI-as in Kitchens and Laundry, a “dual” function breaker is available

AFCI and GFCI

33

(A) Dwelling Units. (3) A listed supplemental arc protection circuit breaker

installed at the origin of the branch circuit in combination with a listed outlet branch-circuit type arc-fault circuit interrupter installed at the first outlet box on the branch circuit where all of the following conditions are met:◦ a. The branch-circuit wiring shall be continuous from the branch-

circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter.

◦ b. The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 15.2 m (50 ft) for a

◦ 14 AWG conductor or 21.3 m (70 ft) for a 12 AWG conductor.◦ c. The first outlet box in the branch circuit shall be marked to

indicate that it is the first outlet of the circuit.

34

Presenter
Presentation Notes
As of early 2014… # 3 Not available

(A) Dwelling Units. (4) A listed outlet branch-circuit type arc-fault circuit interrupter

installed at the first outlet on the branch circuit in combination with a listed branch-circuit overcurrent protective device where all of the following conditions are met:

a. The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter.

b. The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed (50 ft) for a 14 AWG conductor or (70 ft) for a 12 AWG conductor.

c. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit.

d. The combination of the branch-circuit overcurrent device and outlet branch-circuit AFCI shall be identified as meeting the requirements for a system combination–type AFCI and shall be listed as such.

35

Presenter
Presentation Notes
As of early 2014 # 4 not available

(A) Dwelling Units. (5) If RMC, IMC, EMT, Type MC, or steel-armored Type AC cables

meeting the requirements of 250.118, metal wireways, metal auxiliary gutters, and metal outlet and junction boxes are installed for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, it shall be permitted to install a listed outlet branch-circuit type AFCI at the first outlet to provide protection for the remaining portion of the branch circuit.

(6) Where a listed metal or nonmetallic conduit or tubing or Type MC cable is encased in not less than (2 in.) of concrete for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, it shall be permitted to install a listed outlet branch-circuit type AFCI at the first outlet to provide protection for the remaining portion of the branch circuit.

36

Presenter
Presentation Notes
This was an accepted practice in 2011 code so #5 is not new . This was OK in the 2011 NEC so # 6 is not new.

(B) Dormitory Units. 15-20 A circuits that supply outlets and devices in dormitory bedrooms, living rooms, hallways, closets, bathrooms, and similar rooms shall be protected by the same methods

37

NEW (C) Guest rooms and guest suites- All circuits supplying devices or outlets shall have AFCI

(D) Modifications to dwelling and dormitory circuits are to be AFCI protected except: if the modification is not more than 6 ft. and does not include additional outlets or devices. (re-routing circuits)

38

(1) General. Branch-circuit conductors shall have an ampacity not less than maximum load to be served. Conductors shall be sized to carry not less than the larger of 210.19(A)(1)(a) or (b). (following)

(a) Minimum branch-circuit conductor size shall have an allowable ampacity not less than non-continuous load plus 125 percent of continuous load.

(b) The minimum branch-circuit conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of any adjustment or correction factors.

39

(2) Multioutlet Branch Circuits. Conductors of branch circuits supplying more than one receptacle for cord-and-plug-connected portable loads shall have an ampacity of not less than the rating of the BC.

(3) Household Ranges and Cooking Appliances. shall have an ampacity not less than the rating of the branch circuit and not less than the maximum load to be served. For ranges of 8-3/4 kW or more rating, minimum branch-circuit rating shall be 40A.

40

4) Other Loads. Branch-circuit conductors that supply loads other than those specified in 210.3 and other than cooking appliances as covered in 210.19(A)(3) shall have an ampacity sufficient for the loads served and shall not be smaller than 14 AWG.(see exceptions)

41

(A) Continuous and Noncontinuous Loads. Rating of the overcurrent device shall not be less than noncontinuous load plus 125 percent of the continuous load.

42

Presenter
Presentation Notes
Exception for 100 % rated overcurrent devices. The overcurrent is required to handle the load including 125% for continuous loads of 3 hours or more.

B) Conductor Protection. Conductors shall be protected in accordance with 240.4. (Specific requirements) Flexible cords and fixture wires shall be protected in accordance with 240.5.(D) Outlet Devices. Rating or setting shall not exceed that specified in 210.21 for outlet devices.

43

Presenter
Presentation Notes
A 15 A receptacle can be on a 20A branch circuit if it is Not a single receptacle. Duplex or more is OK. Maximum load is 12 A or 80% or 15A rating

(B) Receptacles. (1) Single Receptacle on an Individual Branch Circuit. A

single receptacle installed on an individual branch circuit shall have an ampere rating not less than that of the branch circuit. (with exceptions)

(2) Total Cord-and-Plug-Connected Load. Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle shall not supply a total cord-and-plug-connected load in excess of the maximum specified in Table 210.21(B)(2). (Previous slide)

44

(3) Receptacle Ratings. Where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings shall conform to the values listed in Table 210.21(B)(3).

45

46

47

(A) Dwelling Unit Branch Circuits. Branch circuits in each dwelling unit shall supply only loads within or associated with that dwelling unit.

(B) Common Area Branch Circuits. Branch circuits required for the common areas of a multifamily dwelling, or a multi-occupancy building shall not be supplied from equipment that supplies an individual dwelling unit or tenant space.

48

Required outlets

49

(A) Cord pendants .. A cord connectorsupplied by a permanent cord pendantis considered a receptacle outlet.

(B) If the cord is permanently connected, a receptacle is not required.

(C) Receptacle for specific equipment shall be installed within 6 ft. of the appliance location.

50

This section provides requirements for 125V,15-& 20A receptacle outlets. Receptacles required by this section shall be in addition to any receptacle that is:

(1) Part of a luminaire or appliance, or (2) Controlled by a wall switch in {210.70(A)(1),Ex. No. 1}

Other than kitchens and bathrooms a wall switch may control a receptacle for lighting

(3) Located within cabinets or cupboards(4) Located more than 5-1/2 ft above floorReceptacles in baseboard heating -as a separate assembly -are permitted as required receptacles

51

(A) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed in accordance with the general provisions specified in 210.52(A)(1) through (A)(4).

(1) Spacing. Receptacles shall be installed such that no point measured horizontally along the floor line in any wall space is more than 6 ft from a receptacle outlet.

52

2) Wall Space. shall include the following: (1) Any space 2 ft or more in width (including space measured around corners) and unbroken along the floor line by doorways and similar openings, fireplaces, and fixed cabinets that do not have counter tops or similar work surfaces

If there are no countertops for fixed cabinets along the floor line, they do not count as wall space

53

Change 210.52(A)(4) Countertops and similar work surfaces: Clarifies that receptacles for counter top and other similar surfaces are not counted as required receptacle as required by 210.52(A). (wall outlets) This is also part of 210.52(A)(2) for wall spaces that do not have countertops or similar surfaces.

Has countertop = wall space = do count

Don’t count

(2) Space occupied by fixed panels in walls, excludingsliding panelsDoes include space with fixed panel but not sliding panels

(3) Space afforded by fixed room dividers such as freestanding bar-type counters or railings

55

56

3) Floor Receptacles. Receptacle outlets in or on floors shall not be counted as part of the required number of receptacle outlets unless located within 18 in. of the wall.

(4) Receptacles installed in countertops and similar work surfaces(such as kitchens, pantries and dining rooms, etc. shall be as in 210.52 (C) 1-5 are not considered as receptacle outlets (in general requirements)

57

(B) Small Appliances. (1) Receptacle Outlets Served. In the kitchen, pantry, breakfast room, dining

room, or similar area of a dwelling unit, the two or more 20A small-appliance branch

circuits required by 210.11(C)(1) shall serve all wall and floor receptacle outlets covered by 210.52(A), all countertop outlets covered by 210.52(C), & receptacle outlets for

refrigeration equipment. (see exception for a specific appliance)

58

2- 20A ckt may include refrigeration and other recpt.

2-20A ckts for the counter top. Other wall outlets can be served by other circuits

59

Presenter
Presentation Notes
Notice the switched recept. in dining room can be on a different circuit. Refrigeration recpt could be on individual branch circuit not part of the small appliance ckt.

(2) No Other Outlets. The two or more small-appliance branch circuits specified in 210.52(B)(1) shall have no other outlets.

(exceptions allow clock recpt. on small appliance branch circuit. AND power for a gas range controls- are permitted on small appliance ckt.)

60

(3) Kitchen Receptacle Requirements. Receptacles installed in a kitchen to serve countertop

surfaces shall be supplied by not fewer than two small-appliance branch circuits, either or both of which shall also be permitted to supply receptacle outlets in the same kitchen and in other rooms specified in 210.52(B)(1).

Additional small-appliance branch circuits shall be permitted to supply receptacle outlets in the kitchen and other rooms specified in 210.52(B)(1).

No small-appliance branch circuit shall serve more than one kitchen.

61

(C) Countertops and work surfaces. In kitchens, pantries, breakfast rooms, dining rooms, and similar areas of dwelling units, receptacle outlets for countertop spaces shall be installed in accordance with 210.52(C)(1) through (C)(5).

Where a range, counter-mounted cooking unit, or sink is installed in an island or peninsular countertop and the width of the countertop behind the range, counter-mounted cooking unit, or sink is less than 12 in., the countertop space is considered two separate countertop spaces as defined in 210.52(C)(4).

Each separate countertop space shall comply with the applicable requirements in 210.52(C).

62

63

Presenter
Presentation Notes
If over 12” then the counter is continuous and the wall space requirements are applied

(1) Wall Countertop Spaces. A receptacle outlet shall be installed at each wall countertop space that is 12 in. or wider.

Receptacle outlets shall be installed so that no point along the wall line is more than 24 in. measured horizontally from a receptacle outlet in that space.

Exceptions for recept. mounted behind ranges, etc.

64

(2) Island Countertop Spaces. At least one receptacle shall be installed at each island countertop space with a long dimension of 24 in. or greater and a short dimension of 12 in. or greater.

(3) Peninsular Countertop Spaces. At least one receptacle outlet shall be installed at each peninsular countertop space with a long dimension of 24 in. or greater and a short dimension of 12 in. or greater. A peninsular countertop is measured from the connected perpendicular wall.

65

At least one recpt.

Change 210.52(C)(3): For each peninsular countertop with a long dimension greater than 24” and a short dimension of 12” or more, the countertop is measured from the connected perpendicular wall.

Measure from here

(4) Separate Spaces. Countertop spaces separated by rangetops, refrigerators, or sinks shall be considered as separate countertop spaces. On islands or peninsular counters: the cooking units/ sinks may divide the counter into two spaces (see Article)

(5) Receptacle Outlet Location. ◦ Receptacle outlets shall be located above, but not more than

20 in. above, the countertop. Assemblies permitted in countertop.

◦ Receptacle outlets rendered not readily accessible by appliances fastened in place, appliance garages, sinks, or range tops as covered in 210.52(C)(1), Exception, or appliances occupying dedicated space shall not be considered as these required outlets.

67

68

Not more than 12” under counter and counter does not extend more than 6 in.

Assembly listed for use in countertops

(D) Bathrooms. (dwelling units)

• At least one receptacle outlet shall be installed in bathrooms within 3 ft of outside edge of each basin.

• Receptacle outlet shall be located on a wall or partition that is adjacent to the basin or basin countertop, located on the countertop, or installed on side or face of the basin cabinet.

• In no case shall receptacle be located more than (12 in.) below the top of the basin.

• Receptacle outlet assemblies listed for the application shall be permitted to be installed in the countertop.

69

E) Outdoor Outlets. Outdoor receptacle outlets shall be installed in accordance with (E)(1) through (E)(3). (1) One-Family & Two-Family Dwellings. For a one-family dwelling and each unit of a two-family dwelling that is at grade level, at least one receptacle outlet readily accessible from grade level and not more than 6-1/2 ft above grade shall be installed at the front and back of the dwelling.See (2) for multifamily dwellings

70

(E) (3) Balconies, Decks, and Porches.

Balconies, decks, and porches that are attached to the dwelling unit and are accessible from inside the dwelling unit shall have at least one receptacle outlet accessible from the balcony, deck, or porch.

Receptacle outlet shall not be located more than (61⁄2 ft) above the balcony, deck, or porch walking surface.

71

72

F) Laundry Areas. In dwelling units, at least one receptacle outlet shall be installed in areas designated for the installation of laundry equipment.

73

G) Basements and Garages.For a one-family dwelling, at least one receptacle outlet shall be installed in the areas specified in 210.52(G)(1) through (3). These receptacles shall be in addition to receptacles required for specific equipment.

(1) Garages. In each attached garage and in each detached garage with electric power. ◦ Branch circuit supplying this receptacle(s) shall not supply outlets

outside of the garage. ◦ At least one receptacle outlet shall be installed for each vehicle bat

and not over 5-1/2 ft above the floor. (dedicated ckt.) (2) Accessory Buildings.

In each accessory building with electric power. (3) Basements.

In each separate unfinished portion of abasement.

74

(H) Hallways in dwelling units that are 10ft or more in length shall have at least one recpt.

I) Foyers. Foyers that are not part of a hallway in accordance with 210.52(H) and that have an area that is greater than (60 sq. ft) shall have a receptacle(s) located in each wall space (3 ft) or more in width. Doorways, door-side windows that

extend to the floor, and similar openings shall not be considered wall space.

75

(H) Hallways. In dwelling units, hallways of 10 ft or more in length shall have at least one receptacle outlet.Hall length shall be considered the length along the centerline of the hall without passing through a doorway.

76

Presenter
Presentation Notes
Hallways 10’ or more need at least one recpt, but could have more.

A 125V, single-phase, 15- or 20A receptacle outlet shall be installed at an accessible location for the servicing of HVAC equipment.

Receptacle shall be located on the same level & within 25 ft of the HVAC equipment.

Receptacle outlet shall not be connected to load side of equipment disconnecting means.

77

At least one receptacle shall be installed within 25 ft of the service location and shall be in the same room.

Exception for one and two family dwellings See exception 2 for voltage over 120bv to

ground

78

(A) Dwelling Units. In dwelling units, lighting outlets shall be installed in accordance with 210.70(A)(1), - (A)(3).(1) Habitable Rooms.

At least one wall switch–controlled lighting outlet shall be installed in every habitable room, kitchen, & bathroom.

See exceptions

79

2) Additional Locations. Additional lighting outlets shall be installed in accordance with (1),(2),&(3).

(1) At least one wall switch–controlled lighting outlet shall be installed in hallways, stairways, attached garages, and detached garages with electric power

(2) For dwelling units, attached garages, & detached garages with electric power, at least one wall switch–controlled lighting outlet shall be installed to for illumination on the exterior side of outdoor entrances or exits with grade level access.

A vehicle door in a garage shall not be considered as an outdoor entrance or exit.

80

(3) Where one or more lighting outlet(s) are installed for interior stairways, there shall be a wall switch at each floor level, and landing level that includes an entryway, to control the lighting outlet(s) where the stairway between floor levels has six risers or more.

81

Entry on landing for up and down stairs

(4) Lighting controls for the additional locations and storage space shall not be of the dimming type, unless they provide the full range of dimming at EACH location

82

(A) (3) Storage or Equipment Spaces. For attics, underfloor spaces, utility rooms, and basements, at least one lighting outlet containing a switch or controlled by a wall switch shall be installed where these spaces are used for storage or contain equipment requiring servicing.

At least one point of control shall be at the usual point of entry to these spaces. The lighting outlet shall be provided at or near the equipment requiring servicing.

83

Sizing of Branch circuits General requirements

84

(A) Voltages. Unless other voltages are specified, for purposes of calculating branch-circuit and feeder loads, nominal system voltages of 120, 120/240, 208Y/120, 240, 347, 480Y/277, 480, 600Y/347, and 600 volts shall be used.

(B) Fractions of an Ampere. Where calculations result in a fraction of an ampere that is less than 0.5, such fractions shall be permitted to be dropped.Fractions of a n amp .5 or larger are rounded up

85

Branch-circuit loads shall be calculated as shown in: 220.12220.14 220.16

86

A unit load of not less than that specified in Table 220.12 for occupancies specified, shall constitute the minimum lighting load. The floor area for each floor shall be calculated from the outside dimensions of the building, dwelling unit, or other area involved. For dwelling units, the calculated floor area shall not include open porches, garages, or unused or unfinished spaces not adaptable for future use.

87

Exception: Where the building is designed and constructed to comply with an energy code adopted by the local authority, the lighting load shall be permitted to be calculated at the values specified in the energy code where the following conditions are met:

(1) A power monitoring system is installed that will provide continuous information regarding the total general lighting load of the building. Energy management system (EMS)

(2) The power monitoring system will be set with alarm values to alert the building owner or manager if the lighting load exceeds the values set by the energy code.

(3) The demand factors specified in 220.42 are not applied to the general lighting load.

88

89

How many 15-amp general-purpose branch circuits for lighting are required for a 2-story dwelling unit measuring 35’X35’?

Section 210.11(A), 220.12

35 X 35 X 2 = 2450 sq.ft.2450 x 3VA/ sq ft. = 7350VA7350VA = 61.25 amps120V61.25 = 4.0833 = 5 circuits15A

90

In all occupancies, the minimum load for each outlet for general-use receptacles and outlets not used for general illumination shall not be less than that calculated in 220.14(A) through (L), the loads shown being based on nominal branch-circuit voltages.

(A) Specific Appliances or Loads. An outlet for a specific appliance or other load not covered in 220.14(B) through (L) shall be calculated based on the ampere rating of the appliance or load served.

91

B) Electric Dryers and Electric Cooking Appliances in Dwellings and Household Cooking Appliances Used in Instructional Programs.

Load calculations shall be permitted as specified in 220.54 for electric dryers and in 220.55 for electric ranges and other cooking appliances.

(C) Motor Outlets. Loads for motor outlets shall be calculated with the requirements in 430.22, 430.24, and 440.6.

(D) Luminaires. An outlet supplying luminaires shall be calculated on the maximum volt-ampere rating of the equipment and lamps for which the luminaires is rated.

92

(J) Dwelling Occupancies. In one-family, two-family, and multifamily dwellings the outlets below (J) (1) –(3) are included in the general lighting load calculations of 220.12. No additional load calculations shall be required for such outlets.

(1) All general-use receptacle outlets of 20-A rating or less, including receptacles connected to the circuits in 210.11(C)(3) – Bathrooms

(2) Receptacle outlets specified in 210.52(E)&(G)-balconies and garages

(3) Lighting outlets specified in 210.70(A) and (B) –lighting in habitable rooms

93

220.40 General: The calculated load for a feeder or service shall not be less that the sum of the loads of the branch circuits supplied- As determined by previous part II, after any applicable demand factors permitted have be applied.

Apply lighting demand factors -220.42 Fixed electric space heating – 220.51

94

(A) Small-Appliance Circuit Load. In each dwelling unit, the load shall be calculated at 1500 volt-amperes for each 2-wire small-appliance branch circuit as covered by 210.11(C)(1).

Where the load is subdivided through two or more feeders, the calculated load for each shall include not less than 1500 volt-amperes for each 2-wire small appliance branch circuit.

These loads shall be permitted to be included with the general lighting load and subjected to the demand factors provided in Table 220.42.

95

(B) Laundry Circuit Load. A load of not less than 1500 volt-amperes shall be included for each 2-wire laundry branch circuit installed as covered by 210.11(C)(2).

This load shall be permitted to be included with the general lighting load and subjected to the demand factors provided in Table 220.42.

96

Other than ranges, clothes dryers, space heating equipment or Air conditioning equipment , four or more appliance fastened in place may use a demand factor of 75% to the sum of the nameplate ratings

97

Part V

Dryer calculations

98

Load for household electric clothes dryers in a dwelling unit(s) shall be either 5000 watts (VA) or the nameplate rating, whichever is larger, for each dryer served.

Use of the demand factors in Table 220.54 shall be permitted.

Kilovolt-amperes (kVA) shall be considered equivalent to kilowatts (kW) for loads

99

100

Section: 220.14(B), 220.54, 220.5

5000VA = 20.833 amps240v

20.833 amps

240.4(D) - #10 for a 30 amps circuit

101

Section: 220.543 X 5 = 15KW4 X 4.75 = (220.54) count as 5 KW each4 X 5 = 20 KW calculated

(Table 220.54 use7 Units = 65%)

15KW + 20KW = 35KW X .65 = 22.75KW

Neutral (220.61) 22.75 X .7 = 15.925KW

102

The End Part 1