TRANSCRIPT

Communications Systems | PVA-FMP-AT Fireman microphone panel

PVA-FMP-AT Fireman microphone panel

www.boschsecurity.com

u Fireman microphone panel according toÖNORM F3033 for PAVIRO system

u Fault and status LED indication

u 7 buttons with LED indicators

u Handheld microphone

The fireman microphone panel includes a handheldmicrophone for fire alarm announcements. The sidetalk button of the microphone is non‑latching and canbe operated with gloves. The housing isnon‑flammable, has a viewing window and the frontdoor can be locked using a key, in compliance withEN 54‑11 (for manual call points).By pressing buttons 1‑5, predefined alarmannouncements stored in the electro‑acousticemergency system (ENS) can be called‑up. When thehand microphone is picked up, ongoingannouncements will stop. By pressing the microphoneside talk button, an announcement can be made in allareas of the electro‑acoustic emergency system (ENS).

System overview

The following indicators and controls are available:

1. Buzzer2. Handheld microphone3. Status LED indicators4. Acknowledge / reset5. All‑clear button6. Alarm announcement buttonsThe labeling of the optical display elements andoperating elements are according to theÖNORM F3033.

Certifications and approvals

IEC 60065

EN 61000‑6‑3

EN 50130‑4

ÖNORM F 3033 Electro‑acoustic emergency system

Parts included

Quantity Component

1 Fireman microphone panel

2 Door lock keys, in compliance with EN 54‑11

1 Installation and operation manual

1 Safety instructions

Technical specifications

Electrical

Main power supply Nominal voltage Maximum voltage range

24 VDC (-10%/+30%)15‑58 VDC

Max. current consumption Idle mode Alarm mode

53 mA at 24 VDC75 mA at 24 VDC

External connectors Call station busconnector (powersupply, control data,audio)

Audio NF output nominal level NF output maximum level

+6 dBu+12 dBu

Frequency response 200‑16000 Hz,+0/-3 dB

Maximum mic. input level -21 dBu

Maximum NF output level +12 dBu

Signal‑to‑noise ratio ≥60 dB

Microphone Type Polar pattern Frequency response Sensitivity

HandheldOmnidirectional280‑14000 Hz3.1 mV/Pa +/-4 dB

Environmental

Temperature Operating Storage and transport

-5 to +40°C-10 to +60°C

Mechanical

Dimensions (WxHxD) 200 x 300 x 110 mm

Case Material Color

Sheet steelRed (RAL 3000)

Weight 3.8 kg

Ingress protection IP30 DIN 40050

Ordering information

PVA-FMP-AT Fireman microphone panelIncludes handheld microphone with coiled cable foremergency announcements.Order number PVA-FMP-AT

2 | PVA-FMP-AT Fireman microphone panel

Represented by:

Europe, Middle East, Africa: Germany: North America: Asia-Pacific:Bosch Security Systems B.V.P.O. Box 800025600 JB Eindhoven, The NetherlandsPhone: + 31 40 2577 284emea.securitysystems@bosch.comemea.boschsecurity.com

Bosch Sicherheitssysteme GmbHRobert-Bosch-Ring 585630 GrasbrunnGermanywww.boschsecurity.com

Bosch Security Systems, Inc.130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 9180onlinehelp@us.bosch.comwww.boschsecurity.us

Robert Bosch (SEA) Pte Ltd, Security Systems11 Bishan Street 21Singapore 573943Phone: +65 6571 2808Fax: +65 6571 2699apr.securitysystems@bosch.comwww.boschsecurity.asia

© Bosch Security Systems 2019 | Data subject to change without notice68535009547 | en, V1, 08. Jul 2019

top related